DEA Report of Bldg-1 - Final - 14!08!2018
DEA Report of Bldg-1 - Final - 14!08!2018
Assessed by
Engr. Md. Mehedi Hasan
Lead Structural Engineer,
Sthapona Consultants
M.Sc. (Structural Engineering, BUET) B.Sc. (BUET),
MIEB -24748, Rajuk Reg. DMINB-CE0233.
May, 2016
Office:
1st Floor, House #18, Road #20,
STHAPONA CONSULTANTS Nikunja-2, Dhaka-1229.
Phone: +880-2-8900838
Email: sthaponaconsultants@gmail.com
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD., DETAILED ENGINEERING ASSESSMENT REPORT
KUNIA, BOARDBAZAR, GAZIPUR.]
TABLE OF CONTENTS
1 INTRODUCTION ..................................................................................................................... 2
2 GENERAL OVERVIEW OF THE BUILDING .................................................................. 2
3 DESTRUCTIVE & NON-DESTRUCTIVE TESTING ...................................................... 3
3.1 EVALUATION OF CONCRETE STRENGTH FROM CORE TEST .................... 3
3.2 VERIFICATION OF REINFORCEMENT USING FERRO-SCANNER &
REMOVING CONCRETE COVER ................................................................................................ 4
4 ANALYSIS FOR STRUCTURAL ADEQUACY ................................................................ 5
4.1 STRUCTURAL SYSTEM ..................................................................................................... 5
4.2 CODES AND PRACTICES .................................................................................................. 7
4.3 MATERIAL PROPERTY ..................................................................................................... 7
5 EVALUATION OF STRUCTURAL MEMBERS ............................................................. 14
5.1 CHECKING ADEQUACY OF FOUNDATION WITH 63PSF LIVE LOAD .. 14
5.2 CHECKING ADEQUACY OF COLUMN WITH 63 PSF LIVE LOADING ... 18
5.3 CHECKING ADEQUACY OF BEAMS WITH 63 PSF LIVE LOADING ........ 35
5.4 CHECKING ADEQUACY OF SLAB WITH 63 PSF LIVE LOAD ..................... 39
6 CONCLUSION ........................................................................................................................ 45
7 RECOMMENDATION .......................................................................................................... 45
8 EVALUATION OF STRUCTURAL MEMBERS AFTER RETROFITTING ............ 46
8.1 CHECKING ADEQUACY OF FOUNDATION AFTER RETROFITTING ... 46
9 CHECKING ADEQUACY OF COLUMN AFTER RETROFITTING .............................. 50
9.1 CHECKING ADEQUACY OF BEAMS AFTER RETROFITTING .................. 62
10 DISCLAIMER ......................................................................................................................... 64
STHAPONA CONSULTANTS i
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD., DETAILED ENGINEERING ASSESSMENT REPORT
KUNIA, BOARDBAZAR, GAZIPUR.]
Figure 4-1: Flat plate Slab System of Typical Floors (Typical Floor) .......................................... 5
Figure 4-4: Applied Live Load in Typical Floor (63 psf) for BNBC .......................................... 12
STHAPONA CONSULTANTS 3
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD., DETAILED ENGINEERING ASSESSMENT REPORT
KUNIA, BOARDBAZAR, GAZIPUR.]
Figure 5-21: Beam Layout Plan of 1st, 2nd, 3rd, 8th, 9th & 10th floor. ..................................... 36
Figure 5-22: Beam Conditions of 1st, 2nd, 3rd, 8th, 9th & 10th floor for 63 psf live load. .............. 37
Figure 5-23: Beam Conditions of 4th to 7th floor for 63 psf live load. (Red colour denotes
overstressed beams for excessive shear & torsion). .................................................................. 38
Figure 5-24: DCR ratio for punching of 2nd Floor Flat slab for 63 psf Live Load............................. 39
Figure 5-25: 2nd Floor Slab Bottom Reinforcement Requirement in Direction-1 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 40
Figure 5-26: 2nd Floor Slab Top Reinforcement Requirement in Direction-1 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 40
Figure 5-27: 2nd Floor Slab Bottom Reinforcement Requirement in Direction-2 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 41
Figure 5-28: 2nd Floor Slab Top Reinforcement Requirement in Direction-2 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 41
Figure 5-29: DCR ratio for punching of 8th Floor Flat slab for 63 psf Live Load ............................ 42
Figure 5-30: 8th Floor Slab Bottom Reinforcement Requirement in Direction-1 for63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 43
Figure 5-31: 8th Floor Slab Top Reinforcement Requirement in Direction-1 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 43
Figure 5-32: 8th Floor Slab Bottom Reinforcement Requirement in Direction-2 for63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 44
Figure 5-33: 8th Floor Slab Top Reinforcement Requirement in Direction-1 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0) ................................................................................................................ 44
STHAPONA CONSULTANTS 4
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD., DETAILED ENGINEERING ASSESSMENT REPORT
KUNIA, BOARDBAZAR, GAZIPUR.]
