DPWH Building Plans

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

GENERAL CONSTRUCTION NOTES

GENERAL NOTES NOTES ON CONCRETE SLABS

CONF. REINF.
7.0 ACI REFERS TO AMERICAN CONCRETE INSTITUTE, AISC TO AMERICAN INSTITUTE OF JOINT HOOP SPACE @ "2Sh" WHEN THERE
1.0 STANDARD AND REFERENCE STEEL CONSTRUCTION AND ASTM TO AMERICAN SOCIETY FOR TESTING MATERIALS. 1. ALL SLABS REINFORCEMENTS SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM ARE BEAMS HAVING WIDTH OF AT LEAST

D
8.0 CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS THE TOP OF SLAB. ONE-HALF THE COLUMN WIDTH & DEPTS
THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND CONSTRUCTION OTHERWISE SHOWN OR NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET 2. UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINUOUS ELEVATED SLAB SHALL BE NOT LESS THAN THREE QUARTERS OF THE

JOINT REINF.
OF THE PROJECT. SPECIAL CONDITIONS. CUT AS FOLLOWS: DEEPEST BEAM THAT FRAME INTO FOUR
9.0 SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL BENT BAR SIDES OF THE COLUMN. ALL OTHER
1.1 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP), VOL.1, 7TH STEELS, MISCELLANEOUS IRON, PRE-CAST CONCRETE, ETC. SHALL BE SUBMITTED FOR
L1 L2 CONDITIONS USE HOOPS @ "Sh" CENTERS.
EDITION 2015 ENGINEERS APPROVAL BEFORE FABRICATION

CONF. REINF. PER SCHEDULE CONF. REINF.


10.0 CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, STOOLS, L1/4 L1/4 L2/4 BENT BAR

Sh
2.0 DESIGN CRITERIA EQUIPMENTS AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, TOP BAR

D
ELECTRICAL AND MECHANICAL DRAWINGS.
2.1 LOADINGS 11.0 ALL RESULTS OF MATERIAL TESTING FOR CONCRETE, REINFORCING BARS, &
FOR COL. BAR SPLICES SEE TABLE OF

COLUMN TIES AS
A. DEAD LOAD: STRUCTURAL STEEL MUST BE NOTED & APPROVED BY THE STRUCTURAL DESIGNER.
MIN. LAP SPLICE LENGTH OF COLUMN
CONCRETE 24 kN/m
STEEL 76.93 kN/m NOTES ON CONCRETE MIXES & PLACING BOTTOM BAR
REINFORCEMENT (SPACING OF TIES
BOTTOM BAR ALONG THIS REGION SHALL NOT BE
150mm THK. CHB WALL 3.38 kPa 1. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY
EIGHT (28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMPS AS FOLLOWS: LESS THAN 100mm)
100mm THK. CHB WALL 2.38 kPa
3. IF SLABS ARE REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE
B. LIVE LOAD LOCATION 28 DAYS STRENGTH MAX. SIZE OF MAX. SLUMP PLACED BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER THE LONGER
ROOF 1.00 kPa AGGREGATE SPAN FOR REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE

D
OFFICE 2.40 kPa ALL OTHERS, INCLUDING COLUMN STRIPS SHALL BE NOT BE MORE THAN ONE AND A HALF (1-1/2) SLAB THICKNESS.
BALCONY 2.90 kPa SUSPENDED SLAB 3000 PSI (20.7 MPa) 20 mm 100 mm 4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN THE

JOINT REINF.
MULTIPURPOSE AREA / 4.80 kPa TENSION AND SHALL NOT BE LESS THAN 0.0025 X GROSS CROSS-SECTIONAL AREA (Ag) OF THE
CONFERENCE HALL / ROOM COLUMNS 3000 PSI (20.7 MPa) 20 mm 100 mm SLAB. (SEE SCHEDULE BELOW) NOTE:
LOBBY / CORRIDORS 3.80 kPa ALL CONCRETE REINF. DETAIL SHOULD
BEAMS, SLABS 3000 PSI (20.7 MPa) 20 mm 100 mm SCHEDULE OF MINIMUM SLAB REINFORCEMENT BE DONE IN ACCORDANCE WITH THE

CONF. REINF.
C. WIND LOAD (NSCP 2015) THICKNESS MINIMUM TEMPERATURE BARS LATEST EDITION OF ACI DETAILING
BASIC WIND VELOCITY, V = 280 KPH SLAB ON FILL 2500 PSI (17.5 MPa) 20 mm 100 mm MANUAL

D
P = qh [(GCpf) - (GCpi)] (DESIGN WIND PRESSURE) 2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS: 100 mm 10 mmØ @ 250mm EACH WAY
WHERE: qh = VELOCITY PRESSURE, kPa SUSPENDED SLABS _______________________________________ 20mm 125 mm 10 mmØ @ 225mm EACH WAY
GCpf = EXTERNAL PRESSURE COEFFICIENT SLAB ON GRADE _______________________________________ 40mm 150 mm 10 mmØ @ 185mm EACH WAY
GCpi = INTERNAL PRESSURE COEFFICIENT WALLS ABOVE GRADE _______________________________________ 25mm
BEAM STIRRUPS AND COLUMN TIES ___________________________ 40mm 175 mm 10 mmØ @ 150mm EACH WAY TYPICAL COLUMN ELEV. SHOWING
D. SEISMIC LOAD (NSCP 2015) WHERE CONCRETE IS EXPOSED TO 200 mm 10 mmØ @ 140mm EACH WAY DOWELS AND TIES SPACING
EARTH BUT POURED AGAINST FORMS __________________________ 50mm
WHERE CONCRETE IS DEPOSITED 5. UNLESS OTHERWISE NOTED IN THE PLANS, ALL BEDDED SLABS SHALL BE REINFORCED LAP SPLICE LENGTH:
CvI DIRECTLY AGAINST EARTH ____________________________________ 75mm WITH 10mm Ø AT 250mm O.C. EACH WAY TO CENTER OF SLAB AND CONSTRUCTION JOINTS AT ANY LEVEL NO MORE THAN
V= W (DESIGN BASE SHEAR)
RT 3. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, FOR SAME SHALL NOT BE LESS THAN 3.65 METER APART. ALTERNATE BARS SHOULD BE
2.50 CaI 0.80 ZNvl RE-HANDLING OR PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS OR 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB (TWO ADJACENT DISCONTINUOUS SPLICED. MIN. DISTANCE BET.
Vmax = W Vmin = W (ZONE 4)
RT R WHEELBARROWS, NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM EDGES) AS SHOWN BELOW. TWO ADJACENT BARS SPLICES
Vmin = 0.11CaIW HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT 7. CONCRETE SLAB REINFORCEMENTS SHALL BE PROPERLY SUPPORTED WITH 10mm Ø SHALL BE 600mm.
EXCEED SIX (6) METERS IN AGGREGATE LENGTH.

