Professional Documents
Culture Documents
46 MW (IEC), Chilled Water, 40000 M: (Reference Design 102)
46 MW (IEC), Chilled Water, 40000 M: (Reference Design 102)
DESIGN HIGHLIGHTS
High reliability
Reduced TTM
Scalable design
Minimized initial CapEx
Flexible IT space
[Reference Design 102] 2
Facility Power
UTILITY CONNECTION
The data centre is designed for a maximum demand of 80 MVA, which requires a connection to the electric utility’s high voltage (HV)
sub-transmission network. Depending on the country, the supply voltage can vary from 90 kV (e.g. France), to 110 kV (e.g.
Finland), and up to 132 kV (e.g. UK). The utility company will be responsible for building the HV substation that provides metered
power supplies “A” and “B”. Therefore, the change of ownership occurs after the metering point, which means that the data centre
owner will specify and procure the HV/MV transformer.
KWh KWh
HV HV HV HV
40MVA 40MVA 40MVA MV 40MVA
MV MV MV
Facility Power
SECONDARY MEDIUM VOLTAGE DISTRIBUTION
This design aims for a simple MV distribution, optimizing the number of MV feeders in order to minimize MV cabling cost. Each section
feeds a group of three IT blocks, as does a dedicated MV backup diesel generator power plant. Automatic transfer between the mains
power and backup generators is built into the design.
Eight Premset switchgear lineups, rated at 17.5 kV, 1250 A and 25 kA (3s) make up the entire MV secondary distribution. Each pair of
Premset lineups feeds three IT blocks in a 2N architecture, to provide A- and B-side power. The two switchgear lineups are connected
by a “coupling cable” to maintain redundancy downstream of a failure. The diesel generator backup power is connected to the MV
distribution network via a Premset switchoard. Thirteen 2500 kVA, 400 V generators with N+2 redundancy are coupled to the MV
network with a LV/MV step-up 2500 kVA Trihal cast resin transformer with a 6% short circuit impedance. This backup generator plant
configuration provides high reliability and safety, while minimizing cost. For full Tier III compliance, a set of redundant Premset MV
switchgear could be added to the design. Fuel storage and piping can also be added to the design in accordance with country habits
and regulations.
MV Distribution to Blocks
MV Primary Dist. MV Primary Dist.
SWG B
SWG A
DESIGN OPTIONS
Three Blocks This reference design can be modified
G
13x 2500 kVA units
G as follows without a significant effect on
LV LV the design’s performance attributes:
MV MV
Facility Power
LOW VOLTAGE DISTRIBUTION
Downstream of the MV secondary distribution, each block is composed of three pairs of A-side and B-side MV/LV transformers that
serve LV switchboards. Two of these pairs are dedicated to the two IT rooms in the block, while the third pair is dedicated to the block’s
cooling system and auxiliaries. In A total of 72 Trihal 2500 kVA transformers are used to transform voltage from 17.5 kV to 400 V with
6% impedance, in a close-coupled installation.
Similarly, 72 Okken LV switchgear lineups make up the complete LV distribution sub-system, with each lineup rated at 400 V and 80 kA
(1s) with a 4000 A bus. This busbar nominal current rating is maximized to achieve cost-effectiveness and make the most of IT
capacity.The power train for each IT room is made up of two Okken lineups that feed Galaxy 7000 UPSs in a 2N configuration, allowing
for A and B-side power distribution in the IT room. Finally, a combination of LV switchgear and iBusway systems with built-in
intelligence feeds 2N power to the IT load. The power train for a single block’s cooling system and auxiliaries is comprised of two Okken
LV switchgear lineups providing A and B-side distribution to chillers, pumps, lighting, monitoring, security and automation systems, etc.,
while providing fault protection to cooling units in the IT and electrical rooms
The facility power system is designed to also support integrated peripheral devices like fire panels, access control systems, and
environmental monitoring and control devices. Power meters in the electrical path monitor power quality and allow for predictive
maintenance & diagnostics of the system. These meters also integrate with StruxureWare Power Monitoring Expert.
Every component in this Reference Design is built and tested to the applicable IEC standards. Further design details and schematics
are available in the engineering package available upon request.
