Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1

A backup Protection Technique for Three-


Terminal Multisection Compound Transmission
Lines
Ahmed Saber, Ahmed Emam, and Hany Elghazaly

 data to obtain the fault location for three-terminal transposed


Abstract—This paper presents a backup non-iterative transmission lines based on symmetrical components
protection technique for three-terminal multisection compound transformation. Brahma [14] used synchronized voltage
untransposed double-circuit transmission lines using
measurements to locate a fault on multi-terminal transmission
synchronized phasor measurement units. The proposed
technique is based on a distributed line model taking into account lines where current transformers measurements are avoided.
the mutual couplings between the two circuits. Synchronized Brahma [15] adopted positive-sequence components of
voltage and current measurements in the phase domain are synchronized voltage and current signals to locate a fault on a
utilized for fault detection, classification, and location. The single-circuit multi-terminal transmission lines. Izykowski et
proposed technique can discriminate internal transmissions lines al. [16] utilized synchronized current samples at all ends and
faults from other load change conditions or external faults and
voltage phasor at only one end to obtain the fault location of
identify correctly the faulty branch and fault type, as well as
determine accurately the fault location. The proposed algorithm three-terminal transmission lines using Newton-Raphson
is tested under different fault resistances, different fault iterative method. Liu et al. [17] used positive-sequence
locations, different fault inception angles, different fault types, components of synchronized voltage and current
non-linear high impedance faults, evolving faults and measurements at all ends to identify the faulty branch and
synchrophasor errors, as well as transmission line parameters obtain the fault location for single- or double- circuit multi-
errors. Extensive simulation studies carried out using MATLAB terminal transmission lines.
software show that the proposed protection technique yields
acceptable performance for all simulated cases. However, the above methods are not suitable for protection
of multisection compound lines such as underground cables
Index Terms—Transmission Lines, phasor measurement units, combined with overhead lines that have been vastly used in
fault location. some countries. Therefore, these nonhomogeneous lines have
been considered in other research papers [18]-[22]. Gilany et
I. INTRODUCTION
al. [18] used two-terminal synchronized voltage and current

T RANSMISSION lines are vital components for reliable


operation of electrical power network. As transmission
lines are always exposed to various faults, fault detection and
measurements to locate a fault on an underground cable
combined with an overhead line. Also, Gilany et al. [19]
employed three-terminal voltage traveling waves to determine
accurate fault location are crucial requirements to repair the the faulty branch and obtain the fault location for two-section
faulty area, restore the normal condition, and reduce the underground cables. These two methods [18], [19] are limited
outage time. Generally, Distance relay is used as a primary to two-section nonhomogeneous lines and the fault type
protection for transmission line while overreaching zones and should be initially identified before locating the fault. Yang et
earth fault overcurrent of distance relay are used as a backup al. [20] applied iterative operation using Newton–Raphson
protection [1], [2]. Due to the problems associated with method to locate a fault on multi-section underground power
conventional backup protection and recent advance of cables. This method suffers from convergence issues as the
synchrophasor measurements technology, the use of Newton–Raphson technique is utilized. Liu et al. [21]
synchronized phasor measurement units (PMUs) for employed positive-sequence components of synchronized
transmission lines protection has been presented in open voltage and current measurements to locate a fault on two-
literature [3]-[11]. terminal multi-section double-circuit compound transmission
Nowadays, multi-terminal transmission lines are used in lines. In addition, Lin et al. [22] employed positive-sequence
power system due to right of way restriction. The applications components of synchronized voltage and current
of PMUs for three- and multi-terminal transmission lines have measurements to recognize the faulty branch and pinpoint the
been introduced in some research papers [12]-[17]. Reference fault location for three-terminal multi-section
[12] employed three-terminal pre-fault and post-fault nonhomogeneous transmission lines. The proposed techniques
synchronized voltage data to pinpoint the fault location where in the two works [21], [22] are unaffected by source
the effect of current transformer saturation is avoided. Lin et impedance, fault resistance, and fault type. However, the
al. [13] used two-terminal synchronized voltage and current double-circuit line is treated as two independent single-circuit
lines and the potential couplings between the two circuits are
The authors are with the Department of Electrical Power and Machines,
Cairo University, Giza, Egypt (e-mail: a_saber_86@yahoo.com).
not considered. Also, the two proposed methods [21], [22] are

