42°

The information and know-how on this drawing are the property of P.T. Freeport Indonesia, and may not be copied or reproduced without the written permission of P.T. Freeport Indonesia, nor may they be used,in any manner directly or indirectly detrimental to the interest of P.T. Freeport Indonesia. This print is lent upon the express condition that it, and all copies thereof, are subject to return upon demand.
1 2 3 4

NORTH
19046
(REF)
7131 11915
(REF) (REF)

UP
PLANT

UP UP

C 02

WALL CONSTRUCTION:
12.7 mm PLYWOOD

1935
90 mm METAL STUD
12.7 mm PLYWOOD

C:\Users\jvicari\OneDrive - Freeport-McMoRan Inc\Documents\2210_GRS_35_ARCH_jvicari.rvt


WALL CONSTRUCTION:
OPEN TO BELOW 12.7 mm PLYWOOD WALL CONSTRUCTION:
90 mm METAL STUD 12.7 mm PLYWOOD
12.7 mm PLYWOOD 90 mm METAL STUD
(REF)
7701

STOR.

3885
OPEN TO BELOW
10
__________ 202
GA-22144110

SEE STRUCTURAL 11
__________
DRAWING ________
12951
(REF)

03
FOR LANDINGS AND GA-22144110

700
UP DN STAIR, TYP.

B
WALL CONSTRUCTION:
12.7 mm PLYWOOD
90 mm METAL STUD 1922
12.7 mm PLYWOOD
DN
01

OPEN AREA
201

OPEN TO BELOW
5250

FLOOR PLAN - LEVEL 2 @ EL. 2957.858


SCALE: 1 : 50

NOTES:
1. DIMENSIONS ARE IN MILLIMETERS AND ELEVATIONS ARE IN METERS.

2. SEE 02022918-GS-00000012 FOR FRAMING DETAILS.


DOOR SCHEDULE - LEVEL 2

LAST EDIT: 10/22/2021 10:30:07 FLOOR PLAN - LEVEL 2


DOOR FIRE FRAME DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW WEATHER
MARK WIDTH HEIGHT THICKNESS FINISH COMMENTS
TYPE RATING TYPE CLOSER EXIT DEVICE FLUSHBOLT KICKPLATE PASSAGE SILENCERS STORAGE LOCK THRESHOLD STRIPPING

01 914 mm 2032 mm 44 mm PTD. GALV. 1 H. M. * * * * * * 1 2


02 914 mm 2032 mm 44 mm PTD. GALV. 1 H. M. * * * * * *
MILL OPTIMIZATION FOR UG ORES - PHASE 1
03 914 mm 2032 mm 44 mm PTD. GALV. 1 H. M. * * * * DOOR TYPES
SCALE: 1 : 75 MILL - E-HOUSE (GRS-35, AF'S, 2-BC-0700)
GBC PRECRUSHER PROJECT (SAG3)
REV.No DATE BY REVISION NOTES. REV.No DATE BY REVISION NOTES. DRAWING REFERENCES:
ISSUED FOR : PRELIMINARY BID GRS-35 - E-HOUSE BUILDING
18-A-0007 CONVEYOR GRS-35 DRIVE TOWER - ARCHITECTURAL - ROOF PLAN AND FCX DRAWING NUMBER : FLOOR PLAN - LEVEL 2

AM
ELEVATIONS
MOPH1-DD-2214-ACT-DWG-4100 Designed AAG SCALE: SHOWN EWP: 2214-00-30-01

DISCIPLINE LEAD FMI DISCIPLINE LEAD AREA MANAGER ENGINEERING MANAGER Drawn JSV PTFI DRAWING NUMBER REV.
Checked PJI
Approved
02022918-GA-22144100 -
42°
1 2 3 4

The information and know-how on this drawing are the property of P.T. Freeport Indonesia, and may not be copied or reproduced without the written permission of P.T. Freeport Indonesia, nor may they be used,in any manner directly or indirectly detrimental to the interest of P.T. Freeport Indonesia. This print is lent upon the express condition that it, and all copies thereof, are subject to return upon demand.
NORTH
19048
(REF)

6333 11138 1578


(REF) (REF) (REF)

PLANT

SEE STRUCTURAL DRAWING


02022918-GS-XXXXXXXX FOR
LANDINGS AND STAIR, TYP.

