Professional Documents
Culture Documents
Saudi Aramco Test Report: Elect-LV Controlgear - ATS / MTS Calibration, Setting, and Functional Testing SATR-P-3824
Saudi Aramco Test Report: Elect-LV Controlgear - ATS / MTS Calibration, Setting, and Functional Testing SATR-P-3824
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
251 - 600
1000 Vdc (NETA ATS 2007, 7.22.3.2.2)
Perform contact resistance test across main contacts and correct values
SAES-P-116
A5 exceeding 500 micro ohms and values for one pole deviating by more
Sec. 3.2
than 50 percent from other poles. (NETA ATS 2007, 7.22.3.3.1.1)
After completing the test, all switching devices must be switched to SAES-P-116
A6
'Open' position. (NETA ATS 2007, 5.1) Sec. 3.2
B. TEST EQUIPMENT
Schedule Q
B3 The test equipment calibration cycle shall not exceed twelve months.
Att. IV Sec. 7
Equipment 1:
Equipment 2:
Page 1 of 6
Calibration Company and Technician: Calibration Expiration Date:
Page 2 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
ITEM RE-TEST
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
C. TEST RESULTS
A Phase to Ground
B Phase to Ground
C Phase to Ground
A Phase to B Phase
B phase to C Phase
C phase to A Phase
D. CONCLUSIONS
ITEM RE-TEST
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
SAES-P-116
D2 manufacturer's data is not available, investigate any values which deviate
Sec. 3.2
from similar connections by more than 50 percent of the lowest value.
(NETA ATS 2007, 7.22.3.3.2.3)
Test results are acceptable and in accordance with Saudi Aramco Schedule Q
D3
Engineering Standards and contractual requirements. Att. II
Loss of Normal Voltage and Time Delay Settings for Closing Contacts To
Initiate Starting of Emergency or Stand-by Generator:
Set and calibrate the voltage sensing relays to manufacturer's prescribed SAES-P-116
E1
settings or coordinate with PDD/proponent for calculated/design settings Sec. 3.2
for closing contacts to initiate starting of the emergency or stand-by
generator upon loss of phase to phase voltage of the normal source.
Page 3 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
ITEM RE-TEST
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
Loss of Normal Voltage and Time Delay Settings for Transfer to Alternate
Source:
When the alternate source is an emergency or stand-by generator, set
SAES-P-116
E3 and calibrate the voltage sensing relay to manufacturer's recommended
Sec. 3.2
voltage settings or in accordance to PDD/proponent prescribed settings
to transfer to the alternate source immediately at the specified voltage
and frequency of that source.
For switches not involving engine generator sets as power plants, adjust
the time delay relay to transfer to the alternate source after an adjustable
SAES-P-116
E4 time delay recommended by the manufacturer or as per prescribed
Sec. 3.2
adjustments by PDD/proponent to override momentary dips and/or
outages.
If the emergency or standby power should fail while carrying the load,
SAES-P-116
E5 transfer to the normal power shall be made instantaneously upon
Sec. 3.2
restoration of the normal source to satisfactory conditions.
F. FUNCTIONAL TESTING
Apply rated voltage in the incoming terminals of the Normal ACB and SAES-P-116
F1
Emergency ACB. Sec. 3.2
Switch ON the control protection device of the Normal supply. Check SAES-P-116
F3
OFF pilot light indicator. Sec. 3.2
The Normal ACB will turn ON after the pre-set time delay. Check ON
SAES-P-116
F4 Pilot light indicator. Note that if the Emergency ACB is closed, the latter
Sec. 3.2
ACB will open before the closing of the normal ACB.
Page 4 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
ITEM RE-TEST
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
Turn OFF the control protection device of the Normal ACB. It would trip SAES-P-116
F6
immediately when power is cut off. Sec. 3.2
The emergency ACB will close after the pre-set delay of the timer. Check SAES-P-116
F7
pilot light indicator. Sec. 3.2
Close the control protection device of the Normal ACB. The Emergency SAES-P-116
F8
ACB will open and the closing of the Normal ACB follows. Sec. 3.2
SAES-P-116
F9 Simulate loss of emergency source with normal source available.
Sec. 3.2
Manual Operation:
Set ATS Equipment in the Stop mode. Turn selector switch to the Normal SAES-P-116
F11
position to close ACB. Check pilot light indicator and verify the Sec. 3.2
functionality of the mechanical interlock.
Turn selector switch of the ATS Equipment to the Standby position to SAES-P-116
F12
close ACB of the Emergency. Check pilot light indicator. Sec. 3.2
SAES-P-116
F14 Remove and replace malfunctioning units and retest as specified above.
Sec. 3.2
G. TEST RESULTS
Operation Set @ Expected Time Actual time Pass Fail Re-Test Date
Equipment :
Page 5 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
ITEM RE-TEST
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
2. Schedule Q - Quality Requirements (Pro Forma Contract), February 2008
3. SAES-P-116 Switchgear and Control Equipment, 01 March 2008
4. Acceptance Testing Specifications - NETA (2007)
5. NEMA AB4 Guidelines for Inspection and Preventive Maintenance of MCCB Used in Commercial and Industrial Applications, 2002 Edition
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified
purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer
indicates compliance with appropriate standards or performance in a specified manner.
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED
Page 6 of 6