Professional Documents
Culture Documents
Tracer™ SC Air Systems Application Guide
Tracer™ SC Air Systems Application Guide
Air Systems
for Tracer™ SC
Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All trademarks
referenced in this document are the trademarks of their respective owners.
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Zone Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Installing the VAV Discharge Air Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installing a Hot Water Valve (Local Heat and Remote Heat) . . . . . . . . . . . . . 30
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Power Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Air Handler Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Controller Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Air Handler Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Why Use a DAC Profile for an Air Handler on a LonTalk Link? . . . . . . . . . . . 33
Pre-Configuration Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
General LonTalk Controller Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Controller Setup (IntelliPak) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
VAV Box Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2 BAS-APG007-EN, 12/15/2009
Install the MP580/581 on the Tracer SC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Integrating the MP580/581 Controller with Tracer SC . . . . . . . . . . . . . . . . . . 51
Communicating Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Tracer Graphical Programming (in the MP580/581 using Rover) . . . . . . . . . 57
Pre-Packaged Solutions Sample PPS Graphics.tgp . . . . . . . . . . . . . . . . . . . . 58
Programming the Field-Applied BACnet Unit Controllers . . . . . . . . . . . . . . . 59
VAV System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Common Spaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Defining Areas and Selecting Area Members . . . . . . . . . . . . . . . . . . . . . . . . . 62
Assigning the VAS Members . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
How Area and VAS Interact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
How Schedule and Area Determine Operating Mode . . . . . . . . . . . . . . . . . . 68
How Area Determines the Operating Mode of the VAV Box . . . . . . . . . . . . . 71
Tracer SC Application Setup for Variable Air Systems . . . . . . . . . . . . . . 72
Tracer SC Equipment Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Install and Set Up the Variable Air Volume Equipment Types . . . . . . . . . . . 73
Set Up Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Navigating Through the VAS Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
VAV Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Auto-Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Commissioning and Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Standard Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Unoccupied Heating/Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Optimal Start (PreCool/Morning Warm-up . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Humidity Pull Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Warm-up with Normal Start (No Optimal Start) . . . . . . . . . . . . . . . . . . . . . . 126
Daytime Warm-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Optimal Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Night Purge (Night Economizing) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Unoccupied Humidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Unoccupied Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Timed Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
General Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Best Practice for Commissioning: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Air Handler Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Commissioning the Communications Link . . . . . . . . . . . . . . . . . . . . . . . . . . 141
BAS-APG007-EN, 12/15/2009 3
Preliminary Checkout for LonTalk Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Finding a Short . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Finding an Open Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Preliminary Checkout for BACnet Communication Links . . . . . . . . . . . . . . 144
Auto-commission the Tracer VV550/551 and UC400 Controllers . . . . . . . . 149
Things to Consider Before Auto-commissioning . . . . . . . . . . . . . . . . . . . . . 150
Auto-commissioning Individual VAV Boxes with the Service Tools . . . . . 150
Auto-commissioning All VAV Boxes with Tracer SC . . . . . . . . . . . . . . . . . . 152
Interpreting the Auto-commissioning Report . . . . . . . . . . . . . . . . . . . . . . . . 155
Perform Air and Water Balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Duct Static Pressure Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Static Pressure Sensor Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Setup Instructions for a Variable Volume Air Handler . . . . . . . . . . . . . . . . . 157
Setup Instructions for an MP580/581 Air Handler . . . . . . . . . . . . . . . . . . . . . 158
Tracer SC VAS Duct Static Pressure Optimization Setup . . . . . . . . . . . . . . 158
Ventilation Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Zone Level Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
System Level Action ......................................... 166
Ventilation Ratio Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Default Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Ventilation Optimization Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Ventilation Optimization Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Sequences of Operation for Standard Operating Modes . . . . . . . . . . . . . . 196
General Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Optimal Start (Cooling Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Optimal Start (Heating Mode)(Central Heat Used/Local Heat Not Used
or Not Present) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Optimal Start (Heating Mode)(Local Heat with a Central Fan) . . . . . . . . . . 205
Humidity Pull-down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
4 BAS-APG007-EN, 12/15/2009
Normal Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Optimal Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Unoccupied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Unoccupied Heating/Cooling—Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . 216
Unoccupied Heating/Cooling—Heating Mode with Central Heat . . . . . . . . 219
Unoccupied Heating/Cooling—Heating Mode with Local Heat and
a Central Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Unoccupied Heating/Cooling—Heating Mode with
Local Heat and No Central Fan for Night Heat . . . . . . . . . . . . . . . . . . . . . 226
Night Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Unoccupied Humidify . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Unoccupied Dehumidify . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Timed Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Communications Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Isolating Problem VAV Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Appendix A: Controller Flow Settings Worksheet . . . . . . . . . . . . . . . . . . 239
Appendix B: Tracer SC Mapping to MP580/581 Network
Variable Inputs (nvi) and Profile Associations . . . . . . . . 241
Appendix C: Member Occupancy Response to Area and
VAS Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Appendix D: Area and VAS Rank Arbitration for
Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Appendix E: Equipment Response to Operating Modes . . . . . . . . . . . . 245
Appendix F: Tracer SC Priority Levels and Assigned
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Appendix G: Trane Equipment Response to Optimal Start
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Appendix H: Common Tracer SC Enumerations . . . . . . . . . . . . . . . . . . . . 249
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
BAS-APG007-EN, 12/15/2009 5
Introduction
What is VAS?
The Variable-Air-Volume Air System (VAS), available in Tracer SC, permits you to control and
coordinate air handlers and VAV boxes. The Tracer SC VAS includes valuable tools to help manage
tasks that were previously problematic and time consuming, such as:
• Coordinating AHU and VAV box operation
• Commissioning VAV boxes
• Scheduling common spaces
• Optimizing ventilation
• Optimizing duct static pressure
Objectives
This guide presents a process to efficiently implement a basic, single-duct VAV air system.
Following this recommended process should allow you to design and install a VAV air system that
is easy to set up, works well from the outset, and requires minimal adjustment later.
Note: Because this applications guide focuses on standardizing and simplifying the process, it
does not address Hybrid VAV systems such as dual duct, loop duct, and changeover bypass,
which require customization.
With the instructions provided in this guide, you should know or be able to find out:
• What to think about when designing a project
• How best to install the equipment
• The most efficient way to set up the equipment and configure the VAV air system
• Best practices for configuring an MP580/581 using the DAC profile
• How to set up the standard functions for a VAV air system (Unoccupied Heating/Cooling,
Optimal Start, etc.)
• The best way to commission a project
• How to optimize the VAV air system and implement special applications
• How best to maintain the equipment and the VAV air system
Best Practices
The best practices in this manual are interrelated and build on each other. They will help you save
time and reduce cost. They are interspersed throughout the manual in colored boxes with a best
practice star in the margin (as shown below). It is important to follow these best practices at each
phase of the project to help ensure success in later phases.
This is a best practice box. They are located throughout the applications guide to call attention
Best to important information and highlight best practices.
Practice
Maintain
AHU Ductwork
VAV boxes
Unoccupied Heating. Heating options include gas (staged or modulating), hydronic (hot water or
steam), or electric (staged or modulating).
A VAV AHU typically has a variable speed supply fan controlled by a variable frequency drive (VFD)
to maintain static pressure in the ductwork. The AHU may also have exhaust or return air fans
installed, which are not discussed in this applications guide.
Ductwork
Ductwork provides the airflow path for a VAV air system connecting the AHU to the VAV boxes and
diffusers.
VAV boxes
VAV boxes (also referred to as VAV terminal units) contain an airflow damper, an airflow sensor,
a fan (optional), and a heat source (optional). There are four basic types of VAV boxes: Shutoff, VAV
box with reheat, VAV box with parallel fan, VAV with series fan (refer to Figure 3). A project may
use only one type of VAV box throughout the installation; however, it is more common that a variety
of VAV boxes are installed and used for specific purposes depending on their location in the
building or within each zone.