WITHIN CENTER
STEEL CHAIR OR APPROVED EQUIVALENT SPACED AT 1.0 METER ON CENTER BOTHWAYS.

HALF OF "H"
WHERE: W = TOTAL DEAD LOAD 2/3 4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS Ø12 X 1000 LONG AT L/4
T = NATURAL PERIOD = C t (hn) UNLESS AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR UNUSUAL CONDITIONS WHERE DOWN INTO EDGE BEAM. EXTENDED MID-DEPTH OF SLAB AT
WHERE: C = NUMERICAL COEFFICIENT VIBRATIONS ARE EXTREMELY DIFFICULT TO ACCOMPLISH. 4-Ø 12@ 1800 LONG TOP BARS BEND EACH CORNER TOP BARS @ SUPPORT (CONT.)
h = BUILDING HEIGHT 5. ALL ANCHOR BOLTS, DOWELS AND OTHER INSERTS SHALL BE PROPERLY POSITIONED & BARS MIN. OF 1200 (4'-0") INTO BARS. 1-Ø12 TOP & REQ'D. BOTT. BARS @ SUPPORT
SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. BOTT. BARS
I = IMPORTANCE FACTOR = 1.50 6. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN CONSECUTIVE DAY

JT. REINF.
R = NUMERICAL FACTOR = 8.50 IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP, FOG SPRAYING, CURING
SEISMIC COEFFICIENT Ca = 0.44 Nv COMPOUNDS OR OTHER APPROVED METHODS. A

D
Cv = 0.64 Nv 7. STRIPPING OF FORMS AND SHORES:

400
1-Ø12 EA. TOP
FOUNDATION _______________________________________ 24 HRS
& BOT.

0
60
NEAR SOURCE FACTOR (10km) Nv = 2.0 SUSPENDED SLAB EXCEPT WHEN
SPLICE BOTTOM BARS AT MIDSPAN
Na = 1.5 ADDITIONAL LOADS ARE IMPOSED _____________________________ 8 DAYS

0
60
SLAB 38mm
Z = SEISMIC ZONE = 0.40 (ZONE 4) WALLS _____________________________________________________ 21 DAYS OPENING CLEAR EXTRA TOP BARS @ SUPPORT
S = SOIL TYPE = D BEAMS _____________________________________________________ 14 DAYS
COLUMNS __________________________________________________ 21 DAYS 1-Ø12 EA. TYP. DETAIL OF COL. LAP SPLICE &

400
2.2 DESIGN STRESSES 8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE TOP & BOT.

