Preventing Maintenance at 132/220/400K

Time
Sr.No Name of Sub-Station Name of element / Bay Date
From

1 300 Ah Battery bank 2/16/2021 12:00

220 kV s/s Bassi


Pathana

2 100 MVA T-3 2/17/2021 12:15

3 66 kv Sanjeev bhatia 2/18/2021 10:10

20 MVA T-4 and


4 220 kv s/s G-3 11 KV Incomer No. 4
2/18/2021 11:10

20 MVA T-6 and


5 2/18/2021 12:40
11 KV Incomer No. 5
Maintenance at 132/220/400KV Substations for the period of to .
Time
PTW No. Detail of work done
To

Battery installation, wiring from battery bank to


2
charger, charger to DCDB done

100 MVA P/T/F T3, fresh oil top up through


13:45 3
main conservator tank (1 drum)

66 kv Breaker protection testing ,c and r panel


42 cleaning, Marshelling boxes cleaning Breaker
11:10
and isolator Lubrication and changed the
jumper between CT & line isolator of Y phase

20 mva p/t/f protection testing,c and r panel


cleaning, Cleaning of CT and T/F bush discs,
12:35 43 Marshelling boxes cleaning , Breaker
Lubrication. All 11 kv breakers cleaning,
lubrication . terminals contact tightning .

20 mva p/t/f protection testing,c and r panel


cleaning, Cleaning of CT and T/F bush discs,
44 Marshelling boxes cleaning , NTC Repaire
14:30
work, Breaker Lubrication. All 11 kv breakers
cleaning, lubrication . terminals contact
tightning .
to .

Name & Designation of officer/official who Remarks


supervised maintenance work (If any)

Battery Bank permit is in


Er. Sukhraj Singh Cheema SSE Er.
progress, batteries are kept on
Prem Kumar AAE boost charging mode

Er. Sukhraj Singh Cheema SSE Er.


Prem Kumar AAE

Er. Sukhraj Singh Cheema SSE Er.


Narinder Singh JE

Er. Sukhraj Singh Cheema SSE Er.


Narinder Singh JE

Er. Sukhraj Singh Cheema SSE Er.


Narinder Singh JE