AIR-WATER
65 .0

HEAT PUMPS
FOR OUTDOOR OR INDOOR INSTALLATION

TECHNICAL MANUAL
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.

2
TABLE OF CONTENTS

GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - VERY HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NOMINAL performances - HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
NOMINAL performances - STANDARD plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
NOMINAL performances - RADIANT plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
HEATING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Source side aeraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
DESUPERHEATER performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Operating limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

3
4
GENERAL FEATURES

Unit description

This series of air-water heat pumps satisfies the heating, coo- The refrigerant circuit, contained in a box repaired from the air
ling and domestic hot water production requirements of residen- flow to simplify the maintenance operations, is equipped with
tial plants of small and medium size. scroll compressor mounted on damper supports, brazed pla-
All the units are suitable both for outdoor or indoor installation. te heat exchangers, electronic expansion valve, reverse cycle
The possibiliy to produce water at high temperatures makes the- valve, centrifugal fan (plug fan), finned coil realized with cop-
se units particularly suitable to be applied to radiators plants as per pipes and alluminium fins. The circuit is protected by high
well as to fan coil plants and radiant floor plants. and low pressure switches and flow switches on the plate heat
exchanger.
The control system allows to manage not only the refrigerant
circuit but the whole plant with the possibility to choose different The compressor is equipped with vapour and liquid injection
solutions both for the heating and cooling plant and for the do- and is placed on an economized refrigerant circuit with plate
mestic hot water management. The possibility of solar panels or heat exchanger and electronic expansion valve dedicated to the
other heating sources integration is also available. injection.
The heating function optimizes the flow water temperature ac- The plate heat exchanger and all the hydraulic pipes are ther-
cording both to the ambient temperature and to the outdoor tem- mally insulated in order to avoid condensate generation and re-
perature through climatic curves adaptable to the building featu- duce thermal losses.
res. It’s possible to manage a storage tank and two independent The plug fan with electronic control of the rotational speed gua-
circuits (a direct one and a mixed one). rantees high efficiencies and low noise in all the operating con-
The domestic hot water management allows to control the th- ditions and allows to install the unit both outdoor (with protection
ree way valve, the storage tank and the anti-legionella cycles (if caps) or indoor (with ducted air inlet and outlet). It is moreover
necessary). possible to reduce the noise during the night.
The cooling function can be realized through “active cooling” All the units with three-phase power supply are provided with
(refrigerant circuit inversion). When the unit is used in radiant a phase sequence and correct sequence controller device and
floor plants, to avoid condensate generation, a room humidity with an outdoor temperature sensor in order to realize the clima-
sensor can be installed. During cooling mode operation a part of tic control.
the heating power in excess can be recovered for the domestic All the units are accurately built and individually tested in the
hot water production (VD version). factory. Only electric and hydraulic connections are required for
The internal programmer clock allows to define different daily installation.
switching programs for heating, cooling and domestic hot water
production.

Unit identification code

The codes that identify the units and the meaning of the letters used are described below.

HMP HT IP 45.1 VB AB 0 H 5

Power supply

Unit type 1 - 230V - 1 - 50 Hz


5 - 400V - 3N - 50 Hz
IP - Units suitable for hydronic plant in-
stallation operating as reversible heat
pumps
Operating range

H - High temperature.
The unit is suitable to produce
Unit model water at high temperature.

Refrigerant type
N° compressors
0 - R410A

Unit version
Acoustic setting up
VB - Base version
VD - Desuperheater version AB - Base setting up

