Professional Documents
Culture Documents
7 Decentralized Load Sharing in A Low-Voltage Direct Current Microgrid With An Adaptive Droop Approach Based On A Superimposed Frequency
7 Decentralized Load Sharing in A Low-Voltage Direct Current Microgrid With An Adaptive Droop Approach Based On A Superimposed Frequency
7 Decentralized Load Sharing in A Low-Voltage Direct Current Microgrid With An Adaptive Droop Approach Based On A Superimposed Frequency
Abstract— Conventional droop methods for load sharing To control and operate dc-based power grids, a suitable
control in low-voltage direct current microgrids suffer from poor power management system is required. A hierarchical load
power sharing and voltage regulation, especially in the case sharing control system has been presented in three levels,
when operating many dc sources with long feeders. Hence, the
communication-based approaches are employed to improve the including primary, secondary, and tertiary controllers [4]–[11].
load sharing accuracy and voltage regulation. To avoid using Tertiary controller is in charge of optimal power flow control in
such an infrastructure and the corresponding effects on the microgrids, which in most cases should be implemented by a
reliability and stability, an adaptive droop controller based on a low-bandwidth communication network. Secondary controller
superimposed frequency is proposed in this paper. Load sharing also requires a communication network to regulate the voltage
accuracy is improved by adapting the droop gains utilizing an
introduced ac power. The secondary controller locally estimates of the system within an acceptable region. Primary controller
and compensates the voltage drop due to the droop controller. locally carries out resilient load sharing among different
The proposed power sharing approach can properly control the sources, generally by utilizing a virtual resistor as a droop
load sharing and voltage regulation without utilizing any extra controller.
communication system. The effectiveness of the proposed control A simple droop method is employed to properly control the
system is verified by simulations and experimental tests.
load sharing among dc converters. In this approach, the line
Index Terms— Adaptive droop control, dc microgrid, droop resistances are usually neglected, and the dc bus voltage is
method, frequency injection, power sharing. the same for all the converters [9], [12]–[14]. Therefore, with
I. I NTRODUCTION a small virtual resistor, an appropriate load sharing can be
achieved. However, considering the line resistance effect, large
T HE concept of microgrid technology has been introduced
in the last decade in order to improve the power system
stability, reliability, and efficiency as well as to decrease
virtual resistors should be utilized to carry out the appropriate
load sharing. Large virtual resistors cause large voltage drop
the losses and operational costs. Although most studies have within the grid, which in most cases are compensated by
focused on ac microgrid, dc microgrid is becoming more employing a secondary control layer reinforced by a commu-
popular due to its major advantages over the ac power nication network. Point-to-point communication [8], [15] and
system [1]–[3]. Most of the energy units including renewable sparse communication among converters [4], [6] are employed
energies and storages are commonly dc or have a dc coupling to reach the power management objectives, including pro-
in their conversion stage. Also, electronic and power electronic portional load sharing and acceptable voltage regulation.
loads can be operated by dc power. Meanwhile, eliminating However, the communication network may affect the stability
the power conversion stages in full converter-based sources and reliability of the system [4], especially in the case of
and variable speed drives will further reduce the expenses. operating many sources along long feeders.
