Professional Documents
Culture Documents
MMR - Evaluation of Damping Ratio For The Seismic Analysis of Tall Buildings
MMR - Evaluation of Damping Ratio For The Seismic Analysis of Tall Buildings
Abstract: This paper examines damping ratios in tall buildings in California inferred from motions recorded in instrumented buildings
Downloaded from ascelibrary.org by "California,Univ Of Irvine" on 04/30/18. Copyright ASCE. For personal use only; all rights reserved.
during earthquake motions. A total of 41 measured seismic responses from 14 buildings with 20 or more stories are analyzed using a para-
metric least-squares system identification technique in the time domain. The reliability of the inferred damping ratios is first examined based
on the sensitivity of the structural response to variations in modal damping ratios. Using only inferred damping ratios deemed reliable, it is
found that the damping ratios of the fundamental mode decrease with increasing building height, reaching values lower than 2.5%—the
damping value that is commonly recommended for seismic design in the United States for buildings taller than 150 m. The variation of
damping of higher modes with frequency is then examined by studying the results of those buildings where damping ratios of at least the first
three modes are reliably inferred. It is shown that the variation of damping with frequency follows an approximately linear trend. No evidence
was found to suggest that a mass-proportional model could be appropriate. The amplitude dependency of damping is then analyzed for
buildings having four or more recorded earthquakes, finding no statistical correlation between the peak roof drift ratio and the identified
fundamental damping ratio. DOI: 10.1061/(ASCE)ST.1943-541X.0001628. © 2016 American Society of Civil Engineers.
Introduction no new strong-motion data was added. The work of Satake et al.
(2003) collected data from various sources in Japan to assemble
Estimation of the response of tall buildings to seismic loading a new database of damping values coming from 205 buildings.
requires knowledge of the damping in the building. Unlike mass The majority of the data, however, corresponds to low-amplitude
and stiffness matrices, which can be determined from the geometry motions: only 18 of the 205 buildings were subjected to earthquakes,
of the structure, the only reliable way to assess the damping in a of which only 4 were higher than 150 m. Fritz et al. (2009) collected
building is through measurements of the structural response when 1,572 damping ratio measurements from full-scale tests on 972 dif-
subjected to dynamic loads. Several studies have gathered data on ferent buildings. The database was compiled from smaller datasets
damping ratios from the recorded response of buildings. Using and other public sources, and had a fair share of strong motion data:
simplified methods, Blume (1970) estimated 38 values of damping 260 data points came from 93 buildings subjected to earthquakes,
ratio for the fundamental mode of 5 buildings, all in the range of but only 10 of those buildings were analyzed using parametric
20–30 stories, subjected to small tremors caused by underground system identification schemes. Furthermore, the vast majority of
nuclear detonations. In a later publication, Blume studied 230 damp- high-quality damping data corresponds to low-amplitude sources.
ing ratios from 74 buildings subjected to low-amplitude motions There is a general agreement that damping is expected to increase
(Scholl 1975). The resulting histograms for damping from these two with amplitude at small deformation levels (Tamura and Yoshida
publications represent the first attempt to describe uncertainty in 2008; Spence and Kareem 2013), and therefore, it is not clear to what
damping. Haviland (1976) analyzed a set of 244 damping values extent damping data from low-amplitude motions is applicable to
gathered from 139 buildings and constructed probability distribu- seismic analysis. Jeary (1986) showed that damping ratio increased
tions for the damping ratio of the fundamental mode. The damping with increasing amplitude in 17 buildings subjected to forced vibra-
estimates were collected through a literature survey of 39 references, tions at very low amplitudes (the peak roof displacement in these
where the vast majority of the data came from low-amplitude sour- tests was less than 3 mm), proposing a piecewise linear model for
ces such as nuclear, forced, micro-tremors, wind, and ambient vi- amplitude dependency. Li et al. (2000) confirmed this trend in a
brations. Davenport and Hill-Carroll (1986) developed a database series of observations of a 120-m-tall building subjected to ampli-
of 165 buildings subjected to full-scale damping tests, including all tudes up to a peak roof drift ratio of about 0.01%. Tamura et al.