60
A. CONCRETE FOR FOOTING, COLUMNS, EXT. GIRDER TO COL. CONNECT

0
CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE
BEAMS, AND SLAB ON FILL POURING FOR APPROVAL. SECTION "A"
4-Ø12 BOTT. BARS
(COMPRESSIVE STRENGTH @ 28 DAYS) fc' = 20.7MPa (3,000 psi) 9. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS AND SHORINGS UNTIL IN TWO WAY SLAB
B. REINFORCING STEEL BARS EXTEND BARS UP TO NOTES ON BEAMS AND GIRDERS
THE CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH. TYPICAL CORNER SLAB DETAIL
a. FOR BARS 16mmØ AND GREATER fy = 275 MPa (40,000 psi) BEAM SUPPORT 1. UNLESS OTHERWISE NOTED IN PLANS, CAMBER ALL BEAMS AND GIRDERS AT LEAST
b. FOR BARS LESS THAN 16mmØ fy = 230 MPa (33,000 psi)
NOTES ON FOOTINGS OMIT TRIMMER BARS WHERE 6mmØ FOR EVERY 4.50M OF SPAN, EXCEPT CANTILEVERS FOR WHICH THE CAMBER
C. STRUCTURAL STEEL, ASTM-A36 1. FOOTINGS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 96 KPa (2000 psf). OPENING IS FRAMED BY BEAM SHALL BE AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER BUT IN NO
FOR TRUSSES, BRACINGS & STRUTS fy = 248 MPa (36,000 psi) CONTRACTOR SHALL REPORT TO THE ENGINEER, IN WRITING, THE ACTUAL SOIL CONDITIONS CASE LESS THAN 20mm FOR EVERY 3.0M OF FREE SPAN.
UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING
TYPICAL SLAB OPENING DETAIL 2. TYPICAL BARS BENDING AND CUTTING DETAILS SHALL BE AS SHOWN IN FIG. B-1.
D. PURLINS
COLD FORMED LIGHT GAGE SHAPES fy = 248 MPa (36,000 psi) CONCRETE. NOTES ON COLUMNS 3. IF THE BEAM REINFORCING BARS END IN A WALL THE CLEAR DISTANCE FROM THE BAR
E. MASONRY UNIT (CHB) 2. FOOTING SHALL REST AT LEAST 1500mm BELOW NATURAL GRADE LINE UNLESS OTHERWISE 1. PROVIDE EXTRA SETS OF TIES AT 100mm O.C. FOR TIED COLUMN REINFORCEMENT TO THE FARTHER FACE OF THE WALL NOT BE LESS THAN 25mm. EMBEDMENT LENGTH
NON-LOAD BEARING CHB WALLS fm' = 3.45 MPa (500 psi) INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL. ABOVE AND BELOW BEAM-COLUMN CONNECTIONS FOR A DISTANCE FROM FACE OF SHALL BE AS SHOWN IN A TABLE "A" FOR TENSION BARS AND TABLE "B" FOR
F. WELDS - USED E-70xx ELECTRODE 3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENTS SHALL BE 75mm CLEAR FOR CONNECTION EQUAL TO THE GREATER OF THE OVERALL THICKNESS OF COLUMN, 1/6 COMPRESSION BARS UNLESS SPECIFIED IN PLAN. TOP BAR SHALL NOT BE SPLICED
G. STRUCTURAL BOLTS, ASTM-A307 CONCRETE DEPOSITED ON THE GROUND AND 50mm FOR CONCRETE DEPOSITED AGAINST A THE CLEAR HEIGHT OF COLUMN OR 450mm. WITHIN THE COLUMN OR WITHIN A DISTANCE TWICE THE MEMBER DEPTH FROM THE
a. Ft = 96.60 MPa (14,000 psi) FORMWORK. 2. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE FACE OF THE COLUMN. AT LEAST TWO STIRRUPS SHALL BE PROVIDED AT ALL
b. Fv = 69 MPa (10,000 psi) 4. IN CASES WHERE THE SOIL CONDITION IS SUCH THAT THE MINIMUM ALLOWABLE SOIL CAST MONOLITHICALLY WITH THE CORE WITH THE MINIMUM THICKNESS OF 40mm AND SPLICES.
PRESSURE OF 96 KPa (2000 psf) CAN NOT BE ATTAINED AT PRACTICAL DEPTHS, THE USE OF NOT LESS THAN 40 TIMES THE MAXIMUM SIZE OF COARSE AGGREGATE IN MILLIMETERS.
3.0 IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL MICROPILES, BORED PILES, OR DRIVEN PILES, MAY BE ADOPTED IN LIEU OF STANDARD 3. WHERE COLUMNS CHANGE IN SIZE, VERTICAL REINFORCEMENTS SHALL BE OFFSET AT A TOP BARS
GOVERN AND DISTANCES AND SIZES SHALL NOT BE SCALED FOR CONSTRUCTION ISOLATED FOOTINGS. L2 L3
SLOPE OF NOT MORE THAN 1 IN 6 AND EXTRA 10mm TIES AT 100mm SHALL BE PROVIDED
PURPOSES. NOTES ON REINFORCEMENT THRU OUT THE OFFSET REGION. L2 /3 L2 /3 L3 /3 L3 /3
4.0 IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR 1. UNLESS OTHERWISE NOTED IN PLANS, THE YIELD STRENGTH OF REINFORCING BARS 4. UNLESS OTHERWISE INDICATED IN THE PLANS, LAP SPLICES FOR VERTICAL COLUMN
DEPRESSIONS IN FLOOR SLABS, OPENINGS IN THE WALLS AND SLABS, INTERIOR SHALL BE: REINFORCEMENTS SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND
PARTITIONS, LOCATION OF DRAINS, ETC. A. FOOTINGS, FOOTING TIE BEAMS, AND GIRDERS __________fy = 275 MPa (40,000 psi) THE SPLICE LENGTH SHALL NOT BE LESS THAN 40 BAR DIAMETERS. WELDING OR
5.0 IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS, AND ELEVATIONS B. COLUMNS AND SHEAR WALLS _________________________ fy = 275 MPa (40,000 psi) APPROVED BARS ARE WELDED OR MECHANICALLY SPLICED AT ANY LEVEL AND THE L2/5 L2/5 L3/5 L3/6
BETWEEN THE STRUCTURAL PLANS, AND ARCHITECTURAL DRAWINGS, THE C. BEAMS AND GIRDER _________________________________ fy = 275 MPa (40,000 psi) VERTICAL DISTANCES BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS
CONTRACTOR SHALL NOTIFY BOTH THE STRUCTURAL ENGINEER AND THE D. NON - LOAD BEARING WALL PARTITIONS, THAN 600mm. CROSS-TIE BOTTOM BARS
2-Ø 12mm WEB BARS
ARCHITECT.

350mm MAX.
BEDDED SLABS,FLOOR & ROOF SLABS, PARAPETS, SIDE BARS
6.0 ALL CONCRETE WORK SHALL BE DONE IN ACCORDANCE WITH THE ACI 318-95 CATCH BASIN, SIDE WALKS ____________________________ fy = 227.5 MPa (33,000 psi)
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND ALL 2. ALL REINFORCING BARS SIZE 10mm OR LARGER SHALL BE DEFORMED IN ACCORDANCE 10
dM

H
STRUCTURAL STEEL WORK ACCORDING WITH AISC SPECIFICATION (9th EDITION) WITH ASTM A706. BARS SMALLER THAN 10mm MAY BE PLAIN. IN.
IN SO FAR AS THEY DO NOT CONFLICT WITH THE LOCAL BUILDING CODE 3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN
REQUIREMENT. ACCORDANCE W/ TABLE A & TABLE B (TABLE OF LAP SPLICES & ANCHORAGE LENGTH) UNLESS
OTHERWISE SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. B