Moreover, nonlinear and reactive loads do not exist in Although less common, independence of communication
dc systems, which in ac systems introduce power loss, lifetime is possible, as demonstrated in [16], where a load-sharing
reduction, and so on, over the transformers, capacitors, and approach based on frequency encoding of output current of
other equipment. Therefore, integrating dc sources, storages, converters has been introduced. Another technique, named as
and loads into a dc microgrid will enhance the overall perfor- power talk, has also been presented in [17], where sources
mance of the system compared with the ac microgrid. in the dc microgrid “talk” to each other by modulating their
respective power levels without employing external commu-
Manuscript received June 24, 2016; revised September 21, 2016, nication system. The approach is, however, prone to line,
October 29, 2016, and January 22, 2017; accepted February 19, 2017. Date
of publication February 23, 2017; date of current version July 31, 2017. load, and other grid parameter changes, which, in practice, are
Recommended for publication by Associate Editor Q.-C. Zhong. unpredictable. Another frequency-based control approach is
S. Peyghami and H. Mokhtari are with the Department of Electrical presented in [18] for energy management purpose in dc micro-
Engineering, Sharif University of Technology, 1458889694, Tehran, Iran (e-
mail: saeed_peyghami@ee.sharif.edu; mokhtari@sharif.edu). grids without utilizing a communication network. However,
F. Blaabjerg is with the Department of Energy Technology, Aalborg Uni- the expandability of the system is limited due to the additional
versity, DK-9220 Aalborg East, Denmark (e-mail: fbl@et.aau.dk). currents required by the converters to sustain a certain ac
Color versions of one or more of the figures in this paper are available
online at http://ieeexplore.ieee.org. signal. Moreover, this approach is only suitable for energy
Digital Object Identifier 10.1109/JESTPE.2017.2674300 management level, which requires slow dynamic response,
2168-6777 © 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
1206 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 5, NO. 3, SEPTEMBER 2017
Cdc Line 1
Vin1 S1 Vo1 VPCC
Converter 2 Io2 X2 R2
Line 2
Vin2 Cdc Vo2
S2
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
PEYGHAMI et al.: DECENTRALIZED LOAD SHARING IN A LV DIRECT CURRENT MICROGRID 1207
Fig. 4. Block diagram of the proposed control system. (a) Adaptive controller.
(b) Conventional droop controller.
The output of the central controller, as a restoration term δv,k is A. AC Signal Generator
sent to all of the units to shift up their droop characteristics as
To ensure appropriate load sharing between converters,
shown in Fig. 3(b). To implement the central voltage regulator,
a small ac voltage is superimposed onto the output dc voltage
a communication network is required between the central
by each converter. The frequency of the injected ac voltage is
controller and converters, which affects the reliability and
proportional to the output dc current of the converter, which
stability. To improve the overall reliability and stability, some
can be defined as
decentralized approaches are represented [6], [24]. In these
approaches, sparse communication among the neighboring fk = f ∗ − dfk i ok (3)
converters is employed, and a dynamic consensus protocol-
based control algorithm guarantees the voltage regulation in where f ∗ and fk are the rated and injected frequency, i ok
the microgrid. is the output current, dfk is the frequency droop gain, and k
However, load sharing cannot be accurately performed by denotes the kth converter. The injected frequency should be
increasing the droop gains, and stability issues may occur smaller than the bandwidth of the inner voltage controller to
using higher droop gains. Therefore, some average current reg- be properly generated by the converter.
ulators and circular chain controllers are presented in [25]–[29] The injected ac voltage causes ac current flow in the
to increase the sharing accuracy. In fact, these methods regu- microgrid, which is proportional to the phase angle (θk ) of
late the per unit output current of the converters by adapting the ac voltages as well as the line impedances. According to
the slope of the droop characteristics as shown in Fig. 3(b), Fig. 4(a), the phase angle of the ac voltage of the kth converter
where δr,k is the output of the average current regulator. can be found as
