Abstract – Significant penetration of induction motor loads into residential neighborhood and
commercial regions of local transmission systems at least partially determine a vulnerability to a fault
induced delayed voltage recovery (FIDVR) event. Highly concentrated induction motor loads with
constant torque could stall in response to low voltages associated with system faults. FIDVR is caused
by wide spread stalling of small HVAC units (residential air conditioner) during transmission level
faults. An under voltage load shedding scheme (UVLS) can be an effective component in a strategy to
manage FIDVR risk and limit the any potential disturbance. Under Voltage Load Shedding take
advantage of the plan to recovery the voltage of the system by shedding the load ways to alleviation
FIDVR.
Keywords: Fault induced delayed voltage recovery, Under voltage load shedding, Stall phenomenon,
Induction motor loads, Locked rotor current
406
Yun-Hwan Lee, Bo-Hyun Park, Seung-Chan Oh, Byong-Jun Lee, Jeong-Hoon Shin and Tae-Kyun Kim
increasing air conditioning load is further increased the shedding amount is set to about 1500MW, and it is shed
probability. The low voltage condition persists for a few whole amount at a time. [9]
seconds, the motor voltage cannot recovery quick and the The limitations of the current UVLS scheme for voltage
motor begins to stalling. Motor loads stalling is the reactive instability applied to the power system is that it does not
power consumption dramatically increase of the voltage consider the induction motor loads. The proportion of
instability occurs. [1] induction motor loads is highly (50-60% of the entire
It has been mentioned several ways in order to reduce system consumes reactive power), there are limitations in
the effect of FIDVR. Voltage recovery characteristics that review ignored.
vary greatly depending on the fault clearing time of after In the current scheme does not reflect the induction
the fault, there are ways to reduce the fault clearing time. motor load. Also, induction motor stall phenomenon cause
Considering the regional characteristics of the motor to FIDVR is not considered.
load proportion and the injection SVC and STATCOM in The characteristic of the ZIP model, the voltage
FIDVR occurs, reduces the effectiveness of the FIDVR. To decreased and the load decreased, alleviate the severity of
quickly reset the relay operation time, the plan shall take the system. If the motor load is considered to reflect the
into account the improvement of the performance of the load voltage recovery characteristics instability occurs.
equipment and protection coordination. It refers to the Voltage begins to drop gradually, and when a certain
phenomenon of delayed voltage recovery after the fault by level to fall rapidly lead to system instability. Due to the
the induction motor load stall. Planning studies have not characteristic of the motor load decreases, the voltage
been able to simulate FIDVR events very accurately reactive power consumption increases. The voltage drop in
because of inaccurate modeling of loads. [2] the motor load has the load recovery characteristics.
An under voltage load shedding scheme (UVLS) can be Progressively more reactive power is absorbed, the more
an effective component in a strategy to manage FIDVR voltage drop indicates the instability eventually causes
risk and limit the any potential disturbance. UVLS is the voltage. And selection of low-maintenance time is a
generally viewed as ineffective in preventing fast voltage very difficult problem. Low-maintenance time should be
collapse, quite effective in preventing voltage collapse. selected through the dynamic analysis noted.
Under Voltage Load Shedding take advantage of the plan to Long-term dynamics into consideration when performing
recovery the voltage of the system by shedding the load induction motor loads, OXL, ULTC and so on. Review the
ways to alleviate FIDVR. ZIP load model by applying the dynamics common to the
In this paper, we proposed the ways to alleviate scheme grid to be stable. In the case of static analysis, constant
for the delay voltage recovery by considering the power load model is unstable because after the fault, the
proportion of induction motor loads in the actual system. limit point of the grid is determined.
Load modeling is most important factor to calculate
amount of load shedding. Because of limited information,
2. The Current UVLS Scheme it is very difficult that select proper load model and load
in KEPCO System parameter. If proper load model is selected, it is possible
that sets minimum amount of load shedding. Statistics
The existing SPS applied to the KEPCO system has been can be used to select load model and load parameter.