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 2

limited by the line asymmetry as the untransposed lines cannot


be decoupled using symmetrical components transformation. [ ] [ ]
In this paper, two main contributions are presented. First, a ( ) ( )
new technique is proposed to recognize the faulty branch for [ ]
( ) ( )
three-terminal multisection compound untransposed double-
circuit transmission lines. The derivation of the proposed where VR, Vk, Ik,R and IR,S are 6x1 voltage and current phasors
technique is based on a distributed-parameter line model in the at point k and bus R, respectively. Q(L) is the transformation
phase-coordinates without any assumptions. Comparing with matrix and is the distance between bus R and point k in
the pervious method in [22], the faulty branch can be easily per unit. The G, H, M and N are 6x6 transmission line
recognized in a simple manner with a low computational parameters matrices and can be expressed in terms of infinite
complexity and high efficiency. Second, an improved fault series as [23]:
location technique is applied to untransposed parallel
transmission lines as the proposed algorithm in [22] is limited 𝑧𝑦 ( ) 𝑧𝑦 ( )
( )
by the line asymmetry. The proposed technique is robust
against different fault resistances, different fault locations, 𝑧𝑦 𝑧( )
different fault types, different fault inception angles and ( ) 𝑧
transmission line parameters errors, as well as synchrophasor 𝑧𝑦 𝑧( )
errors. Also, the proposed technique takes into account the
effect of non-linear high impedance faults and evolving faults.
The paper is divided as follows. The proposed technique is 𝑧 𝑧𝑦 ( )
( ) 𝑧 𝑧𝑦
presented in section two. The test results are discussed in
section three. Finally, section four concludes the paper. 𝑧 𝑧𝑦 ( )
II. PROPOSED BACKUP PROTECTION TECHNIQUE
The proposed technique is developed based on the following 𝑧 𝑧𝑦 𝑧( )
assumptions: ( )
• Three-terminal synchronized measurements are available. 𝑧 𝑧𝑦 𝑧( )
• Communication channels are available.
A. Review of Two-Terminal Untransposed Double-Circuit
Transmission Lines Fault Location Algorithm
k
Due to the mutual couplings between the adjacent circuits,
symmetrical components transformation cannot be used for
decoupling untransposed transmission lines. Reference [23]
has been proposed a fault location technique for two-terminal
untransposed single-circuit long transmission line. This
f
technique can be extended to untransposed double-circuit long
transmission line as explained below:
Consider the double-circuit transmission line (S-R) shown in
fig. 1 with line length L. The series impedance and shunt Fig. 1. Faulted two-terminal double-circuit transmission line.
admittance matrices per unit length can be written as [24]: Assume that a fault occurred on point f which is Df in per
𝑧 𝑧 𝑧 𝑧 𝑧 𝑧 unit away from the sending end (S). The voltage phasor at
𝑧 𝑧 𝑧 𝑧 𝑧 𝑧 fault point f can be obtained by applying Kirchhoff voltage
𝑧 𝑧 𝑧 𝑧 𝑧 𝑧 law from the two ends of the line as follows:
𝑧 𝑧 𝑧 𝑧 𝑧 𝑧 𝑧
[ ( ) ( )] [ ]
𝑧 𝑧 𝑧 𝑧 𝑧 𝑧
[𝑧 𝑧 𝑧 𝑧 𝑧 𝑧 ] [ ( ) ( )] [ ]
𝑦 𝑦 𝑦 𝑦 𝑦 𝑦
𝑦 𝑦 𝑦 𝑦 𝑦 𝑦 where [ ] . If the
𝑦 𝑦 𝑦 𝑦 𝑦 𝑦 voltage and current phasors are known at both ends of the line,
𝑦 𝑦 𝑦 𝑦 𝑦 𝑦 𝑦 the fault distance will be the only unknown variable in
𝑦 𝑦 𝑦 𝑦 𝑦 𝑦 the above equation. A and B are only expanded to three terms
[𝑦 𝑦 𝑦 𝑦 𝑦 𝑦 ] because the simulation results assure that expansion of more
terms will not result in increasing the fault location accuracy.
where the dimensions of z and y are 6x6. The voltage and
As a result, equation (9) is rewritten and six polynomial
current phasors in the phase-coordinates at point k can be
equations for fault distance are obtained as follows:
derived as [25]:

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 3

presented to replace the conventional backup protection. The


[ ][ ]
proposed scheme is used as a backup protection based on the
where the dimensions of the coefficient matrices (X1, X2, X3, speed of communication system. The delay time associated
X4, X5, and X6) are 6x1and they are obtained from the with communication links is important issue and should be
following equations: considered in power system protection. More information
𝑧𝑦 𝑧𝑦 about delay time calculations is introduced in [26]. The delay
[ ]
time is in the range of 50-150 ms in digital microwave links
and fiber-optic cables [27], [28].
𝑧 𝑧𝑦 𝑧 𝑧𝑦 𝑧 The first step is to distinguish internal transmission lines
[ ]
faults inside the protected zone from different operating
𝑧𝑦 𝑧𝑦 conditions or external faults outside the protected zone. To do
[ ] 𝑧 so, consider the three-terminal nonhomogeneous transmission
line shown in fig. 2. Three PMUs are connected to buses S, R,
𝑧 𝑧𝑦 𝑧 𝑧𝑦 𝑧 and T. Therefore, the synchronized voltage phasors and
[ ] current phasors of all lines connected to these buses can be
obtained utilizing the GPS technique. All data are collected in
𝑧𝑦 𝑧𝑦 𝑧𝑦 the central protection system through communication links.
[ ] [ ]
Assume that the number of line sections of line branches S-P,
R-P, and T-P are respectively u, v, and w, where P is the tee-
𝑧𝑦 𝑧 𝑧𝑦 𝑧
[ ] point. The length of each line section from terminals S, R, and
T to tee-point P are respectively ,
𝑧𝑦 𝑧𝑦 𝑧 and . Each line section
[ ] [ ] is either underground cable or overhead line. In general, the
line parameters of two successive sections are not identical.
𝑧𝑦 𝑧 𝑧𝑦 𝑧 The proposed scheme for fault detection is divided into the
[ ]
three following steps:
Step 1: The instantaneous value of voltage magnitude
𝑧𝑦 𝑧𝑦 𝑧𝑦 𝑧 for each phase at buses S, R, and T is obtained using full
[ ] [ ] [ ]
cycle Discrete Fourier Transform [26], where subscript i
𝑧𝑦 𝑧 𝑧𝑦 𝑧 denotes lines a1, b1, c1, a2, b2, and c2. The instantaneous value
[ ] [ ] of voltage magnitude changes continuously due to load
change conditions or fault conditions. For each periodic cycle,
As a result, the fault distance is obtained by solving assume that the absolute difference between maximum and
(10). The real part of fault distance is accepted as the minimum instantaneous value of voltage magnitude for each
correct fault location. Also, the current phasor at fault point f phase at each bus is . The value of will be equal to
can be derived as: zero, if no change in the network occurs. However, if any
change in the network occurs, the instantaneous value of
[ ( ) ( )] [ ] will change accordingly [26]. The method introduced in
[26] compares positive-sequence voltage magnitude of buses
[ ( ) ( )] [ ] to obtain the nearest bus to the faulty line. After this bus is
where [ ] identified, the faulty line is obtained by comparing the
absolute difference of positive-sequence current angles at both
B. Fault Detection Unit ends of each line connected to the identified bus. However, in
Nowadays, distance relays are widely used as a main case of high fault impedance, the reduction of positive-
protection for transmission lines, while overreaching zones sequence voltage magnitude may be very low and the absolute
and earth fault overcurrent of distance relays are used as a difference of positive-sequence current angles at both ends of
backup protection. The operation of conventional backup the faulty line may not be high enough. Consequently, the
protection depends on standalone decision according to local backup protection may not operate in such case. The threshold
measurements. In addition, the conventional backup protection value of ΔV in [26] is equal to 0.05 per unit. In this paper,
is not able to adapt with different operating conditions and it is threshold value ( of is equal to 0.01 per unit so that
affected by fault resistance. As a result, the conventional transmission lines faults with high fault impedance can be
protective relays are not able to distinguish between detected. If the value of of each phase at each bus is less
symmetrical faults and other stressed normal conditions. than , no fault is detected. While, if any value of of any
Furthermore, Cascaded outages may occur due to mal- phase at any bus is greater than , the next step is applied. It
operation of conventional backup protection. is important to note that the fault detection decision is not only
In this paper, an improved backup protection scheme is based on the value of although the value of is only
used as indication for power system change.