5
GENERAL FEATURES

Description of components

External structure. Basement, supporting structure and lateral The refrigerant circuit of each unit contains moreover solid
panels are made of galvanized and painted sheet-steel to core hermetic filter dryer (5) to restrain impurity and moisture
guarantee good resistance to atmospheric agents. Accessibility residuals that could be present in the circuit, high and low
to internal parts is possible removing the lateral panels. For pressure switches in order to assure the compressor to
extraordinary manteinances also the other panels can be operate inside the permitted limits, 4 way reverse cycle valve
removed. (6) to allow operating mode change reversing the refrigerant
Refrigerant circuit. It is contained inside a compartment flow, liquid receiver (7) to compensate the different refrigerant
separated from the air flow to simplify maintenance and control charge required in heating and in cooling mode and pressure
operations. connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket
and blind nut, as required for the use of R410A refrigerant (they
allow the complete check of the refrigerant circuit: compressor
inlet pressure, compressor outlet pressure and expansion valve
upstream pressure). All the pipes of the refrigerant circuit are
properly insulated to avoid condensate generation and minimize
thermal losses
The plug fan (8) is equipped with an high efficiency electronically
commutated (EC) motor and guarantees enough available static
pressure to allow both the outdoor and the indoor installation.
Hydraulic circuit. All the pipes are thermally insulated to avoid
condensate generation and minimize thermal losses. The circuit
can be equipped with a standard, high head or modulating
circulation pump (option). The circuit is always equipped also
with expansion vessel, safety valve and air vents.
Electrical panel. It contains all the power, control and security
components necessary to guarantee the unit to work properly.
The unit is managed by a microprocessor controller to which
all the electrical loads and the control devices are connected.
The user interface, to be placed indoor, allows to view and to
modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor,
to be installed outside, in order to realize the climatic control.

The hermetic scroll compressor (1) is mounted on damper


supports and is protected against overtemperatures and
overcurrents. It is equipped with an electrcal heater, that is
activated when the compressor turns off, to keep the compressor
crankcase oil temperature high enough to prevent migration of
the refrigerant during winter stops and to evaporate any liquid
present in the crankcase, in order to prevent possible liquid
rushes on starting.
The compressor is equipped with vapour and liquid injection
and is placed on an economized refrigerant circuit with plate
heat exchanger and electronic expansion valve dedicated to the
injection. 8
The plant side heat exchanger (2) is a brazed stainless steel 3
plate heat exchanger, properly insulated to avoid condensate
generation and to minimize thermal losses, and protected by a
flow switch that detects whatever water flow lack.
The source side heat exchanger (3) is a finned coil realized 6
with grooved copper pipes and hydrophilic aluminium fins with
waved profile to increase the heat exchange coefficient. A tray
is placed under the coil to collect the condensate generated in 2
heating mode.
4
The expansion device (4), an electronic expansion valve,
allows the unit to adjust itself to the different operating conditions 7
keeping steady the set superheating.

5
1

6
GENERAL FEATURES

Control system

The microprocessor controller is able to manage not only the


unit itself but also all that components of the plant which allow to
realize a complete system.
The main functions of the control system are :
- room temperature control according to the outdoor temperatu-
re (climatic control) 18:28
- domestic hot water production (management of 3 way valve,
storage tank, anti legionella cycles…)
20.5 C
Room temperature
- management of a heating and/or cooling mixed circuit (pump
and 3 way mixing valve)
- management of a heating direct circuit (only pump)
- management of a storage tank for heating and/or cooling
- management of electrical heaters for heating and domestic
hot water (3 steps logic)
- solar panels integration
- room humidity control for cooling with radiant systems
- internal programmer clock (for heating, cooling and domestic
hot water)
- digital input for electrical energy low tariff
- alarm memory management and diagnostic
- compressor and pump operating hour counter
- possibility to manage more units in cascade (maximum 16)

The unit controller is able to manage a lot of different plant so-


Besides the user interface of the unit to be placed indoor, wi- lutions enabling automatically the necessary control algorythms
red or wireless remote thermostats are available which allow to according to the components which have been connected. The
control all the operating parameters of the unit and to acquire management of such components is possible through additional
the temperature in the different zones in order to realize a more expansion modules which communicate with the unit by means
precise and comfortable control. of an internal bus and provide all the inputs and outputs required
to fulfil a complete system.

