Industrial Medium Voltage Cables: Construction: Resistance

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

INDUSTRIAL MEDIUM VOLTAGE CABLES

N2XSY 6/10 kV, 12/20 kV, 18/30 kV, 20/35 kV PVC- jacket

Construction: Resistance:
Conductor: stranded red copper conductor Cl.2 Flame retardant acc. to:
acc.to IEC 60228 DIN VDE 0482 part 265-2-1
EN 50265-2-1
Inner
IEC 60332-1-2
semi-conductive
layer: extruded compound On request:
IEC 60332-3/22 or 60332-3/24,
Insulation: XLPE compound DIN VDE 0482-332-3 part 266-4-2 or 266-5-2
EN 60322-3
Outer
semi-conductive
layer: extruded compound

Screen: red copper wires and one or two


copper tape(s) applied helically
Features:
Outer sheath: red (RAL 3000), PVC type DMV6 according to IEC 60502-2 or DIN VDE 0276-620

re: circular solid conductor

rm: circular stranded conductor


Technical data:
sm: sector-shaped stranded conductor
Nominal voltage: 6/10 kV, 12/20 kV, 18/30 kV, 20/35 kV

6/10 kV = 17 kV se: sector-shaped solid conductor


Test voltage:
12/20 kV= 29 kV
18/30 kV = 45 kV
20/35 kV = 50 kV

Temperature range: - 5 oC / + 70 oC
Applications:
Max. conductor
temperature: + 90 °C Suitable for installation mostly for power supply
stations, in indoors and in cable ducts, outdoors,
Max short circuit underground, and in water as well as for installation
temperature: + 250 oC on cable trays for industries, switch-boards and power
stations. Due to the good laying characteristics, this
Min. bending radius: 15 x d can also be laid easily in difficult line guideways.
See DIN VDE 0298 part 1 .

6/10 kV
No.of cores Outer-Ø Copper Cable
AWG
Part no. x cross section ca.mm weight weight approx.
no.*)
n x mm2 ± 10% kg/km kg/km
48190QRL010M64 1x35 rm/16 25,5 518 905 2
48190QRL010M65 1x50 rm/16 26,5 662 1080 1
48190QRL010M66 1x70 rm/16 28,5 860 1310 2/0
48190QRL010M67 1x95 rm/16 29,5 1098 1580 3/0
48190QRL010M68 1x120 rm/16 31,5 1340 1860 4/0
48191QRL010M69 1x150 rm/16* 32,5 1622 2040 250 MCM
48190QRL010M69 1x150 rm/25 32,5 1725 2210 250 MCM
48191QRL011M70 1x185 rm/16* 36,5 1958 2450 350 MCM
48190QRL010M70 1x185 rm/25 36,5 2059 2580 350 MCM
48191QRL011M71 1x240 rm/16* 38,5 2486 3000 450 MCM
48190QRL010M71 1x240 rm/25 38,5 2587 3130 450 MCM
48190QRL010M72 1x300 rm/25 38,5 3163 3780 550 MCM
48190QRL010M73 1x400 rm/35 42,5 4234 4670 750 MCM
48190QRL010M74 1x500 rm/35 45.5 5194 5750 1000 MCM

www.elettrotekkabel.com 119
INDUSTRIAL MEDIUM VOLTAGE CABLES

N2XSY 6/10 kV, 12/20 kV, 18/30 kV, 20/35 kV PVC- jacket

12/20 kV
No.of cores Outer-Ø Copper Cable
AWG
Part no. x cross section ca.mm weight weight approx.
no.*)
n x mm2 ± 10% kg/km kg/km
48190URL010M64 1x35 rm/16 29,5 518 1110 2
48190URL010M65 1x50 rm/16 30,5 662 1250 1
48190URL010M66 1x70 rm/16 32,5 860 1510 2/0
48190URL010M67 1x95 rm/16 33,5 1098 1780 3/0
48190URL010M68 1x120 rm/16 35,5 1340 2070 4/0
48191URL011M69 1x150 rm/16* 36,5 1622 2310 250 MCM
48190URL010M69 1x150 rm/25 36,5 1725 2420 250 MCM
48191URL011M70 1x185 rm/16* 38,5 1958 2650 350 MCM
48190URL010M70 1x185 rm/25 38,5 2059 2810 350 MCM
48191URL011M71 1x240 rm/16* 41,5 2486 3260 450 MCM
48190URL010M71 1x240 rm/25 41,5 2587 3360 450 MCM
48190URL010M72 1x300 rm/25 43,5 3163 4020 550 MCM
48190URL010M73 1x400 rm/35 46,5 4234 4930 750 MCM
48190URL010M74 1x500 rm/35 49,5 5194 6050 1000 MCM

18/30 kV
No.of cores Outer-Ø Copper Cable
AWG
Part no. x cross section ca.mm weight weight approx.
no.*)
n x mm2 ± 10% kg/km kg/km
48190XRL010M65 1x50 rm/16 35,5 662 1480 1
48190XRL010M66 1x70 rm/16 37,5 854 1730 2/0
48190XRL010M67 1x95 rm/16 38,5 1094 2060 3/0
48190XRL010M68 1x120 rm/16 40,5 1334 2330 4/0
48190XRL010M69 1x150 rm/25 41,5 1723 2720 300 MCM
48190XRL010M70 1x185 rm/25 43,5 2059 3100 350 MCM
48190XRL010M71 1x240 rm/25 45,5 2587 3730 500 MCM
48190XRL010M72 1x300 rm/25 48,5 3163 4000 600 MCM
48190XRL010M73 1x400 rm/35 51,5 4234 5330 750 MCM
48190XRL010M74 1x500 rm/35 54,5 5194 6480 1000 MCM

20/35 kV
No.of cores Outer-Ø Copper Cable
AWG
Part no. x cross section ca.mm weight weight approx.
no.*)
n x mm2 ± 10% kg/km kg/km
48190YRL010M65 1x50 rm/16 35 662 1516 1
48190YRL010M66 1x70 rm/16 37 854 1776 2/0
48190YRL010M67 1x95 rm/16 39 1094 2103 3/0
48190YRL010M68 1x120 rm/16 40,5 1334 2401 4/0
48190YRL010M69 1x150 rm/25 42 1723 2803 300 MCM
48190YRL010M70 1x185 rm/25 43 2059 3229 350 MCM
48190YRL010M71 1x240 rm/25 46,5 2587 3874 500 MCM
48190YRL010M72 1x300 rm/25 49 3163 4501 600 MCM
48190YRL010M73 1x400 rm/35 52 4234 5503 750 MCM
48190YRL010M74 1x500 rm/35 56 5194 6662 1000 MCM
* For cables laying in earth a screen-cross section of 16 mm is permitted. Other dimensions and colours available on request.

120 www.elettrotekkabel.com

You might also like