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 4

Central
In normal conditions or external faults, equations (18), (19),
Protection
System and (20) will be valid and consequently equation (21) will be
valid. Accordingly, the values of will be ideally equal to
PMU PMU zero based on Kirchhoff current law. On the other hand, in
𝑆1 𝑆2 𝑆𝑢 𝑅𝑣 𝑅2 𝑅1
𝐆𝐒 𝐆𝑹
case of internal transmission lines faults, one of the equations
𝑃𝑅
𝑆 𝑃𝑆 P 𝑅
(18), (19), and (20) will not be valid and consequently
S 𝑃𝑇 R equation (21) will not be valid. Therfore, the values of will
𝑇𝑤

be greater than zero for faulty phases. To consider the


𝐕𝑺 𝐕𝑹
𝑇2
expected errors in measurement instruments and calculations,
threshold value will be set at a small value higher than
𝑇1
𝑇
PMU 𝐕𝐓 zero in real application. The value of is equal to 0.1 per unit
T
in this paper. As a result, the values of are used to
𝐆𝑻 differentiate internal transmission lines faults from other
events.
Fig. 2. Three-terminal nonhomogeneous transmission lines. C. Faulty branch Identifier unit
Step 2: In this step, we verify if the change of is due to As stated earlier, three voltage phasors at tee-point
bus fault or not by applying bus differential protection. All are calculated by applying a series of
current phasors at buses S, R, and T are measured directly by substitution steps from the measured voltage and current
the PMUs installed at these buses. By applying Kirchhoff phasors at buses S, R, and T. In normal conditions or external
current law at each bus, the vector sum of all current phasors faults, equations (18), (19), and (20) will be valid and the three
∑ for each phase at each bus can be calculated. Based on voltage phasors are approximately equal. On
Kirchhoff current law, the absolute value of ∑ for all the other hand, in case of internal transmission lines faults,
phases at each bus will be equal to zero, if no bus fault occurs. one of the equations (18), (19), and (20) will not be valid and
However, if bus fault occurs, the absolute value of ∑ for only two voltage phasors from the three voltage phasors are
faulty phases at the faulted bus will be greater than zero. To approximately equal and the third voltage phasor is
consider the expected errors in measurement instruments and corresponding to the faulty branch. Let assume that:
calculations, threshold value will be set at a small value 𝑥
higher than zero in real application. If the absolute value of 𝑥
∑ for any phase at any bus is greater than , bus fault is 𝑥
detected. On the other hand, if the absolute value of ∑ for { }
all phases at each bus is less than , the third step is applied.
The value of is equal to 0.05 per unit in this paper. The maximum absolute value of difference between each
Step 3: By using the boundary conditions at buses S, R, and two voltage phasors is obtained from (22)–(24). The value of
T, the voltage and current phasors at tee-point P can be F is equal to the minimum value of { }. If the
obtained by applying a series of substitution steps from the value of F is equal to , this means that the voltage phasors
measured voltage and current phasors at buses S, R, and T and are approximately equal and the faulty branch is
considering the line parameters of corresponding line section. T-P. Similarly, if the value of F is equal to , this means
Therefore, three voltage phasors and three that the voltage phasors and are approximately equal
current phasors at tee-point P are obtained as and the faulty branch is R-P. Also, if the value of F is equal to
follows: , this means that the faulty branch is S-P. Comparing
with the pervious method in [22], the faulty branch can be
[ ] [ ] easily identified in a simple manner with a low computational
complexity, high efficiency, and without any threshold values
[ ] [ ] to be initially determined.
D. Fault Location Unit
[ ] [ ] Once the transmission line fault is detected and the faulty
branch is identified, the next step is to estimate the fault
where Q(LS1), Q(LS2),…, and Q(LSu) are respectively location. The voltage and current phasors at the two ends of
transformation matrices of line sections 1, 2,.., and u between faulty branch are initially needed to be determined. Let
bus S and tee-point P. Consequently, Q(LR1), Q(LR2),…, and assume that the faulty branch is R-P. The voltage and current
Q(LRv) are respectively transformation matrices of line phasors at bus R are measured directly because a PMU is
sections 1, 2, ..., and v between bus R and tee-point P. In installed at this end. While the outgoing current phasor at tee-
addition, Q(LT1), Q(LT2),…, and Q(LTw) are respectively point P in the direction of P-R can be calculated as follows:
transformation matrices of line sections 1, 2,..., and w between
bus T and tee-point P. Suppose that [29]:
In addition, the voltage phasor at tee-point P is equal

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 5

to or . It is supposed that the bus R is selected as a circuit transmission line consisting of three branches (S-P, R-
reference point. The algorithm for fault location estimation P, and T-P) as shown in fig. 4. The line branch (S-P) consists
can be described in the following three steps: of two transmission line sections with lengths LS1and LS2. The
Step 1: It is assumed that each line section between bus R line branch (R-P) consists of three transmission line sections
and tee-point P is the faulty line section. For the first line with lengths LR1, LR2, and LR3. Also, the line branch (T-P)
section (LR1), the voltage and current phasors at both ends of consists of two transmission line sections with lengths LT1and
LR1 are needed to be determined in order to calculate the LT2. The transmission lines (1-S), (2-R), and (3-T) have the
corresponding fault distance. The voltage and current phasors same line parameters and they are used for simulating external
at the end R are known because a PMU is installed at this end faults. Loads are connected to buses S, R and T to simulate
while the voltage and current phasors at the various loading conditions. All lines parameters, all lines
other end of LR1 can be obtained from: lengths, and generator data are given in Appendix A. Three
PMUs are connected to buses S, R, and T and all
[ ] [ ] measurements are collected in the central protection system
through communication links. The obtained current and
As a result, the fault distance corresponding to first line voltage measurements are passed through a low-pass second
section can be obtained by solving (10). Similarly, this is order Butterworth filter with cut-off frequency 400 Hz.
repeated for each line section connected between bus R and Consequently, the output data are sampled at 2500 Hz and a
tee-point P and the estimated fault distance corresponding to digital mimic filter is utilized to remove the dc component
each line section is calculated. [30]. The 50 Hz fundamental component is extracted using
Step 2: Starting from the first line section, if its full cycle Discrete Fourier Transform. To evaluate the
corresponding estimated fault distance is within the interval accuracy of fault location, the percentage error in fault
[0, 1] and the other estimated fault distances are less than zero, location is defined as [31]:
the first line section is accepted as the faulty line section and | 𝑢 |
the estimated fault distance is accepted as the estimated fault
location. While, if the estimated fault distance corresponding
to first line section is greater than 1, the next line section is
verified. start
Step 3: For the second line section, if its corresponding
estimated fault distance is within the interval [0, 1] and the Read time data of voltage
and current phasors at
next estimated fault distances are less than zero, the second buses S, R, and T

