CONCRETE COLLARS FOR PIPE OR BOX CULVERT EXTENSIONS

Bill of Materials General Notes

EXPANSION CONCRETE REINF. Concrete Collars shall be constructed of Class SI Concrete in


DIMENSIONS h Bar U Bar
BOLTS COLLAR BARS accordance with Section 503 of the Standard Specifications

STATION X Y No. No. Length No. Cu. Yd LBS


Existing
Reinforcement bars shall conform to Section 508 of the
376+67.44 2’-8" 2’-0" 4 6’-8" 4 0.3 20 Standard Specifications.
Box Culvert

8 8 Existing Headwall The concrete will be paid for at the contract unit price per cubic
yard for CONCRETE COLLAR. Reinforcement will be paid for
at the contract unit price per pound for REINFORCEMENT BARS.
Expansion Bolts, when required, will be paid for at the contract unit
price each for EXPANSION BOLTS of the size indicated, which price

12
shall include furnishing, drilling holes, and installing the expansion
bolts complete in place. These bolts shall extend at least 8 inches
U Bars into the new concrete.
3/4 } Exp.
Bolts
Total 4 0.3 20 (See Table for Spacing) 12 12
All h Bars 18 Long

REMOVE PORTION OF
ALL DIMENSIONS ARE IN INCHES
Proposed Pipe or HEADWALL IF NEEDED
UNLESS OTHERWISE NOTED.
Box Culvert Extension
NO. 4 h
PLAN OF CULVERT WITH STRAIGHT HEADWALL
BARS AT 12
Existing Box Culvert
CTS.

3/4 } Exp.
8 8 12 Bolts
U1 Bar U Bar U Bar
(See Table for Spacing)

12

CTS. (EACH SIDE)


U Bar

BARS* AT 12
Concrete Wingwall

12
Removal
Existing Box Culvert

NO. 4 h
Clear Height
U Bar
h Bar U1 Bar
Existing Culvert Clear
No. 4 h Span
Bars at 12
Cts. (TOP ONLY)

No. 4 h
Bars at 12
Lap Bars SIDE
Cts. Each Side
PROPOSED PIPE OR 16
SIDE
BOX CULVERT EXTENSION 8 3/4 } Exp.
3/4 } EXPANSION BOLT
Bolts
2 - #4 U BARS
(See Table for Spacing)
PLAN OF CULVERT WITH ANGLED WING WALLS & 1 - #4 U1 BARS
Proposed Pipe or
Box Culvert Extension PER COLLAR
FRONT PLACEMENT DETAILS
Proposed Pipe or FOR EXPANSION BOLTS
Box Culvert Extension
NUMBER OF EXPANSION BOLTS REQUIRED PER SIDE
EXTENSIONS < 15’ EXTENSIONS > 15’
12 12
H OR S NUMBER SPACING NUMBER SPACING
No. 4 h Bars

U OR U1 BARS at 12 Cts.
24 * *
30 2 18 2 18
Y
X
h BARS 36 2 24 2 24
HEIGHT

(H)

48 3 18 3 18

LAP BARS CLEAR SPAN (S) 60 4 16 3 24


(#4) U BAR
16
CLEAR

72 5 15 4 20
Proposed
Existing
Culvert
8 8 Culvert 84 5 18 4 24

96 15 21
6 5

108 19 24
6 5

120 18 21
Z 7 6

3/4 }EXP. 132 17 24


4 - #4 U BARS 8 6
BOLTS PER COLLAR
144 19 22
8 7
(SEE TABLE FOR SPACING) (#4) U1 BAR
CULVERT CONNECTION WITHOUT *MINIMUM ONE PER SIDE
EXISTING HEADWALL
FRONT
CONCRETE COLLARS FOR PIPE OR BOX CULVERT EXTENSIONS 33.1
F.A.P TOTAL SHEET
FILE NAME = USER NAME = Elgin 110 DESIGNED - REVISED - 10-17-11 SECTION COUNTY
RTE. SHEETS NO.
...\CADD SHEETS\Z00793SPL2014.dgn DRAWN - REVISED - STATE OF ILLINOIS REGION 2 / DISTRICT 2 STANDARD 303 129R WINNEBAGO 968 712
PLOT SCALE = 20.0000 ’ / IN. CHECKED - REVISED - DEPARTMENT OF TRANSPORTATION CONTRACT NO. 64988
PLOT DATE = 5/2/2013 DATE - REVISED - SCALE: SHEET NO. OF SHEETS STA. TO STA. FED. ROAD DIST. NO. ILLINOIS FED. AID PROJECT