Figure 10-13: Beam Conditions of 1st, 2nd, 3rd, 8th, 9th & 10th floor for 63 psf live load. (Red
colour denotes overstressed beams for excessive shear & torsion). ........................................ 62
Figure 10-14: Beam Conditions of 4th to 7th floor for 63 psf live load. (Red colour denotes
overstressed beams for excessive shear & torsion). ..................................................................... 63
STHAPONA CONSULTANTS 5
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD., DETAILED ENGINEERING ASSESSMENT REPORT
KUNIA, BOARDBAZAR, GAZIPUR.]
List of Tables
Table 2.1: Basic information RCC Building#1 ................................................................... 3
Table 5.1: Checking Adequacy of Foundation for Bearing Capacity (63 psf) ................. 17
Table 5.2: Checking Adequacy of Foundation for Punching Shear (63 psf) .................... 18
STHAPONA CONSULTANTS 6
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
EXECUTIVE SUMMARY
Building-1 of Rupa Knitwear (Pvt) Ltd & Rupa Fabrics Ltd. is a ten storied RC flat slab
structure.
A team from ALLIANCE (BV) conducted visual assessment of the building#1 on 29th
May, 2014. They recommended to perform check for structural integrity of the factory
building. In this concern, Rupa Knitwear (Pvt) Ltd & Rupa Fabrics Ltd. engaged
Sthapona Consultants for performing Detail Engineering Assessment along with
checking architectural and structural drawing of the factory building.
For Detail Engineering Assessment one of the key inputs is the concrete strength. We
collected sixteen cores (twelve from columns, four from slabs of different floors). We
found equivalent concrete strength for column is 2996 psi, for slab is 3726 psi. The
equivalent concrete strength has been calculated according to ACI 562.
We incorporated existing live load, concrete strength, rebar information etc. in the finite
element model of this building. Considering the concrete strength suggested by ACI 562,
all the columns and flat slab has been analyzed for 63 psf live load. All of the foundations
are adequate for bearing capacity & some of the foundation is overstressed for punching shear.
Live load reduction factor has been applied where applicable according to BNBC 2006.
Considering BNBC 2006 load combinations (i.e. gravity and lateral load) some columns
& shear walls are f o u n d t o b e overstressed and flat slab are overstressed, few
beams are overstressed due to shear and torsion. Shear walls require more reinforcement
than provided.
1 INTRODUCTION
Sthapona Consultants was assigned to conduct Detail Engineering Assessment of the RCC
Building#1. The scope of work of the project has been shown below, which has been
summarized based on visual inspection report done by BV (ALLIANCE) team.
(i). Develop the required documents to confirm the structural integrity of the
building.
(ii). Confirm and document that provision have been made to accommodate
concentrated load at ground floor.
(iii). The Detail Engineering Assessment of the building, which includes the
following items:
Highlight any variations between as-built and structure design drawings (if
applicable)
Results of geotechnical assessment and testing/investigation
Details of assumptions, loading, inputs and results of computer modelling
Commentary on adequacy/inadequacy of elements of the structure and
further action plan
The Building#1 of Rupa Knitwear (Pvt) Ltd & Rupa Fabrics Ltd. is a 10‐storied reinforced
concrete structure located at KUNIA, BOARD BAZAR, GAZIPUR Dhaka-1230
(Latitude: 23°56'14.34"N; Longitude: 90°23'12.58"E). Total area of the building is
about 127,270 sft (Table 2.1).
