Professional Documents
Culture Documents
A Backup Protection Technique For ThreeTerminal Multisection Compound Transmission
A Backup Protection Technique For ThreeTerminal Multisection Compound Transmission
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 2
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 3
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 4
Central
In normal conditions or external faults, equations (18), (19),
Protection
System and (20) will be valid and consequently equation (21) will be
valid. Accordingly, the values of will be ideally equal to
PMU PMU zero based on Kirchhoff current law. On the other hand, in
𝑆1 𝑆2 𝑆𝑢 𝑅𝑣 𝑅2 𝑅1
𝐆𝐒 𝐆𝑹
case of internal transmission lines faults, one of the equations
𝑃𝑅
𝑆 𝑃𝑆 P 𝑅
(18), (19), and (20) will not be valid and consequently
S 𝑃𝑇 R equation (21) will not be valid. Therfore, the values of will
𝑇𝑤
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 5
to or . It is supposed that the bus R is selected as a circuit transmission line consisting of three branches (S-P, R-
reference point. The algorithm for fault location estimation P, and T-P) as shown in fig. 4. The line branch (S-P) consists
can be described in the following three steps: of two transmission line sections with lengths LS1and LS2. The
Step 1: It is assumed that each line section between bus R line branch (R-P) consists of three transmission line sections
and tee-point P is the faulty line section. For the first line with lengths LR1, LR2, and LR3. Also, the line branch (T-P)
section (LR1), the voltage and current phasors at both ends of consists of two transmission line sections with lengths LT1and
LR1 are needed to be determined in order to calculate the LT2. The transmission lines (1-S), (2-R), and (3-T) have the
corresponding fault distance. The voltage and current phasors same line parameters and they are used for simulating external
at the end R are known because a PMU is installed at this end faults. Loads are connected to buses S, R and T to simulate
while the voltage and current phasors at the various loading conditions. All lines parameters, all lines
other end of LR1 can be obtained from: lengths, and generator data are given in Appendix A. Three
PMUs are connected to buses S, R, and T and all
[ ] [ ] measurements are collected in the central protection system
through communication links. The obtained current and
As a result, the fault distance corresponding to first line voltage measurements are passed through a low-pass second
section can be obtained by solving (10). Similarly, this is order Butterworth filter with cut-off frequency 400 Hz.
repeated for each line section connected between bus R and Consequently, the output data are sampled at 2500 Hz and a
tee-point P and the estimated fault distance corresponding to digital mimic filter is utilized to remove the dc component
each line section is calculated. [30]. The 50 Hz fundamental component is extracted using
Step 2: Starting from the first line section, if its full cycle Discrete Fourier Transform. To evaluate the
corresponding estimated fault distance is within the interval accuracy of fault location, the percentage error in fault
[0, 1] and the other estimated fault distances are less than zero, location is defined as [31]:
the first line section is accepted as the faulty line section and | 𝑢 |
the estimated fault distance is accepted as the estimated fault
location. While, if the estimated fault distance corresponding
to first line section is greater than 1, the next line section is
verified. start
Step 3: For the second line section, if its corresponding
estimated fault distance is within the interval [0, 1] and the Read time data of voltage
and current phasors at
next estimated fault distances are less than zero, the second buses S, R, and T
line section is accepted as the faulty section and the estimated Calculate (∆Vi ) at buses S, R, and T
fault distance is accepted as the estimated fault location. No fault
While, if the estimated fault distance corresponding to second No
Is ∆Vi > 1?
line section is greater than 1, the next line section is verified in Yes
similar way. By repeating this step, the faulty line section and Apply vector sum of all current
the corresponding estimated fault location can be obtained. phasors at each bus (ΣӀi)
determined, the fault type can be classified. As the voltage and Load change conditions Yes
or external fault
current phasors at both ends of the faulty line section are
obtained, the current phasor at fault point is calculated by Calculate the value of F and
identify the faulty branch
end
solving (17). Based on Kirchhoff current law, the value of
current phasor at fault point is ideally equal to zero for healthy Calculate the fault distance
of each line section
phases and is greater than zero for faulty phases. In addition,
determine the faulty section
to distinguish between line-to-line fault and double-line-to- and fault location
ground fault, the current phasors of the two faulty phases are Fig. 3. Flowchart of the proposed technique.