PROJECT/LOCATION: SHEET CONTENT: PREPARED BY: CHECKED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED BY: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
NATIONAL CAPITAL REGION
IMPROVEMENT / EXTENSION OF SPD
METRO MANILA FIRST ENGINEERING DISTRICT
FIRING RANGE AND CONSTRUCTION S-01
WEST BANK ROAD, MANGGAHAN FLOODWAY
ROSARIO, PASIG CITY OF COVERED PARKING, SOUTHERN
AS INDICATED FAUSTO F. FAUSTO MARY JESSICA S.J. PEREZ ELINO V. CASTRO LAMBERTO C. DE LEON MEDEL F. CHUA
ENGINEER II ENGINEER II CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER 9 13
POLICE DISTRICT
ENGINEER III
GENERAL CONSTRUCTION NOTES
FIG. B-1 REINFORCING CONCRETE LINTEL BEAM IN
4. UNLESS OTHERWISE SPECIFIED ALL WELDING RODS SHALL CONFORM AWS E60
DOWEL TO MATCH ELECTRODES.
TABLE 'A' CONCRETE BLOCK WALLS DOWEL TO MATCH CHB VERT. BARS 5. ALL BOLTS USED UNLESS OTHERWISE SPECIFIED SHALL BE ASTM A307 BOLTS.
TENSION BARS CHB VERT. BARS WHERE NOTES ON EMBEDDED PIPES
LINTELS IN BLOCK WALLS

DOWEL
300 DEPRESSED SLAB

DOWEL
EMBEDMENT LENGTHS AND LAPPED 300 300

400
1. ALL EMBEDDED PIPES FOR UTILITIES, ETC. THAT PASS THRU BEAMS SHALL NOT EXCEED

400
MIN. MIN. MIN. OCCURS
SPLICED IN MILLIMETERS CLEAR TOTAL MIN. HEIGHT OF R E I N F O R C E M E N T 100mm IN DIAMETER OR 13 BEAM DEPTH WHICHEVER IS LESS, UNLESS OTHERWISE
SPAN LENGTH fc' LINTEL (mm) FIN. FLR. LVL FIN. FLR. LVL APPROVED IN WRITING BY THE STRUCTURAL ENGINEER.
BAR SIZE fc' = 20.7 MPa (3000psi) fc' = 27.6 MPa (4000psi) ("L") (L+0.40m) (MPa) BOTTOM TOP STIRRUPS 2. NO PIPES SHALL BE ALLOWED TO PASS THRU BEAM VERTICALLY.

250
250
(DEFORMED) EMBEDMENT LAPPED EMBEDMENT LAPPED 3. NO PIPES SHALL BE EMBEDDED IN COLUMNS.
1.20 m 1.60 m 200 1 - Ø10 1 - Ø10 Ø6mm @ 200mm
10mm Ø 300 300 300 300 3- Ø10 BOTT. BARS 3- Ø10 BOTT. BARS NOTES ON CONSTRUCTION JOINTS IN CONCRETE
1.50 m 1.90 m 14.0 200 1 - Ø10 1 - Ø10 Ø6mm @ 200mm @ 300mm O.C.
12mm Ø 300 300 300 300 @ 300mm O.C. 1. WHERE A CONSTRUCTION JOINT IS TO BE MADE, THE SURFACE OF CONCRETE SHALL BE
1.80 m 2.20 m 200 1 - Ø10 1 - Ø10 Ø6mm @ 200mm 400 400
16mm Ø 300 400 300 400 CLEANED AND ALL LAITANCE AND STANDING WATER REMOVED. SHEAR KEY SHALL BE
2.10 m 2.50 m 250 1 - Ø12 1 - Ø10 Ø6mm @ 200mm
PROVIDED AT THE JOINT.
20mm Ø 400 550 350 500
2.40 m 2.90 m 17.0 250 1 - Ø12 1 - Ø10 Ø6mm @ 200mm TYPICAL CHB FOOTING DETAILS
MAIN REINFORCEMENTS TO BE
25mm Ø 600 800 550 750 (WHERE APPLICABLE)
2.70 m 3.10 m 250 1 - Ø16 1 - Ø12 Ø10mm @ 200mm CONTINUOUS (TOP & BOTT. BARS)
28mm Ø 750 1000 650 850 DOWEL BARS TO WHERE JOINTS IS AT
3.00 m 3.40 m 300 1 - Ø16 1 - Ø12 Ø10mm @ 200mm MATCH VERT.
32mm Ø 950 1300 850 1100 FLR. SLAB OR BEAM POINT OF STRESS,
3.30 m 3.70 m 20.0 300 1 - Ø16 1 - Ø12 Ø10mm @ 200mm BARS MAIN REINFORCEMENTS TO BE

VERIFY DEPRESSION
30 BAR DIA. 30 BAR DIA. PROVIDE SHEAR RODS
NOTE: TOP PLAIN BARS, MULTIPLY VALUE BY 2 3.60 m 4.00 m 300 1 - Ø20 1 - Ø12 Ø10mm @ 200mm WITH ENGINEERS CONTINUOUS (TOP & BOTT. BARS)
(MIN) (MIN)

D = FOR BEAM
t = FOR SLAB
APPROVAL Ø10 x 1000 LONG

DOWEL
TABLE 'B' 12 THK. EXPANSION

400
1. ALL JOINTS AND CELLS 30 BAR DIA. 30 BAR DIA. @ 300 O.C.
COMPRESSION BARS JOINT WITH MASTIC
1-Ø16 VERT. BARS CONTAINING REINFORCING MIN. 50 MIN.