designed to operate during extreme contingencies Ministry of Knowledge Economy announce first time the
including the outage of one route 765kV double circuit “power consumption map of the country” that contain 227
lines in the load concentrated area. [9] municipalities. [16]
The operation process of existing SPS is as follows. If a
contingency occurs, transmission line is dropped out within
5 cycles by protective relays that is operated at each end of 3. FIDVR Phenomenon
the transmission line. The signal that detected by protective
relay about contingency is transferred to the SCADA 3.1 A typical of FIDVR phenomenon
system in the KEPCO system. There are predefined 345kV
pilot buses which are sensitive with variation of the voltage Heavily loaded transmission lines during low voltage
to monitoring low voltage bandwidth violation. If one of conditions can result in operation of protective relays
two 345kV pilot bus voltage is lower than 340kV (0.9885 causing some transmission lines to trip in a cascading
p.u.) during 200 millisecond period, under voltage relays mode. Following fault clearing with transmission outages,
send the signal to the same SCADA system. If the SCADA motor loads draw very high current while simultaneously
system receives these two signals, in order to prevent attempting to reaccelerate, thereby making delayed the
voltage collapse, predetermined loads become shedding. voltage recovery process. While trying to recover, if the
The locations of shedding load are set by simulation results. voltage drops to a very low point for a sustained duration
Load shedding locations are selected among the location of due to system’s inability to provide reactive support, some
UFLS (Under Frequency Load Shedding). Currently, load motors may stall. Such radical stalling of motor further
407
Implementation of Under Voltage Load Shedding for Fault Induced Delayed Voltage Recovery Phenomenon Alleviation
408
Yun-Hwan Lee, Bo-Hyun Park, Seung-Chan Oh, Byong-Jun Lee, Jeong-Hoon Shin and Tae-Kyun Kim
power requirements in the stalled state, and the tripping Table 1. Induction motor parameter
caused by thermal protection. The induction motor load Parameters Value
must be modeled such that it is sensitive to dynamic Stator resistance (Rs) 0.078
variations in voltage and frequency, and emulates the Stator reactance (Xs) 0.065
typical characteristic of consuming more power at Rotor resistance (Rr) 0.044
increased speeds. Rotor reactance (Xr) 0.049
Magnetizing reactance (Xm) 2.67
Inertia Constant (H) 0.5
3.4.1 ZIP load model
The most commonly used static load model is the ZIP The only difference between the two types is where the
model. The ZIP model is a polynomial load model first rotor inductance is placed on a parallel circuit, or
expressed by a summation of exponential models that series circuit, with the second rotor inductance for a
represent constant impedance (Z), constant current (I), and double-cage machine. If a single-cage induction motor is
constant power (P) loads. The ZIP model is represented the used for analysis, X2 and R2 are set to 0 and the machine
power relationship to voltage magnitude as a polynomial type can be neglected. The CIM5 induction motors fully
equation, usually in the following from [1]: model rotor transient, making them third-order induction
machine models, and CIM5 can model online, or offline,
⎡ ⎤ motor starting. [15]
2 1
⎛V ⎞ ⎛V ⎞
P= P ⎢p ⎜ V ⎟ +p ⎜ V ⎟ +p ⎥
L 0 1 2 3 Table 1, shows the induction motor parameter. The
⎣⎢ ⎝ ⎠ 0 ⎝ ⎠ ⎥⎦ 0
(1) following are sample data for induction motor equivalents
⎡ ⎛V ⎞ ⎤
2 1
⎛V ⎞ representing small induction motor load. [17]
Q =Q ⎢ q ⎜ ⎟ +q ⎜ ⎟ +q ⎥
L 0
⎢⎣ ⎝ V ⎠
1
⎝V ⎠ ⎥⎦0
2
0
3
CIM5 load model this set of parameters can represent
the stalling process of induction motor load responding to
system disturbances on the whole.
Where p1 ,q1 are constant impedance load parameters, Eq. (2) shows the CIM5 type models use the following
p2 ,q2 are constant current load parameters, and p3 ,q3
equation as its representation for mechanical load torque
are constant power load parameters. And p1 +p2 +p3 =1 , (Tload). [6-7]
q1 +q2 +q3 =1 when V=V0 . ZIP model can, depending on
the coefficients, represent the constant impedance, the
Tload = Tnom (1 + Δω ) D (2)
constant current load and the constant MVA load.
Where Δω is the motor speed deviation from nominal
3.4.2 CIM5 load model
(per unit slip), D is the load damping factor. And the motor
The CIM5 models can be used to model either single- load torque at synchronous speed (Tnom). These CIM5
cage or double-cage induction motors including rotor flux models use the more conventional torque equation where
dynamics. The motor is modeled in the power flow as a bus Tnom is the initialized load torque. Tnom is initialized by
load where the entire load at a specific load id is taken as setting the polynomial component equal to one during
the steady-state motor load. These models may be applied initialization. At initialization, the CIM5 type models
to an individual load or a subsystem of loads. For example, pick up the total power for the specified load id at the
the CIM5 model can be applied to a specific load in order bus and together with the equivalent circuit data and the
to model a specific induction motor. The CIM5 model can bus voltage, calculates the initial slip and reactive power
be applied to all loads in a specific area in order to model consumption of the motor. The models include a relay
generic motor load using typical data. The load composition that can be used to trip the motor for an under voltage
can be any percentage of constant MVA, constant current condition. [7]
or constant admittance. The data input for the model are
the equivalent circuit impedances for either a Type 1 or a 3.5 Induction motor load modeling
Type 2 equivalent circuit model. [15]
Induction motor load model could be tripped off because
of under voltage protection, motor speed deviation is little
or great when disturbance occurrence. So the induction
motor load model with tuned parameters will be employed
for simulation of the problem on the delayed voltage
recovery and motor stalling, during and after the fault.