C
06

OPEN TO
BELOW

WALL CONSTRUCTION:

C:\Users\jvicari\OneDrive - Freeport-McMoRan Inc\Documents\2210_GRS_35_ARCH_jvicari.rvt


1-LAYER 15.8 mm M.R. GYP. BD.

4611
WALL CONSTRUCTION: 2 HR. WALL 90 mm METAL STUD
2-LAYERS 15.8 mm M.R. GYP. BD. UNFACED BATT INSULATION
(REF)
6176

90 mm METAL STUD
UNFACED BATT INSULATION
REMOVEABLE 2-LAYERS 15.8 mm M.R. GYP. BD.
GUARDRAIL, SEE 38 mm CHANNEL
STRUCTURAL DRAWING PREFINISHED METAL SIDING
02022918-GS-________

WALL CONSTRUCTION: 2 HR. WALL


2-LAYERS 15.8 mm M.R. GYP. BD. 05
SEE STRUCTURAL DRAWING
02022918-GS-XXXXXXXX FOR 90 mm METAL STUD
LANDINGS AND STAIR, TYP. UNFACED BATT INSULATION

1340
2-LAYERS 15.8 mm M.R. GYP. BD.
38 mm CHANNEL

12396
12951

PREFINISHED METAL SIDING


(REF)

B
WALL CONSTRUCTION:
1-LAYER 15.8 mm M.R. GYP. BD.
ELECTRICAL ROOM
(REF)

90 mm METAL STUD
2371

UNFACED BATT INSULATION


301
6190 12301

04

6361
WALL CONSTRUCTION:
WALL CONSTRUCTION: 1-LAYER 15.8 mm M.R. GYP. BD.
(REF)
4404

1-LAYER 15.8 mm M.R. GYP. BD. 90 mm METAL STUD


90 mm METAL STUD UNFACED BATT INSULATION
UNFACED BATT INSULATION

FLOOR PLAN - LEVEL 3 @ EL. 2964.081


SCALE: 1 : 50

NOTES:
1. DIMENSIONS ARE IN MILLIMETERS AND ELEVATIONS ARE IN METERS.
DOOR SCHEDULE - LEVEL 3
2. SEE 02022918-GS-00000012 FOR FRAMING DETAILS.

LAST EDIT: 10/22/2021 10:30:07 FLOOR PLAN - LEVEL 3


DOOR FIRE FRAME DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW WEATHER
MARK WIDTH HEIGHT THICKNESS FINISH COMMENTS
TYPE RATING TYPE CLOSER EXIT DEVICE FLUSHBOLT KICKPLATE PASSAGE SILENCERS STORAGE LOCK THRESHOLD STRIPPING

04 914 mm 2032 mm 44 mm PTD. GALV. 1 H.M. * * * * * *


05 2438 mm 2438 mm 44 mm PTD. GALV. 2 H. M. * * * * * * * 1 2
06 914 mm 2032 mm 44 mm PTD. GALV. 1 H. M. * * * * * *
DOOR TYPES MILL OPTIMIZATION FOR UG ORES - PHASE 1
SCALE: 1 : 75 MILL - E-HOUSE (GRS-35, AF'S, 2-BC-0700)
GBC PRECRUSHER PROJECT (SAG3)
REV.No DATE BY REVISION NOTES. REV.No DATE BY REVISION NOTES. DRAWING REFERENCES:
ISSUED FOR : PRELIMINARY BID GRS-35 - E-HOUSE BUILDING
18-A-0007 CONVEYOR GRS-35 DRIVE TOWER - ARCHITECTURAL - ROOF PLAN AND FCX DRAWING NUMBER : FLOOR PLAN - LEVEL 3