VERIFY ARCHITECTURAL
FILLER
EMBEDMENT LENGTHS AND LAPPED CHB WALL BARS SHALL BE FILLED 40

D/3
FOR SIZE AND SPACING OF WITH CONCRETE GROUT.
SPLICED IN MILLIMETERS

D/3

D
HOR. & VERT. BARS SEE D = FOR BEAM 2. FOR REINFORCEMENTS,

t
D/3
SEE CONSTRUCTION

(DOWEL)
BAR SIZE fc' = 20.7 MPa (3000psi) fc' = 27.6 MPa (4000psi) CONSTRUCTION NOTES. 2t = FOR SLAB SLAB
1-Ø16 VERT. BARS NOTES. BEAM

400
(DEFORMED) EMBEDMENT LAPPED EMBEDMENT LAPPED 30 BAR DIA.
CHB WALL (MIN) TYPICAL SLAB & BEAM
10mm Ø 225 300 200 300
FOR SIZE AND SPACING OF TYPICAL DETAIL FOR BEAM 1 - Ø16 CONT. HOR. CONSTRUCTION JOINT DETAIL

(DOWEL)
12mm Ø 275 300 250 300
BARS FOR FLOOR

400
HOR. & VERT. BARS SEE
16mm Ø 350 400 325 400
CONSTRUCTION NOTES. OR SLAB CHANGE SOFFIT SLAB ONLY
20mm Ø 450 500 475 500 OPENING OR END WALL
38mm
25mm Ø 550 625 550 625 CORNER WALL CLEAR WINDOW
28mm Ø 625 675 625 675 OPENING
CHB WALL R.C. COLUMN OR WALL
32mm Ø 700 775 700 775 1-Ø16 VERT. BARS
TYP. SECTION OF MASONRY
DOWEL BARS TO MATCH
NOTE: TOP PLAIN BARS, MULTIPLY VALUE BY 2 12 THK. EXPANSION CHB HOR. BARS PARTITION REINFORCEMENTS DOOR
12 THK. EXPANSION OPENING
VALUES GIVEN ABOVE CAN ALSO BE USED FOR COLUMNS JOINT WITH MASTIC
JOINT WITH MASTIC NOTE:
4. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USE 25mmØ BAR FILLER NOTES ON CONCRETE WALLS PROVIDE THESE ADDITIONAL BARS FOR ALL OPENINGS
FILLER
SEPARATORS SPACED AT 1.0M ON CENTERS. IN NO CASE SHALL THERE BE LESS 1. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL PLUS BARS (NOT SHOWN) PARALLEL TO SIDE OF
THAN TWO (2) SEPARATORS BETWEEN TWO LAYERS OF BARS. REINFORCEMENT UNLESS OTHERWISE INDICATED IN THE PLANS. OPENING EQUAL TO THE NUMBER OF TERMINATED
(DOWEL)

5. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS OR STEEL SHAPES SHALL BARS AT OPENING
400

BE AS SHOWN IN FIG. B-2 UNLESS SPECIFIED ELSEWHERE. WALL REINFORCEMENT VERTICAL


FOR SIZE AND SPACING OF THICKNESS HORIZONTAL VERTICAL REMARKS SECTION
b HOR. & VERT. BARS SEE 400 SEE ARCHITECTURAL & MECHANICAL PLANS FOR SLAB
(DOWEL) 100mm Ø10mm @ 250mm O.C. Ø10mm @ 300mm O.C. HORIZONTAL BARS AT OPENING LOCATION.
D

SLEEVES FOR CONSTRUCTION NOTES.


t

VERT. BARS
4

CENTERS VERTICAL
1

UTILITY PIPES 125mm Ø10mm @ 200mm O.C. Ø10mm @ 250mm O.C.


TYP. EXTERIOR WINDOW & DOOR OPENING
t OR
t

INTERSECTION R.C. COL. OR WALL BARS STAGGERED OUT HORIZ. BARS


D

MAX. 15D 150mm Ø12mm @ 250mm O.C. Ø12mm @ 300mm O.C.


SEE NOTE INTERSECTION WALL
WEB BARS REINFORCING BARS SHALL HAVE 25mm CLEAR CONCRETE COVER FROM FACE OF WALL NOTES ON STIRRUPS
ht

TYPICAL CONNECTION DETAIL OF MASONRY WALL EXCEPT FOR WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 60mm SHALL BE
1. ALL REINFORCEMENT SHALL BE BENT COLD UNLESS OTHERWISE PERMITTED BY THE
SEE NOTE PROVIDE 3-Ø10 EXTRA 200 200 PROVIDED, AND FOR EXPOSED FACES OF FORMED WALLS WHERE THE MINIMUM SHALL BE
STRUCTURAL ENGINEER.
STIRR. EACH SIDE OF MIN. MIN. 50mm CLEAR.
2. AS SHOWN IN THE DESIGN DRAWINGS OR PERMITTED BY THE STRUCTURAL ENGINEER,
0.025M Ø SLEEVES 2. CARRY VERTICAL BARS AT LEAST 60mm ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES
SEE NOTE FOR SIZE AND SPACING TIES & CLOSE STIRRUPS MUST BE BENT AT 135°.
SEPARATOR WHEN NECESSARY STOP AT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALL
NOTE 1 Ø10 L
TYP. DET. FOR SLEEVES THRU OF HOR. & VERT. BARS, ENDS VERTICAL AND HORIZONTAL BARS SHALL BE SPLICED BY LAPPING A DISTANCE EQUAL

db
20mm CLEAR FOR JOIST STIRRUPS @ SEE CONSTRUCTION
CONCRETE BEAM TO 30 DIAMETERS AND WIRED SECURELY WITH 16 G.I. WIRE PROVIDED THAT SPLICES IN

D db
40mm CLEAR FOR BEAMS 150 O.C.