Information Description
Sixteen cores from different locations of column & slab has been collected to examine the
concrete strength. These cores have been sent and tested in BUET lab by UTM (Universal
Testing Machine) to find its compressive strength. Equivalent concrete strength (As per ACI562)
for column is 2996 psi (using combined failure at eleven columns and excluding mortar failure
at one column) and for beam & slab is 3726 psi respectively. Detail of core test results have
presented in Annex-I.
For Column:
For Slab:
Diame
Core Diamet Modified
ter of
Sample test er Core test
Core
result Effect result
(inch)
1 5570 2.72 1.0384 5783.888 f c (avg)= 4807.792 psi
2 4800 2.72 1.0384 4984.32
Standard Deviation of
3 4280 2.72 1.0384 4444.352 761.32 psi
Core strength=
4 3870 2.72 1.0384 4018.608
Coefficient of variation, V= 0.16
Number of Sample, n=
4
Coefficient of variation
1.28
modification factor, kc=
f c (eq)= 3726 psi
Figure 4-1: Flat plate Slab System of Typical Floors (Typical Floor)
STHAPONA CONSULTANTS 10 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
4.3 LOADS
The loads that may act upon the structure are as follows:
STHAPONA CONSULTANTS 10 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Live load is the gravity load due to non-permanent objects like machines, furniture, and
human. Analysis has been carried out based on load recommended by BNBC (2006).
According to BNBC we have considered 63 psf live load for analysis. And for NTPA
compliance (When the structure seems not compliant with BNBC loading condition) we
have used reduced live load=42 psf.
Regarding the earthquake resistant structural design, it essential that the specific design
code is followed. For the analysis and design checking of this building, Equivalent Static
Force Method of BNBC (2006) is followed. The main considerations for calculation of
earthquake load are given below.
STHAPONA CONSULTANTS 10 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
These seven basic load cases are analysed by ETABS-V9.7.4. The results are then
combined in accordance with BNBC. These are as follows:
1.4 D
1.4 D + 1.7 L
0.9 D + 1.3 (W or 1.1 E)
0.75 (1.4 D + 1.7 L + 1.7 (W or 1.1 E))
Where D stands for total dead load i.e. D = DL + SDEAD, L stands for live load i.e. L=LL,
W stands for wind load and E stands for earthquake load. When these seven basic load
cases are combined accordingly considering the direction of lateral loads, we obtain, after
simplification, the following twenty-two combination cases:
STHAPONA CONSULTANTS 10 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
But in ETABS analysis, we do not calculate last four combination cases (Combination
case 27, 28, 29 & 30).
STHAPONA CONSULTANTS 10 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 11 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 4-4: Applied Live Load in Typical Floor (63 psf) for BNBC
STHAPONA CONSULTANTS 12 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 13 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 14 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 15 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Table 5.1: Checking Adequacy of Foundation for Bearing Capacity (63 psf)
STHAPONA CONSULTANTS 16 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Table 5.2: Checking Adequacy of Foundation for Punching Shear (63 psf)
STHAPONA CONSULTANTS 17 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 18 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 19 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 20 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 21 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 22 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 23 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 24 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 25 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 26 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 27 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 28 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 29 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 30 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 31 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 32 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 33 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 34 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 35 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-21: Beam Layout Plan of 1st, 2nd, 3rd, 8th, 9th & 10th floor.
STHAPONA CONSULTANTS 36 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-22: Beam Conditions of 1st, 2nd, 3rd, 8th, 9th & 10th floor for 63 psf live load.
(Red colour denotes overstressed beams for excessive shear & torsion).
STHAPONA CONSULTANTS 37 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-23: Beam Conditions of 4th to 7th floor for 63 psf live load. (Red colour denotes overstressed
beams for excessive shear & torsion).
