4.

5 Test Reports

4.5.1 Routine Test Report

4.5.2 Type Test Report

4.5.3 Calculation of losses and efficiency


Calculation of losses and efficiency of 3000KW/4P/11KV/ MGF 630 Motor for PA Fan
a/c Jaypee Nigrie project

% Load 100% 75% 50% 25%


Input Power to Stator (
3091140 2322610 1556220 782970
Watts)
Stator Current ( I amps) 177.9 135 94.1 56.4
Statot Cu Loss ( Watts) =3
x I²R ,
(Where R= Hot 20550 11830 5750 2070
Resistance of Stator
winding)

3070590 2310780 1550470 780900


Rotor Input= Input Power-
Stator Copper Loss
Motor RPM 1493.2 1495.1 1497.0 1498.6
Slip = ( Ns- N )/Ns 0.004503333 0.00324 0.001973333 0.000913333
Rotor Cu Loss = Rotor
13828 7487 3060 713
Input x Slip
Iron Loss * 21393 21393 21393 21393
Mechanical losses * 19808 19808 19808 19808

Stary Load losses ( 0.5% 15456 11613 7781 3915


of Input Power to Stator)
Total Losses ( Watts) 91035 72131 57792 47899
Output ( Watts ) = Input -
3000105 2250479 1498428 735071
Total Losses
% Efficiency= Output /
97.05 96.89 96.29 93.88
Input * 100

Committed Efficiency as 96.5 96.3 96 -


per approved data-sheet

Note :
1. * Please see test certifcate -page 5 /8 for S. No. 1012525921
2. Corrosponding to 11020 V, the Iron losses are calculated and mentioned as 21393 Watts.
3. Below also the mechanical losses of 19808 Watts is mentioned. ( The mechanical losses are obtained by
extrapoliting the curve upto the Y- axis where the voltage is zero ).