not equal for double-line-to-ground fault [29] while the
current magnitudes of faulty phases are equal to each other All simulations are developed by MATLAB software on a
with angle difference 180º for line-to-line fault [29]. 2.1 GHz Core 2 Duo CPU with 2 GB of RAM. The estimated
computational time for fault detection and faulty branch
III. PERFORMANCE EVALUATION identification is less than 1ms while the total computational
To assess the performance of the proposed algorithm, it is time including fault location calculations is about 19 ms.
applied to three-terminal multi-section untransposed double- Various loading conditions, Generator outages, external
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 6
transmission lines faults, bus faults, and internal transmission considering three different fault locaiton at 10%, 50%,
lines faults are simulated in the following sections considering and 90% of the line length, all fault types, 3 different fault
different fault resistances, different fault locations, resistances having 1, 50 and 100 ohm, and 90º fault
transmission line parameters errors, different fault types and inception angle . A total of 108 fault cases (3x3x4x3x1)
fault inception angles, as well as synchrophasor errors. Also, are conducted on the three lines. In all simulated cases, the
the effect of non-linear high impedance faults and evolving maximum obtained value of is equal to 0.0244 per unit. As
faults have been verified. Again, the values of , , and this value is less than 0.1 per unit, the results of the fault
are respectively equal to 0.01, 0.05, and 0.1 per unit. detection unit are EF or LCC for all simulated cases. To show
Central
the performance of the proposed technique for very low and
Protection very high fault impedance, Table 2 summarizes the results for
System
different fault types and different fault location. As observed,
PMU PMU
the maximum value of is equal to 0.03164 per unit.
1 S R 2
𝑆1 𝑆2 𝑅3 𝑅2 𝑅1 Therfore, the results of the fault detection unit are EF or LCC
𝐆𝐒 𝐆𝑹
Line (1-S)
Circuit 1
Line (2-R) for all cases in Table II.
P In addition, phase a to ground fault at bus S is simulated
Load S
Circuit 2
𝑇2
with Rf =0.01 Ω and δf = 0º. The instantaneous value of at
𝐕𝑺 𝐕𝑹 Load R
bus S for different phases is shown in fig. 6. As expected, the
𝑇1
instantaneous value of voltage magnitude for phase a is
T 𝐕𝐓 decreased while the instantaneous value of voltage magnitude
PMU
for other phases is increased. The absolute value of vector
Line (3-T)
3
Load T sum of phase a at bus S ∑ is equal to 12.134 per unit so
that bus fault is detected.
𝐆𝑻
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 7
the results for various fault cases are depicted in Table III for D. Influence of Line Parameters Errors
different line sections. The maximum values of for buses The variations of lines parameters have been considered in
S, R, and T are not shown in the tables. However, these values the proposed algorithm. Therefore, 1%, 5%, and 10%
are greater than 0.01 per unit. The last column in the table increasing and decreasing in impedances and admittances of
shows the percentage fault location error (F.L error %). For all line sections have been considered at the same time to
example, case 1 is phase a1 to ground fault at 15% of with assess the performance of the proposed method. Each line
0.001 ohm fault resistance and 0º fault inception angle. All section is tested under various fault conditions considering
values of are less than 0.1 per unit except the value four different locations at 20%, 40%, 60%, and 80% of the
corresponding to phase a1. Therefore, transmission line fault is line section length, all fault types and 3 different fault
detected. To identify the faulty branch, the value of F is equal resistances having 1, 50 and 100 ohm, as well as 180º fault
to 0.0030 per unit which is equal to the value of . inception angle. A total of 48 fault cases are simulated for
Therefore, the voltage phasors and are approximately each line section. The maximum and average estimation errors
equal and the faulty branch is S-P. Accordingly, the calculated in fault location for each line section are shown in fig. 8
fault distances corresponding to and are respectively considering variations of -1%, -5%, -10%, 1%, 5%, and 10%
equal to 0.1457 and -0.277 per unit so that is accepted as in all lines parameters at the same time. As observed, the
the faulty line section and the estimated fault location is equal maximum and average percentage error are respectively equal
to 0.1445 per unit. The percentage error in fault location is to 4.267% and 1.055% for 10% decreasing in all line
equal to 0.1375% in this case. parameters of all line sections at the same time. While the
Statistical results for several fault cases conducted on each maximum and average percentage error are respectively equal
line section are shown in fig. 7. Each line section is tested to 3.696% and 0.904% for 10% increasing in all line
with considering five different locations at 10%, 30%, 50%, parameters of all line sections at the same time. In all
70%, and 90% of the line section length, all fault types and 3 simulated cases, the faulty branch and faulty line section are
different fault resistances having 1, 50 and 100 ohm, as well as correctly identified.
fault inception angle at 90º. A total of 60 fault cases for each
line section are simulated. In all cases, the transmission line
faults inside the protected zone are correctly detected and the
faulty line branch and the fault type are correctly identified.
As observed in fig. 7, the maximum percentage error is equal
to 0.214% and the total percentage average error is equal to
0.039%.
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 8
F. Non-Linear High Fault Impedance Effect and 𝑢 is the stationary arc voltage. The stationary arc voltage
To evaluate the effect of non-linear high impedance fault on is calculated from:
the proposed technique, the model of time-varying arc 𝑢 𝑢 | |
resistance is simulated based on the equations below [33],
[34]: where 𝑢 is the constant voltage per unit length of arc, is the
resistive component per unit length of arc, and is the arc
𝑅
length. The fault is simulated using the following data [33],
[34]; τ=1ms, 𝑢 =9.6 V/cm, r=1.6 mΩ/cm, =350 cm.
∫ The same cases in Table III are examined at the same
| | conditions. The maximum and average percentage errors in
fault location are respectively equal to 0.375% and 0.135%
𝑢
compared with 0.290% and 0.125% in table III. It can be
where 𝑅 is the time-varying arc resistance, is the time-
concluded that the time-varying arc resistance has a small
varying arc conductance, is the stationary arc
effect on the fault location accuracy.
conductance, τ is the arc time constant, is the arc current,
TABLE I
DIFFERENT TEST CASES FOR VARIOUS LOADING CONDITIONS
S 100 180º 0.0113 0.0021 0.0021 0.00007 0.00028 0.00039 0.00007 0.00028 0.00039 EF or LCC
S 200 90º 0.0356 0.0052 0.0054 0.00119 0.00058 0.00058 0.00119 0.00058 0.00058 EF or LCC
R 100 60º 0.0033 0.0189 0.0023 0.00004 0.00041 0.00051 0.00004 0.00041 0.00051 EF or LCC
R 200 150º 0.0049 0.0293 0.0033 0.00067 0.00065 0.00101 0.00067 0.00065 0.00101 EF or LCC
T 100 120º 0.0028 0.0018 0.0182 0.00034 0.00025 0.00080 0.00034 0.00025 0.00080 EF or LCC
T 200 30º 0.0059 0.0042 0.0383 0.00016 0.00003 0.00053 0.00016 0.00003 0.00053 EF or LCC
----- 90º 0.1029 0.0176 0.0150 0.00057 0.00020 0.00060 0.00057 0.00020 0.00060 EF or LCC
----- 60º 0.0990 0.0454 0.0062 0.00010 0.00032 0.00049 0.00010 0.00032 0.00049 EF or LCC
----- 150º 0.0067 0.0053 0.0337 0.00023 0.00030 0.00050 0.00023 0.00030 0.00050 EF or LCC
TABLE II
DIFFERENT TEST CASES FOR EXTERNAL FAULTS
cg1 0.15 0.001 70 0.7319 0.0511 0.0741 0.00134 0.00136 0.00129 0.00134 0.00136 0.00129 EF or LCC
1-S
acg 0.95 1000 180 0.0068 0.0014 0.0012 0.00026 0.00028 0.00055 0.00026 0.00028 0.00055 EF or LCC
bg 0.7 1000 150 0.0008 0.0040 0.0016 0.00019 0.00024 0.00062 0.00019 0.00024 0.00062 EF or LCC
2-R
abc 0.95 0.001 180 0.0716 0.4885 0.0547 0.02647 0.03164 0.02161 0.02647 0.03164 0.02161 EF or LCC
abg 0.6 0.001 50 0.1026 0.0756 0.8021 0.00922 0.00367 0.01054 0.00922 0.00367 0.01054 EF or LCC
3-T
bc 0.8 1000 170 0.0048 0.0031 0.0133 0.00254 0.00259 0.00099 0.00254 0.00259 0.00099 EF or LCC
1
a, b, and c represent respectively lines a, b, and c while g represents the ground.
TABLE III
RESULTS OF DIFFERENT TEST CASES FOR DIFFERENT FAULTY SECTIONS
Fault condition Ip at tee-point P (p.u.) (p.u.)
Faulty F.L
section 𝑅 Line Line Line Line Line Line
type (p.u.) (p.u.) (p.u.) section error%
(p.u.) a1 b1 c1 a2 b2 c2
a1g1 0.15 0.001 0 10.45 0.0318 0.0472 0.0329 0.0305 0.0446 4.0428 4.0423 0.0030 0.1445 -0.277 ------ 0.1375
a2c2 0.8 1000 90 0.0006 0.0007 0.0015 0.4212 0.0006 0.4206 0.0804 0.0804 0.0024 0.7884 -0.064 ------ 0.2900
a1b1g 0.7 0.001 135 6.9476 6.6563 0.0099 0.0113 0.0063 0.0127 1.4879 0.0019 1.4888 2.1255 0.7027 -0.185 0.0864
a1b1c1 0.8 1000 180 0.2467 0.2488 0.2506 0.0004 0.0012 0.0009 0.0507 0.0023 0.0492 2.1753 0.8053 -0.116 0.1696
b 1g 0.55 0.001 0 0.0065 3.8838 0.0066 0.0052 0.0103 0.0114 0.0047 0.0194 0.0237 1.2127 0.5500 ------ 0.0000
b1c1 0.3 1000 45 0.0008 0.4367 0.4358 0.0012 0.0009 0.0007 0.0060 0.3334 0.3314 1.1100 0.3023 ------ 0.0657
1
a1, b1, c1, a2, b2, and c2 represent respectively lines a1, b1, c1, a2, b2, and c2 while g represents the ground.
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 9
TABLE IV
OUTPUT RESULTS OF FAULT CLASSIFICATION UNIT FOR DIFFERENT TEST CASES
IV. CONCLUSION
A backup protection scheme for three-terminal
untransposed double-circuit nonhomogeneous transmission
lines has been proposed. The voltage and current phasors are
employed for fault detection, faulty line section identification
and fault location, as well as fault classification. Simulation
studies demonstrate the robustness of the proposed technique
under different loading conditions, external faults, different
fault types and different fault inception angles, as well as
different fault resistances. Furthermore, the proposed
technique shows acceptable performance against transmission
line parameters errors, synchrophasor errors, non-linear high
impedance faults, and evolving faults. For all simulated test
cases, the proposed technique can distinguish internal faults
from other external faults or load change conditions. For all
internal faults, the faulty line branch and fault type are
correctly determined. In addition, the maximum estimation
Fig. 9. Effect of Synchrophasor errors on the fault location estimation. error of fault location does not exceed 4.267% in all simulated
test cases.
G. Testing of Evolving Faults
The evolving faults are earth faults beginning in one line APPENDIX A
and spreading to another line after some time at the same The lengths of different transmission lines are shown in the
location [35], [36]. To verify the effect of evolving faults on following table:
the proposed technique, the following case is tested. A single
Line section Line Line Line
line to ground fault in phase b 1 at 50% of in branch S-P is Line
(1-S) (2-R) (3-T)
simulated with 1 ohm fault resistance and 0º fault inception
Length (km) 40 120 50 80 120 200 80 50 50 50
angle. Another fault in phase b2 is simulated with 100 ohm
fault resistance and 180º fault inception angle at the same The transmission lines (1-S), (2-R), and (3-T) have the same
location. The values of are equal to [0.0016 4.3614 0.0041 line parameters and they are shown in the following table:
0.0025 1.0329 0.0042] per unit. As some values of are
Positive-sequence Zero-sequence
greater than 0.1 per unit, internal transmission line fault is
R L C R L C
detected. Consequently, the values of , , and (Ω/km) (mH/km) (nF/km) (Ω/km) (mH/km) (nF/km)
are repectiveluy equal to 0.6896, 0.6892, and 0.0031 per unit. 0.038 0.896 13.1 0.248 2.686 7.12
Therfore, the value of F is equal to 0.0031 per unit which is
corresponding to the value of . As a result, the faulty The generator data are shown in the following table:
branch is S-P. Accordingly, the estimated fault distances Base Voltage Power Flow Short Circuit Level X/R
Generator
corresponding to and are respectively equal to 2.5502 (kV) Angle (GVA) Ratio
and 0.5005 per unit so that is accepted as the faulty line GS 220 20º 20 15
section. The estimated fault location is equal to 0.5005 per GR 220 0º 20 15
GT 220 10º 20 15
unit and the percentage error in fault location is equal to
0.0375%. It can be concluded that the proposed technique has The series impedance and shunt admittance matrices of each
a successful performance against evolving faults. line section are as follows:
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 10
𝑧 𝑧 𝑧
[ ]
𝑦 𝑦 𝑦 𝑆
[ ]
𝑧 𝑧 𝑧 (
[ ]
𝑦 𝑦 𝑦 𝑆
[ ]
[ ]
𝑦 𝑆
[ ]
REFERENCES algorithm,‖ IEEE Trans. Smart Grid, vol. 2, no. 3, pp. 468-475,
Sep. 2011.
[1] A. G. Phadke and J. S. Thorp, Computer Relaying for Power [10] J. Zare, F. Aminifar, and M. Sanaye-Pasand, ―Synchrophasor-
Systems, New York, USA: Wiley, 2009. based wide-area backup protection scheme with data requirement
[2] P. M. Anderson, Power System Protection, New York, USA: analysis,‖ IEEE Trans. Smart Grid, vol. 30, no. 3, pp. 1410–1419,
McGraw-Hill, 1999. Mar. 2015.
[3] M. G. Adamiak, A. P. Apostolov, and M. M. Begovic, et al., [11] A. S. Dobakhshari and A. M. Ranjbar, ―A novel method for fault
―Wide area protection—Technology and infrastructures,‖ IEEE location of transmission lines by wide-area voltage measurements
Trans. Power Del., vol. 21, no. 2, pp. 601–609, Apr. 2006. considering measurement errors,‖ IEEE Trans. Smart Grid, vol. 6,
[4] M. Kezunovic, J. Mrkic, and B. Perunicic, et al., ―An accurate no. 2, pp. 874–884, Mar. 2015.
fault location algorithm using synchronized sampling,‖ Elect. [12] J. Miñambres, I. Zamora, A. Mazon, M. Zorrozua, and R. Alvarez-
Power Syst. Res. J., vol. 29, no. 3, pp. 161–169, May 1994. Isasi, ―New technique, based on voltages, for fault location on three-
[5] C. J. Lee, J. B. Park, J. R. Shin, and Z. M. Radojevié, ―A new two- terminal transmission lines,‖ Elect. Power Syst. Res., vol. 37-2, no. 2,
terminal numerical algorithm for fault location, distance pp. 143–151, May 1996.
protection, and arcing fault recognition,‖ IEEE Trans. Power Syst., [13] Y. H. Lin, C. W. Liu, and C. S. Yu, ―A new fault locator for three-
vol. 21, no. 3, pp. 1460–1462, Aug. 2006. terminal transmission lines—Using two-terminal synchronized
[6] Y. Liao and M. Kezunovic, ―Optimal estimate of transmission line voltage and current phasors,‖ IEEE Trans. Power Del., vol. 17, no. 2,
fault location considering measurement errors,‖ IEEE Trans. pp. 452–459, Apr. 2002.