D + 2db
NOTES

DOWEL
ADJACENT BARS ARE STAGGERED AT LEAST 1.50M.O.C.
AND GIRDERS

400
FIG. B-2 FIG. B-3 3. UNLESS OTHERWISE NOTED IN THE PLANS, ALL OPENINGS IN WALLS 250mm OR THICKER

L
DOWEL BARS TO MATCH

12db
CHB SHALL BE REINFORCED AROUND WITH 2-20mm Ø BARS FOR 225mm, 200mm, 175mm, 150mm,
CHB VERT. BARS
6. WHEN A BEAM CROSSES A GIRDER, REST BEAM ON TOP OF GIRDER BARS, BEAM USE 2-16mmØ. FOR 125mm AND 100mm WALLS, USE 2-12mmØ BARS. ALL WALLS SPANNING 4db or 65mm 90° END HOOKS
REINFORCING BAR SHALL BE SYMMETRICAL ABOUT CENTER LINE WHENEVER POSSIBLE. 2 -Ø 12 TOP BARS SHALL HAVE VERTICAL REINFORCEMENT BENT TO A U-FORM LIKE STIRRUPS AND SPACED
180° END HOOKS D
200

7. GENERALLY NO SPLICES SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING ACCORDING TO THE SCHEDULE UNLESS OTHERWISE NOTED (SEE FIG.1)
STRESSES OCCUR, SPLICES WHERE SO PERMITTED SHALL BE INDICATED IN THE TABLE 'A' OPENING 2 -Ø 12 TOP BARS
AND 'B'. WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125% OF THE SPECIFIED 1-Ø16 VERT
MAIN BAR END HOOKS db
YIELD STRENGTH OF THE BAR. NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION BARS. TYP. SECTION 4-Ø16 VERT. 4-Ø16 VERT. (ALL GRADES)
IS ALLOWED TO BE SPLICED THEREIN. BARS BAR SIZE DIAMETER 180° HOOK 90° HOOK

550
BARS

550
(DEFORMED) (mm) D+2db L L

550
NOTES ON CONCRETE HOLLOW BLOCK WALLS

L
10mm Ø 60 75 125 150
1. UNLESS OTHERWISE SHOWN IN PLANS ALL CONCRETE HOLLOW BLOCKS AND CERAMIC FIN. FLR. LVL.
12mm Ø 75 100 150 200 135° HOOKS
BLOCKS SHALL BE REINFORCED AS SHOWN IN THE SCHEDULE OF CONCRETE HOLLOW TYP. DET. OF LINTEL BEAM AT CHB 550
BLOCKS AND CERAMIC BLOCK REINFORCEMENT. 16mm Ø 95 125 175 250
2. PROVIDE 150mm x 300mm STIFFENER COLUMN REINFORCED WITH 4-12mm WITH 6mmØ
ELEVATION WALL OPENING 550
20mm Ø 115 150 200 300
TIES AT 150mm ON CENTER WHERE CONCRETE HOLLOW BLOCK TERMINATES AND AT TYPICAL CONNECTION DETAIL 25mm Ø 150 200 230 450
EVERY 3.0m LENGTH OF CONCRETE HOLLOW BLOCK WALLS UNLESS NOTED IN SEE CONSTRUCTION
STRUCTURAL PLANS. NOTES FOR CHB WALL OF R.C. WALL AT CORNERS 28mm Ø 240 300 350 550

6d
NOTES ON WELDS

b
FIN. FLR. LVL REINFORCEMENTS (TYP.) 32mm Ø 300 335 450 600 D
SCHEDULE OF CONCRETE HOLLOW BLOCK AND CERAMIC BLOCK REINFORCEMENT 1. USE E70xx ELECTRODES FOR ALL MEMBERS WELDED.
VARIES

2. WELDS SHALL DEVELOP THE FULL STRENGTH OF MEMBERS JOINED UNLESS OTHERWISE
BLOCK
REINFORCEMENT NOTES
SHOWN OR DETAILED IN THE DRAWINGS.
STIRRUPS AND TIE HOOKS
THICKNESS HORIZONTAL VERTICAL A. MINIMUM LAPS AT SPLICE = 0.25M
NAT. GRD. LVL. NOTES ON STRUCTURAL STEEL (ALL GRADES)
B. PROVIDE RIGHT ANGLED DOWEL BARS TO MATCH
CHB VERTICAL BARS 1. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS STRUCTURE BAR SIZE DIAMETER
CONNECTED. 180° HOOK 90° HOOK
REINFORCEMENT AT
75 mm 10mmØ @ EVERY 3RD LEVEL 10mmØ @ 600mm O.C. SHALL COMPLY WITH ALL THE PERTINENT PROVISION OF AISC SPECIFICATION FOR THE (DEFORMED) (mm) D+2db L L
CORNERS 0.92M LONG Ø10 BOTT. BARS @ 90° HOOKS
DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDING LATEST 40 125 85 100
MIN.

C. WHERE CHB OR CER. BLK. 10mm Ø


600

125 mm 10mmØ @ EVERY 3RD LEVEL 10mmØ @ 600mm O.C. 300mm O.C.
WALL DOWELS JOIN COL. R.C. EDITION. 12mm Ø 50 165 115 115 L
2. ALL STRUCTURAL STEEL SHAPES SHALL CONFORM TO ASTM A36 STRUCTURAL STEEL
250

150 mm 10mmØ @ EVERY 3RD LEVEL 10mmØ @ 600mm O.C. BEAMS AND WALL DOWELS 3- Ø10 BOTT. BARS @ L1
UNLESS OTHERWISE INDICATED. 16mm Ø 65 200 140 150
WITH THE SAME SIZE AS VERT. OR 300mm O.C.
HOR. REINFORCEMENTS SHALL BE 3. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE MEMBERS 20mm Ø 115 250 165 300
200 mm 12mmØ @ EVERY 3RD LEVEL 10mmØ @ 600mm O.C.
PROVIDED 400 25mm Ø 150 365 230 405

