Multilin GPM-S: 100% Stator Ground Protection Module
Multilin GPM-S: 100% Stator Ground Protection Module
Applications
• Medium to large generator applications
• Generators with high impedance grounding
• Deployable with redundant generator protection systems
• Suitable for unit transformer connected systems
GPM-S 100% Stator Ground Protection Module
Protection & Control G60 Generator Protection System G60 Generator Protection Integration
The G60 Generator Protection System provides
Stator Ground Protection Module:
comprehensive protection for medium and
Stator ground module works in combination with large generators, including large steam
UR G60 to provide a 100% stator ground fault and combustion turbines, combined-cycle
protection that is operational during generator generators and multi-circuit hydro units.
start-up, running and stopped conditions. In The G60 includes advanced automation and
the 100% stator ground fault protection based communication capabilities, extensive I/O
on sub-harmonic injection, a 20Hz voltage is options, and powerful fault recording features
injected to detect ground faults at any point that can simplify postmortem disturbance • The G60, GPM-S, and GPM-F modules provide
across 100% of the winding thereby protecting analysis and help minimize generator downtime. complete generator protection
the complete stator winding and allowing early • GPM-S & GPM-F Protection units are
20Hz Injection Module connected directly to the G60 relay
detection of stator ground fault conditions.
• All configuration and monitoring is performed
Key components of the ground protection Using sub-harmonic injection provides early through the G60
scheme: detection of stator ground fault conditions.
This is accomplished by the injection module
• G60 Generator Protection System
generating a square wave pulse of 20Hz with
Coupling filter
• 20Hz Injection Module: GPM-S-G a magnitude of +/-26V into the stator winding. The coupling filter is used to meet two functions:
• Coupling Filter: GPM-S-B The injection module monitors the frequency to smooth the square wave and convert it into
and magnitude of the signal it generates, which a sine wave and to protect the injection module
• CT: ITI Part # 204-SD-43737
allows for the Stator module to determine if a from AC voltage impressed from the secondary
• Sensitive ground CT/VT module in G60 ground fault has occurred in the stator winding. of neutral grounding transformer. Coupling
In addition, the stator module is also equipped filter contains only passive components. It also
with a critical-fail relay that can be wired to contains voltage divider circuits to be used on
alarm failure. applications with NGT secondary voltage greater
than 500V.
Stator Module
CT
Neutral Grounding Transformer
2 GEDigitalEnergy.com
GPM-S 100% Stator Ground Protection Module
DEVICE
FUNCTION
NUMBER
Close 21P Phase Distance Backup
52
Trip 25 24 Volts Per Hertz
25 Synchronism Check
24 27P 59P 59_2 59N 81O 81U 81R
27P Phase Undervoltage
27TN Third Harmonic Neutral Undervoltage
27X Auxiliary Undervoltage
32 Sensitive Directional Power
40 Loss of Field Relay
32 40 50/27 21P 50P 50N 51P 51N 46 67P 67_2 67N 68 78 46 Generator Unbalance
49 Thermal Overload RTD
49 50G Ground Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
G EX GPM-F 64F 50P Phase Instantaneous Overcurrent
50SP Split Phase Instantaneous Overcurrent
50/27 Accidental Energization
Metering 51G Ground Time Overcurrent
87S 51P Phase Time Overcurrent
59N Neutral Overvoltage
59P Phase Overvoltage
59X Auxiliary Overvoltage
87G 50G 51G 59_2 Negative Sequence Overvoltage
27TN 27X 59X 64F Field ground protection
64S Sub-harmonic stator ground protection
R 64TN
64TN 100% stator ground
67_2 Negative Sequence Directional Overcurrent
64S 67N Neutral Directional Overcurrent
G60 Generator Protection System 67P Phase Directional Overcurrent
68 Power Swing Blocking
78 Out-of-Step Protection
81O Overfrequency
81R Rate of Change of Frequency
81U Underfrequency
87G Restricted ground fault
87S Generator Stator Differential
Dimensional Data
17.760
7.500
8.451
7.500
8.451 11.870
11.870
Front Front
7.310
5.250
7.869
7.310
5.250 19.160
9.370
7.869
8.300
19.160
9.370
8.300
GEDigitalEnergy.com 3
7.250
Ordering
Ordering
GPM-S Description
Included Components: 20Hz Generator
Band Pass Filter
Current Transformer
GEDigitalEnergy.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.
GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.