Project Falcon - U Value
Project Falcon - U Value
Project Falcon - U Value
GLASS
OPTICAL AND THERMAL PERFORMANCE
CUSTOMER : ADVANCED ALUMINIUM SYSTEM :
PROJECT :
DOUBLE GLAZED UNIT
6mm Clear Float Glass
12mm Air Space
6mm Clear Float Glass
NOTES
The above data has been estimated and approximated from computer analysis on the LBNL Window v7.3.8.0 Fenestration Product Thermal Analysis
Program and Optics 6.
The above performance figures are related to glass (center) only with no spacer or framing.
The considered environmental condition: NFRC 100-2010 (outside air temperature 32○C \ inside air temperature 24○C).
Performances scheduled may vary from actual depending on manufacturers permitted variations in color and coatings.
EXPLANATION OF TERMS
Light = (visible) radiant energy covering wavelength range of 380 nm to 780 nm:
% Transmission = percentage of visible light directly transmitted through the glass
% Reflection Outdoors = percentage of outdoor visible light directly reflected from the glass back outdoors
% Reflection Indoors = percentage of indoor visible light directly reflected from the glass back indoors
Solar Energy = radiant energy from the sun having a wavelength range of 300 nm to 2500 nm at an air mass of 1.0, global.
% Transmission = percentage of solar energy directly transmitted through the glass
% Reflection Outdoors = percentage of solar energy directly reflected from the glass back outdoors.
Shading coefficient (SC) is the ratio of solar heat gain passing through a particular product compared to 3-mm clear glass under the same conditions.
The lower the SC, the better the glasses ability to reduce summer heat gain and, therefore, reduce air- conditioning costs. Clear glass has the highest
SC, followed in general by tinted glass; pyrolytic coated glass, then sputter-coated glass and Heat Mirror™. Glass with a SC approaching 1.0 obviously
has a close heat gain characteristic to 3-mm clear glass.
U-Value is the overall coefficient of heat transmission due only to a difference in indoor and outdoor air temperatures. The lower the ‘U’ value, the
less heat is transmitted through a material in a given time for a given temperature difference. ‘U’ value is expressed in terms of Btu/hr ft² °F or
W/m². °C.
ASHRAE ‘U’ values are expressed for two different sets of environmental conditions:
Summer ‘U’- outside air temperature 32°C, inside air temperature 24°C, wind speed 3.4 m/sec; direct solar intensity 783 W/m².
Winter ‘U’ - outside air temperature -17°C, inside air temperature 24°C, wind speed 6.7 m/sec, direct solar intensity zero.
European calculated U-Values are similar to ASHRAE winter except the outdoor air temperature allowed for is 0°C having the effect that the
ASHRAE winter ‘U’ value for the same product will register slightly lower.
Relative Heat Gain (RHG): gives the design professional a ready guide in reviewing comparative glass types as to their performance to reduce cooling
costs.
The ASHRAE standard RHG is calculated using both SC and ‘U’ value for a standard set of environmental conditions:
RHG = (SC*630) + (U-Value summer *7.8)
cca
me
NOTES:-
B C
6600 6600 4
H H
GL1
03 03
6601 03 6601
6602 03 03
6601 6602
01 02 01 02 02
6601 6601 6602 6602 6601
04 04
6601 6602
04 04 04
6601 6602 6601
DXB061-ARC-00-ZZ-DR-A-4002 C Elevation-3 - South elevation Part 1 & 2
A ELEVATION B SECTION C SECTION DXB061-APC-00-SD-A-6602 0 SECTION DETAILS OF ALUM. UNITS SECURITY CONTROL
ROOM, SECURITY VESTIBULE @ SOUTH ELEVATION
6600 SCALE 1:25 6600 SCALE 1:25 6600 SCALE 1:25