line section is accepted as the faulty section and the estimated Calculate (∆Vi ) at buses S, R, and T
fault distance is accepted as the estimated fault location. No fault
While, if the estimated fault distance corresponding to second No
Is ∆Vi > 1?

line section is greater than 1, the next line section is verified in Yes

similar way. By repeating this step, the faulty line section and Apply vector sum of all current
the corresponding estimated fault location can be obtained. phasors at each bus (ΣӀi)

Similarly, the faulty line section and fault location can be


Yes
obtained if the faulty branch is S-P or T-P. The flow chart of Is abs(ΣӀi) At any bus > 2?

the proposed technique is shown in fig. 3. Bus fault at the bus No


Corresponding to
Calculate Ip
abs(ΣӀi) > 2
E. Fault Classification Unit
end No
After the faulty line section and fault location are Is Ip > 3?

determined, the fault type can be classified. As the voltage and Load change conditions Yes
or external fault
current phasors at both ends of the faulty line section are
obtained, the current phasor at fault point is calculated by Calculate the value of F and
identify the faulty branch
end
solving (17). Based on Kirchhoff current law, the value of
current phasor at fault point is ideally equal to zero for healthy Calculate the fault distance
of each line section
phases and is greater than zero for faulty phases. In addition,
determine the faulty section
to distinguish between line-to-line fault and double-line-to- and fault location
ground fault, the current phasors of the two faulty phases are Fig. 3. Flowchart of the proposed technique.
not equal for double-line-to-ground fault [29] while the
current magnitudes of faulty phases are equal to each other All simulations are developed by MATLAB software on a
with angle difference 180º for line-to-line fault [29]. 2.1 GHz Core 2 Duo CPU with 2 GB of RAM. The estimated
computational time for fault detection and faulty branch
III. PERFORMANCE EVALUATION identification is less than 1ms while the total computational
To assess the performance of the proposed algorithm, it is time including fault location calculations is about 19 ms.
applied to three-terminal multi-section untransposed double- Various loading conditions, Generator outages, external

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 6

transmission lines faults, bus faults, and internal transmission considering three different fault locaiton at 10%, 50%,
lines faults are simulated in the following sections considering and 90% of the line length, all fault types, 3 different fault
different fault resistances, different fault locations, resistances having 1, 50 and 100 ohm, and 90º fault
transmission line parameters errors, different fault types and inception angle . A total of 108 fault cases (3x3x4x3x1)
fault inception angles, as well as synchrophasor errors. Also, are conducted on the three lines. In all simulated cases, the
the effect of non-linear high impedance faults and evolving maximum obtained value of is equal to 0.0244 per unit. As
faults have been verified. Again, the values of , , and this value is less than 0.1 per unit, the results of the fault
are respectively equal to 0.01, 0.05, and 0.1 per unit. detection unit are EF or LCC for all simulated cases. To show
Central
the performance of the proposed technique for very low and
Protection very high fault impedance, Table 2 summarizes the results for
System
different fault types and different fault location. As observed,
PMU PMU
the maximum value of is equal to 0.03164 per unit.
1 S R 2
𝑆1 𝑆2 𝑅3 𝑅2 𝑅1 Therfore, the results of the fault detection unit are EF or LCC
𝐆𝐒 𝐆𝑹
Line (1-S)
Circuit 1
Line (2-R) for all cases in Table II.
P In addition, phase a to ground fault at bus S is simulated
Load S
Circuit 2
𝑇2
with Rf =0.01 Ω and δf = 0º. The instantaneous value of at
𝐕𝑺 𝐕𝑹 Load R
bus S for different phases is shown in fig. 6. As expected, the
𝑇1
instantaneous value of voltage magnitude for phase a is
T 𝐕𝐓 decreased while the instantaneous value of voltage magnitude
PMU
for other phases is increased. The absolute value of vector
Line (3-T)
3
Load T sum of phase a at bus S ∑ is equal to 12.134 per unit so
that bus fault is detected.
𝐆𝑻

Fig. 4. Simulated three-terminal double-circuit nonhomogeneous transmission


lines.

A. Various Loading Conditions


Different cases are tested by connecting different loads at
buses S, R and T at different switching angles. Also, the
outages of all generators and sudden loss of all loads are
simulated to verify the robustness of the suggested technique.
The results are shown in Table I. the load values are selected
to be 100 and 200 MVA at each bus. The vector sum of all
current phasors at buses S, R, and T is not shown due to space
restrictions. However, these values are less than 0.05 per unit.
For example in case 1, 100 MVA load is connected to bus S at
Fig. 5. The instantaneous value of corresponding to the phases of
switching angle 180º. The maximum values of at buses S, maximum at buses S, R, and T.
R, and T are respectively equal to 0.0113, 0.0021, and 0.0021
per unit. The maximum value of is less than 0.1 per unit and
it is equal to 0.0039 per unit so that no transmission line fault
is detected inside the protected zone. Also, the last case is
generator (GT) outage. The maximum values of at buses
S, R, and T are respectively equal to 0.0067, 0.0053, and
0.0337 per unit. The maximum value of is equal to 0.00053
per unit. Therefore, the result of the fault detection unit is
external fault (EF) or load change conditions (LCC). In
addition, sudden loss of all loads at buses S, R, and T are
simulated at 90º switching angle. The instantaneous value of
corresponding to the phases of maximum at buses S, R,
and T are shown in fig. 5. The maximum value of is equal
to 0.004 per unit so that the result of the fault detection unit is
EF or LCC. As a result, it is clear that the proposed scheme Fig. 6. The instantaneous values of at bus S for different phases due to bus
can discriminate all external events correctly. fault.