the data from Haviland (1976). Unfortunately, the database did not (2000) corrected the piecewise linear model to take into account char-
add any new data on damping inferred from high-amplitude motion. acteristics observed in the Japanese damping database. An increase in
Lagomarsino (1993) extended this database to a total of 185 build- damping with amplitude has also been observed when comparing
ings, adding data points collected from other investigations. Again, values inferred from ambient vibrations with those obtained from
seismic motions. Celebi et al. (1993) and Celebi (1996) studied
1
Ph.D. Candidate, Dept. of Civil and Environmental Engineering, the damping ratios of five buildings, first under ambient vibrations
Stanford Univ., Stanford, CA 94305 (corresponding author). E-mail: and then subjected to the 1989 Loma Prieta earthquake, observing in
ccruzd@stanford.edu all cases that the damping ratios inferred from strong-motion data for
2
Associate Professor, Dept. of Civil and Environmental Engineering, the first mode were significantly larger than those obtained from am-
Stanford Univ., Stanford, CA 94305. E-mail: emiranda@stanford.edu
bient-vibration data. All these investigations lead to the conclusion
Note. This manuscript was submitted on November 12, 2015; approved
on June 18, 2016; published online on July 25, 2016. Discussion period that damping recommendations for earthquake-resistant design
open until December 25, 2016; separate discussions must be submitted should come from the analysis of strong-motion data.
for individual papers. This paper is part of the Journal of Structural En- There are few studies on damping values inferred from the
gineering, © ASCE, ISSN 0733-9445. seismic response of buildings. Using simplified spectral methods,
attention should be paid to damping ratios of buildings subjected to between the recorded and predicted responses in the time domain.
earthquake motions and inferred employing modern system iden- This technique is further investigated to establish confidence inter-
tification techniques. Beck and Jennings (1980) and McVerry vals for the damping estimates, as well as to assess the reliability
(1979) developed a system identification technique based on the of inferred damping ratios. Using only damping ratios deemed
least-squares minimization between the measured seismic response reliable, the relationship between the damping ratio of the funda-
of a building and that predicted by a parametric model. The former mental mode and the building height is evaluated and compared to
formulated the problem in the time domain and applied it to a published recommendations. In the same spirit, the relationship be-
42-story building in Los Angeles, and the latter did it in the fre- tween the damping ratio of higher modes and their corresponding
quency domain, analyzing 10 buildings subjected to the San modal frequencies is studied and compared to the commonly used
Fernando earthquake of 1971, of which three buildings had 20 sto- Rayleigh damping. Finally, the relationship between damping and
ries or more. Li and Mau (1991) and Mau and Aruna (1994) used a amplitude of structural response is examined.
similar formulation in the time domain to analyze three buildings
of 6, 13, and 15 stories. Li and Mau (1997) analyzed 21 buildings
subjected to the 1987 Whittier and 1989 Loma Prieta earthquakes, Buildings Analyzed
with only three buildings having 20 stories or more. Safak (1991)
A total of 41 seismic responses, coming from 14 buildings with
presented a discrete-time filter approach to the identification of
20 stories or more, were analyzed. Table 1 shows a summary of
structural parameters under earthquake conditions that was applied
the 14 buildings, including their location, number of stories, height,
to five buildings after the 1989 Loma Prieta earthquake (Safak and
lateral-force resisting system, material, and number of earthquakes
Celebi 1991, 1992; Celebi and Safak 1991, 1992; Celebi et al.
analyzed. Table 2 shows information about the earthquakes consid-
1993; Celebi 1996), only two of which exceeded 20 stories in
ered. All recorded data was obtained from the Center for Engineer-
height. Goel and Chopra (1997) identified the damping ratio of
ing Strong Motion Data (USGS, CGS, and ANSS 2014).
