Professional Documents
Culture Documents
2) Service Manual Warming Cabinets
2) Service Manual Warming Cabinets
bin
Chapter 1 Introduction
Chapter 3 Calibration
Chapter 4 Construction
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
Introduction
The enclosed information is a service guideline only, offering an overview of service aspects of the
above mentioned product. It is understood that there may be slight differences between the
information contained in this manual and the actual specification of the unit purchased. It is also
understood that only qualified personnel who is occupational familiar with the risks of maintenance
and service works on electrically operated apparatus should carry out service on Binder products
and additionally it is recommended that these service personnel should have attended service
training offered by Binder. Binder accepts no responsibility for any harm, also harmful effects on
health of service personnel caused by servicing which is not carried out by Binder. Unrestrictedly
included are all harms caused by lost profits, business interruption or any financial loss also when
it can be regarded as in direct connection with any action described in this service manual.
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
ED, FD (E1)
Main switch
Safety thermostat class 2.0
24 hours timer
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
Connections to R2 controller:
heating element
directly supplied with sizes 53 and 115.
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
Connections RD2
power supply
PT 100 probe
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
Changing the heating element (several elements with larger sizes of this chambers)
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
Bolt (2 pc. )
axis sea
Bolt lever
screw M5 (3 pc.)
washer 5,3
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
50
Insert the measuring instrument probe at the measuring point, located in the centre of the
usable volume.
Operate the unit until it reaches the required nominal temperature and allow to settle. When the
unit has reached the required temperature, please allow it to continue running for approx. 1
hour - only then is the unit reliably set for calibration.
Read off the temperature displayed on your measuring instrument and compare this with the
controller display.
Note:
The controller has its best accuracy at the calibration temperature. So a calibration temperature
next to the most common user temperature is recommended. The calibrating procedure can be
repeated if the first adjustment does not bring the desired accuracy.
The calibration point of the final testing at the factory is 37°C (incubators), resp. 150°C (drying
ovens).
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
37.0
Insert the measuring instrument probe at the measuring point, located in the centre of
the usable volume.
Operate the unit until it reaches the required nominal temperature and allow to settle.
When the unit has reached the required temperature, please allow it to continue
running for approx. 1 hour - only then is the unit reliably stable for calibration.
Read off the temperature displayed on your measuring instrument and compare this
with the controller display.
Any variation can be changed on the controller. To do this, press the start/stop button
and stop the controller. Now press the actual/set value button, the mode button, the
arrow up and arrow down buttons simultaneously. A point will flash in the display. Now
you can input the temperature displayed on your measuring instrument by repeatedly
pressing the on and off button. Confirm the entry by pressing the actual/set value
button. Now press the start/stop button to start the controller.
Re-check the input temperature with your measuring instrument once the unit has been
re-heated. This adjustment on the controller must be performed rapidly, in order to
ensure that any variation is as small as possible.
The calibration point of the final testing at the factory is 37°C (incubators), resp. 150°C (drying
ovens).
To check the PT100 sensor a resistance measurement can be made at two different temperatures.
The resistance between the two white wires (directly connected) and the single red wire should be
108: at 20 °C and 131: at 80°C.
BB / JTU 25.06.2000
Service – documentation series ED,FD,BD / EED,FED,BED
Chapter 4
The example pictures of this chapter show the construction of this chamber types.
Only small size cabinets with one door are shown.
The principal construction however is similar for all sizes of this types of warming chambers.
The major difference with 3-phase chambers are solid state relays at the lower back side of the
chamber to control the heating elements.
A low voltage DC heating output is used on the controller in this case. For chambers with only one
phase the heating elements are directly controlled by a power switching element on the controller
PCB.
BB / JTU 25.06.2000
construction of warming chambers
types ED,EED, FD, FED, BD,BED size 53 and 115
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
Inner chamber
of ED, EED, BD,BED size 115
rear wall of inner chamber = outer
chamber wall
side parts without ventilation holes
FD/FED 115
INTELLIGENTE TEMPERATURTECHNIK
APT-Line
Advanced Preheating chamber
Technology
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK