Woodlands Health Campus P4 - Struc Calc For Single Arm Monitor - Rev 0 (25.01.21)
Woodlands Health Campus P4 - Struc Calc For Single Arm Monitor - Rev 0 (25.01.21)
KC SIEW ENGINEERING
CONSULTANTS
Project Title:
Document Title:
Part 4 / Rev.0
Project:
Designer:
Checked By:
Date:
Project:
Designer:
Checked by:
Date:
TABLE OF CONTENTS
Introduction:
The Structural Calculation report is the Analysis of Soffit Steel Frame Support & Connection for Single Arm Monitor . The
Design Values are taken from the given design Load and the review of the System are based on the given parameters below.
Selfweight (SW)
An Additional 10 % of Selfweight if considered to the frames for Accessories
Deadload (DL)
Unit Weight for Steel Plate & Steel Frame DL = 7700 kg/m3 or 77 kN/m3
Net Weight of Single Monitor Arm P DL-sl = 130 kg or 1.30 kN
Liveload ( LL)
Tensile Force PLL = 2300 N or 2.30 kN
Torque at Ceiling ( For All Direction ) MLL = 2400 Nm or 2.40 kN-m
1.5 SERVICEABILITY
1
Project:
Designer:
Checked by:
Date:
2
Project:
Designer:
Checked by:
Date:
Selfweight (SW)
The Selfweight is considered with additional +10% due to Accessories & fixings.
Weight of Dia 110x 6t Conduit Pipe PDL-pipe = 1 no. x 1332 mm2 (Area) x 1100 mm (Length) x ws
= 0.11 kN
Design Deadload with +10% for Fixings PDL = 1.1 * ( PDL-sl + PDL-pipe )
= 1.55 kN
Design Liveload ( LL )
Load Combination
Combo 1 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLz Strength Check
Combo 2 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLx Strength Check
Combo 3: 1.0 SW + 1.0 DL Serviceability
Combo 4: 1.0 SW+1.0 PLL ± 1.0 MLLz Serviceability
Combo 5: 1.0 SW+1.0 PLL ± 1.0 MLLx Serviceability
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Project:
Designer:
Checked by:
Date:
Reference Drawing :
3.1 DESIGN REACTION LOAD ( Refer to Part 2 ,STAAD ANALYSIS OUTPUT , Reaction Summary Table )
44
Project:
Designer:
Checked by:
Date:
● Section Properties
● Weld Capacity
45
Project:
Designer:
Checked by:
Date:
Rh = Fx
= 0.08 kN Maximum Horizontal Load
Rv = Fy
= 9.33 kN Maximum Vertical Load
Rl = Fz
= 0.21 kN Maximum Horizontal Load
46
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 1
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:
1 Input data
Anchor type and diameter: HSA-F M12 hnom1
Effective embedment depth: hef = 50 mm, hnom = 64 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 8/28/2017 | -
Proof: Design method ETAG (No. 001 Annex C/2010)
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: S275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.100
lx x ly x t = 75 mm x 150 mm x 10 mm; (Recommended plate thickness: calculated (7 mm))
Profile: Square hollow; (L x W x T) = 50 mm x 50 mm x 5 mm
Base material: uncracked concrete, , fc,cube = 25.00 N/mm2; h = 150 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
47
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 2
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
48
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 3
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
49
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 4
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with ETAG 001, Annex C(2010)Section 7! The software
considers that the grout is installed under the anchor plate without creating air voids and before application of the loads.
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of ETAG 001, Annex C! For larger
diameters of the clearance hole see Chapter 1.1. of ETAG 001, Annex C!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
50
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 5
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:
8 Installation data
Anchor plate, steel: S275; E = 210,000.00 N/mm2; fyk = 275.00 N/mm2 Anchor type and diameter: HSA-F M12 hnom1
Profile: Square hollow; 50 x 50 x 5 mm Installation torque: 0.050 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 10 mm Hole depth in the base material: 72 mm
Recommended plate thickness: calculated (7 mm) Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
38 38
25
2
75
100
x
75
1
25
38 38
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
51
www.hilti.com.sg Profis Anchor 2.8.1
Company: Page: 6
Specifier: Project: WHC - PART 4 CALC
Address: Sub-Project I Pos. No.: PART 3.4 ANCHOR
Phone I Fax: | Date: 24/1/2021
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
52
Project:
Designer:
Checked by:
Date:
Selfweight (SW)
The Selfweight is considered with additional +10% due to Accessories & fixings.
Load Combination
Combo 1 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLz Strength Check
Combo 2 : 1.35 (SW+ DL) +2.0 PLL ± 2.0 MLLx Strength Check
Combo 3: 1.0 SW + 1.0 DL Serviceability
Combo 4: 1.0 SW+1.0 PLL ± 1.0 MLLz Serviceability
Combo 5: 1.0 SW+1.0 PLL ± 1.0 MLLx Serviceability
53
54
55
56
57
58
59
60
61
62
63
Project:
Designer:
Checked by:
Date:
APPENDIX
64
65
66