DXB061-APC-00-SD-A-6601 0 SECTION DETAILS OF ALUM. UNITS SECURITY CONTROL
ROOM, SECURITY VESTIBULE @ SOUTH ELEVATION
ED
ED
D
ED
WE
ITT
OV
REV.NO. DATE REVISION
K
AW
VIE
BM
EC
PR
CH
SU
AP
DR
RE
Shop Drawing
PROJECT:-
AWS
CONSULTANT:-
MAIN CONTRACTOR:-
ABSAL PAUL
CONTRACTING
Office #611, 6th Floor, Falcon Tower
Bldg. #60, Diplomatic Area
Block #317, Road 1701,
Manama, Kingdom of Bahrain
Subcontractor
ADAL
ADAL
DRAWING DESCRIPTION:-
SIZE:- A1
DXB061-APC-00-SD-A-6600 01
Calculation of thermal transmittance" Ucw
For façades
PROJECT NAME : PROJECT FALCON
Proceed with evaluation of the individual components - in accordance with" EN ISO 12631:2012
Transom 90 mm - 324460
Mullion 85 mm - 324230
Insulation principle
6.Glass edge seal Psi W/(mK) Length m Heat loss W/K Psi
value * length"
Glass 24 mm (6-12-6), Ug=2.8 W/m²K, 0.17 21.720 3.69
Aluminium, from standard - Transom
90 mm - 324460
Glass 24 mm (6-12-6), Ug=2.8 W/m²K, 0.17 36.160 6.15
Aluminium, from standard - Mullion 85
mm - 324230
8.Total
Total area of the façade 30.1784 m²
The nominal value of the thermal transmittance Ucw for curtain walling is calculated in accordance with EN ISO
12631:2012. The specifications on this output list which have been calculated by the program must be checked
for accuracy."
Whilst we have carefully checked this program and all the information, we cannot take responsibility for the
accuracy of the results.
For a U value calculation using a calculcation module checked for plausibility by ift Rosenheim in accordance
with ift guideline WA-05/2, please use our calculation software SchüCal.
c ca
me
D
B 6609
6609
NOTES:-
03 03
6610
6610
03 03 03 03 03
6610 6610 6610 6610 6610
GL1
01 02 05 02
6610 6610 6610 6610
04 04
04 6610 04 04 04 04 6610
6610 6610 6610 6610 6610
C ELEVATION D SECTION
A ELEVATION B SECTION
6609 SCALE 1:25 6609 SCALE 1:25
6609 SCALE 1:25 6609 SCALE 1:25 LEGENDS:-
F DXB060- ARC- 02- ZZ- DR- A-2000 C Guard House - Plan, Elevations and Sections
6609
DRAWING NUMBER REV DRAWING TITLE
G-2
DXB061-APC-00-SD-A-6610 0 SECTION DETAILS OF ALUM.UNITS
H-01,02,03 & 04 @GUARD HOUSE
01 03
6610 6610
0 18/03/2021 SUBMISSION FOR APPROVAL PK MS AR
01
ED
D
D
ED
E
WE
ITT
OV
REV.NO. DATE REVISION
K
AW
VIE
BM
EC
PR
6610
CH
DR
SU
AP
RE
01 HANDED
Shop Drawing
6610 04
A E 04 6610
HANDED PROJECT:-
6609 6609 6610
PROJECT FALCON
02 05 02 CLIENT:-
6610 6610 6610
G-1 AWS
CONSULTANT:-
ADAL
DRAWING DESCRIPTION:-
SIZE:- A1
DXB061-APC-00-SD-A-6609 00
PROJECT No. : P757
PROJECT NAME : PROJECT FALCON
Although this estimation has been made accurately to the best knowledge of EFP, European Facade Products BV cannot accept responsibility for any errors or omissions and customer needs to check all data
The customer needs to check all the data, in case of errors please inform EFP International / EFP European Facade Products.
EFP International BV
De Factorij 26, 9363 TN Marum, (The Netherlands)
t: +31 (0) 594-510382, f: +31 (0) 594-510396, e: info@efpeurofacade.com
Page: 1
Total pages: 2
PROJECT No. : P757
PROJECT NAME : PROJECT FALCON
Although this estimation has been made accurately to the best knowledge of EFP, European Facade Products BV cannot accept responsibility for any errors or omissions and customer needs to check all data
The customer needs to check all the data, in case of errors please inform EFP International / EFP European Facade Products.
EFP International BV
De Factorij 26, 9363 TN Marum, (The Netherlands)
t: +31 (0) 594-510382, f: +31 (0) 594-510396, e: info@efpeurofacade.com
Page: 2
Total pages: 2