LV Distribution to final loads per Block
MV Secondary MV Secondary
Dist. SWG A Dist. SWG B
DESIGN OPTIONS
This reference design can
One Block
Trihal be modified as follows
MV 2.5MVA MV MV 2.5MVA MV MV 2.5MVA MV
LV LV LV LV LV LV without a significant effect on
Okken
LV Crit. SWB A LV Crit. SWB B LV Crit. SWB A LV Crit. SWB B LV Crit. SWB A LV Crit. SWB B the design’s performance
4000A, 400V 4000A, 400V 4000A, 400V 4000A, 400V 4000A, 400V 4000A, 400V
attributes:
UPS UPS UPS UPS
Change UPS batteries
Location
LV Dist. A LV Dist. B LV Dist. A LV Dist. B
Type
IT Room 1: 1.9MW IT Rooml 2: 1.9MW Cooling for one Block
attributes:
Number of LV critical switchgear 4 2
LV critical bus amps 4000 4000 A
Change UPS batteries
LV critical bus voltage 400 400 V
Location
LV critical switchgear short time withstand current 80 (1) 80 (1) kA (s)
Type
2N: IT room CRAHS and
UPS redundancy 2N secondary pumps
N: UPS-room CRAHs
Total UPS capacity per block 4500 360 kW
UPS runtime @ rated load 5 5 minutes
UPS output voltage 400 400 V
Facility Power
POWER MONITORING
and capacity planning. Block2 Block 2 Block 2 Block 5 Block 5 Block 5 Block 8 Block 8 Block 8 Block 11 Block 11 Block 11
ITroom 1 ITroom 2 Mechanical ITroom1 ITroom 2 Mechanical ITroom 1 ITroom 2 Mechanical ITroom1 ITroom2 Mechanical
Block3 Block 3 Block 3 Block 6 Block 6 Block 6 Block 9 Block 9 Block 9 Block 12 Block 12 Block 12
ITroom 1 ITroom 2 Mechanical ITroom1 ITroom 2 Mechanical ITroom 1 ITroom 2 Mechanical ITroom1 ITroom2 Mechanical
Facility Cooling
This facility cooling system is optimized for oceanic climates, in Cooling system for 1 Block
places like Dublin or San Francisco, with warm summers and cool (Shown 1 of 12)
winters, though it can be easily adapted to work in other types of CHWR CHWS CHWS CHWR
IT & ER IT & ER IT & ER IT & ER
climates.
The design is made up of twelve identical stand-alone cooling DAS DAS
VFD
VFD
VFD
VFD
VFD
VFD
systems, one dedicated for each block. Each chilled water system ET ET
CHWR
continuous cooling after a power outage or chiller restart. These
ER A
CHWS CHWS
tanks would be sized accordingly for the ramp-up time of the
chillers and building topology. IT Room IT Room
1 2
The redundant piping architecture of the mechanical system feeds
InRow RC units in the IT rooms and Uniflair chilled water room-
CHWR
ER B
based computer room air handlers (CRAHs) in both IT rooms and
in the LV electrical room. Additional air handling units are added
to supply fresh air in the building and direct expansion (DX) units
are provisioned for the rooms containing the generator switchgear,
MV switchgear and UPS batteries.
DESIGN OPTIONS
This reference design can be modified as follows without a
This design is instrumented to work with StruxureWare Building
significant effect on the design’s performance attributes:
Operation for cooling control and monitoring. Further design
details such as dimensions, equipment placement, temperature
Add StruxureWare Building Operation
set points, pipe sizing, flow rates, and pressure drops are
available in the engineering package.
FACILITY COOLING ATTRIBUTES
IT Space
Twelve independent IT blocks can be built one by one to make up the IT DESIGN OPTIONS
space of this design. One block includes two IT rooms of 1908 kW This reference design can be
apiece. Each room is split into two zones: a medium-density area with
modified as follows without a
150 NetShelter racks of 6 kW each, and a high-density area with 112
significant effect on the design’s
NetShelter racks of 9 kW each. Altogether, they constitute 45.8 MW of IT
performance attributes:
capacity for the whole site.
In this design, each IT room is powered by redundant (2N) iBusway Add environmental and security
systems. Every rack has the capacity to accept dual power feeds, since management
each is configured with redundant (2N) metered rack-mount power Change rack options
distribution units (PDUs) which offer remote monitoring for improved Tall
efficiency and capacity management. Wide
Deep
In medium-density zones, heat is removed by Uniflair chilled water room- Change rack power distribution options
based CRAHs in an N+2 redundant configuration at the room level. In Basic
high-density zones, heat is removed by InRow RC-HT units in an N+2 Metered
redundant configuration for each pair of rows. Considerations can be Switched
made with respect to return air ducting systems and/or raised floors, to Add StruxureWare Data Center Expert
improve the coolers’ performance. Redundant valves and piping are also
added to ensure continuous cooling with high reliability.
The security of the room is maintained at multiple points. At the rack
level, access is controlled by a door lock and sensor. At the room level,
security cameras are utilized for monitoring.
IT SPACE ATTRIBUTES