Figure 3. VAV boxes: how they work and how they are used
Figure 3. VAV boxes: how they work and how they are used (continued)
Diffusers
Diffusers are typically located in the ceiling, above the occupied spaces, and downstream (in the
airflow path) of the VAV boxes.
BAS Technician(s)
Inst
Insta
stal
stalll
al
BAS Technician(s)
Maintain
Design Considerations
This section provides information to consider while designing a project that contains a VAV air
system. Choosing the right equipment is the most important element in designing a VAV air
system. Choosing the wrong equipment can add substantial cost and setup time to the project.
Use a variable setpoint that is based on the position of the VAV terminal dampers (refer to “Duct
Best Static Pressure Optimization,” p. 157).
Practice
Choose an AHU that can control its discharge air temperature while cooling. Air
handlers in a Tracer SC VAS should be able to control their discharge air temperature while cooling.
Trane AHUs do this, although some (IntelliPak™ and ReliaTel™) do not control their discharge air
temperature during certain heating scenarios. If using non-Trane air handlers, make sure they can
control the discharge air temperature while cooling.
Climate Changers need to be ordered with an MP580 controller (refer to Table 1), which is a native
LonTalk controller. Order IntelliPaks, Commercial Self-Contained, and Commercial Voyagers with
a LonTalk Communication Interface (LCI) card, not a Tracer Communication Interface (TCI).
Table 1. Equipment and controller pairings
Equipment Controller
Line voltage power is required for the Tracer MP581. If possible, the electrical contractor
should bring line voltage power to the AHU controller to power the control transformer. However,
if that is not possible, allocate enough time and material to run the line voltage power to the
controller. Work with the consulting engineer to ensure that the electrical prints show power
coming to the AHU controller. Know the voltage of this power source to order the correct step-down
(to 24 Vac) transformer with the Tracer MP581.
Do not wire critical inputs and outputs to EX2 expansion modules. Instead, wire them
directly to the MP580/581 controller. If communications fail to the EX2, the control fails to the last
state. Use EX2s for ancillary points.
Do not hard-wire a space temperature sensor to the air handler. In comm loss situations,
the AHU goes into Occupied mode 15 minutes after it loses communication. If the AHU has a heat
source, and morning and/or daytime warm-up are enabled, the AHU could go into a warm-up cycle
as needed. If the VAV boxes downstream cannot communicate with the AHU to see that it is going
into a constant volume mode of operation (Max Heat), the VAV box air dampers will not drive to
max to accommodate the increased airflow. This could result in damage to the duct system.
Are airflow measurement stations required? If the design engineer has specified ventilation
airflow requirements for the VAV boxes, an airflow measurement station at the AHU may be
necessary to measure and control the amount of outdoor air being brought into the system.
• Order Traq™ dampers with the IntelliPak and Climate Changer.
Note: If using a Climate Changer for a 100% outdoor air unit in a dedicated ventilation system,
Traq dampers may not be necessary.
• Traq dampers on Self-Contained units are only offered on 20 to 80 ton water-cooled units with
air-side economizers. Instead of using Traq dampers to measure the amount of outdoor air
delivered to your CSC (or if you have a water-side economizer with your CSC), use a VAV box
(if the building design allows for it). The VAV box in this case is part of a dedicated ventilation
system (refer to “Dedicated Ventilation Systems,” p. 181).
Note: Depending on the amount of ventilation air required, or if the space the CSC serves has
more than one Area, more than one VAV box may be needed.
• Although Traq dampers are not offered on the VAV Commercial Voyager, the unit has a function
called OA CFM Compensation Control, which modifies the OA damper minimum position
based on the reported unit airflow.
Note: OA Flow Compensation control is NOT compatible with ventilation optimization. Refer
to the guide on ReliaTel Microprocessor Controls, RT-SVD03C-EN, for additional
details on OA CFM Compensation.
When required to report AHU supply fan airflow, a suitable substitution may be the summation
of all VAV box airflows.
VAV Boxes
Consider the following information when selecting VAV boxes for the project:
Order a zone sensor with the VAV box. •
• If it is necessary to initiate or cancel Timed Override from a zone sensor, order a sensor with
an ON button or ON/CANCEL buttons.