The main causing the delayed voltage recovery is
stalling behavior of induction motor loads. To understand
the delayed voltage recovery phenomena, reasonable
Fig. 2. Type 1, 2 used in CIM5 models in PSS/E induction motor load model should be developed. This
409
Implementation of Under Voltage Load Shedding for Fault Induced Delayed Voltage Recovery Phenomenon Alleviation
410
Yun-Hwan Lee, Bo-Hyun Park, Seung-Chan Oh, Byong-Jun Lee, Jeong-Hoon Shin and Tae-Kyun Kim
the induction motor load model under several different Fig. 5 shows the considering at a low proportion has the
scenarios. This simulation result demonstrates that the highest voltage, while the others lower voltage and delayed
same type of fault with different proportion of induction voltage recovery during the stalled condition. It indicates
motor loads can result in dramatically different voltage that the more the proportion motor loads, the delayed
stability problem. The dynamic models of induction motor voltage recovery process. And then, in this simulation, the
loads were further split equally into three different slip of induction motor model continuously increases after
proportions: i.e., considering at a high proportion, fault clearing and stops at last. Considering at a high
considering at a middle proportion, and considering at a proportion has the highest slip, while the others lower slip
low proportion. The fault at 2 sec consists of the voltage condition. The proportion of the motor load increases,
changes caused by the occurrence of an emergency. [1] voltage is lowered and a longer start-up time of the motor
And the evaluate voltage response of induction motor may damage the motor. To increase the rotor of the motor
loads was performed the simulation can be summarized as output torque arising from this should be larger. Increasing
follows: the load on the output of the induction motor slip increases.
• Low proportion induction motor loads on the total
loads: 40%
• Middle proportion induction motor loads on the total 5. Implementation UVLS Scheme for FIDVR
loads: 50% Phenomenon Alleviation
• High proportion Induction motor loads on the total
loads: 60% In this paper, evaluate the voltage response of induction
motor loads with under voltage load shedding, the dynamic
The loads except induction motor loads were applied by behaviors with the severe fault but different proportion of
constant current model about active power loads and induction motor loads.
constant impedance model about reactive power loads. The simulation can be summarized as follows:
• Load shedding observed before and after the voltage
recovery;
• Initial voltage recovery after the clearing of a fault to
less than 90 percent of pre-contingency voltage;
• Voltage recovery after the fault, a delay of more than
several seconds when the phenomenon is FIDVR;
• Induction motor stall: Q-V characteristic curve
observed, stall area less than 0.7 [pu].
411
Implementation of Under Voltage Load Shedding for Fault Induced Delayed Voltage Recovery Phenomenon Alleviation
Numerous variations in proportion induction motor load load shedding was done 0.5 sec after the occurrence of
have been considered. We found that the alleviated fault the emergency. The under voltage load shedding scheme
induced delayed voltage recovery process as shown in shows the voltage magnitude results after the emergency.
Fig. 6. In Fig. 6 are shown simulated voltage recovery time When the voltage is reduced to a certain value, the motors
plots at three different cases and implementation UVLS will be disconnected from the grid.
scheme for FIDVR phenomenon mitigation. After UVLS operation, the reduction in voltage recovery
Implementation UVLS scheme for FIDVR mitigation, time can be observed. Any action taken quickly will have
a more beneficial effect and could lead to an overall
Fig. 6. Implementation UVLS scheme for FIDVR mitiga- Fig. 7. Q-V characteristic curve with and without UVLS:
tion: (a) Considering at a low proportion; (b) (a) Considering at a low proportion; (b) Considering
Considering at a middle proportion; (c) Considering at a middle proportion; (c) Considering at a high
at a high proportion. proportion.
412
Yun-Hwan Lee, Bo-Hyun Park, Seung-Chan Oh, Byong-Jun Lee, Jeong-Hoon Shin and Tae-Kyun Kim
reduction in the delayed voltage recovery time of UVLS supplying heavy a/c motor loads.
required.