PROJECT/LOCATION: SHEET CONTENT: PREPARED BY: CHECKED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED BY: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
NATIONAL CAPITAL REGION
IMPROVEMENT / EXTENSION OF SPD
METRO MANILA FIRST ENGINEERING DISTRICT
FIRING RANGE AND CONSTRUCTION S-02
WEST BANK ROAD, MANGGAHAN FLOODWAY
ROSARIO, PASIG CITY OF COVERED PARKING, SOUTHERN
AS INDICATED FAUSTO F. FAUSTO MARY JESSICA S.J. PEREZ ELINO V. CASTRO LAMBERTO C. DE LEON MEDEL F. CHUA
ENGINEER II ENGINEER II CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER 10 13
POLICE DISTRICT
ENGINEER III
1 2 3 4 5 6 7 8 9 10 11

40.00

4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00
L

CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1

FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1
A

WF-1 Y - BARS
X - BARS

W
6.00

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2
CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1
PLAN
12.00

B
FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1
100mm THK CONC. SLAB
ON FILL WITH 10mm Ø
REBARS SPACED AT
17.55

6.00

0.3mm O.C. BOTHWAYS


FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2

FTB-2
FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 FTB-1 NGL
C
CF-1 / C-1 FTB FTB
FTB-1

FTB-1
3.00

CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1 CF-1 / C-1
Y - BARS

D
FTB-1
5.55

X - BARS

WF-1

WF-1
D CF-1 / C-2 CF-1 / C-2
WF-1
2.55

WF-1 WF-1 WF-1 WF-1

T
E 100mm THK
FTB-1 GRAVEL BEDDING

CF-1 / C-2 CF-1 / C-2


FOUNDATION PLAN L

SECTION

10mm Ø CHAIR
BARS AT
300mm Ø O.C.

10mm Ø
0

S C H E D U L E O F F O O T I N G T I E B E A M
0.1

0.35 NOSING BAR


SPACED AS
SHOWN SIZES (mm) REINFORCEMENT BARS
FOOTING SCHEDULE
STIRRUPS SIZE DIMENSIONS REINFORCEMENTS
FLOOR MARK REMARKS THICKNESS DEPTH
0.20

LEVEL BREADTH DEPTH SUPPORT MIDSPAN WEB BARS AND SPACING MARK
WIDTH LENGTH (T) (D) X-BARS Y-BARS
0.40

B D TOP BOTTOM TOP BOTTOM


NGL CF-1 2500mm 2500mm 300mm 1500mm 8 - 16mm Ø 8 - 16mm Ø
100mm THK.
WELL 10mm Ø TEMP. GROUND 10MM - 1@50,
COMPACTED BAR SPACED FLOOR FTB-1 300 500 5 - 20mmØ 3 - 20mmØ 3 - 20mmØ 5 - 20mmØ - 10@100, REST @ -
0.30

GRAVEL FILL AS SHOWN LEVEL 150mm O.C.


10mm Ø MAIN
BARS AT
300mm Ø O.C.
0.10
FOOTING DETAILS
10MM - 1@50,
FTB-2 300 500 5 - 25mmØ 4 - 25mmØ 4 - 25mmØ 5 - 25mmØ - 10@100, REST @ -
STAIRS ON FILL DETAILS 150mm O.C.

PROJECT/LOCATION: SHEET CONTENT: PREPARED BY: CHECKED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED BY: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
NATIONAL CAPITAL REGION
IMPROVEMENT / EXTENSION OF SPD
METRO MANILA FIRST ENGINEERING DISTRICT
FIRING RANGE AND CONSTRUCTION S-03
WEST BANK ROAD, MANGGAHAN FLOODWAY
ROSARIO, PASIG CITY OF COVERED PARKING, SOUTHERN
AS INDICATED FAUSTO F. FAUSTO MARY JESSICA S.J. PEREZ ELINO V. CASTRO LAMBERTO C. DE LEON MEDEL F. CHUA
ENGINEER II ENGINEER II CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER 11 13
POLICE DISTRICT
ENGINEER III
1 2 3 4 5 6 7 8 9 10 11
NGL
10mm Ø VERT. BARS
SPACED AT 600mm O.C.
40.00
150mm THK CHB

VARIES
10mm Ø HORIZ.
BARS SPACED AT
4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 600mm O.C.

B-1 B-1 B-1 B-1 B-1 B-1 B-1 B-1 B-1 B-1
A

0.50
FTB (SEE SCHEDULE)

100 mm THK

0.10
OPEN BELOW
GRAVEL

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW
6.00 S-2 BEDDING

G-1

G-1

G-1

G-2

G-2

G-2

G-2

G-2

G-2

G-1

G-1
B-1

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-4
S-2 S-2 S-1 S-2

DETAIL OF WALL ON FTB


12.00

B
B-2 B-2 B-2 B-2 B-2 B-2 B-2 B-2 B-2 B-2
150mm THK. CHB
(ALL CELLS ARE
FILLED W/ MORTAR) 10mm Ø VERT.