FS

The controller is able to manage up to two zones in heating For each zone the following parameters can be set :
(one by means of a mixed circuit and the other by means of a - set point
direct circuit) and one zone in cooling (by means of a mixed
- daily or weekly operating time table
circuit).
- climatic control curve
It’s possible to realize more complex plants connecting to the
heat pump controller further expansion modules in order to - room control sensor : it can be in common with the other
extend without limits the number of zones to be managed. zones or independent (in that case it’s necessary to install
an additional room thermostat)

7
GENERAL FEATURES

Options

Allows to recover a part of the available heating power (and otherwise not used
Version VD - Desuperheater version
during cooling operating mode) for the domestic hot water production.

Standard pump Allows the circulation of the water on the plant side.
Plant side
Allows the circulation of the water on the plant side and guarantees a higher
flow rate High head pump
available static head.
management
Allows the circulation of the water on the plant side keeping constant the
Modulating pump
temperature difference between inlet and outlet.
Domestic hot water Allow to divert the hot water produced by the heat pump from the heating circuit
3 way valve
production to the domestic hot water circuit.
Integrate or replace the heating power supplied by the heat pump and are
Integrative electrical heaters
managed by the unit controller with a 3 step logic.

Soft starter Reduces the compressor start current.

The controller flexibility and the big number of options available the type of plant to which the heat pump will be connected, both
allow to get, for each model, a lot of different configurations that for what concerning the heating and cooling circuits, and for
integrate inside the heat pump many components of the plant what concerning the domestic hot water management.
and allow to realize compact and tested installations.
In order to select the right configuration it is necessary to define

Reversible heat pump (IP) without options Opzione "Version" : "Desuperheater version (VD)"

Option “Plant side flow rate management” Option “Integrative electrical heaters”
Pump (standard or high head or modulating)

8
GENERAL FEATURES

Option “Domestic hot water production”


3 way valve
In this configuration the heat pump can
be coupled to a domestic hot water
tank equipped with a coil designed for
a maximum water temperature between
55°C and 60°C.
The anti legionella cycles have to be
performed by means of electrical heaters
placed on the heat pump outlet (see
option “Integrative electrical heaters”) or
directly inside the tank.

9
GENERAL FEATURES

Accessories

Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor
Rubber vibration dampers
and by the fans in their normal operating mode.

Adjustable rubber Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor
vibration dampers and by the fans in their normal operating mode. Their height can be adjusted to fit to the ground unevenness.

Protect th external surface of the finned coil when it is installed on the air suction side) and the fan (when it is
Protection cap
installed on the air expulsion side) and reduce the noise emitted by the unit.
Protect the fan and reduce the noise emitted by the unit. It must be connected to one of the two lateral air flow
Lateral expulsion cap
openings and requires the installation of the accessory “Frontal shutting panel”.

Frontal shutting panel Allow to close the frontal air flow opening when the lateral air flow openings are used.

3 way valve
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
for domestic hot water
Remote thermostat Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order
(wired or wireless) to realize a climatic control.
Remote control Replicates all the control and visualization functionalities of the controller installed on the unit. The on board
(wired or wireless) temperature sensor can be used in order to realize a climatic control.

LPB bus interface Connected to the unit controller, allows to communicate on the LPB bus, required for the cascade management.

Connected to the unit controller, allows to communicate with wireless remote control and wireless outdoor
Wireless transmitter
temperature sensor.
Connected to the communication bus (BSB) of the unit controller, allows to communicate with the wireless remote
BSB wireless transmitter
control and the wireless outdoor temperature sensor.

Wireless repeater Extends wireless operating range.

Wireless adaptor for


Allows to transform the wired outdoor temperature sensor, standard for all the units, in a wireless sensor.
outdoor temperature sensor

Condensate sensor In cooling mode it allows the minimum flow temperature control when condensate generation occurs.

Room hygrostat In cooling mode it allows the minimum flow temperature control according to the room humidity.