• If a communication stub is wired to the space sensor, order a space sensor with a
communication jack.
• If using wireless zone sensors, order the VAV box with a factory-mounted wireless receiver to
avoid field installation
Note: Do not order a zone sensor for VAV boxes that are configured for Flow Tracking or
Ventilation Flow Control because they do not use the sensor. Refer to “Special
Applications,” p. 181 for more information.
Order a LonTalk DDC controller (Tracer VV550/551) or UC400 controller with the VAV
box. The Tracer SC VAS has several features designed around Trane controllers. These features
include ventilation optimization, CO2 demand-controlled ventilation, and auto-commissioning,
which significantly enhances the VAV air system.
Order an auxiliary temperature sensor with any fan-powered VAV box (VSxx, VPxx) or
any single-duct VAV box with reheat (VCWF, VCEF). (Specify that it be installed in the
discharge air stream). This sensor is crucial for monitoring performance and for
troubleshooting. It is installed by the controls electrician (so budget accordingly) in the discharge
air stream of the VAV box and is used for the controller auto-commissioning sequence.
Note: When a VAV box is used only for ventilation (as is found in a dedicated ventilation system,
for example), in northern climates, order electric or hot water reheat with the VAV box if the
AHU supplying that outdoor air has limited or no reheat capabilities. An auxiliary
temperature sensor is required for VAV boxes that have reheat and are configured for
Ventilation Flow Control.
©2009 Trane. All Rights Reserved.
14 PROPRIETARY INFORMATION OF TRANE. BAS-APG007-EN, 12/15/2009
MAY ONLY BE USED IN THE CONDUCT OF TRANE BUSINESS.
Design Considerations
Is an occupancy sensor necessary? If the sequence of operation calls for occupied stand-by
operation (using alternate temperature and airflow setpoints during occupied hours if the zone is
vacant), purchase an occupancy sensor (dry contacts only) for that VAV box. The controls
electrician installs this sensor, so budget accordingly.
Is CO2 level monitoring required? When using Tracer UC400 controllers on VAV boxes, the
controller has a CO2 sensor terminal on the board; however, the Tracer VV550/551 does not support
a hardwired input for CO2; only communicated values are accepted. If it is necessary to monitor
or control the amount of CO2 in the space served by the VAV box (a CO2-based demand-controlled
ventilation zone application), purchase a CO2 sensor. The controls electrician installs this sensor,
so budget accordingly.
On systems that require CO2-based demand controlled ventilation, avoid having to provide a
Best CO2 sensor in every zone. Work with the design engineer so CO2 sensors only get specified in
Practice those zones (conference rooms, for example) that can be densely occupied but experience
widely varying patterns of occupancy.
Do not use hot water heat in Ventilation Flow Control (VFC) boxes on a dedicated
ventilation VAS. There is no freeze protection for VAV boxes with hot water heat when they are
used as VFC boxes in a dedicated ventilation system. Instead, use shutoff VAV boxes or electric
reheat VAV boxes as the VFC box. Refer to “Dedicated Ventilation Systems,” p. 181 for more
information.
For single-duct VAV terminal units (VCCF, VCWF). Often, the customer’s design engineer or
architect will not bring 120 Vac power to the VAV box if the box does not have a fan (series or
parallel) or electric reheat. The cost to bring 24 Vac to the VAV boxes by centrally mounting a
transformer and then running 24 Vac to each VAV box after the fact will be much more expensive
if the design engineer does not specify 120 Vac power initially. Be sure to incorporate the
appropriate costs in the estimate for supplying power to VAV boxes without fans or reheat that still
require power.
Important: Do not order a factory-mounted transformer with single-duct terminal units (VCCF,
VCWF). If the factory-mounted transformer is ordered, it may not get used because
it is too expensive to have the electrical contractor bring 120 Vac to the box (the 120
Vac would likely need to be in conduit).