Power Del., vol. 22, no. 3, pp. 1335–1341, Jul. 2007. [14] M. Brahma, ―Fault location scheme for a multi-terminal transmission
[7] J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke, line using synchronized voltage measurements,‖ IEEE Trans. Power
―Synchronized phasor measurement applications in power Del., vol. 20, no. 2, pp. 1325–1331, Apr. 2005.
systems,‖ IEEE Trans. Smart Grid, vol. 1, no. 1, pp. 20–27, Jun. [15] M. Brahma, ―New fault-location method for a single multi-
2010. terminal transmission line using synchronized phasor
[8] J. Izykowski, E. Rosolowski, P. Balcerek, M. Fulczyk, and M.M. measurements,‖ IEEE Trans. Power Del., vol. 21, no. 3, pp. 1148–
Saha, ―Accurate non-iterative fault location algorithm utilizing two- 1153, Jul. 2006.
end unsynchronized measurements,‖ IEEE Trans. Power Del., vol. [16] J. Izykowski, E. Rosolowski, M. M. Saha, M. Fulczyk, and P.
25, no. 1, pp. 72–80, Jan. 2010. Balcerek, ―A fault-location method for application with current
[9] J. Ma, J. Li, J. S. Thorp, A. J. Arana, Q. Yang, and A. G. Phadke,
―fault steady state component-based wide area backup protection
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2693322, IEEE
Transactions on Smart Grid
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 11
differential relays of three-terminal lines,‖ IEEE Trans. Power Del., [33] M. Kizilcay and T. Pniok, ―Digital simulation of fault arcs in
vol. 22, no. 4, pp. 2099–2107, Oct. 2007. power systems,‖ ETEP J., vol. 1, no. 1, pp. 55–60, Jan. 1991.
[17] C. W. Liu, K. P. Lien, C. S. Chen, and J. A. Jiang, ―A universal fault [34] H. Livani and C. Y. Evrenosoglu, ―A Machine Learning and
location technique for N-terminal transmission lines,‖ IEEE Trans. Wavelet-Based Fault Location Method for Hybrid Transmission
Power Del., vol. 23, no. 3, pp. 1366–1373, Jul. 2008. Lines,‖ IEEE Trans. Smart Grid, vol. 5, no. 1, pp. 51–59, Jan.
[18] M. Gilany, E. S. T. Eldin, M. M. A. Aziz, and D. K. Ibrahim, ―An 2014.
accurate scheme for fault location in combined overhead line with [35] A. Yadav, ―Comparison of single and modular ANN based fault
underground power cable,‖ in Proc. IEEE Power Eng. Soc. Gen. detector and classifier for double circuit transmission lines,‖ Int. J.
Meet., San Francisco, CA, Jun. 12–16, 2005, vol. 3, pp. 2521–2527. Eng. Sci. Technol., vol. 4, no. 2, pp. 122–136, 2012.
[19] M. Gilany, D. K. Ibrahim, and E. S. T. Eldin, ―Traveling-wave-based [36] A. Swetapadma, A. Yadav, ―All shunt fault location including
fault-location scheme for multiend-aged underground cable system,‖ cross-country and evolving faults in transmission lines without
IEEE Trans. Power Del., vol. 22, no. 1, pp. 82–89, Jan. 2007. fault type classification,‖ Elect. Power Syst. Res., vol. 123, pp. 1–
[20] X. Yang, M. S Choi, S. J. Lee, C.W. Ten, and S. I.Lim, ―Fault 12, 2015.
location for underground power cable using distributed parameter
approach,‖ IEEE Trans. Power Syst., vol. 23, no. 4, pp. 1809–1816,
Nov. 2008.