B. External faults cases C. Internal faults cases


Different external faults are conducted on transmission lines To verify the performance of the proposed technique
(1-S), (2-R), and (3-T). The three lines are simulated with against very low impedance and very high fault impedance,

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 7

the results for various fault cases are depicted in Table III for D. Influence of Line Parameters Errors
different line sections. The maximum values of for buses The variations of lines parameters have been considered in
S, R, and T are not shown in the tables. However, these values the proposed algorithm. Therefore, 1%, 5%, and 10%
are greater than 0.01 per unit. The last column in the table increasing and decreasing in impedances and admittances of
shows the percentage fault location error (F.L error %). For all line sections have been considered at the same time to
example, case 1 is phase a1 to ground fault at 15% of with assess the performance of the proposed method. Each line
0.001 ohm fault resistance and 0º fault inception angle. All section is tested under various fault conditions considering
values of are less than 0.1 per unit except the value four different locations at 20%, 40%, 60%, and 80% of the
corresponding to phase a1. Therefore, transmission line fault is line section length, all fault types and 3 different fault
detected. To identify the faulty branch, the value of F is equal resistances having 1, 50 and 100 ohm, as well as 180º fault
to 0.0030 per unit which is equal to the value of . inception angle. A total of 48 fault cases are simulated for
Therefore, the voltage phasors and are approximately each line section. The maximum and average estimation errors
equal and the faulty branch is S-P. Accordingly, the calculated in fault location for each line section are shown in fig. 8
fault distances corresponding to and are respectively considering variations of -1%, -5%, -10%, 1%, 5%, and 10%
equal to 0.1457 and -0.277 per unit so that is accepted as in all lines parameters at the same time. As observed, the
the faulty line section and the estimated fault location is equal maximum and average percentage error are respectively equal
to 0.1445 per unit. The percentage error in fault location is to 4.267% and 1.055% for 10% decreasing in all line
equal to 0.1375% in this case. parameters of all line sections at the same time. While the
Statistical results for several fault cases conducted on each maximum and average percentage error are respectively equal
line section are shown in fig. 7. Each line section is tested to 3.696% and 0.904% for 10% increasing in all line
with considering five different locations at 10%, 30%, 50%, parameters of all line sections at the same time. In all
70%, and 90% of the line section length, all fault types and 3 simulated cases, the faulty branch and faulty line section are
different fault resistances having 1, 50 and 100 ohm, as well as correctly identified.
fault inception angle at 90º. A total of 60 fault cases for each
line section are simulated. In all cases, the transmission line
faults inside the protected zone are correctly detected and the
faulty line branch and the fault type are correctly identified.
As observed in fig. 7, the maximum percentage error is equal
to 0.214% and the total percentage average error is equal to
0.039%.

Fig. 8. Effect of errors in line parameters on the fault location estimation.

E. Effect of Synchrophasor Errors


To meet IEEE standard accuracy requirements, a maximum
of 1% total vector error must be considered in synchronized
measurements [32]. Therefore, a maximum of ±31° time error
for a 50 Hz system and ±1% magnitude error are introduced in
Fig. 7. The maximum and average percentage error in fault location for all
line sections
voltage and current phasors measurements. A total of 48 fault
cases are simulated for each line section. The maximum and
In addition, the results of fault classification unit are shown average estimation errors in fault location for each line section
in Table IV. For example, the third case in the table is line-to- are shown in fig. 9. As observed, the maximum percentage
line fault (a2c2) in . As shown, the value of current phasor error is equal to 0.5154% and the total average error in all
at fault point is very small except the values of phase a2 and cases is equal to 0.0997%. In all simulated cases, the faulty
phase c2. The fault current Ia2 is approximately equal to -Ic2. branch and faulty line section are correctly recognized. The
Therefore, the result of fault classification unit is line-to-line obtained results assure that the proposed technique provides
fault. As a result, it can be concluded that the proposed acceptable performance even with considering the
technique yields acceptable results for all fault cases. synchrophasor errors.

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 8

F. Non-Linear High Fault Impedance Effect and 𝑢 is the stationary arc voltage. The stationary arc voltage
To evaluate the effect of non-linear high impedance fault on is calculated from:
the proposed technique, the model of time-varying arc 𝑢 𝑢 | |
resistance is simulated based on the equations below [33],
[34]: where 𝑢 is the constant voltage per unit length of arc, is the
resistive component per unit length of arc, and is the arc
𝑅
length. The fault is simulated using the following data [33],
[34]; τ=1ms, 𝑢 =9.6 V/cm, r=1.6 mΩ/cm, =350 cm.
∫ The same cases in Table III are examined at the same
| | conditions. The maximum and average percentage errors in
fault location are respectively equal to 0.375% and 0.135%
𝑢
compared with 0.290% and 0.125% in table III. It can be
where 𝑅 is the time-varying arc resistance, is the time-
concluded that the time-varying arc resistance has a small
varying arc conductance, is the stationary arc
effect on the fault location accuracy.
conductance, τ is the arc time constant, is the arc current,

TABLE I
DIFFERENT TEST CASES FOR VARIOUS LOADING CONDITIONS

Load condition max (p.u.) Ip at tee-point P (p.u.) Fault detection


Bus Load (MVA) Angle S R T Line a1 Line b1 Line c1 Line a2 Line b2 Line c2 result

