Professional Engineer:

KC SIEW ENGINEERING
CONSULTANTS

Project Title:

WOODLAND HEALTH CAMPUS

Document Title:

Structural Calculation of Single Arm


Monitor Steel Frame Support & Connection

Part 4 / Rev.0

Project:

Designer:

Checked By:

Date:
Project:
Designer:
Checked by:
Date:

TABLE OF CONTENTS

PART 1: DESIGN INFORMATION SHEET 1 ~ 2

ANALYSIS OF SINGLE ARM MONITOR STEEL FRAME


PART 2: 3 ~ 43
SUPPORT

DESIGN OF TYPICAL ANCHOR AND BASEPLATE


PART 3: 44 ~ 52
CONNECTION

PART 4: ANALYSIS OF 15 MM SOFFIT STEEL PLATE 53 ~ 63

SPECIFICATIONS & LOAD REFERENCE , STEEL FRAME


APPENDIX: 64 ~ 66
SECTION PROPERTIES
Project:
Designer:
Checked by:
Date:

PART 1 : DESIGN INFORMATION SHEET

Introduction:

The Structural Calculation report is the Analysis of Soffit Steel Frame Support & Connection for Single Arm Monitor . The
Design Values are taken from the given design Load and the review of the System are based on the given parameters below.

1.1 DESIGN CODES

SS EN 1990: Basic of structural design


EN 1991-1-1:2002 Actions on structures – General actions – Densities, selfweight,
imposed loads for buildings
SS EN 1993-1-1: Design of steel structures – General rules and rules for
buildings
Eurocode 3: Joints in steel construction: Simple connections

1.2 MATERIAL PROPERTIES

Structural Steel : S275


Allowable tensile strength py = 275 MPa
Modulus of elasticity E = 205000 MPa
Unit Weight ws = 77 kN/m3

1.3 DESIGN LOAD

Selfweight (SW)
An Additional 10 % of Selfweight if considered to the frames for Accessories

Deadload (DL)
Unit Weight for Steel Plate & Steel Frame DL = 7700 kg/m3 or 77 kN/m3
Net Weight of Single Monitor Arm P DL-sl = 130 kg or 1.30 kN

Liveload ( LL)
Tensile Force PLL = 2300 N or 2.30 kN
Torque at Ceiling ( For All Direction ) MLL = 2400 Nm or 2.40 kN-m

1.4 LOAD COMBINATION

1.35 (SW+ DL) +2.0 PLL ± 2.0 MLL Strength Check


1.0 SW + 1.0 DL Serviceability
1.0 SW+1.0 PLL ± 1.0 MLL Serviceability

1.5 SERVICEABILITY

Steel Cantilever Frame L/180 or 20 mm


Steel Simply Supported Frame L/240 or 20 mm

1.6 STRUCTURAL SYSTEM


• The Single Arm Monitor System is connected to the Vertical Steel Pipe.
• The Vertical Steel Pipe is attached to 15 mm Thick Steel Plate.
• The 15 mm Thick Steel Plate is welded all around to the Supporting Ceiling Steel Frame.
• The Supporting Ceiling Steel frame is bolted to the Soffit Slab at each vertical post locations.

1
Project:
Designer:
Checked by:
Date:

DRAWING REFERENCE: SINGLE ARM MONITOR

2
Project:
Designer:
Checked by:
Date:

PART 2: ANALYSIS OF SINGLE ARM MONITOR STEEL FRAME SUPPORT

2.1 DESIGN LOAD & COMBINATION

Selfweight (SW)
The Selfweight is considered with additional +10% due to Accessories & fixings.

Design Deadload (DL)

Unit Weight of Steel Plate & Steel Frame ws = 77.00 kN/m3

Net Weight of Surgical Light PDL-sl = 130.00 kg


= 1.300 kN

Weight of Dia 110x 6t Conduit Pipe PDL-pipe = 1 no. x 1332 mm2 (Area) x 1100 mm (Length) x ws
= 0.11 kN

Design Deadload with +10% for Fixings PDL = 1.1 * ( PDL-sl + PDL-pipe )
= 1.55 kN

Design Liveload ( LL )

Design Tension Load P LL = 2300.00 N


= 2.30 kN
Design Torque Moment at Z Direction MLL-z = 2400.00 N-m
= 2.40 kN-m (All Direction)
Design Torque Moment at X Direction MLL-x = 2400.00 N-m
= 2.40 kN-m (All Direction)

