Professional Documents
Culture Documents
Open Circuit & Short Open Circuit & Short Circuit Test Single Phase Transformer Tests of Rmer
Open Circuit & Short Open Circuit & Short Circuit Test Single Phase Transformer Tests of Rmer
Open Circuit & Short Open Circuit & Short Circuit Test Single Phase Transformer Tests of Rmer
AIM:
To perform the open circuit and short circuit tests on a single phase transformer.
transformer
OBJECTIVES:
Determine the voltage regulation and the efficiency of a given transformer.
Study the performance of a given transformer at a different load conditions.
Draw the equivalent circuit of a given transformer.
APPARATUS REQUIRED:
THEORY:
The efficiency and regulation of a transformer on any load condition and at any power factor
condition can be predetermined by indirect loading method. In this method, the actual load is not
used on transformer. But the equivalent circuit parameters of a transformer are determined by
conducting two tests
ts on a transformer which are,
1. Open circuit test (O.C Test)
2. Short circuit test (S.C.Test)
The parameters calculated from these test results are effective in determining the regulation and
efficiency of a transformer at any load and power factor condition, without actually loading the
transformer. The advantage of this method is that without much power loss the tests can be
performed and results can be obtained. Let us discuss in detail how to perform these tests and
Page1
In the open circuit test, no load current is very small and hence copper losses are very small. It is
neglected so the wattmeter reading gives the iron or core loss of the transformer. In this test H.V.
side is kept open circuited,, while L.V. side is supplied with its rated voltage.
In the short circuit test usually the L.V. side is short circuited and H.V. side is supplied with
reduced voltage just sufficient to circulate a rated full load current in the transformer winding.
The voltage
oltage applied to the H.V. side is about 10% to 15% of the rated value. Hence the iron loss
is negligible and the wattmeter reads only copper loss of both of the windings collectively
occurring at particular load.
If the value of the current is other than the full load current, the full load copper loss can be
found out by the following expression.
2
IL
Wcu ( FL ) = × Wattmeter reading
Ammeter reading
The efficiency of the transformer can be found out with the help of wattmeter reading at open
circuit test and short circuit test.
Output in kW
%η = ×100
Output in kW + Wi + Wcu
If the output is x times the rated value
xkVA × cos φ
%η = ×100
xkVA × cos φ + Wi + x 2Wcu
CIRCUIT DIAGRAM:
PROCEDURE:
OBSERVATION TABLE:
(A) Open circuit test
CALCULATIONS:
(A) Calculation of Basic Electrical Parameters of Transformer
From Open Circuit Test Data
W0
• W0 = V0 I 0 cos φ0 ⇒ cos φ0 =
V0 I 0
• I m = I 0 sin
cos φ0 and I c = I 0 cos
sin φ0
V0 V0
• R0 = Ω and X0 = Ω
Ic Im
From Short Circuit Test Data
WSC
• WSC = VSC I SC cos φSC ⇒ cos φSC =
VSC I SC
WSC
• 2
WSC = I SC R01 = total copper loss ⇒ R01 = 2
Ω
I SC
• R02 = K 2 R01 Ω
VSC
• Z SC = = Z 01 Ω
I SC
Page4
• Z 02 = K 2 Z 01 Ω
• X 01 = Z 012 − R012 Ω
• X 02 = K 2 X 01 Ω
Important Note:: If the transformer is step up transformer, its primary is L.V. while
secondary is H.V. winding. In S.C. test, supply is given to H.V. winding and L.V is
shorted. In such case we connect meters on H.V. side which is transformer secondary
through for S.C.
.C. test purpose H.V side acts as primary. In such case the parameters
calculated from S.C. test readings are referred to secondary which are R02, Z02 and X02.
So before doing calculations it is necessary to find out where the readings are recorded
on transformer primary or secondary and accordingly the parameters are to be
determined. In step down transformer, primary is high voltage itself to which supply is
given in S.C. test. So in such case test results give us parameters referred to primary i.e.
R01, Z01 and X01.
Key point:: In short, if meters are connected to primary of transformer in S.C. test,
calculations give us R01 and Z01 if meters are connected to secondary of transformer in
S.C. test calculations give us R02 and Z02.
ency of Transformer
(B) Calculation of Efficiency
We know that,
From O.C. test, Wo = Pi
From S.C. test, Wsc = (Pcu) F.L.
xkVA × cos φ
• %η = × 100
xkVA × cos φ + Wi + x 2Wcu
COMPUTATION TABLE:
Power Factor
Fraction of Load Current
# 0.8 lagging 0.8 leading Unity
Load IL Amp
%η
η %VR %η
η %VR %η
η %VR
1. 100%
2. 75%
3. 50%
4. 25%
5. 10%
EQUIVALENT CIRCUIT:
Page6
VECTOR DIAGRAM:
GRAPH:
Load Current IL
Page7
%Efficiency
Efficiency V/S Load Current [for all pf load]
Page8
%Voltage
Voltage Regulation V/S Load Current [for all pf load]
Page9
CONCLUSIONS
Page11
Page12
Page13
Grade/Marks Obtained
Date of Assessment
Page14
Sign of Instructor