22 buildings under the Northridge earthquake of 1994; only three
of the buildings had 20 stories or more. Some of these studies were
summarized and form the basis for damping recommendations in System Identification
the ATC-72-1 document (PEER/ATC 2010) for analysis and design
of tall buildings. Reinoso and Miranda (2005) analyzed six tall System identification is a tool to obtain information about a system
buildings located in California and found damping ratios ranging from its measured dynamic response. System identification tech-
from 4 to 6% for concrete buildings and 0.5–8% for steel buildings. niques can be categorized in two types: nonparametric and para-
More recently, Bernal et al. (2015) analyzed the first mode damping metric. In a nonparametric technique, the system is treated like
ratio of 68 buildings subjected to several earthquakes and provided a “black box” and the objective is to identify a functional relation-
some equations to estimate damping. Only five buildings exceeded ship between the inputs and outputs of the system, typically
20 stories in height. In spite of the advances in modern system iden- through its transfer function. These models have several disadvan-
tification techniques, there is still a large variability and hence un- tages such as the lack of prior information about the structure, the
certainty in estimating damping ratios in tall buildings. The same fact that the inferred function inevitably requires a parametric
building can have different results when analyzed under different model for physical interpretation, and that they are not capable
earthquakes, and different identification methods may yield differ- of predicting the response and therefore are not suitable for the seis-
ent results for the same earthquake (Nakajima et al. 2012). Little mic design of a structure (Beck 1978). Briefly, a parametric system
attention has been devoted to the reliability of the inferred damping identification procedure consists of finding the set of parameters
ratios, which has led to damping databases that sometimes include that minimizes the difference between the response recorded by
different values for the same building analyzed by different inves- sensors installed in a building and the one predicted by a numerical
tigators. The lack of reliability testing has also led some of the pre- model of the building. Different identification techniques mainly
viously mentioned studies to report excessively large damping differ in the numerical model employed, in the objective function
ratios for higher modes, or modal period ratios that make no physi- used to measure the difference between the computed and mea-
cal sense. These issues, together with the scarcity of data for tall sured response, and in the optimization algorithm employed to find
buildings, highlight the need for new, reliable damping estimates the parameters that minimize the objective function. If a modal re-
for high-rise buildings. sponse history analysis is used to compute the seismic response of
The Center for Engineering Strong Motion Data (CESMD) is a the model of the structure, the problem involves the estimation of
cooperative center that integrates the earthquake strong-motion the modal periods, critical damping ratios, mode shapes, and modal
data collected by the U.S. Geological Survey (USGS) and the participation factors of the model that will best reproduce the re-
California Geological Survey (CGS). Their database of monitored corded structural response. This process can be conducted in either
structures includes several tall buildings, some of which have been the time domain (e.g., Beck and Jennings 1980) or in the frequency
Table 2. Earthquakes Considered in This Investigation Modal Minimization in the Time Domain
Number Earthquake Year MW Depth (km) In a linear, modal superposition model, the response of each mode
1 Landers 1992 7.3 1.1 is governed by the following equation of motion:
2 Calexico (1) 2010 7.2 32.3
3 Loma Prieta 1989 7.1 18.0 D̈n ðtÞ þ 2ωn ξ n Ḋn ðtÞ þ ω2n Dn ðtÞ ¼ −üg ðtÞ ð1Þ
4 Hector Mine 1999 7.1 6.0
5 Northridge 1994 6.7 19.0 where D̈n , Ḋn , and Dn correspond to the relative acceleration,
6 Big Bear 1992 6.5 1.0 velocity, and displacement of a single degree of freedom system
7 South Napa 2014 6.0 11.3 with unit mass, natural circular frequency ωn, and critical damping
8 Whittier 1987 5.9 9.5 ratio ξ n ; üg = ground acceleration, and the subindex n denotes the
9 Ocotillo 2010 5.7 6.9 mode number. The modal displacements unj at the jth degree of
10 Canyon dam 2013 5.7 11.0 freedom of the structure can then be computed as
11 Sierra Madre 1991 5.6 12.0
12 Alum Rock 2007 5.4 9.2 unj ðtÞ ¼ Γn ϕnj Dn ðtÞ ð2Þ
13 Chino Hills 2008 5.4 13.6
14 Borrego Springs 2010 5.4 14.0 where Γn = modal participation factor; and ϕnj = mode shape for
15 La Habra 2014 5.1 4.8
mode n evaluated at the jth degree of freedom. Multiplying Eq. (1)
16 Calexico (2) 2010 4.9 5.4
17 Inglewood 2009 4.7 15.0
by Γn ϕnj yields
18 Whittier Narrows 2010 4.4 18.0
ünj ðtÞ þ 2ωn ξ n u̇nj ðtÞ þ ω2n unj ðtÞ ¼ −Γn ϕnj üg ðtÞ ð3Þ
19 Encino 2014 4.4 9.9
20 Berkeley (2) 2011 4.0 9.8
21 Berkeley (1) 2011 3.8 9.6 where ünj , u̇nj , and unj correspond to the acceleration, velocity, and
22 LA Airport 2012 3.7 10.8 displacement of the jth degree of freedom for mode n relative to the
ground, respectively.