Load Combination

Combo 1 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLz Strength Check
Combo 2 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLx Strength Check
Combo 3: 1.0 SW + 1.0 DL Serviceability
Combo 4: 1.0 SW+1.0 PLL ± 1.0 MLLz Serviceability
Combo 5: 1.0 SW+1.0 PLL ± 1.0 MLLx Serviceability

2.2 STEEL FRAME SUPPORT & LOAD REFERENCE

3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Project:
Designer:
Checked by:
Date:

PART 3 : DESIGN OF TYPICAL ANCHOR AND BASEPLATE CONNECTION

Reference Drawing :

3.1 DESIGN REACTION LOAD ( Refer to Part 2 ,STAAD ANALYSIS OUTPUT , Reaction Summary Table )

Fx = 0.08 kN Design Reaction Load at X-Axis


Fy = 9.33 kN Design Reaction Load at Y-Axis ( Max value for Tension & compression )
Fz = 0.21 kN Design Reaction Load at Z-Axis

44
Project:
Designer:
Checked by:
Date:

3.2 ANALYSIS OF WELD CONNECTION

● Section Properties

Grade = Grade 275 Grade of Steel Section


a = 4.00 mm Thickness of Weld
t = 2.83 mm Throat length of weld
d = 50.00 mm Width of Steel Beam
b = 50.00 mm Depth of Steel Beam
l = 55.66 mm Length of Weld per side ( Width + 2* t)
z = (b + 2* t) /2 Distance Z to centroid Z
= 27.83 mm
y = l /2 Distance Y to centroid Y
= 27.83 mm
A = 597.59 mm2 Area of Weld
2
S = t ( b*l + b /3 )
4
= 10226.43 mm Polar Moment of Inertia
JW = t ( b+l)3/6 Polar Moment of Inertia
= 555917.89 mm4
fu = 430.000 N/mm2 Ultimate Strength of Steel EC3 Table 3.1
βw = 0.850 Correlation Factor EC 3 Part 1-8 Table 4.1
γM2 = 1.250 Material Factor EC 3 Part 1-8 Table 2.1

fvw,d = fu/((3)0.5*βw * γM2 ) EC 3 Part 1-8 Section 4.5.3.3


= 233.657 N/mm2 Design Strength of Fillet Weld

● Weld Capacity

Vx = Fx / A Shear Stress along X-axis,


= 0.13 N/mm2
Vy = Fy / A Shear Stress along Z-axis,
= 15.61 N/mm2
Vz = Fz / A Shear Stress along Y-axis,
= 0.34 N/mm2
V = [ ( VX1 )2 + ( Vy1 ) 2+ ( Vz1 ) 2 ]1/2
= 15.61 N/mm2 Resultant Shear Stress

Since V < fvw,d Therefore the Weld Capacity is SUFFICIENT

45
Project:
Designer:
Checked by:
Date:

3.30 ANALYSIS OF BASEPLATE

Fy = 9.3 kN Maximum Design Axial Load ( Compression)


MAT = C Base Material , (C=Concrete, S=Steel)
fcu = 30 N/mm2 Grade of Concrete
L = 150 mm Base Plate Length
W = 75 mm Base Plate Width
tact = 10 mm Actual Thickness of Base Plate
pyp = 220 N/mm2 Design Strength of Base Plate
TYPE = R Column Type , (C=circle, R=Rectangular, L=Line)
D = 50 mm Depth of Column
B = 50 mm Width of Flange
tc = 4 mm Thickness of Column
A = 518 mm2 Area required
c = 0.59 mm perpendicular dist. From the
Clause
edge 4.13 .2.2
w = 18 N/mm2 0.60*fcu , Pressure under the
Clause
baseplate
4.13 .2.2
0.50
tp = c [ 3w / pyp]
= 0.293 mm Minimum Required thickness
Clause
of Base
4.13.2.2
Plate

Since tp < tact therefore the Steel


ADEQUATE.
base Plate is

3.40 DESIGN OF ANCHOR BOLTS

Rh = Fx
= 0.08 kN Maximum Horizontal Load
Rv = Fy
= 9.33 kN Maximum Vertical Load
Rl = Fz
= 0.21 kN Maximum Horizontal Load

46
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 1
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:

Specifier's comments: SINGLE ARM MONITOR STEEL FRAME ANCHORS

1 Input data
Anchor type and diameter: HSA-F M12 hnom1
Effective embedment depth: hef = 50 mm, hnom = 64 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 8/28/2017 | -
Proof: Design method ETAG (No. 001 Annex C/2010)
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: S275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.100
lx x ly x t = 75 mm x 150 mm x 10 mm; (Recommended plate thickness: calculated (7 mm))
Profile: Square hollow; (L x W x T) = 50 mm x 50 mm x 5 mm
Base material: uncracked concrete, , fc,cube = 25.00 N/mm2; h = 150 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
47
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 2
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads
2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 4.665 0.112 0.040 0.105
2 4.665 0.112 0.040 0.105 x
Tension

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 9.330 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]
1
Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load (ETAG, Annex C, Section 5.2.2)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 4.665 28.857 17 OK
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 9.330 19.838 48 OK
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
40.400 1.400 28.857 4.665

3.2 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm]
37,500 22,500 75 150
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
10.100 17.854 1.500 19.838 9.330

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
48
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 3
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:

4 Shear load (ETAG, Annex C, Section 5.2.3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 0.112 23.600 1 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 0.225 39.677 1 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
29.500 1.250 23.600 0.112

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] k-factor
37,500 22,500 75 150 2.000
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
17.854 1.500 39.677 0.225

5 Combined tension and shear loads (ETAG, Annex C, Section 5.2.4)

bN bV a Utilization bN,V [%] Status


0.470 0.006 1.500 33 OK
baN + baV ≤ 1.0

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 3.456 [kN] dN = 0.122 [mm]
VSk = 0.083 [kN] dV = 0.010 [mm]
dNV = 0.122 [mm]
Long term loading:
NSk = 3.456 [kN] dN = 0.285 [mm]
VSk = 0.083 [kN] dV = 0.016 [mm]
dNV = 0.285 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
49
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 4
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility! 
• Checking the transfer of loads into the base material is required in accordance with ETAG 001, Annex C(2010)Section 7! The software
considers that the grout is installed under the anchor plate without creating air voids and before application of the loads.
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of ETAG 001, Annex C! For larger
diameters of the clearance hole see Chapter 1.1. of ETAG 001, Annex C!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
50
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 5
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:

8 Installation data
Anchor plate, steel: S275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2 Anchor type and diameter: HSA-F M12 hnom1
Profile: Square hollow; 50 x 50 x 5 mm Installation torque: 0.050 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 10 mm Hole depth in the base material: 72 mm
Recommended plate thickness: calculated (7 mm) Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Installation torque control bar with suitable
• Properly sized drill bit screw driver or torque wrench
• Hammer
y

38 38

25

2
75
100

x
75

1
25

38 38

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0 -50 - - - -
2 0 50 - - - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
51
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 6
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
52
Project:
Designer:
Checked by:
Date:

PART 4: ANALYSIS OF 15 MM SOFFIT STEEL PLATE

4.1 DESIGN LOAD & COMBINATION

Selfweight (SW)
The Selfweight is considered with additional +10% due to Accessories & fixings.

Design Deadload (DL)


Unit Weight of Steel Plate & Steel Frame ws = 77.00 kN/m3
Net Weight of Surgical Light PDL-sl = 130.00 kg
= 1.30 kN
Weight of Dia 110x 6t Conduit Pipe PDL-pipe = 1 no. x 1332 mm2 (Area) x 1100 mm (Length) x ws
= 0.11 kN
Total Deadload with +10% for Fixings PDL = 1.1 * ( PDL-sl + PDL-pipe )
= 1.55 kN

Design Liveload ( LL)

Direct Tension Load ( PLL)

Direct Tension Load P LL = 2300.00 N

Case 1 : Liveload Torque Moment at Z Axis ( MLLz)

Design Torque Moment MLLz = 2400.00 N-m or 2.40 kN-m

Case 2 : Liveload Torque Moment at X Axis ( MLLx)

Design Torque Moment MLLx = 2400.00 N-m or 2.40 kN-m

Load Combination

Combo 1 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLz Strength Check
Combo 2 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLx Strength Check
Combo 3: 1.0 SW + 1.0 DL Serviceability
Combo 4: 1.0 SW+1.0 PLL ± 1.0 MLLz Serviceability
Combo 5: 1.0 SW+1.0 PLL ± 1.0 MLLx Serviceability

4.2 LOAD DIAGRAM

53
54
55
56
57
58
59
60
61
62
63
Project:
Designer:
Checked by:
Date:

APPENDIX

64
65
66