EEB - ELECTRICAL EQUIPMENT BUILDING
LCP - LOCAL CONTROL PANEL
DS - DRUM SCREEN
WWP - WASH WATER PUMP
SWBD - SWITCHBOARD
This drawing and the design it covers are the property of POWER & WATER UTILITY COMPANY FOR JUBAIL AND YANBU (MARAFIQ). They are merely loaned and on the borrower's express
agreement that they will not be reproduced, copied, loaned, exhibited, nor used except in the limited way and private use permitted by any written consent given by the lender to the borrower.

FINAL ACCEPTANCE AS BUILT


PROJECT FIELD ENGINEER

SHEET CONTRACTOR DATE


DRAWING NO. REV. DRAWING TITLE
NO. NAME

0 5 10 20 30 40 50 60 70
7200043000-JSWC-EB-002 01 1 COVER SHEET WITH DRAWING LIST AND DETAILS

7200043000-JSWC-EB-002 02 1 ELECTRICAL LOAD LIST GRAPHIC SCALE

1 09JUN22 REVISED AS PER COMMENTS AA AA HH


0 26APR22 ISSUED FOR REVIEW / APPROVAL AA AA HH

GEMS - GLOBAL ENVIRONMENTAL


MANAGEMENT SERVICES LTD.

REPLACEMENT OF
SWC-1 D/SCRN (7 NOS)
& LCP IN SWC-2

ELECTRICAL LOAD LIST


FOR SWC-2

7200043000
7200043000-JSWC-EB-002
NTS SHEET 01 OF 02 1
NOTES:
VOLT. Continuous Intermittent Standby
AREA Panel Absorbed Rated Load Nature of
DESCRIPTION Feed From TAG NO. PHASE COS ⌀ Efficiency Remarks
REFERENCE Location (V) Power Power Factor Load
KW KVAR KW KVAR KW KVAR

MOTOR OPERATED
PUMP PUMP LEGENDS:
VALVE FOR DRUM LCP 2-1 MOV-1200 3 480 0.83 0.295 0.375 0.79 0.85 INT. 0.35 0.23
CHAMBER CHAMBER EEB - ELECTRICAL EQUIPMENT BUILDING
SCREEN 2-1 LCP - LOCAL CONTROL PANEL
DS - DRUM SCREEN
MOTOR OPERATED WWP - WASH WATER PUMP
PUMP PUMP SWBD - SWITCHBOARD
VALVE FOR DRUM LCP 2-1 MOV-1205 3 480 0.83 0.295 0.375 0.79 0.85 INT. 0.35 0.23
This drawing and the design it covers are the property of POWER & WATER UTILITY COMPANY FOR JUBAIL AND YANBU (MARAFIQ). They are merely loaned and on the borrower's express

CHAMBER CHAMBER
agreement that they will not be reproduced, copied, loaned, exhibited, nor used except in the limited way and private use permitted by any written consent given by the lender to the borrower.

SCREEN 2-2
MOTOR OPERATED
PUMP PUMP
VALVE FOR DRUM LCP 2-1 MOV-1210 3 480 0.83 0.295 0.375 0.79 0.85 INT. 0.35 0.23
CHAMBER CHAMBER
SCREEN 2-3
MOTOR OPERATED
PUMP PUMP
VALVE FOR DRUM LCP 2-1 MOV-1215 3 480 0.83 0.295 0.375 0.79 0.85 INT. 0.35 0.23
CHAMBER CHAMBER
SCREEN 2-4
MOTOR OPERATED
PUMP PUMP
VALVE FOR DRUM LCP 2-1 MOV-1220 3 480 0.83 0.295 0.375 0.79 0.85 INT. 0.35 0.23
CHAMBER CHAMBER
SCREEN 2-5
MOTOR OPERATED
PUMP PUMP
VALVE FOR DRUM LCP 2-1 MOV-1225 3 480 0.83 0.295 0.375 0.79 0.85 INT. 0.35 0.23
CHAMBER CHAMBER
SCREEN 2-6
MOTOR OPERATED
PUMP PUMP
VALVE FOR DRUM LCP 2-1 MOV-1300 3 480 0.83 0.295 0.375 0.79 0.85 INT. 0.35 0.23
CHAMBER CHAMBER
SCREEN 2-7

PUMP LOCAL CONTROL PANEL MTS / ATS SWC-2


EEB-2 3 480 0.85 16.70 44.52 1.00 0.85 CONT. 19.65 12.18
CHAMBER (LCP 2-1) (EEB-2) -ATS-02

FINAL ACCEPTANCE AS BUILT


PROJECT FIELD ENGINEER

CONTRACTOR DATE

NAME

0 5 10 20 30 40 50 60 70

GRAPHIC SCALE

1 09JUN22 REVISED AS PER COMMENTS AA AA HH


0 24APR22 ISSUED FOR REVIEW / APPROVAL AA AA HH

GEMS - GLOBAL ENVIRONMENTAL


MANAGEMENT SERVICES LTD.

REPLACEMENT OF
SWC-1 D/SCRN (7 NOS)
& LCP IN SWC-2

ELECTRICAL LOAD LIST


FOR SWC-2

7200043000
7200043000-JSWC-EB-002
NTS SHEET 02 OF 02 1