Room humidity sensor In cooling mode it allows the minimum flow temperature control according to the room dew point, calculated from
(with or without display) the measured room humidity.
Transformer
It assures the correct power supply for the condensate sensor and for the room humidity sensor.
230V / 24V - 3VA

N.B. For OUTDOOR INSTALLATION is MANDATORY one of the two following solutions :
- installation of the accessory “Protection cap” on the air expulsion side
- installation of the accessories “Lateral expulsion cap” and “Frontal shutting panel”

10
TECHNICAL DATA AND PERFORMANCES

Technical data

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Refrigerant
Type R410A -
Compressor
Type scroll with vapour injection (EVI) -
Quantity 1 n°
Power steps 0 - 100 %
Oil charge 3,4 3,4 3,4 3,4 3,4 kg
Plant side heat exchanger
Type stainless steel brazed plates -
Quantity 1 n°
Water volume 4,18 4,18 4,18 5,14 5,14 l
Source side heat exchanger
Type finned coil -
Quantity 1 n°
Frontal surface 1,10 1,10 1,10 1,43 1,43 m2
Fans
Type plug fan with high efficiency EC motor -
Quantity 1 n°
Diameter 630 630 630 630 630 mm
Maximum rotational speed 680 680 680 1200 1200 rpm
Total installed power 0,54 0,54 0,54 2,80 2,80 kW
Plant side hydraulic circuit
Expansion vessel volume 10 10 10 10 10 l
Safety valve set point 3 bar
Plant pump - standard (option)
Type centrifugal pump -

Quantity 1 n°
Installed power 0,7 0,7 0,7 1,0 1,0 kW
Plant pump - high head (option)
Type centrifugal pump -

Quantity 1 n°
Installed power 1,2 1,2 1,2 1,6 1,6 kW
Plant pump - high efficiency (option)
Type inverter glandless pump -
Quantity 1 n°
Installed power 0,31 0,31 0,31 0,31 0,31 kW
Integrative electrical heaters (option)
Total installed power 18,0 18,0 18,0 18,0 18,0 kW
Power steps 0 - 33 - 66 - 100 %

11
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - VERY HIGH TEMPERATURE plants

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Heating A7W65 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 30,7 36,1 40,5 46,3 53,0 kW
Power input 12,3 14,5 16,2 18,6 21,3 kW
COP 2,50 2,49 2,50 2,49 2,49 -
Water flow rate plant side 2686 3158 3543 4051 4628 l/h
Pressure drops plant side 6 9 11 9 12 kPa
Heating A2W65 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 26,3 31,0 34,7 39,7 45,3 kW
Power input 12,4 14,5 16,2 18,6 21,2 kW
IP
COP 2,12 2,14 2,14 2,13 2,14 -
Water flow rate plant side 2301 2712 3036 3473 3963 l/h
Pressure drops plant side 5 6 8 7 9 kPa
Heating A-7W65 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 23,0 27,1 30,3 34,7 39,6 kW
Power input 12,4 14,6 16,3 18,7 21,3 kW
COP 1,85 1,86 1,86 1,86 1,86 -
Water flow rate plant side 2012 2371 2651 3036 3464 l/h
Pressure drops plant side 4 5 6 5 7 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

12
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - HIGH TEMPERATURE plants

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Heating A7W55 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 30,0 35,3 39,7 45,4 51,7 kW
Power input 9,89 11,6 13,1 15,0 17,1 kW
COP 3,03 3,04 3,03 3,03 3,02 -
Water flow rate plant side 3269 3846 4315 4936 5623 l/h
Pressure drops plant side 9 12 15 14 17 kPa
Heating A2W55 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 25,6 30,1 33,7 38,6 44,1 kW
Power input 9,91 11,6 13,0 14,9 17,1 kW
IP
COP 2,58 2,59 2,59 2,59 2,58 -
Water flow rate plant side 2789 3280 3672 4206 4794 l/h
Pressure drops plant side 7 9 11 10 13 kPa
Heating A-7W55 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 22,1 26,1 29,2 33,4 38,1 kW
Power input 9,94 11,7 13,1 15,0 17,1 kW
COP 2,22 2,23 2,23 2,23 2,23 -
Water flow rate plant side 2408 2844 3182 3639 4152 l/h
Pressure drops plant side 5 7 9 8 10 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