If only N modes are considered to have a significant influence in
domain (e.g., McVerry 1979). An important advantage of these the seismic response of the building, then the response of the struc-
methods is that the inferred parameters correspond to those that ture can be calculated as
need to be used by practicing structural engineers to reproduce X
N
the recorded response using conventional modal analyses. Another û¨ tj ðtÞ ≈ üg ðtÞ þ Γn ϕnj D̈n ðtÞ ð4Þ
family of methods for the identification of linear structures is the n¼1
use of discrete-time filters (Safak 1991). In this case, the identifi-
cation problem consists of obtaining the optimal parameters of the where û¨ tj = total (absolute) acceleration at the jth degree of
filter that will best reproduce the output signals. These parameters freedom.
of the filter can later be related to the dynamic properties of the The objective function considered in this study is defined as the
¨
difference squared between the predicted relative acceleration ûðtÞ
structure. These methods are widely used in other engineering
fields, so there are several software packages available to perform and the one measured by the sensors in the building üðtÞ normal-
the identification (e.g., Ljung 1999, 2003). Another commonly ized by the measured relative acceleration summed over all times
used family of methods uses a subspace approach (Van Overschee and sensors
and De Moor 1994; Di Ruscio 1996). The advantages of these
methods can be found in Viberg (1995) and Favoreel et al.
X
N sen X
τ
½üj ðiΔtÞ − û¨ j ðiΔtÞ2
JðθÞ ¼ Pτ 2
ð5Þ
(2000). There are numerous other system identification procedures, j¼1 i¼1 k¼1 ½üj ðkΔtÞ
whose details can be found in several literature review articles
(e.g., Ghanem and Shinozuka 1995; Beck 1996; Safak 2001; where N sen = number of sensors above ground level Δt and τ = the
Gevers 2006; Papagiannopoulos and Beskos 2012). time step and the number of points in the signal, respectively. This
where
08 9 8 9 2 31
> ω1 > > ξ1 > Γ1 ϕ11 ··· ΓN ϕN1
>
< >
= >
< > = 6
B . . .. .. .. 7C
θ¼B 6
@> .. >; > .. >; 4 . . . 7C
5A ð7Þ
>
: > >
; : ; >
ωN ξN Γ1 ϕ1N sen ··· ΓN ϕNN sen
Fig. 1. Continuum model (reprinted from Miranda and Akkar 2006,
When designing buildings, the most commonly used type of © ASCE)
analysis is linear elastic response spectrum modal analysis. Further-
more, the base of the structure is typically assumed as fixed.
Eqs. (2)–(4) provide the time history response of fixed-base struc- Mode Inclusion Criteria
tures, so identified modal properties by minimization of the objec-
tive function [Eq. (5)] provide the estimation of modal periods and It is well known that only a small number of modes contribute sig-
damping ratios that best reproduce the measured response in com- nificantly to the seismic response of buildings. Therefore, there is a
bination with the type of analysis in which these properties will be need for cut-off criteria to eliminate parameters of modes that have
used. In particular, the damping ratios identified in this study do not a negligible contribution to the response parameter being consid-
correspond to those of the superstructure alone or what is some- ered at instrumented locations in the structure. This is important
times referred to as the inherent structural damping, but rather they because, if a mode does not contribute significantly to the response
represent the damping ratio of the combined soil-foundation- of the structure, the identified damping ratio may not be reliable.
structure system which include radiation damping due to rocking This study uses cut-off criteria based on the Arias modal contribu-
of the soil–structure interaction. These dynamic properties are often tion factor defined in Eq. (8). This parameter measures the relative
referred to as the “effective” dynamic properties of the equivalent, contribution of the Nth mode with respect to the total calculated
fixed-base model of the building (Veletsos 1977). Therefore, the response with N modes of vibration. In this investigation, only
identified damping ratios correspond to those that will best repro- those modes with an Arias modal contribution higher than 5% were
duce the measured response of the building of a fixed-base linear considered as relevant for the response of the structure.