Implementation UVLS scheme for FIDVR mitigation,
load shedding was done 0.5 sec after the occurrence of the Acknowledgements
emergency. Steady state was attained 0.5 sec after the
emergency. The under voltage load shedding scheme This work was supported by the Human Resources
shows the voltage magnitude results after the emergency. Development program(No. 20134030200340) of the Korea
When the voltage is reduced to a certain value, the motors Institute of Energy Technology Evaluation and Planning
will be disconnected from the grid. (KETEP) grant funded by the Korea government Ministry
After UVLS operation, the reduction in voltage recovery of Trade, Industry and from the National Research
time can be observed. Any action taken quickly will have a Foundation of Korea (NRF) funded by the Korea
more beneficial effect and could lead to an overall government (MEST) (No. 2013-0017650) and Energy and
reduction in the delayed voltage recovery time of UVLS the Korea Electric Power Research Institute.
required.
And Table 4 shows the recovery time with and without
UVLS results under severe contingency. The effectiveness References
of the UVLS scheme was demonstrated through different
proportion of induction motor load case studies. [1] Hongbin Wu, Hsiao-Dong Chiang, Byoung-Kon Choi,
In Fig. 7 are shown simulated Q-V characteristic curve “Slow voltage recovery response of several load
observed plots at three different cases and implementation models: Evaluation study”, IEEE, Power and Energy
UVLS scheme for FIDVR phenomenon mitigation. Society General Meeting - Conversion and Delivery
Mechanical characteristic of induction motor load cause of Electrical Energy in the 21st Century, 2008.
stall phenomenon occurs. In this paper, we observed the [2] NERC Transmission Issues Subcommittee and
Ql curve, Ql is reactive power by mechanical load. And System Protection and Control Subcommittee, “A
Ql curve is observed with and without UVLS operation. Technical Reference Paper Fault-Induced Delayed
Induction motor stall area, generally the voltage 0.7 [pu] Voltage Recovery”, Version 1.2, June, 2009.
below. Considering the induction motor load stall occurred [3] Robert William Delmerico, Einar Vaughn Larsen,
in the case that can be observed. After UVLS operation, the Nicholas W. Miller, Reigh Allen Walling, “Method
Q-V characteristic curve in the stall area, go to run area can and apparatus for control of fault-induced delayed
be observed. We found that the alleviated fault induced voltage recovery (fidvr) with photovoltaic and other
delayed voltage recovery process as shown in Fig. 7. inverter-based devices”, United State Patent Appli-
cation Publication, No. US 2012/0049629 A1, 2012.
[4] Halpin, S.M., Harley, K.A., Jones, Robert A., Taylor,
6. Conclusion L.Y., “Slope-Permissive Under-Voltage Load Shed
Relay for Delayed Voltage Recovery Mitigation”,
This paper has proposed the UVLS schemes can be Power Systems, IEEE Transactions, Vol. 23, Issue. 3,
used against severe emergencies to alleviation FIDVR. p.1211~1216, 2008
When the stalled induction motor loads enter the stalled [5] Stewart, V., Camm, E.H., “Modeling of stalled motor-
condition, they will draw on considerable reactive power. loads for power system short-term voltage stability
The “sustained” increase in reactive power demand tends analysis”, Power Engineering Society General Meeting,
to delayed voltage recovery and can even cause voltage IEEE., Vol. 2, p.1887∼1892, 2005
collapse in certain situations. When the stalled motors are [6] Rui Esteves Araujo, “Induction Motors-Modelling
tripped from the grid, the voltage will enter the delayed and Control, Role of Induction Motors in Voltage
recovery condition. The more the stalled motors load, Instability and Coordinated Reactive Power Plann-
delayed the voltage recovery time. When voltage instability ing”, ISBN 978-953-51-0843-6, INTECH, 2012
occurred, load shedding was implemented. The voltage [7] Mingming Du, MinXiao Han, Zhihui Cao; Chu, F.,
recovery response is a very important dynamic Ei-Kady, M., “Utilizing STATCON to Resolve Delayed
characteristic of load behaviors. The ability of different Voltage Recovery Problem in SEC-WR”, Power and
proportion of induction motor loads to capture the fault Energy Engineering Conference, APPEEC 2009.
induced delayed voltage recovery time is evaluated in this Asia-Pacific, 2009.