13
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - STANDARD plants

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 29,6 34,8 39,1 44,6 51,0 kW
Power input 8,07 9,54 10,7 12,2 14,0 kW
COP 3,67 3,65 3,65 3,66 3,64 -
Water flow rate plant side 5127 6013 6761 7716 8811 l/h
Pressure drops plant side 22 29 36 32 41 kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 25,1 29,5 33,1 37,8 43,2 kW
Power input 8,06 9,52 10,6 12,2 14,0 kW
COP 3,11 3,10 3,12 3,10 3,09 -
Water flow rate plant side 4345 5109 5735 6552 7473 l/h
Pressure drops plant side 16 21 27 23 30 kPa
IP
Heating A-7W45 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 21,5 25,4 28,4 32,5 37,1 kW
Power input 8,08 9,54 10,7 12,2 13,9 kW
COP 2,66 2,66 2,65 2,66 2,67 -
Water flow rate plant side 3737 4397 4918 5631 6430 l/h
Pressure drops plant side 12 16 20 17 22 kPa
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 22,7 26,6 29,9 34,1 38,9 kW
Power input 7,15 8,42 9,44 10,8 12,4 kW
EER 3,17 3,16 3,17 3,16 3,14 -
Water flow rate plant side 3896 4582 5148 5869 6710 l/h
Pressure drops plant side 13 18 22 19 25 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

14
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - RADIANT plants

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 29,2 34,4 38,6 44,1 50,4 kW
Power input 6,32 7,48 8,40 9,59 11,0 kW
COP 4,62 4,60 4,60 4,60 4,58 -
Water flow rate plant side 5039 5923 6650 7602 8676 l/h
Pressure drops plant side 21 28 35 31 40 kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 24,7 29,0 32,6 37,2 42,5 kW
Power input 6,32 7,46 8,36 9,55 11,0 kW
COP 3,91 3,89 3,90 3,90 3,86 -
Water flow rate plant side 4260 5005 5628 6425 7325 l/h
Pressure drops plant side 15 21 26 22 29 kPa
IP
Heating A-7W35 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 21,0 24,8 27,8 31,7 36,2 kW
Power input 6,34 7,47 8,37 9,57 10,9 kW
COP 3,31 3,32 3,32 3,31 3,32 -
Water flow rate plant side 3637 4277 4797 5472 6252 l/h
Pressure drops plant side 11 15 19 17 21 kPa
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 29,8 35,0 39,3 44,9 51,2 kW
Power input 7,74 9,15 10,2 11,7 13,4 kW
EER 3,85 3,83 3,85 3,84 3,82 -
Water flow rate plant side 5155 6069 6811 7776 8880 l/h
Pressure drops plant side 22 30 37 32 42 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

15
TECHNICAL DATA AND PERFORMANCES

HEATING performances

Heating capacity

1.6 The graphs allow to get the corrective factors to


be applied to the nominal performances in order
to obtain the real performances in the selected
1.4
operating conditions.
A
The reference nominal condition is :
1.2
B A7W35
source : air in 7°C d.b. 6°C w.b.
C plant : water in 30°C out 35°C
1.0
D Outlet temperature
plant side :
0.8 E A = 65°C
B = 55°C
C = 45°C
0.6 D = 35°C
E = 25°C

0.4
-20 -15 -10 -5 0 5 10 15 20 25 30

Inlet air temperature w.b. [°C]

Power input COP

2.2 2.2

2.0 2.0
E
1.8 1.8
D
1.6 1.6

C
1.4 1.4

1.2 1.2 B

1.0 1.0 A
0.8 0.8

0.6 0.6

0.4 A B C D E 0.4

0.2 0.2
-20 -15 -10 -5 0 5 10 15 20 25 30 -20 -15 -10 -5 0 5 10 15 20 25 30

Inlet air temperature w.b. [°C] Inlet air temperature w.b. [°C]