S 100 180º 0.0113 0.0021 0.0021 0.00007 0.00028 0.00039 0.00007 0.00028 0.00039 EF or LCC
S 200 90º 0.0356 0.0052 0.0054 0.00119 0.00058 0.00058 0.00119 0.00058 0.00058 EF or LCC
R 100 60º 0.0033 0.0189 0.0023 0.00004 0.00041 0.00051 0.00004 0.00041 0.00051 EF or LCC
R 200 150º 0.0049 0.0293 0.0033 0.00067 0.00065 0.00101 0.00067 0.00065 0.00101 EF or LCC
T 100 120º 0.0028 0.0018 0.0182 0.00034 0.00025 0.00080 0.00034 0.00025 0.00080 EF or LCC
T 200 30º 0.0059 0.0042 0.0383 0.00016 0.00003 0.00053 0.00016 0.00003 0.00053 EF or LCC
----- 90º 0.1029 0.0176 0.0150 0.00057 0.00020 0.00060 0.00057 0.00020 0.00060 EF or LCC
----- 60º 0.0990 0.0454 0.0062 0.00010 0.00032 0.00049 0.00010 0.00032 0.00049 EF or LCC
----- 150º 0.0067 0.0053 0.0337 0.00023 0.00030 0.00050 0.00023 0.00030 0.00050 EF or LCC

TABLE II
DIFFERENT TEST CASES FOR EXTERNAL FAULTS

Fault condition max (p.u.) Ip at tee-point P (p.u.) Fault detection


Line
type (p.u.) 𝑅 S R T Line a1 Line b1 Line c1 Line a2 Line b2 Line c2 result

cg1 0.15 0.001 70 0.7319 0.0511 0.0741 0.00134 0.00136 0.00129 0.00134 0.00136 0.00129 EF or LCC
1-S
acg 0.95 1000 180 0.0068 0.0014 0.0012 0.00026 0.00028 0.00055 0.00026 0.00028 0.00055 EF or LCC
bg 0.7 1000 150 0.0008 0.0040 0.0016 0.00019 0.00024 0.00062 0.00019 0.00024 0.00062 EF or LCC
2-R
abc 0.95 0.001 180 0.0716 0.4885 0.0547 0.02647 0.03164 0.02161 0.02647 0.03164 0.02161 EF or LCC
abg 0.6 0.001 50 0.1026 0.0756 0.8021 0.00922 0.00367 0.01054 0.00922 0.00367 0.01054 EF or LCC
3-T
bc 0.8 1000 170 0.0048 0.0031 0.0133 0.00254 0.00259 0.00099 0.00254 0.00259 0.00099 EF or LCC
1
a, b, and c represent respectively lines a, b, and c while g represents the ground.

TABLE III
RESULTS OF DIFFERENT TEST CASES FOR DIFFERENT FAULTY SECTIONS
Fault condition Ip at tee-point P (p.u.) (p.u.)
Faulty F.L
section 𝑅 Line Line Line Line Line Line
type (p.u.) (p.u.) (p.u.) section error%
(p.u.) a1 b1 c1 a2 b2 c2
a1g1 0.15 0.001 0 10.45 0.0318 0.0472 0.0329 0.0305 0.0446 4.0428 4.0423 0.0030 0.1445 -0.277 ------ 0.1375
a2c2 0.8 1000 90 0.0006 0.0007 0.0015 0.4212 0.0006 0.4206 0.0804 0.0804 0.0024 0.7884 -0.064 ------ 0.2900
a1b1g 0.7 0.001 135 6.9476 6.6563 0.0099 0.0113 0.0063 0.0127 1.4879 0.0019 1.4888 2.1255 0.7027 -0.185 0.0864
a1b1c1 0.8 1000 180 0.2467 0.2488 0.2506 0.0004 0.0012 0.0009 0.0507 0.0023 0.0492 2.1753 0.8053 -0.116 0.1696
b 1g 0.55 0.001 0 0.0065 3.8838 0.0066 0.0052 0.0103 0.0114 0.0047 0.0194 0.0237 1.2127 0.5500 ------ 0.0000
b1c1 0.3 1000 45 0.0008 0.4367 0.4358 0.0012 0.0009 0.0007 0.0060 0.3334 0.3314 1.1100 0.3023 ------ 0.0657
1
a1, b1, c1, a2, b2, and c2 represent respectively lines a1, b1, c1, a2, b2, and c2 while g represents the ground.

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 9

TABLE IV
OUTPUT RESULTS OF FAULT CLASSIFICATION UNIT FOR DIFFERENT TEST CASES

Faulty Fault condition Current phasor at fault point (p.u.)


section type (p.u.) 𝑅 Line a1 Line b1 Line c1 Line a2 Line b2 Line c2
c1g 0.4 45 110 0.0006-0.0024i 0.0016-0.0004i 0.1416-4.3318i -0.0002+0.0002i -0.0002+0.0036i -0.0010+0.0018i
b1c1g 0.8 30 50 -0.0018+0.0354i 4.2756+2.5136i -2.8748-5.2686i -0.0018+0.0344i 0.0248-0.0206i -0.0286-0.0036i
a2c2 0.2 150 20 -0.0008-0.0002i -0.0006-0.0006i -0.0002-0.0006i -1.6302+2.2644i -0.0002-0.0002i 1.6302-2.265i
a1b1c1 0.95 70 60 -2.8108+1.621i 2.8578+1.6956i -0.0836-3.3944i -0.0000-0.0010i -0.0008+0.0000i 0.0000-0.0002i
a2g 0.5 0.1 90 -0.0020-0.0020i -0.0034-0.0006i 0.0008-0.0010i -0.1868+3.8686i -0.0010+0.0010i 0.0038+0.0000i
a2c2g 0.7 2 45 0.0018-0.0014i -0.0012-0.0008i -0.0010+0.0052i 1.2916+5.3858i -0.0034-0.0008i -3.7484-4.4672i
b2c2 0.6 25 180 -0.0012-0.0012i 0.0032-0.0020i 0.0058+0.0054i -0.0034-0.0018i 5.7178+2.1164i -5.7216-2.1166i