t
This correction term adjusts the droop slope, such that the
θk (t) = 2π f k dτ . (4)
appropriate load sharing is achieved. τ =0
Both voltage and current regulators in secondary layer Considering the same ac voltage magnitude denoted as A, and
require communication of the current and voltage information the load impedance is higher than the line impedances, the
among the converters. To avoid such an infrastructure and ac current flowing between the converters i o1 and i o2 can be
its accompanied complications as well as to improve the calculated as
reliability and stability of the system, in Section III, a proposed
A θ1 − A θ2
load sharing approach without a communication network is i o1 ≈ = − i o2 . (5)
presented. R1 + R2 + j (X 1 + X 2 )
If the injected frequency is low enough, the line reactance can
III. P ROPOSED L OAD S HARING A PPROACH
be neglected [30]. Therefore, the ac current can be found as
The proposed control system based on a superimposed
A θ1 − A θ2
frequency is shown in Fig. 4, including conventional droop i o1 ≈ = −
i o2 . (6)
controller, an ac signal generator, adaptive droop controller, R1 + R2
and a secondary controller. Conventional droop control is According to (6), the ac currents contain the information of
discussed in Section VI. AC signal generator superimposes voltage phases as well as line resistances. On the other hand,
a small ac voltage onto the dc voltage to be modulated by the phase angles are proportional to the output currents of the
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
1208 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 5, NO. 3, SEPTEMBER 2017
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
PEYGHAMI et al.: DECENTRALIZED LOAD SHARING IN A LV DIRECT CURRENT MICROGRID 1209
to (16), the internal voltage of both converters is the same. According to (8), the small variation of the ac reactive power
Therefore, it can be estimated and regulated by the secondary can be calculated as
regulator to compensate the voltage drop due to the droop
gains. By measuring the output voltage (v ok ) and calculating Q 1 = −Q 2 = kδ (θ1 − θ2 )
the adaptive correction term (δr,k ), the internal voltage (E k ) A2
kδ = . (22)
can be found as 2(R1 + R2 )
E k = v ok + δr,k . (17) Considering the relative angle of the injected voltage (θ =
θ1 − θ2 ) as a state variable, the linear form of (3) and (4) can
Therefore, the secondary correction term (δv,k ) can be be defined as
generated by a PI controller (G sec (s)) to regulate the internal 2π
voltage at the reference value as θ = (θ1 − θ2 ) = (d f 2 i o2 − d f 1 i o1). (23)
s
δv,k = (V ∗ − E k )G sec (s). (18) Furthermore, based on the equivalent electric circuit of the
According to Fig. 4, the reference voltage of the kth system shown in Fig. 5, the small signal model of the output
converter can be calculated as voltage can be calculated as
∗
v ok = V ∗ + δv,k − δr,k − Rdk i ok . (19) v o1 = (R1 + Rl )i o1 + R2 i o2
(24)
v o2 = R1 i o1 + (R2 + Rl )i o2
Considering the fast dynamics for the internal voltage and
current loops in comparison to the secondary layer, the output where Rl is the load resistance. Combining (21) to (24), the
voltage of the converter can properly track the reference value, characteristic equation (s) of the system can be calculated
and hence as
∗ 1
v ok = v ok = V ∗ − Rdk i ok − dq G(s)Q k . (20) 2π G(s)dq kδ
1 + G sec (s) (s) = 1 + df
s ρ1 ρ2 − Rl2
As it can be seen in (20), the conventional droop resistor × (ξρ1 + ρ2 + Rl (ξ + 1)) (25)
effect will be canceled at the steady state by the secondary
PI regulator (G sec (s)), since the term 1/(1 + G sec (s)) in (20) where
is very small at low frequencies. Therefore, the voltage drop ⎧
⎪ Rd1
on the droop resistor can be compensated by the decentralized ⎨ρ1 = R1 + Rl +
G sec (s)
(26)
secondary regulator employing the local voltage and current ⎪
⎩ρ2 = R2 + Rl + Rd2 .
information. G sec (s)
In the presence of converter based loads, the input capacitor
The dominant closed loop pole places of the system shown
of the converter consumes a reactive power, which is very
in Fig. 1 can be obtained by (25), and they are shown in Fig. 6.
small due to the low ac voltage and frequency. This reactive
The effects of the frequency droop gain (d f ), voltage coupling
power needs to be supplied by one or more sources, and hence,
gain (dq ), and conventional droop gain (Rd ) on the closed
the rdk value in (15) is not equal for the source converters.