16
TECHNICAL DATA AND PERFORMANCES

COOLING performances

Cooling capacity

2.2 The graphs allow to get the corrective factors to


be applied to the nominal performances in order
2.0 to obtain the real performances in the selected
operating conditions.
1.8
The reference nominal condition is :
1.6 A35W7
source : air in 35°C d.b.
1.4 plant : water in 12°C out 7°C

1.2 Outlet temperature


plant side :
1.0 A = 24°C
B = 18°C
0.8 C = 12°C
A B C D
D = 7°C
0.6

0.4
0 5 10 15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C]

Power input EER

2.2 2.2

2.0 2.0 A

1.8 1.8 B

1.6 1.6 C

1.4 1.4 D
B
1.2 1.2

A
1.0 1.0

0.8 D 0.8

0.6 C 0.6

0.4 0.4
0 5 10 15 20 25 30 35 40 45 50 0 5 10 15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C] Inlet air temperature d.b. [°C]

17
TECHNICAL DATA AND PERFORMANCES

Plant side hydraulic performances

Pressure drops - unit without options

60

50.1
50
45.1

40.1
40
Pressure drops [ kPa ]

35.1

30.1
30

20

10

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

Pressure drops to be added - unit with option “Integrative electrical heaters”

60

50

40
Pressure drops [ kPa ]

30

20

10

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

18
TECHNICAL DATA AND PERFORMANCES

Available static head - unit with option “Plant side flow rate management” : “Standard pump”

240

200
45.1
50.1
Available static head [ kPa ]

160

120

80
30.1
35.1
40.1

40

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

Available static head - unit with option “Plant side flow rate management” : “High head pump”

240

200
Available static head [ kPa ]

160

120
30.1
35.1
40.1
80

45.1
50.1
40

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

19
TECHNICAL DATA AND PERFORMANCES

Available static head - unit with option “Plant side flow rate management” : “Modulating pump”
240

200
Available static head [ kPa ]

30.1
160
35.1
40.1
45.1
120 50.1

80

40

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

20
TECHNICAL DATA AND PERFORMANCES

Source side aeraulic performances

Available static head - unit without accessory “Protection cap” or “Lateral expulsion cap”

90

80

70
30.1
Available static head [ Pa ]

60

50
35.1

40

30 40.1 45.1

20
50.1
10

0
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000

Flow rate [ m /h ]
3

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Maximum static head


available for ducted installation
50 50 50 150 150 U.M.

In case of ducted installation the total pressure drops in the inlet and outlet ducts can not exceed the maximum available static head.
The minimum duct section must guarantee that the medium air velocity does not exceed 2,5 m/s in order to avoid noise problems and to keep
the pressure drops as lower as possible.

The graphs are referred to units operating with air at the temperature of 15°C (density 1,2 kg/m3).

21
TECHNICAL DATA AND PERFORMANCES

Performances DESUPERHEATER

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Cooling A35W7-W45
( source : air in 35°C d.b. / plant : water in 12°C out 7°C / heat recovery : water in 40°C out 45°C )
Cooling capacity 23,5 27,7 31,1 35,5 40,5 kW

Power input 6,94 8,18 9,18 10,5 12,1 kW

EER 3,39 3,39 3,39 3,38 3,35 -

IP Water flow rate plant side 4050 4771 5354 6109 6985 l/h

Pressure drops plant side 14 19 24 21 26 kPa

Heating capacity (desuperheater) 6,97 8,20 9,20 10,5 12,0 kW

EER with heat recovery 4,39 4,39 4,39 4,38 4,34 -

Water flow rate desuperheater side 1211 1425 1599 1825 2086 l/h

Pressure drops desuperheater side 0,7 0,9 1,2 1,5 1,9 kPa

Data declared according to EN 14511. The values are referred to units with the only option "VD - Desuperheater version".

Pressure drops desuperheater - unit "VD - Desuperheater version"

30

25

20
Pressure drops [ kPa ]

15

10

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500

Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

22
TECHNICAL DATA AND PERFORMANCES

Operating limits

The graphs reported below show the operating area inside which the correct working of the unit is guaranteed.