IV. CONCLUSION
A backup protection scheme for three-terminal
untransposed double-circuit nonhomogeneous transmission
lines has been proposed. The voltage and current phasors are
employed for fault detection, faulty line section identification
and fault location, as well as fault classification. Simulation
studies demonstrate the robustness of the proposed technique
under different loading conditions, external faults, different
fault types and different fault inception angles, as well as
different fault resistances. Furthermore, the proposed
technique shows acceptable performance against transmission
line parameters errors, synchrophasor errors, non-linear high
impedance faults, and evolving faults. For all simulated test
cases, the proposed technique can distinguish internal faults
from other external faults or load change conditions. For all
internal faults, the faulty line branch and fault type are
correctly determined. In addition, the maximum estimation
Fig. 9. Effect of Synchrophasor errors on the fault location estimation. error of fault location does not exceed 4.267% in all simulated
test cases.
G. Testing of Evolving Faults
The evolving faults are earth faults beginning in one line APPENDIX A
and spreading to another line after some time at the same The lengths of different transmission lines are shown in the
location [35], [36]. To verify the effect of evolving faults on following table:
the proposed technique, the following case is tested. A single
Line section Line Line Line
line to ground fault in phase b 1 at 50% of in branch S-P is Line
(1-S) (2-R) (3-T)
simulated with 1 ohm fault resistance and 0º fault inception
Length (km) 40 120 50 80 120 200 80 50 50 50
angle. Another fault in phase b2 is simulated with 100 ohm
fault resistance and 180º fault inception angle at the same The transmission lines (1-S), (2-R), and (3-T) have the same
location. The values of are equal to [0.0016 4.3614 0.0041 line parameters and they are shown in the following table:
0.0025 1.0329 0.0042] per unit. As some values of are
Positive-sequence Zero-sequence
greater than 0.1 per unit, internal transmission line fault is
R L C R L C
detected. Consequently, the values of , , and (Ω/km) (mH/km) (nF/km) (Ω/km) (mH/km) (nF/km)
are repectiveluy equal to 0.6896, 0.6892, and 0.0031 per unit. 0.038 0.896 13.1 0.248 2.686 7.12
Therfore, the value of F is equal to 0.0031 per unit which is
corresponding to the value of . As a result, the faulty The generator data are shown in the following table:
branch is S-P. Accordingly, the estimated fault distances Base Voltage Power Flow Short Circuit Level X/R
Generator
corresponding to and are respectively equal to 2.5502 (kV) Angle (GVA) Ratio
and 0.5005 per unit so that is accepted as the faulty line GS 220 20º 20 15
section. The estimated fault location is equal to 0.5005 per GR 220 0º 20 15
GT 220 10º 20 15
unit and the percentage error in fault location is equal to
0.0375%. It can be concluded that the proposed technique has The series impedance and shunt admittance matrices of each
a successful performance against evolving faults. line section are as follows:

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 10

𝑧 𝑧 𝑧

[ ]

𝑦 𝑦 𝑦 𝑆

[ ]

𝑧 𝑧 𝑧 (

[ ]

𝑦 𝑦 𝑦 𝑆

[ ]

[ ]

𝑦 𝑆

[ ]

REFERENCES algorithm,‖ IEEE Trans. Smart Grid, vol. 2, no. 3, pp. 468-475,
Sep. 2011.
[1] A. G. Phadke and J. S. Thorp, Computer Relaying for Power [10] J. Zare, F. Aminifar, and M. Sanaye-Pasand, ―Synchrophasor-
Systems, New York, USA: Wiley, 2009. based wide-area backup protection scheme with data requirement
[2] P. M. Anderson, Power System Protection, New York, USA: analysis,‖ IEEE Trans. Smart Grid, vol. 30, no. 3, pp. 1410–1419,
McGraw-Hill, 1999. Mar. 2015.
[3] M. G. Adamiak, A. P. Apostolov, and M. M. Begovic, et al., [11] A. S. Dobakhshari and A. M. Ranjbar, ―A novel method for fault
―Wide area protection—Technology and infrastructures,‖ IEEE location of transmission lines by wide-area voltage measurements
Trans. Power Del., vol. 21, no. 2, pp. 601–609, Apr. 2006. considering measurement errors,‖ IEEE Trans. Smart Grid, vol. 6,
[4] M. Kezunovic, J. Mrkic, and B. Perunicic, et al., ―An accurate no. 2, pp. 874–884, Mar. 2015.
fault location algorithm using synchronized sampling,‖ Elect. [12] J. Miñambres, I. Zamora, A. Mazon, M. Zorrozua, and R. Alvarez-
Power Syst. Res. J., vol. 29, no. 3, pp. 161–169, May 1994. Isasi, ―New technique, based on voltages, for fault location on three-
[5] C. J. Lee, J. B. Park, J. R. Shin, and Z. M. Radojevié, ―A new two- terminal transmission lines,‖ Elect. Power Syst. Res., vol. 37-2, no. 2,
terminal numerical algorithm for fault location, distance pp. 143–151, May 1996.
protection, and arcing fault recognition,‖ IEEE Trans. Power Syst., [13] Y. H. Lin, C. W. Liu, and C. S. Yu, ―A new fault locator for three-
vol. 21, no. 3, pp. 1460–1462, Aug. 2006. terminal transmission lines—Using two-terminal synchronized
[6] Y. Liao and M. Kezunovic, ―Optimal estimate of transmission line voltage and current phasors,‖ IEEE Trans. Power Del., vol. 17, no. 2,
fault location considering measurement errors,‖ IEEE Trans. pp. 452–459, Apr. 2002.
Power Del., vol. 22, no. 3, pp. 1335–1341, Jul. 2007. [14] M. Brahma, ―Fault location scheme for a multi-terminal transmission
[7] J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke, line using synchronized voltage measurements,‖ IEEE Trans. Power
―Synchronized phasor measurement applications in power Del., vol. 20, no. 2, pp. 1325–1331, Apr. 2005.
systems,‖ IEEE Trans. Smart Grid, vol. 1, no. 1, pp. 20–27, Jun. [15] M. Brahma, ―New fault-location method for a single multi-
2010. terminal transmission line using synchronized phasor
[8] J. Izykowski, E. Rosolowski, P. Balcerek, M. Fulczyk, and M.M. measurements,‖ IEEE Trans. Power Del., vol. 21, no. 3, pp. 1148–
Saha, ―Accurate non-iterative fault location algorithm utilizing two- 1153, Jul. 2006.
end unsynchronized measurements,‖ IEEE Trans. Power Del., vol. [16] J. Izykowski, E. Rosolowski, M. M. Saha, M. Fulczyk, and P.
25, no. 1, pp. 72–80, Jan. 2010. Balcerek, ―A fault-location method for application with current
[9] J. Ma, J. Li, J. S. Thorp, A. J. Arana, Q. Yang, and A. G. Phadke,
―fault steady state component-based wide area backup protection