paper. It is also demonstrated that the severe the fault, [8] Hua Bai, Venkataramana Ajjarapu, “A Novel Online
implementation UVLS has reduced the voltage recovery Load Shedding Strategy for Mitigating Fault-Induced
time. Future works on the implementation of synchro- Delayed Voltage Recovery”, Power Systems, IEEE
phasor measurement units (PMUs), high sampling Transactions on, Vol. 26, Issue. 1, p.294~304, 2011.
measurement devices, in recent years have enable utilities [9] Jeonghoon Shin, Suchul Nam, Jaegul Lee, Young do
to recorded FIDVR events in the grid, especially in areas Choy, Taekyun Kim, Hwachang Song, “Application
413
Implementation of Under Voltage Load Shedding for Fault Induced Delayed Voltage Recovery Phenomenon Alleviation
of Multi-step Under voltage Load Shedding Schemes Bo-Hyun Park He received B.S.
to the KEPCO System” Journal of Electrical Engin- degree in Electrical Engineering from
eering & Technology Vol.4, No.4, p. 476-484, 2009. Korea University, Korea in 2012. He is
[10] Diaz de Leon, J.A., Kehrli, B., “The Modeling Re- currently pursuing Unified M.S. and
quirements for Short-Term Voltage Stability Studies”, Ph.D. degree in the School of Electrical
Power Systems Conference and Exposition, IEEE PES, Engineering at Korea University.
2006
[11] Pourbeik, P.; Agrawal, B., “A hybrid model for
representing air-conditioner compressor motor be-
havior in power system studies”, Power and Energy
Society General Meeting - Conversion and Delivery Seung-Chan Oh He received B.S.
of Electrical Energy in the 21st Century, 2008 IEEE. degree in Electrical Engineering from
[12] NERC, “Real-Time Application of Synchrophasors Korea University, Korea in 2011. He is
for Improving Reliability”, October, 2010. currently pursuing Unified M.S. and
[13] Philip Irminger, “Air Conditioning Stall Phenom- Ph.D. degree in the School of Electrical
enon. Testing, Model Development, and Simulation”, Engineering at Korea University.
Transmission and Distribution Conference and Ex-
position (T&D), 2012 IEEE PES,
[14] N Lu, YL Xie, Z Huang, “Air Conditioner Com-
pressor Performance Model”, Pacific Northwest, August. Byong-Jun Lee He received the M.S.
2008 and Ph.D. degrees in electrical engin-
[15] PTI, “PSS/E Program Operational Manual,” Vol. 2. eering from Iowa State University,
[16] DSA POWER TOOLS, “TSAT User Manual”, TSAT, Ames, in 1991 and 1994, respectively.
Power-Tech. He is currently a Professor in the
[17] Ministry Knowledge Economy, “Power consumption Department of Electrical Engineering,
map of the country”, http://www.mke.go.kr Korea University.
[18] P. Kundur, Power System Stability and Control. New
York: McGraw-Hill, 1994.
[19] Glavic, M, Novosel, D.; Heredia, E.; Kosterev, D.
“See It Fast to Keep Calm: Real-Time Voltage Control Jeong-Hoon Shin He received his B.S,
Under Stressed Conditions”, IEEE Power and Energy M.S and Ph.D. degrees in Electrical
Magazine, vol. 10, issue 4, July 2012 Engineering from Kyung Pook Na-
[20] “Under voltage Load Shedding Protection”, Working tional University, Korea, in1993, 1995
Group C-13, System Protection Subcommittee IEEE and 2006 respectively. He is a senior
PES Power System Relaying Committee Draft 4.1 member of the Technical Staff in the
[21] Mahari, A., “A fast online load shedding method for Power System Analysis Center at
mitigating FIDVR based on novel stability index”, KEPRI which is a research center of
Electrical Engineering (ICEE), 2013 21st Iranian Korea Electric Power Corporation (KEPCO), Korea.
Conference on. May 2013
[22] N. Lu, B. Yang, Z. Huang, and R. Bravo, “The system
impact of air conditioner under-voltage protection Tae-Kyun Kim He received his B.S,
schemes,” in Proc. IEEE Power Eng. Soc. General M.S and Ph.D. degrees in Electrical
Meeting, Jul. 2009. Engineering from Hanyang University,
Korea, in1986, 1989 and 1993 respect-
ively. He is a principal member of the
Technical Staff in the Power System
Yun-Hwan Lee He received the M.S. Analysis Center at KEPRI which is a
degree in electrical engineering from research center of Korea Electric
Korea University, Seoul, Korea, in Power Corporation (KEPCO), Korea. He has been project
2010. He is currently a Ph.D. candidate leader in several simulator studies related to development
in the Department of Electrical Engin- of various models and operation.
eering, Korea University.