HEATING

75

70
DT = 10 °C
65

60
Outlet temperature - plant side [°C]

55

50

45

40

35

30

25

20

15

10

5
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

Inlet air temperature d.b. [°C]

COOLING

45

40
Outlet temperature - plant side [°C]

35

30

25

20

15

10

-5
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

Inlet air temperature d.b. [°C]

Temperature difference between unit inlet and outlet Plant side


DT max Maximum value 11 °C

DT min Minimum value 3 °C

23
TECHNICAL DATA AND PERFORMANCES

Electrical data

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Unit
Power supply 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 V-ph-Hz
F.L.A. Maximum total current input 22,0 24,5 27,0 34,7 39,2 A
F.L.I. Maximum total power input 13,9 15,5 17,1 21,6 24,5 kW
Maximum total start current 160 171 183 209 243 A
M.I.C. Maximum total start current
94 102 111 131 151 A
with soft starter (option)

Integrative electrical heaters (option)


230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
Power supply V-ph-Hz
400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50
Maximum total current input
78,3 78,3 78,3 78,3 78,3 A
( 230V - 1 - 50Hz )
F.L.A.
Maximum total current input
26,0 26,0 26,0 26,0 26,0 A
( 400V - 3N - 50Hz )
F.L.I. Maximum total power input 18,0 18,0 18,0 18,0 18,0 kW

Plant side pump - standard (option)


Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz
F.L.A. Maximum total current input 3,6 3,6 3,6 5,1 5,1 A
F.L.I. Maximum total power input 0,7 0,7 0,7 1,0 1,0 kW

Plant side pump - high head (option)


Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz
F.L.A. Maximum total current input 6,1 6,1 6,1 8,2 8,2 A
F.L.I. Maximum total power input 1,2 1,2 1,2 1,6 1,6 kW

Plant side pump - modulating (option)


Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz
F.L.A. Maximum total current input 1,6 1,6 1,6 1,6 1,6 A
F.L.I. Maximum total power input 0,31 0,31 0,31 0,31 0,31 kW

24
TECHNICAL DATA AND PERFORMANCES

Noise levels

Unit without accessory “Protection cap” or “Lateral expulsion cap”

Sound pressure level


Sound power levels [dB] Sound power
Model by octave bands [Hz] level at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
30.1 84,7 79,0 73,9 72,8 70,9 68,0 62,2 57,2 86 76 60 50 44
35.1 85,8 80,1 75,0 73,9 72,0 69,1 63,3 58,3 88 77 61 51 45
40.1 85,8 80,1 75,0 73,9 72,0 69,1 63,3 58,3 88 77 61 51 45
45.1 86,8 81,1 76,0 74,9 73,0 70,1 64,3 59,3 89 78 62 52 46
50.1 86,8 81,1 76,0 74,9 73,0 70,1 64,3 59,3 89 78 62 52 46

Reference conditions
Performances referred to units operating in heating mode at nominal conditions A7W35.
Unit placed in free field on reflecting surface (directional factor equal to 2).
The sound power level is measured according to ISO 3744 standard.
The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.

Unit with accessory “Protection cap” on the air suction side


and with accessory “Protecion cap” or “Lateral expulsion cap” on the air expulsion side

Sound pressure level


Sound power levels [dB] Sound power
Model by octave bands [Hz] level at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
30.1 81,2 75,5 70,4 69,3 67,4 64,5 58,7 53,7 83 72 56 46 41
35.1 82,3 76,6 71,5 70,4 68,5 65,6 59,8 54,8 84 73 57 47 42
40.1 82,3 76,6 71,5 70,4 68,5 65,6 59,8 54,8 84 73 57 47 42
45.1 83,3 77,6 72,5 71,4 69,5 66,6 60,8 55,8 85 74 58 48 43
50.1 83,3 77,6 72,5 71,4 69,5 66,6 60,8 55,8 85 74 58 48 43

Reference conditions
Performances referred to units operating in heating mode at nominal conditions A7W35.
Unit placed in free field on reflecting surface (directional factor equal to 2).
The sound power level is measured according to ISO 3744 standard.
The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.