loop pole places are shown in Fig. 6(a)–(c), respectively. The
Since the reactive power consumption by the load capacitors
blue graph shows the poles of the system with equal converter
is small, it cannot affect the voltage regulation unlike the
ratings (ξ = 1) and the red one is related to the unequal
conventional droop approaches. However, in the case of very
converter ratings (ξ = 2). The designed control parameters
large dc capacitors of loads, the performance of the control
are given in Table I, and shown by “X” in Fig. 6. The effect
system may be limited. In this case, the control system may
of load variation on the closed loop poles with the designed
be redesigned to reduce the effect of capacitors’ reactive power
control parameters is shown in Fig. 6(d), where the load is
consumption on the voltage regulation by reducing the injected
varying from 0.1 to 10 kW. As it can be seen, the system still
frequency, and/or reducing the voltage-power coupling gain
remains stable at a wide range of load variation, and dominant
and increasing the virtual resistor to have an appropriate
poles are not extremely affected by the load variation.
dynamic response as well as small voltage regulation error.
Furthermore, the effect of injected ac voltage on the converter- IV. S IMULATION R ESULTS
based constant power loads behavior is explained in the
In order to demonstrate the performance of the proposed
Appendix.
control system, a simplified dc microgrid with two converters,
like the one shown in Fig. 1, is considered. Without losing
D. Dynamic Stability the generality, conventional boost topologies are considered.
In order to ensure the stability of the control system as The control parameters and converter specifications are given
well as to design the control system parameters, a small signal in Table I. Meanwhile, since the bandwidth of the voltage
model of the system is established. Considering (x) as a controller is 900 Hz, the injected frequency is considered as
small variation of variable x, the linear form of (20) can be 50 Hz to be properly generated by the converters.
obtained as The effectiveness of the power sharing approach is verified
1 with three case studies. In Case I, equal converter ratings are
v ok = − Rdk i ok − dq G(s)Q k . (21)
1 + G sec (s) considered, and in Case II, the rating of the second converter
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
1210 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 5, NO. 3, SEPTEMBER 2017
Fig. 6. Closed loop dominant place of system poles (λi denotes ith pole).
(a) Effect of frequency droop gain—dq = 25, Rd = 5, and Pload = 2 kW.
(b) Effect of voltage-power coupling gain—d f = 0.3, Rd = 5, and
Pload = 2 kW. (c) Effect of conventional droop gain—dq = 25 and
Pload = 2 kW. (d) Effect of load variation—d f = 0.3, Rd = 5, and d p = 25 Fig. 7. Simulation results of Case I (see Table I) with the equal converter
(blue: ξ = 1 and red ξ = 2). Desired pole places for λ1 and λ2 are depicted ratings. (a) Output current of first and second converters. (b) Output voltage
by X, for Rd = 5, d f = 0.3, Pload = 2 kW, dq = 25, and ξ = 1, 2. of first and second converters, and (c) Injected frequency.
TABLE I
S PECIFICATIONS OF THE DC M ICROGRID AND C ONTROL
S YSTEM ω∗ = 2π f ∗
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
PEYGHAMI et al.: DECENTRALIZED LOAD SHARING IN A LV DIRECT CURRENT MICROGRID 1211
Fig. 11. Photograph of the implemented hardware setup based on two boost
converters Pload = 1.2 + 0.5 kW.
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
1212 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 5, NO. 3, SEPTEMBER 2017
Fig. 17. Experimental results of (a) frequency droop control in [22] and
(b) adaptive droop approach—In,1 = In,2 , d f 1 = d f 2 = 0.3, dq = 25,
Rd1 = Rd2 = 5 , R1 = 0 , R2 = 1.5 , and V ∗ = 400 V.
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
PEYGHAMI et al.: DECENTRALIZED LOAD SHARING IN A LV DIRECT CURRENT MICROGRID 1213
Fig. 19. Dynamic model and control block diagram of a dc/dc converter
with voltage and current regulators. Fig. 20. Input to output transfer function (Vout / Vin ) of a dc/dc buck
converter—L dc = 2 mH, Cdc = 500 μF, Pout = 2 kW, Vin = 400 V,
Vout = 200 V, G v (s) = 5 + 20/s, and G i (s) = 0.1 + 1/s.
introduced in [22]. Power sharing between the two con-
verters employing the frequency droop controller is shown
in Fig. 17(a). As it can be seen in Fig. 17(a), the output
currents of converters do not converge and the system is
unstable. However, applying the adaptive frequency droop
approach merged by the virtual resistor can properly control
the power sharing between the two converters as shown
in Fig. 17(b).