STHAPONA CONSULTANTS 40 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-24: DCR ratio for punching of 2nd Floor Flat slab for 63 psf Live Load
(DCR more than 1.0 denotes inadequacy)
STHAPONA CONSULTANTS 39 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-25: 2nd Floor Slab Bottom Reinforcement Requirement in Direction-1 for 63 psf Live
Load (unit-in2/ft) (SAFE 16.0.0)
Figure 5-26: 2nd Floor Slab Top Reinforcement Requirement in Direction-1 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0)
STHAPONA CONSULTANTS 40 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-27: 2nd Floor Slab Bottom Reinforcement Requirement in Direction-2 for 63 psf Live
Load (unit-in2/ft) (SAFE 16.0.0)
Figure 5-28: 2nd Floor Slab Top Reinforcement Requirement in Direction-2 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0)
STHAPONA CONSULTANTS 41 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-29: DCR ratio for punching of 8th Floor Flat slab for 63 psf Live Load
(DCR more Than 1.0 denotes inadequacy)
STHAPONA CONSULTANTS 42 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-30: 8th Floor Slab Bottom Reinforcement Requirement in Direction-1 for63 psf Live
Load (unit-in2/ft) (SAFE 16.0.0)
Figure 5-31: 8th Floor Slab Top Reinforcement Requirement in Direction-1 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0)
STHAPONA CONSULTANTS 43 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 5-32: 8th Floor Slab Bottom Reinforcement Requirement in Direction-2 for63 psf Live
Load (unit-in2/ft) (SAFE 16.0.0)
Figure 5-33: 8th Floor Slab Top Reinforcement Requirement in Direction-1 for 63 psf Live Load
(unit-in2/ft) (SAFE 16.0.0)
STHAPONA CONSULTANTS 44 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
6 CONCLUSION
All of the footings are adequate in size (in respect of soil bearing capacity)
Some of the footings are overstressed due to punching shear.
Shear walls, few columns are over-stressed for BNBC load combination.
Few beams are overstressed due to shear and torsion.
The flat slab is overstressed considering 63 psf live load.
7 RECOMMENDATION
STHAPONA CONSULTANTS 45 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 46 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 47 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Provided
Bearing FoS (From Ultimate Load Reaction Available FoS Remarks
Joint Foundation Foundation
Capacity Soil Test Bearing Capacity (DL + LL) (For Existing (Minimum
Label Type Size
Report) Foundation) FoS=2.0)
sft ksf kip kip
873 F6 132.3 8.88 2 2348.76 642.89 3.65 OK
874 F6 132.3 8.88 2 2348.76 599.62 3.92 OK
858 F2 306.3 8.88 2 5439.00 1332.03 4.08 OK
859 F2 306.3 8.88 2 5439.00 1165.93 4.66 OK
871 F5 182.3 8.88 2 3236.76 524.95 6.17 OK
862 F3 280.6 8.88 2 4982.79 974.91 5.11 OK
851 F1 324.0 8.88 2 5754.24 1122.26 5.13 OK
854 F1 324.0 8.88 2 5754.24 1110.05 5.18 OK
857 F1 324.0 8.88 2 5754.24 1109.41 5.19 OK
866 F5 182.3 8.88 2 3236.76 676.36 4.79 OK
870 F5 182.3 8.88 2 3236.76 526.27 6.15 OK
861 F3 280.6 8.88 2 4982.79 970.37 5.13 OK
850 F1 324.0 8.88 2 5754.24 1103.19 5.22 OK
853 F1 324.0 8.88 2 5754.24 1102.25 5.22 OK
856 F1 324.0 8.88 2 5754.24 1127.46 5.10 OK
865 F5 182.3 8.88 2 3236.76 632.96 5.11 OK
849 F1 324.0 8.88 2 5754.24 1090.33 5.28 OK
852 F1 324.0 8.88 2 5754.24 1120.99 5.13 OK
855 F1 324.0 8.88 2 5754.24 1115.41 5.16 OK
869 F5 182.3 8.88 2 3236.76 573.91 5.64 OK
868 F5 182.3 8.88 2 3236.76 606.40 5.34 OK
877
878
875 FC1 718.5 8.88 2 12759.91 3658.04 3.49 OK
893
863
884
891
889
885 FC3 875.4 8.88 2 15546.45 5600.40 2.78 OK
886
887
888
907
860
881
882
921 FC2 815.6 8.88 2 14484.43 3270.23 4.43 OK
920
892
880
883
904
864
867
927
RF1 948.0 8.88 2 16836.48 2755.35 6.11 OK
16
928
2366
879
STHAPONA CONSULTANTS 48 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 49 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 50 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 51 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 52 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 53 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 54 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 55 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 56 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 57 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 58 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 59 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 60 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
STHAPONA CONSULTANTS 61 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 10-13: Beam Conditions of 1st, 2nd, 3rd, 8th, 9th & 10th floor for 63 psf live load.