25
TECHNICAL DATA AND PERFORMANCES

Weights

Frame 1 2
Model 30.1 35.1 40.1 45.1 50.1 U.M.

Components weights
Unit without options 364 366 369 428 430 kg
Desuperheater
Version 12 12 12 12 12 kg
version (VD)
Plant side Standard pump 9 9 9 11 11 kg
Options

flow rate High head pump 12 12 12 13 13 kg


management High efficiency pump 6 6 6 7 7 kg
Domestic hot water production :
6 6 6 7 7 kg
3 way valve
Integrative electrical heaters 10 10 10 11 11 kg
Protection cap 19 19 19 23 23 kg
Accessories

Lateral expulsion cap 10 10 10 10 10 kg


Frontal shutting panel 10 10 10 13 13 kg

Transport weights
Unit without options 375 377 380 443 445 kg
Desuperheater
Version 12 12 12 12 12 kg
version (VD)
Plant side Standard pump 9 9 9 11 11 kg
Options

flow rate High head pump 12 12 12 13 13 kg


management High efficiency pump 6 6 6 7 7 kg
Domestic hot water production :
6 6 6 7 7 kg
3 way valve
Integrative electrical heaters 10 10 10 11 11 kg
Protection cap 30 30 30 38 38 kg
Accessories

Protection caps (quantity 2) 49 49 49 61 61 kg


Lateral expulsion cap 21 21 21 25 25 kg
Frontal shutting panel 11 11 11 14 14 kg

Operating weights
Unit without options 369 371 374 438 440 kg
Desuperheater
Version 18 18 18 18 18 kg
version (VD)
Plant side Standard pump 10 10 10 13 13 kg
Options

flow rate High head pump 13 13 13 15 15 kg


management High efficiency pump 7 7 7 8 8 kg
Domestic hot water production :
9 9 9 10 10 kg
3 way valve
Integrative electrical heaters 14 14 14 15 15 kg
Protection cap 19 19 19 23 23 kg
Accessories

Lateral expulsion cap 10 10 10 10 10 kg


Frontal shutting panel 10 10 10 13 13 kg

26
TECHNICAL DATA AND PERFORMANCES

Overall dimensions

Unit with accessory “Protection cap” on the air suction side and on the air expulsion side

2 2
3 5 3
1 4 1

Unit with accessories “Lateral expulsion cap” and “Frontal shutting panel” on the air expulsion side

2 2
3 5 3
1 4 1

Frame 1 Frame 2 Frame 1 Frame 2


1 Plant return 1" 1/4 M 1" 1/4 M A1 1180 mm 1480 mm
2 Plant flow 1" 1/4 M 1" 1/4 M A2 615 mm 615 mm
3 Domestic hot water flow 1" 1/4 M 1" 1/4 M B1 880 mm 880 mm
4 Desuperheater inlet 1" M 1" M B2 465 mm 465 mm
5 Desuperheater outlet 1" M 1" M H 1620 mm 1620 mm

The accessory “Lateral expulsion cap” can be installed both on the left side or the right side of the unit.

27
TECHNICAL DATA AND PERFORMANCES

Minimum operating area

Respect the free area around the unit as shown in figure in order to guarantee a good accessibility and C 600 mm
facilitate maintenance and control operations. D 600 mm
E 700 mm

Configuration 1 Configuration 2

Configuration 3 Configuration 3
(left side) (right side)

Configuration 4 Configuration 4
(left side) (right side)

28
TECHNICAL DATA AND PERFORMANCES

Configuration 5 Configuration 5
(left side) (right side)

Configuration 6 Configuration 6
(left side) (right side)

Accessories used to realize the configurations shown above

Air suction side Air expulsion side


Type of
Configuration
installation “Lateral “Frontal
“Protection cap” “Protection cap”
expulsion cap” shutting panel”