Finally, the synchronization procedure is shown in Fig. 18,
where the second converter is initially turned ON, and at t =
0.1 s, the first converter is connected. At t = 0.12 s, the
phase-locked loop of the first converter extracts the phase of
Fig. 21. Input to output transfer function (Vout / Vin ) of a dc/dc boost
ac voltage and the second converter, and injects the ac voltage. converter—L dc = 2 mH, Cdc = 500 μF, Pout = 2 kW, Vin = 400 V,
Therefore, both converters are properly synchronized and the Vout = 550 V, G v (s) = 2 + 20/s, and G i (s) = 0.05 + 1/s.
currents are shared between the converters.
regulators, where G v (s) and G i (s) are the voltage and current
VI. C ONCLUSION controllers, and G vg (s), G vd (s), G id (s), and G ig (s) are the
In this paper, an adaptive droop controller is presented for input to output, control to output, input to inductor current,
the primary and secondary power sharing in LV direct current and control to inductor current transfer functions [37]. The
microgrids based on a superimposed frequency. Both the transfer functions modeling the converter dynamic behavior
primary and secondary layers fulfill the power sharing objec- are presented in [37].
tives by utilizing the local voltage, current, and superimposed In order to show the effect of the ac ripple superimposed
frequency information without employing an extra commu- to the input voltage, the closed loop transfer function from
nication network, which implies a higher reliability compared the input to output voltage (or inductor current) should be
with the communication-based power sharing approaches. The analyzed. From Fig. 19, the closed loop input voltage (Vin ) to
output current of the converters is accurately proportional to output voltage (Vout ) transfer function (H (s)) can be calculated
the rated current of converters, and output voltage of converters as
is regulated close to the reference value. The small signal G ig G i
model of the suggested control system for a simplified dc Vout (1+G i G id )G vd + G vg
H (s) = =
microgrid is obtained and its stability is analyzed in order to Vin 1 + TL
design the control parameters. The viability of the proposed
TL = G v G i G vd /(1 + G i G id ). (27)
control approach is ensured for equal and unequal converter
ratings and different line impedances as well as for resistive
According to [37], the loop transfer function TL (s) causes
and constant power loads. The proposed approach is verified
small gains at low frequencies. Therefore, the effect of input
by simulations and experimental tests.
voltage ripple on the system dynamics will be rejected by the
closed loop control system. For instance, H (s) is shown in
A PPENDIX frequency domain for a conventional buck and boost converters
E FFECT OF S UPERIMPOSED AC VOLTAGE ON DC L OADS in Figs. 20 and 21, respectively. The amplitude of H (s) is
In this section, the effect of the superimposed ac voltage very small at low frequencies, and for example, at 50 Hz,
on dc loads is studied by employing the dynamic model of it is −35 dB for buck and −24 dB for boost converter.
loads. Modeling different types of loads is out of the scope Therefore, at low frequencies, the effect of input voltage ripple
of this paper; hence, the most common loads of a dc grid, and disturbances can be rejected by the closed loop control
i.e., constant power loads (converter-based), are considered system. Moreover, the superimposed ac voltage in this paper
in this section. The dynamic model of a dc/dc converter is very small, i.e., 2.5 V, and it cannot affect the load dynamic
can be shown in Fig. 19 with double voltage and current behavior.
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
1214 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 5, NO. 3, SEPTEMBER 2017
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.
PEYGHAMI et al.: DECENTRALIZED LOAD SHARING IN A LV DIRECT CURRENT MICROGRID 1215
Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on October 31,2020 at 16:30:27 UTC from IEEE Xplore. Restrictions apply.