OPEN BELOW
OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW

OPEN BELOW
10mm Ø HOR. BARS AT
17.55

600mm O.C.
6.00

BARS AT
S-2 S-2 S-2 S-1 S-2 12mm Ø TRANSVERSE
G-1

G-1

G-1

G-2

G-2

G-2

G-2

G-2

G-2

G-1

G-1
B-1

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-5

B-4
600mm O.C.
BARS SPACED AT
400mm O.C.
FFL

0.10

0.10
0.15
3 - 12mmØ
C 0.15 0.50 0.15 LONGITUDINAL BARS
B-1 B-1 B-1 B-1 B-1 B-1 B-1 B-1 B-1 B-1 EQUALLY SPACED
3.00

WF-1 SECTION
B-3

B-3

S-2 S-1
5.55

WALL FOOTING DETAILS


D
B-3 B-3
ROOF DECK FRAMING PLAN
2.55

B-3

B-3

S-2

E
B-3

LAP SPLICES ARE ALLOWED LAP SPLICES ARE ALLOWED


ONLY IN THIS PORTION ONLY IN THIS PORTION
L2 L2
L1
L2/3 L2/3 L2/3 L2/3
2D 2D 2D 2D 2D TOP BAR TOP BAR
D

BOTTOM BAR
BOTTOM
L2/5 L2/5 L3/5 L3/6 BAR
2-12mmØ WEB BARS BOTTOM BARS WEB BARS
TOP BARS

TYPICAL BEAM ELEVATION TYPICAL SLAB ELEVATION

PROJECT/LOCATION: SHEET CONTENT: PREPARED BY: CHECKED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED BY: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
NATIONAL CAPITAL REGION
IMPROVEMENT / EXTENSION OF SPD
METRO MANILA FIRST ENGINEERING DISTRICT
FIRING RANGE AND CONSTRUCTION S-04
WEST BANK ROAD, MANGGAHAN FLOODWAY
ROSARIO, PASIG CITY OF COVERED PARKING, SOUTHERN
AS INDICATED FAUSTO F. FAUSTO MARY JESSICA S.J. PEREZ ELINO V. CASTRO LAMBERTO C. DE LEON MEDEL F. CHUA
ENGINEER II ENGINEER II CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER 12 13
POLICE DISTRICT
ENGINEER III
SCHEDULE OF BEAMS AND GIRDERS S C H E D U L E O F C O L U M N S
SIZES (mm) REINFORCEMENT BARS
FLOOR STIRRUPS SIZE FLR DECK TO PARAPET WALL
MARK BREADTH DEPTH SUPPORT MIDSPAN WEB BARS REMARKS MARK FOOTING TO GROUND FLR LEVEL GROUND TO FLR DECK LEVEL
LEVEL AND SPACING LEVEL
B D TOP BOTTOM TOP BOTTOM

500 500 500


FLOOR 10MM - 1@50,
DECK B-1 300 450 3 - 25mmØ 4 - 16mmØ 4 - 16mmØ 3 - 25mmØ 10@100, REST @ -
LEVEL 150mm O.C.

500

500

500
C-1
10MM - 1@50,
B-2 300 450 4 - 25mmØ 4 - 16mmØ 4 - 16mmØ 4 - 25mmØ 10@100, REST @ -
150mm O.C.
12-25mmØ VERT. BARS 12-25mmØ VERT. BARS 12-25mmØ VERT. BARS
W/ 10mm Ø TIES 1@50, W/ 10mm Ø TIES 1@50, W/ 10mm Ø TIES 1@50,
5@100mm, REST @ 5@100mm, REST @ 5@100mm, REST @
10MM - 1@50,
B-3 250 400 3 - 16mmØ 2 - 16mmØ 2 - 16mmØ 3 - 16mmØ - 200mm O.C. 200mm O.C. 200mm O.C.
10@100, REST @
(3 TIES/ SET) (3 TIES/ SET) (3 TIES/ SET)
150mm O.C.

400 400
10MM - 1@50,
B-4 300 450 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ 10@100, REST @ -
150mm O.C.

400

400
10MM - 1@50, C-2
B-5 550 550 4 - 16mmØ 4 - 16mmØ 4 - 16mmØ 4 - 16mmØ 10@100, REST @ -
150mm O.C.

12-20mmØ VERT. BARS 12-20mmØ VERT. BARS


W/ 10mm Ø TIES 1@50, W/ 10mm Ø TIES 1@50,
10MM - 1@50,
G-1 300 450 4 - 25mmØ 3 - 25mmØ 3 - 25mmØ 4 - 25mmØ 2 - 16mmØ - 5@100mm, REST @ 5@100mm, REST @
10@100, REST @
200mm O.C. 200mm O.C.
150mm O.C.
(3 TIES/ SET) (3 TIES/ SET)

10MM - 1@50,
G-2 500 500 5 - 20mmØ 4 - 20mmØ 4 - 20mmØ 5 - 20mmØ 2 - 16mmØ 10@100, REST @ -
150mm O.C.

PARAPET 10MM - 1@50,


WALL PB-1 300 450 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ 3 - 16mmØ 2 - 16mmØ 10@100, REST @ -
LEVEL 150mm O.C.

10MM - 1@50,
PB-2 300 450 4 - 16mmØ 3 - 16mmØ 3 - 16mmØ 4 - 16mmØ 2 - 16mmØ 10@100, REST @ -
150mm O.C.

S C H E D U L E O F S L A B S
REINFORCING BARS
MARK THICKNESS REMARKS
PARALLEL TO LONG SPAN PARALLEL TO SHORT SPAN

10mm Ø TEMPERATURE 10mm Ø @ 150mm O.C. ONE-WAY


S-1 125mm + FIN. BARS @ 150mm O.C. BENT-UP 2 OUT OF 3 @ L/4
FROM FACE OF SUPPORT

12mm Ø @ 130mm O.C. 10mm Ø @ 130mm O.C. TWO-WAY


S-2 125mm + FIN. BENT-UP 2 OUT OF 3 @ L/4 BENT-UP 2 OUT OF 3 @ L/4
FROM FACE OF SUPPORT FROM FACE OF SUPPORT

PROJECT/LOCATION: SHEET CONTENT: PREPARED BY: CHECKED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED BY: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
NATIONAL CAPITAL REGION
IMPROVEMENT / EXTENSION OF SPD
METRO MANILA FIRST ENGINEERING DISTRICT
FIRING RANGE AND CONSTRUCTION S-05
WEST BANK ROAD, MANGGAHAN FLOODWAY
ROSARIO, PASIG CITY OF COVERED PARKING, SOUTHERN
AS INDICATED FAUSTO F. FAUSTO MARY JESSICA S.J. PEREZ ELINO V. CASTRO LAMBERTO C. DE LEON MEDEL F. CHUA
ENGINEER II ENGINEER II CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER 13 13
POLICE DISTRICT
ENGINEER III

You might also like