Jo b/Pro je ct : Re pre se nt at ive :


ESP-Syst e mwize : WIZE-7 4C7 D2 Cre at e d O n: 12 /2 7 /2 02 1 Pho ne :
Lo cat io n/Tag: Email:
Engine e r: Submit t e d By: Dat e :
Co nt ract o r: Appro ve d By: Dat e :

In-Line Fire Pump Selection Criteria NFPA Limits


Pump Mo de l: 6 x6 x11F-L Rat e d Flo w 500 US gpm 140% He ad o f Rat e d He ad 2 10 psi
No m. Spe e d: 3550 rpm Rat e d He ad 150 psi 6 5% He ad at 150% Flo w 97 .5 psi
Marke t : List e d Fire Pump Imp. Dia 10.2 4 in Flo w at 150% 7 50 US gpm
Appro val/List ing: FM/UL Po we r Re quire d at Dut y 85.4 hp He ad at 150% 137 psi
Rat e d Efficie ncy 51.1 % Po we r Re q at 150% 95 hp
Fluid Wat e r Efficie ncy at 150% 6 2 .8 %
T e mpe rat ure 85 ºF Max BHP 100 hp
Sp. Gravit y 1.000 Clo se d Valve He ad 17 5 psi

140% He ad o f Rat e d He ad 210PSI

Typical Performance Curve is shown. Fire Pumps are tested to ANSI/HI 14.6 acceptance grade 1U.
Rated Duty Point is guaranteed within the following tolerances: Flow 0% to + 10%, Head 0% to + 6%.
NO OTHER POINTS ARE GUARANTEED. PLEASE CONSULT FACTORY IF NEEDED.

Pe rfo rmance Curve Dat a


Flo w (US gpm) He ad (psi) Efficie ncy (%) Po we r Re quire d (hp) NPSHr (ft )
0 17 5 0 0 7
12 5 16 8 2 3.6 6 5.1 7
2 50 16 2 33.3 7 2 .2 7
37 5 156 42 .9 7 9.4 7
500 150 51.1 85.4 7 .34
7 50 137 6 2 .8 95 11.2
12 2 6 98.8 7 1.1 99.4 2 1.2