elastic model when using as input a recorded motion at the base of Pτ PN sen 2
the structure. k¼1 j¼1 ½ünj ðkΔtÞ
MCn ¼ PN Pτ PN sen 2
ð8Þ
Because the optimization problem is highly nonlinear, it is very i¼1 k¼1 j¼1 ½üij ðkΔtÞ
important to establish a good starting point for the minimization
algorithm in order to avoid convergence into local minima. To ob- There are some cases where the ground motion is not strong enough
tain a set of initial parameters, a simplified model of the building in certain range of frequencies to significantly excite the first, and
was used. The model considers the building as a continuous system sometimes also the second, mode of the structure. This may occur,
consisting of a cantilever flexural beam laterally attached to a shear for example, in the case of low-magnitude earthquakes that may
beam such that both undergo the same lateral deformation along the produce significant response of higher modes but negligible re-
height (Fig. 1), and it is governed by a small number of parameters: sponse of the first mode. In this case, the contribution of the first
the fundamental period T 1 , the modal damping ratios ξ n , and the mode may be very small and the damping ratio inferred for the first
lateral stiffness ratio α, which measures the relative contribution of mode may not be reliable. The inclusion criteria of inferred damp-
the flexural rigidity and shear rigidity in the flexural and shear ing ratios for the first two modes are based on the amplification Rn
beams, respectively. Based on these parameters, mode shapes, of the 1% damped floor acceleration spectral ordinates averaged in
period ratios, and modal participation factors are easily computed. the vicinity of the modal period in question for the motion recorded
This model has previously been used to obtain approximate floor at the roof with respect to that of the motion recorded at the base of
acceleration and drift ratio demands, and to identify the dynamic the building as follows:
properties of buildings (Miranda and Taghavi 2005; Reinoso and
Miranda 2005; Miranda and Akkar 2006). The mathematical S̄Roof
a ðT n Þ
Rn ¼ ð9Þ
description of the model, as well as recommended values for α S̄Ground
a ðT n Þ
depending on the structural system of the building, can be found
in Miranda and Reyes (2002), whereas closed form equations of where S̄a ðT n Þ corresponds to the average of the 1% damped floor
modes shapes, period ratios, and modal participation factors can acceleration spectral ordinates within the period range defined by
be found in Miranda and Taghavi (2005) and Miranda and Akkar ½0.9T n ; 1.1T n , plus 0.01g. The purpose of the shift in the spectral
(2006). ordinates is to avoid numerical issues when values are close to zero.
1.5 0.6
1.0 0.4
0.5 0.2
0.0 0.0
0 2 4 6 8 0 2 4 6 8
Downloaded from ascelibrary.org by "California,Univ Of Irvine" on 04/30/18. Copyright ASCE. For personal use only; all rights reserved.
Fig. 2. Roof and ground acceleration response spectrum (ξ ¼ 1%) for the E–W direction of building LA-52: (a) 1994 Northridge earthquake;
(b) 2008 Chino Hills earthquake
The cut-off criteria employed were R1 > 2.2 and R2 > 1.6. An than 1% in the objective function. It can be seen that the damping
example of the application of these criteria is illustrated in Fig. 2 interval for the 1992 Landers M W 7.3 earthquake is significantly
for building LA-52. Fig. 2(a) shows ground and roof lightly narrower than the one computed for 1994 Northridge MW 6.7 earth-
damped (1% damped) response spectra for the 1994 M6.7 quake, indicating that there was a larger sensitivity of the acceler-
Northridge earthquake where it can be seen that there is significant ation response to changes in the damping ratio in the Landers
amplification of spectral ordinates of the motion recorded at the earthquake than in the Northridge earthquake. Although a damping
roof relative to spectral ordinates of the motion recorded at the ratio was adequately identified for both events the damping ratio
ground for periods in the vicinity of the first mode period (approx- inferred from the Landers earthquake, an event with larger magni-
imately 6 s); with a computed amplification factor of R1 ¼ 6.97, tude than the Northridge earthquake produces a stronger response
indicating that the first mode is sufficiently excited during this to the first mode and therefore yields a more reliable estimate of the
earthquake. The vertical lines in these figures indicate the period damping ratio of the fundamental period of the building. Similarly,
range used to calculate the first mode amplification factor R1. the damping ratio inferred from the 2014 La Habra M W 5.1 earth-
Meanwhile, Fig. 2(b) shows ground and roof 1% damped response quake, although similar in value to that inferred from the Landers
spectra for the 2008 M5.4 Chino Hills earthquake where almost no earthquake, is less reliable because the objective function is not as
amplification of spectral ordinates occur for periods in the vicinity sensible to small changes in the damping ratio as it was during the
of the first mode in which an amplification factor of R1 ¼ 1.60 is Landers earthquake.