AM
ELEVATIONS
MOPH1-DD-2214-ACT-DWG-4101 Designed AAG SCALE: SHOWN EWP: 2214-00-30-01

DISCIPLINE LEAD FMI DISCIPLINE LEAD AREA MANAGER ENGINEERING MANAGER Drawn JSV PTFI DRAWING NUMBER REV.
Checked PJI
Approved
02022918-GA-22144101 -
42°

The information and know-how on this drawing are the property of P.T. Freeport Indonesia, and may not be copied or reproduced without the written permission of P.T. Freeport Indonesia, nor may they be used,in any manner directly or indirectly detrimental to the interest of P.T. Freeport Indonesia. This print is lent upon the express condition that it, and all copies thereof, are subject to return upon demand.
NORTH
1 2 3 4
19046
(REF)
3225 14244 1578
(REF) (REF) (REF)

PLANT
SEE STRUCTURAL DRAWING
02022918-GS-________ FOR
LANDINGS AND STAIR, TYP.

DN

C
08

LOUVERS, SEE DRAWING 18-A-0007


REMOVEABLE

C:\Users\jvicari\OneDrive - Freeport-McMoRan Inc\Documents\2210_GRS_35_ARCH_jvicari.rvt


GUARDRAIL, SEE
STRUCTURAL DRAWNG
02022918-GS-________

OPEN TO BELOW
(REF)

HVAC & EQUIPMENT


7701

401
12951
(REF)

UP DN

07 REMOVEABLE
GUARDRAIL, SEE
STRUCTURAL DRAWNG
02022918-GS-________
(REF)
5250

FLOOR PLAN - LEVEL 4 @ EL. 2969.546


SCALE: 1 : 50 NOTES:
1. DIMENSIONS ARE IN MILLIMETERS AND ELEVATIONS ARE IN METERS.

2. SEE 02022918-GS-00000012 FOR FRAMING DETAILS.

LAST EDIT: 10/22/2021 10:30:08 FLOOR PLAN - LEVEL 4


DOOR SCHEDULE - LEVEL 4
DOOR FIRE FRAME DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW DOOR HW WEATHER
MARK WIDTH HEIGHT THICKENSS FINISH COMMENTS
TYPE RATING TYPE CLOSER EXIT DEVICE FLUSHBOLT KICKPLATE PASSAGE SILENCERS STORAGE LOCK THRESHOLD STRIPPING

1 2
07 914 mm 2032 mm 44 mm PTD. GALV. 1 H. M. * * * * * * * MILL OPTIMIZATION FOR UG ORES - PHASE 1
08 914 mm 2032 mm 44 mm PTD. GALV. 1 H. M. * * * * * * * DOOR TYPES MILL - E-HOUSE (GRS-35, AF'S, 2-BC-0700)
SCALE: 1 : 75
GBC PRECRUSHER PROJECT (SAG3)
REV.No DATE BY REVISION NOTES. REV.No DATE BY REVISION NOTES. DRAWING REFERENCES:
ISSUED FOR : PRELIMINARY BID GRS-35 - E-HOUSE BUILDING
18-A-0007 CONVEYOR GRS-35 DRIVE TOWER - ARCHITECTURAL - ROOF PLAN AND FCX DRAWING NUMBER : FLOOR PLAN - LEVEL 4

AM
ELEVATIONS
MOPH1-DD-2214-ACT-DWG-4102 Designed AAG SCALE: SHOWN EWP: 2214-00-30-01

DISCIPLINE LEAD FMI DISCIPLINE LEAD AREA MANAGER ENGINEERING MANAGER Drawn JSV PTFI DRAWING NUMBER REV.
Checked PJI
Approved
02022918-GA-22144102 -
The information and know-how on this drawing are the property of P.T. Freeport Indonesia, and may not be copied or reproduced without the written permission of P.T. Freeport Indonesia, nor may they be used,in any manner directly or indirectly detrimental to the interest of P.T. Freeport Indonesia. This print is lent upon the express condition that it, and all copies thereof, are subject to return upon demand.
13 mm PLYWOOD

13 mm PLYWOOD

90 mm, 20 GA. STEEL


STUDS, WITH HORIZONTAL
REINFORCEMENT MAX.
1828 mm O.C.