(Red colour denotes overstressed beams for excessive shear & torsion).
Beam Id. Provided Reif. Provided Reif.
Required Required
In At Top- Edge At Middle-
Reinf. (in2) Reinf. (in2)
Drawing (in2) Bottom(in2)
STHAPONA CONSULTANTS 62 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
Figure 10-14: Beam Conditions of 4th to 7th floor for 63 psf live load. (Red colour
denotes overstressed beams for excessive shear & torsion).
STHAPONA CONSULTANTS 40 | P a g e
[BUILDING#1, RUPA KNITWEAR (PVT) LTD & RUPA FABRICS LTD.,
KUNIA, BOARDBAZAR, GAZIPUR.]
DETAILED ENGINEERING ASSESSMENT REPORT
10 DISCLAIMER
The assessment engineer made the above observations & recommendations from Core
test, NDT results & mathematical modelling of the building. We applied our best
engineering judgments. We do not bear responsibility for any deviation from the predicted
behavior of the structure caused by uncertainties of performance or calamities.
STHAPONA CONSULTANTS 64 | P a g e
ANNEX -I
We have performed detailed rebar scanning using Ferro-Scan at Eight (8) locations to find
the reinforcement used in structural members. Among the Eight, five scans were done for
ground floor column, one scan was done for ground floor slab, and one scan was done for
third floor column and one scan for third floor slab. Also a lot of quick scan were performed
to verify the reinforcement in columns and slab.
We have checked rebar no. and diameter of columns and spacing of slab by removing
concrete cover.
We have performed concrete strength test by cutting Core (Destructive) at sixteen (16)
locations in column and slab. All the cores have been taken from different floor. After
cutting the Core, we have tested it by Universal Testing Machine at BUET lab. We found
that stone chips were used for concreting of column and slab. We found the concrete
strength is on a range from 2460 psi to 4810 psi for column and 3870 psi and 5570 psi for
slab and calculated average concrete strength is of column is 3491 psi and of slab is 4630
psi. However, considering the Guide line of ACI 562, the Equivalent Concrete strength is
2996 psi for column and 3726 psi for slab.
Figure 3.2: Core-1 cutting location Figure 3.3: Core-2 cutting location
Figure 3.4: Core-3 cutting location Figure 3.5: Core-4 cutting location
Figure 3.6: Core-5 cutting location Figure 3.7: Core-6 cutting location
Figure 3.8: Core-7 cutting location Figure 3.9: Core-8 cutting location
Figure 3.10: Core-9 cutting location Figure 3.11: Core-10 cutting location
Figure 3.12: Core-11 cutting location Figure 3.13: Core-12 cutting location
Figure 3.14: Core-13 cutting location Figure 3.15: Core-14 cutting location
Figure 3.16: Core-15 cutting location Figure 3.17: Core-16 cutting location
Figure 3.18: Core-1 taken from 5F Column Figure 3.19: Core-2 taken from 2F Column
Figure 3.20: Core-3 taken from 4F Column Figure 3.21: Core-4 taken from 4F Column
Figure 3.22: Core-5 taken from 5F Column Figure 3.23: Core-6 taken from 6F Column
Figure 3.24: Core-7 taken from 6F Column Figure 3.25: Core-8 taken from 6F Column
Figure 3.26: Core-9 taken from 6F Column Figure 3.27: Core-10 taken from 6F Column
Figure 3.28: Core-11 taken from 6F Column Figure 3.29: Core-12 taken from 6F Column
Figure 3.30: Core-13 taken from 6F Slab Figure 3.31: Core-14 taken from 5F Slab
Figure 3.32: Core-15 taken from 4F Slab Figure 3.33: Core-16 taken from 3F Slab
5. FOUNDATION EXPLORATION