computed. Therefore, the damping ratio inferred for the fundamen-
tal mode under this particular earthquake is not considered in fur-
ther analyses. Application to Tall Buildings
18
16
14
12
10
4
Downloaded from ascelibrary.org by "California,Univ Of Irvine" on 04/30/18. Copyright ASCE. For personal use only; all rights reserved.
0
0 2 4 6 8 10 0 2 4 6 8 10 0 2 4 6 8 10
1
[%] 1
[%] 1
[%]
Fig. 3. Variation of the objective function, J, with changes in the damping ratio of the first mode for building LA-52, during three different
earthquakes
4% 4%
3% 3%
2% 2%
1% 1%
0% 0%
0 50 100 150 200 250 300 0 50 100 150 200 250 300
(a) Building height (m) (b) Building height (m)
Fig. 4. Identified damping ratios for the fundamental mode versus building height, compared to some proposed recommendations: (a) steel buildings;
(b) reinforced concrete buildings
Table 3. Coefficients for Power Regression by Fritz et al. (2009) slightly overestimates the data, and may be
Material A B R2 Function form thought of as an upper bound. For concrete buildings [Fig. 4(b)]
the data is very scarce. However, it is worrisome that, with the ex-
Steel 0.90 −0.76 0.45 ξ1 ¼ A · HB
ception of Satake et al. (2003), all recommendations overestimate
Concrete 15.60 −1.31 0.81
the data for buildings higher than 150 m. The 2% constant value
recommended in the performance-based PEER guidelines also ap-
pears to be high for buildings taller than 180 m. Values of damping
(2010), and Bernal et al. (2015). For recommendations that use the ratios lower than 2% from this investigation are consistent to
number of stories as regressors, an average height of 3.96 m (13 ft) those reported by Smith and Willford (2007) or by Spence and
per story was considered to transform the number of stories into Kareem (2013).
building height. Caution should be taken when comparing these
regressions because they have been calculated from damping ratios
Damping of Higher Modes
that have been collected from different loading conditions, using
different system identification methods and assumptions. Never- To study the damping ratio of higher modes, the three buildings
theless, they all show a similar descending trend with building with the highest number of recorded events were selected: LA-32,
height. For steel buildings [Fig. 4(a)], it can be seen that the curve LA-52, and LA-54. SD-21 and LA-20 also have records available
by Bernal agrees with the data over all the height range. The equa- from several earthquakes, but their response is governed primarily
tion proposed by Satake et al. (2003) underestimates the damping by only the first two translational modes of vibration in each direc-
ratios inferred in this study. This is probably because most of the tion, so they were not considered in this part of the study. Fig. 5
data used by Satake and colleagues is based on very small vibration shows the relation between the identified damping ratios ξ n in each
amplitudes. For buildings over 150 m, the equation recommended of the three buildings in each of the earthquakes when plotted
6% 3% 3%
4% 2% 2%
2% 1% 1%
R² = 0.56 R² = 0.76 R² = 0.48
0% 0% 0%
0.0 1.0 2.0 3.0 4.0 0.0 1.0 2.0 3.0 0.0 0.5 1.0 1.5 2.0
Frequency (Hz) Frequency (Hz) Frequency (Hz)
Downloaded from ascelibrary.org by "California,Univ Of Irvine" on 04/30/18. Copyright ASCE. For personal use only; all rights reserved.
6% 3% 3%
4% 2% 2%
2% 1% 1%
R² = 0.70 R² = 0.44 R² = 0.64
0% 0% 0%
0.0 1.0 2.0 3.0 0.0 1.0 2.0 3.0 0.0 0.5 1.0 1.5 2.0
Frequency (Hz) Frequency (Hz) Frequency (Hz)
Fig. 5. Identified damping ratios versus modal frequencies, in the longitudinal and transverse directions, for three tall buildings in Los Angeles
2% 2% 2%
1% 1% 1%
0% 0% 0%
0.00% 0.10% 0.20% 0.30% 0.00% 0.05% 0.10% 0.15% 0.20% 0.00% 0.05% 0.10% 0.15%
Peak roof drift ratio Peak roof drift ratio Peak roof drift ratio
1 SD-21 (H = 92 m) 1 LA-20 (H = 52 m)
7% 12%
Longitudinal Longitudinal
6%
Downloaded from ascelibrary.org by "California,Univ Of Irvine" on 04/30/18. Copyright ASCE. For personal use only; all rights reserved.