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 11

differential relays of three-terminal lines,‖ IEEE Trans. Power Del., [33] M. Kizilcay and T. Pniok, ―Digital simulation of fault arcs in
vol. 22, no. 4, pp. 2099–2107, Oct. 2007. power systems,‖ ETEP J., vol. 1, no. 1, pp. 55–60, Jan. 1991.
[17] C. W. Liu, K. P. Lien, C. S. Chen, and J. A. Jiang, ―A universal fault [34] H. Livani and C. Y. Evrenosoglu, ―A Machine Learning and
location technique for N-terminal transmission lines,‖ IEEE Trans. Wavelet-Based Fault Location Method for Hybrid Transmission
Power Del., vol. 23, no. 3, pp. 1366–1373, Jul. 2008. Lines,‖ IEEE Trans. Smart Grid, vol. 5, no. 1, pp. 51–59, Jan.
[18] M. Gilany, E. S. T. Eldin, M. M. A. Aziz, and D. K. Ibrahim, ―An 2014.
accurate scheme for fault location in combined overhead line with [35] A. Yadav, ―Comparison of single and modular ANN based fault
underground power cable,‖ in Proc. IEEE Power Eng. Soc. Gen. detector and classifier for double circuit transmission lines,‖ Int. J.
Meet., San Francisco, CA, Jun. 12–16, 2005, vol. 3, pp. 2521–2527. Eng. Sci. Technol., vol. 4, no. 2, pp. 122–136, 2012.
[19] M. Gilany, D. K. Ibrahim, and E. S. T. Eldin, ―Traveling-wave-based [36] A. Swetapadma, A. Yadav, ―All shunt fault location including
fault-location scheme for multiend-aged underground cable system,‖ cross-country and evolving faults in transmission lines without
IEEE Trans. Power Del., vol. 22, no. 1, pp. 82–89, Jan. 2007. fault type classification,‖ Elect. Power Syst. Res., vol. 123, pp. 1–
[20] X. Yang, M. S Choi, S. J. Lee, C.W. Ten, and S. I.Lim, ―Fault 12, 2015.
location for underground power cable using distributed parameter
approach,‖ IEEE Trans. Power Syst., vol. 23, no. 4, pp. 1809–1816,
Nov. 2008.
[21] C. W. Liu, T. C. Lin, C. S. Yu, and J. Z. Yang, ―A fault location
technique for two-terminal multisection compound transmission lines Ahmed Saber was born in Bani-Suef, Egypt, in
using synchronized phasor measurements,” IEEE Trans. Smart Grid, 1986. He received a M.Sc. degree in electrical
vol. 3, no. 1, pp. 113–121, Mar. 2012. power and machines engineering from Faculty of
[22] T.C. Lin, P. Y. Lin, and C. W. Liu, ―An Algorithm for Locating engineering, Cairo University in 2013.
Faults in Three-Terminal Multisection Nonhomogeneous Currently, he is presently a Ph.D. candidate at
Transmission Lines Using Synchrophasor Measurements,‖ IEEE faculty of engineering, Cairo University and works
Trans. Smart Grid, vol. 22, no. 1, pp. 82–89, Jan. 2014. as a teaching assistant at electrical power and
[23] S. Azizi, M. Sanaye-Pasand, and M. Paolone, ―Locating Faults on machines department, Cairo University.
Untransposed, Meshed Transmission Networks Using a Limited
Number of Synchrophasor Measurements,‖ IEEE Trans. Power
Syst, vol. 22, no. 1, pp. 4462–4472, 2016.
[24] S. Jiale, G. B. Song, X. U. Xu, and et al., ―Time-domain fault
location algorithm for parallel transmission lines using
unsynchronized currents,‖ Int. J. Elect. Power and Energy Syst., vol.
28, no. 4, pp. 253–260, 2006. Ahmed Emam received the B.Sc., M.Sc. and the
[25] J. C. Li and Y. P. Wu, ―A distributed circuit model for three-phase PHD degrees in Electrical Engineering from Cairo
transposed and untransposed transmission lines,‖ Elect. Power Syst. University, Egypt, in 1998, 2002 and 2010
Res., vol. 19, no. 6, pp. 187–194, Oct. 1990. respectively. Currently, he is a teacher in the
[26] M. M. Eissa, M. E. Masoud, and M. M. M. Elanwar, ―A novel back Faculty of Engineering, Cairo University. His
up wide area protection technique for power transmission grids research interests are in the area of Electric and
using phasor measurement unit,‖ IEEE Trans. Power Del., vol. 25, Magnetic Fields, Transient overvoltage and Digital
no. 1, pp. 270–278, Jan. 2010. Protection
[27] B. Naduvathuparambil, M. C. Valenti, and A. Feliachi,
―Communication delays in wide area measurement systems,‖ in
Proc. 34th Southeast. Symp. Syst. Theory, Huntsville, AL, USA,
Mar. 2002, pp. 118–122.
[28] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements
and Their Applications, New York, USA: Springer, 2008.
[29] H. Saadat, Power System Analysis, New York, USA: Mc-Graw-Hill, Hany Elghazaly received the Ph.D. degree in high
2002. Voltage Engineering from the Faculty of
[30] G. Benmouyal, ―Removal of DC-offset in current waveforms using Engineering, The University of Western Ontario,
digital mimic filtering,‖ IEEE Trans. Power Del., vol. 10, no. 2, pp. Canada, in 1986. He is presently a full Professor
621–630, Apr. 1995. with the Faculty of Engineering, Cairo University.
[31] IEEE Standard Definitions for the Measurement of Electric Power He has worked on High voltage, Electrostatic and
Quantities under Sinusoidal, Non-sinusoidal, Balanced, or power system protection. Also, he is a Senior
Unbalanced Conditions for Synchrophasor Measurements for Power Member of Industry Application Society, The
Systems, IEEE Std 1459-2010, Feb. 2, 2010. institute of Electrical and Electronic Engineering,
[32] IEEE Standard for Synchrophasor Measurements for Power IEEE, USA.
Systems, IEEE Std C37.118.1-2011, Dec. 28, 2011.

1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like