[21] C. W. Liu, T. C. Lin, C. S. Yu, and J. Z. Yang, ―A fault location
technique for two-terminal multisection compound transmission lines Ahmed Saber was born in Bani-Suef, Egypt, in
using synchronized phasor measurements,” IEEE Trans. Smart Grid, 1986. He received a M.Sc. degree in electrical
vol. 3, no. 1, pp. 113–121, Mar. 2012. power and machines engineering from Faculty of
[22] T.C. Lin, P. Y. Lin, and C. W. Liu, ―An Algorithm for Locating engineering, Cairo University in 2013.
Faults in Three-Terminal Multisection Nonhomogeneous Currently, he is presently a Ph.D. candidate at
Transmission Lines Using Synchrophasor Measurements,‖ IEEE faculty of engineering, Cairo University and works
Trans. Smart Grid, vol. 22, no. 1, pp. 82–89, Jan. 2014. as a teaching assistant at electrical power and
[23] S. Azizi, M. Sanaye-Pasand, and M. Paolone, ―Locating Faults on machines department, Cairo University.
Untransposed, Meshed Transmission Networks Using a Limited
Number of Synchrophasor Measurements,‖ IEEE Trans. Power
Syst, vol. 22, no. 1, pp. 4462–4472, 2016.
[24] S. Jiale, G. B. Song, X. U. Xu, and et al., ―Time-domain fault
location algorithm for parallel transmission lines using
unsynchronized currents,‖ Int. J. Elect. Power and Energy Syst., vol.
28, no. 4, pp. 253–260, 2006. Ahmed Emam received the B.Sc., M.Sc. and the
[25] J. C. Li and Y. P. Wu, ―A distributed circuit model for three-phase PHD degrees in Electrical Engineering from Cairo
transposed and untransposed transmission lines,‖ Elect. Power Syst. University, Egypt, in 1998, 2002 and 2010
Res., vol. 19, no. 6, pp. 187–194, Oct. 1990. respectively. Currently, he is a teacher in the
[26] M. M. Eissa, M. E. Masoud, and M. M. M. Elanwar, ―A novel back Faculty of Engineering, Cairo University. His
up wide area protection technique for power transmission grids research interests are in the area of Electric and
using phasor measurement unit,‖ IEEE Trans. Power Del., vol. 25, Magnetic Fields, Transient overvoltage and Digital
no. 1, pp. 270–278, Jan. 2010. Protection
[27] B. Naduvathuparambil, M. C. Valenti, and A. Feliachi,
―Communication delays in wide area measurement systems,‖ in
Proc. 34th Southeast. Symp. Syst. Theory, Huntsville, AL, USA,
Mar. 2002, pp. 118–122.
[28] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements
and Their Applications, New York, USA: Springer, 2008.
[29] H. Saadat, Power System Analysis, New York, USA: Mc-Graw-Hill, Hany Elghazaly received the Ph.D. degree in high
2002. Voltage Engineering from the Faculty of
[30] G. Benmouyal, ―Removal of DC-offset in current waveforms using Engineering, The University of Western Ontario,
digital mimic filtering,‖ IEEE Trans. Power Del., vol. 10, no. 2, pp. Canada, in 1986. He is presently a full Professor
621–630, Apr. 1995. with the Faculty of Engineering, Cairo University.
[31] IEEE Standard Definitions for the Measurement of Electric Power He has worked on High voltage, Electrostatic and
Quantities under Sinusoidal, Non-sinusoidal, Balanced, or power system protection. Also, he is a Senior
Unbalanced Conditions for Synchrophasor Measurements for Power Member of Industry Application Society, The
Systems, IEEE Std 1459-2010, Feb. 2, 2010. institute of Electrical and Electronic Engineering,
[32] IEEE Standard for Synchrophasor Measurements for Power IEEE, USA.
Systems, IEEE Std C37.118.1-2011, Dec. 28, 2011.
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.