C:\Users\jvicari\OneDrive - Freeport-McMoRan Inc\Documents\2210_GRS_35_ARCH_jvicari.rvt


13 mm PLYWOOD

90 mm, 20 GA. STEEL


STUDS, WITH HORIZONTAL
REINFORCEMENT MAX.
1828 mm O.C.

10 WALL SECTION 11 WALL SECTION


- SCALE: 1:15 - SCALE: 1:15

LAST EDIT: 10/22/2021 10:30:09 TYPICAL WALL TYPES


MILL OPTIMIZATION FOR UG ORES - PHASE 1
MILL - E-HOUSE (GRS-35, AF'S, 2-BC-0700)
GBC PRECRUSHER PROJECT (SAG3)
REV.No DATE BY REVISION NOTES. REV.No DATE BY REVISION NOTES. DRAWING REFERENCES:
ISSUED FOR : PRELIMINARY BID GRS-35 - E-HOUSE BUILDING
FCX DRAWING NUMBER : TYPICAL WALL TYPES

AM
MOPH1-DD-2214-ACT-DWG-4110 Designed AAG SCALE: SHOWN EWP: 2214-00-30-01

DISCIPLINE LEAD FMI DISCIPLINE LEAD AREA MANAGER ENGINEERING MANAGER Drawn JSV PTFI DRAWING NUMBER REV.
Checked PJI
Approved
02022918-GA-22144110 -
42°

The information and know-how on this drawing are the property of P.T. Freeport Indonesia, and may not be copied or reproduced without the written permission of P.T. Freeport Indonesia, nor may they be used,in any manner directly or indirectly detrimental to the interest of P.T. Freeport Indonesia. This print is lent upon the express condition that it, and all copies thereof, are subject to return upon demand.
NORTH
PLANT

1 2 3 4

C:\Users\jvicari\OneDrive - Freeport-McMoRan Inc\Documents\2210_GRS_35_ARCH_jvicari.rvt


C

OPEN TO BELOW

300x300 300x300 300x300

550x350 600x850 550x550 550x350

SUPPLY DOWN FROM LEVEL 4

300x300 SUPPLY DOWN FROM LEVEL 4


B 550x550

700x500 550x850 550x350


LEGEND
300x300 700x350 0
x35
700 700x350 300x300 300x300 FSD FIRE SMOKE DAMPER

450x350 1250x1050
PRE AF PRE AIR FILTER

300x300 HEPA AF HEPA AIR FILTER

RETURN UP TO LEVEL 4
PF PRESSURIZATION FAN

SUPPLY DOWN FROM LEVEL 4 MCD ACTUATED MODULATING CONTROL DAMPER


700x400

SUPPLY AIR DUCT


450x350 700x350 850x700 500x400 350x300

RETURN AIR DUCT

300x300 300x300 300x300 300x300 300x300


FRESH AIR DUCT

A SUPPLY AIR DIFFUSER

NOTES:
1. DUCT DIMENSIONS SHOWN ARE INSIDE DIMENSIONS FOR AIR FLOW.

2. ALL SUPPLY AIR DUCTS ARE TO HAVE 1 INCH OF DUCT INSULATION. FOR FINAL OD DIMENSION ADD 2
INCHES.

3. ALTHOUGH RETURN AIR DUCT INSIDE THE ROOM WILL NOT BE INSULATED, ONLY A PENETRATION
THROUGH THE 4TH FLOOR IS NEEDED.

LAST EDIT: 10/22/2021 10:30:09 HVAC FLOOR PLAN - LEVEL 3


4. THE SMALL BRANCH DUCT SHOWN AT EACH GRILLE IS NOT INTENDED TO BE PROVIDED, JUST A MEANS
HVAC FLOOR PLAN - LEVEL 3 @ EL. 2964.081 OF SHOWING THE GRILLE MORE CLEARLY. PLAN TO HAVE BOTTOM DISCHARGE FROM THE DUCTS.