10%
Transverse Transverse
5%
8%
4%
6%
3%
4%
2%
1% 2%
0% 0%
0.00% 0.05% 0.10% 0.15% 0.00% 0.10% 0.20% 0.30% 0.40%
Peak roof drift ratio Peak roof drift ratio
Fig. 6. Identified damping ratios for the fundamental mode as a function of the peak roof drift ratio
damping has also been observed when comparing values inferred they provide information of the best damping ratios to use in con-
from ambient vibrations with those from strong-motion data nection with the most typical model used in standard engineering
(Celebi et al. 1993; Celebi 1996). However, there is very little in- practice. The reliability of the inferred damping ratios was assessed
formation regarding the variation of damping with increasing am- based on quantifying the sensitivity of the objective function to
plitude under earthquake ground motions, and buildings that have changes in the damping ratio and the amplification of lightly
several recorded events provide an excellent opportunity to study damped roof acceleration spectral ordinates with respect to those
this trend. The variation of inferred damping ratios of the funda- computed with the ground motion. Using only reliable damping
mental mode with changes in PRDR is examined in Fig. 6 for estimates, the variation of the first-mode damping with height
all buildings with four or more earthquakes recorded in the build- was examined and compared to four different existing damping rec-
ing. The plots show the results obtained for all damping ratios, in- ommendations. Results of this investigation concur with previous
ferred from the various ground motions recorded at each building, investigations that have indicated that damping ratios decrease with
that pass the reliability restrictions previously described. The only increasing building height and that damping ratios in concrete
case that shows an increase of damping with amplitude was the structures are higher than those in steel structures. Furthermore,
longitudinal direction of LA-54; in all other cases no clear increase regardless of the material, it was found that all buildings higher
in damping ratio is observed with increases in level of response. To than 150 m had damping ratios lower than the usual 2.5% used
study the correlation between damping and amplitude, the damping in seismic design.
ratios of each building were normalized by the average of the Damping ratios associated with higher modes of vibration were
damping ratios inferred for each building in earthquakes causing examined for three tall buildings that recorded several earthquakes.
a PRDR of less than 0.03% in the same building. When the lon- It was found that damping ratios of higher modes increase with the
gitudinal direction of LA-54 was removed from the data set, no modal frequency, and it was shown that a linear variation is a better
statistical correlation was found between damping and amplitude. fit than the commonly used mass-proportional, stiffness-propor-
The best example of this lack of correlation is building LA-52, tional, or Rayleigh damping models. Finally, it was found that
where the same damping ratio is inferred from earthquakes causing in most cases the damping ratio remains approximately constant
PRDRs of 0.02 and 0.19%, meaning that an increase of 850% even with tenfold increases in peak roof drift ratios. In one case
in the amplitude of the motion does not cause a significant change the damping ratios decreased with increasing amplitude of defor-
in the identified damping ratio. This suggests that the trends mation. These observations on saturation and possible reductions in
observed under low-amplitude motions in which damping ratios damping ratios for earthquake loading are consistent with previous
saturate and do not increase with increasing amplitude may extend observations from wind-induced vibrations and free-vibration tests.
to seismic-induced motion.
Acknowledgments
Conclusions
The authors would like to acknowledge CONICYT—Becas Chile,
The damping ratios of 14 buildings with 20 stories or more, sub- and the Blume Earthquake Engineering Center at Stanford Univer-
jected to earthquake motions, were inferred using a parametric sity for the financial aid for to the first author for conducting doc-
modal system identification technique. Identified damping ratios toral studies at Stanford under the supervision of the second author.
correspond to those that will best reproduce the measured response Ground and structural motions used in this investigation were ob-
of the building of a fixed-base linear elastic model when using as tained from the California Strong Motion Instrumentation Program
input at recorded motion at the base of the structure. In other words, of the California Geological Survey and from the United States