SCALE: 1 : 50

MILL OPTIMIZATION FOR UG ORES - PHASE 1


MILL - E-HOUSE (GRS-35, AF'S, 2-BC-0700)
GBC PRECRUSHER PROJECT (SAG3)
REV.No DATE BY REVISION NOTES. REV.No DATE BY REVISION NOTES. DRAWING REFERENCES:
ISSUED FOR : PRELIMINARY BID GRS-35 - E-HOUSE BUILDING
FCX DRAWING NUMBER : HVAC FLOOR PLAN - LEVEL 3

AM
MOPH1--DD-2214-ACT-DWG-4200 Designed AAG SCALE: SHOWN EWP: 2214-00-30-01

DISCIPLINE LEAD FMI DISCIPLINE LEAD AREA MANAGER ENGINEERING MANAGER Drawn JSV PTFI DRAWING NUMBER REV.
Checked PJI
Approved
02022918-GA-22144200 -
42°

The information and know-how on this drawing are the property of P.T. Freeport Indonesia, and may not be copied or reproduced without the written permission of P.T. Freeport Indonesia, nor may they be used,in any manner directly or indirectly detrimental to the interest of P.T. Freeport Indonesia. This print is lent upon the express condition that it, and all copies thereof, are subject to return upon demand.
NORTH
1 2 3 4
PLANT

UP

DN

C:\Users\jvicari\OneDrive - Freeport-McMoRan Inc\Documents\2210_GRS_35_ARCH_jvicari.rvt


C

SUPPLY DOWN TO LEVEL 3

OPEN TO BELOW
600x850

HVAC & EQUIPMENT

600x850
401

UP DN
550x850
SUPPLY DOWN TO LEVEL 3
B

700x850 850x1800 700x1800


LEGEND
FSD FIRE SMOKE DAMPER

1250x1050
PRE AF PRE AIR FILTER
700
x1 800

700x850
700x1800 HEPA AF HEPA AIR FILTER
RETURN UP FROM LEVEL 3

0
x30
600
PF PRESSURIZATION FAN
700x1800
PRE HEPA PF
600x300
AF AF
MCD ACTUATED MODULATING CONTROL DAMPER

SUPPLY AIR DUCT


850x700

RETURN AIR DUCT

SUPPLY DOWN TO LEVEL 3


FRESH AIR DUCT

A SUPPLY AIR DIFFUSER

NOTES:
1. DUCT DIMENSIONS SHOWN ARE INSIDE DIMENSIONS FOR AIR FLOW.

2. ALL SUPPLY AIR DUCTS ARE TO HAVE 2 INCHES OF DUCT INSULATION. FOR FINAL OD
DIMENSION ADD 4 INCHES.

3. RETURN AIR DUCT TO HAVE 1 INCH OF INSULATION. FOR FINAL OD DIMENSION ADD 2 INCHES.

LAST EDIT: 10/22/2021 10:30:10 HVAC FLOOR PLAN - LEVEL 4


4. FRESH AIR DUCT IS UNINSULATED.

HVAC FLOOR PLAN - LEVEL 4 @ EL. 2969.546


SCALE: 1 : 50

MILL OPTIMIZATION FOR UG ORES - PHASE 1


MILL - E-HOUSE (GRS-35, AF'S, 2-BC-0700)
GBC PRECRUSHER PROJECT (SAG3)
REV.No DATE BY REVISION NOTES. REV.No DATE BY REVISION NOTES. DRAWING REFERENCES:
ISSUED FOR : PRELIMINARY BID GRS-35 - E-HOUSE BUILDING
FCX DRAWING NUMBER : HVAC FLOOR PLAN - LEVEL 4

AM
MOPH1-DD-2214-ACT-DWG-4201 Designed AAG SCALE: SHOWN EWP: 2214-00-30-01

DISCIPLINE LEAD FMI DISCIPLINE LEAD AREA MANAGER ENGINEERING MANAGER Drawn JSV PTFI DRAWING NUMBER REV.
Checked PJI
Approved
02022918-GA-22144201 -