If power is needed at the box, have the electrical contractor use a 100 VA Class 2 120/24 Vac
Best transformer and daisy chain the 24 Vac to a maximum of three boxes. If there is a VAV box nearby
Practice with a fan or electric heat it may also be possible to tap power from its factory-mounted 50 VA
120/24 Vac transformer.
The Trane project engineer should specify the airflow setpoints for each VAV box.
There are many airflow setpoints to address, such as heating and cooling airflow setpoints for
minimum, maximum, and standby airflow. A flow settings worksheet is included in Appendix A of
this guide to assist with this task (refer to “Appendix A: Controller Flow Settings Worksheet,”
p. 239). Use the schedule of VAV boxes obtained from the customer’s engineer or architect to
specify the flow settings for each VAV box on the worksheet. The installing technician and BAS
technician will use this worksheet to set up the VV550/551 controllers and Tracer SC.
If you have to bring power to the box, have the electrical contractor use a 100 VA Class 2 120/
Best 24 Vac transformer and daisy chain the 24 Vac to a maximum of three boxes. If there is a VAV
Practice box nearby with a fan or electric heat it may also be possible to tap power from its factory-
mounted 50 VA 120/24 Vac transformer.
Tracer SC Sizing
The Tracer SC can support up to 120 total devices, including any combination of devices on the two
BACnet MSTP links and the LonTalk link. Currently the Tracer SC can support up to 30 devices on
each of the BACnet MSTP links and 120 devices on the LonTalk link. LonTalk links with more than
60 devices require a repeater, which may include devices other than those associated with the VAV
control system.
Note: If there are MP580/581 devices on the LonTalk link, the total number of devices cannot
exceed 70 (MP580/581s + LonTalk devices).
BAS Technician(s)
Inst
Insta
stal
stalll
al
BAS Technician(s)
Maintain
Sequence of Operation
This section contains text that can be copied and pasted into submittals (or guide specifications).
Use the text as is to ensure there will be no question that Trane equipment will be able to function
according to the requirements. Keep in mind that submittals are for equipment such as AHUs and
VAV boxes and not control systems. The goal is that the person reading the submittal has an
increased understanding of Trane equipment and how it operates.
Flow Tracking
• Occupied and Unoccupied operating modes are not supported. Flow tracking VAVs always
follow the communicated airflow setpoint plus the configured offset.
Reheat Options
Choose the appropriate reheat paragraph for the kind of reheat present in the box.
• Staged Electric—Stage on up to 3 stages of electric heat with a 1 degree interval per stage
as the space temperature falls below the heat setpoint. Stage off the electric heat stages as the
space temperature rises 0.5 degrees above the turn on point.
• Pulse Width Modulation (PWM)—The first, second, and third stage of heating shall be
energized based on time and temperature deviation below the heat setpoint. The heat stages
will be brought on in order, and duty cycled one at a time, to meet the desired heating capacity.
The stages will be duty cycled on a 3 minute period. Desired heating capacity will be distributed
equally among all heat stages that are present.
• Two-Position Hot Water—Open the two-position valve as the space temperature falls below
heating setpoint. Close the valve as the space temperature rises more than 0.5 degrees above
the heating setpoint.
• Proportional Hot Water—The position of the hot water valve is based on time and
temperature deviation below the heat setpoint.
setpoint, the unit shall modulate closed to its minimum heating cfm. The parallel fan shall be
turned off. The reheat shall be turned off. If the air handler is running in the constant volume
mode during occupied heating, the unit shall open its air valve to its maximum heating cfm. The
parallel fan and the reheat are off.
• Unoccupied, primary air is hot
Intermittent Fan Control—As the space temperature falls below the unoccupied heating
setpoint the unit shall open to its maximum heating cfm. The parallel fan shall turn on when
the reheat turns on. If the primary air is hotter than the configured Reheat Enable Setpoint, the
reheat and the parallel fan shall be turned off. As the space temperature rises above the
unoccupied heating setpoint, the unit shall close the air valve. If the air handler is running in
the constant volume mode during unoccupied heating, the unit shall open its air valve to its
maximum heating cfm, the parallel fan and the reheat are off.
• Unoccupied, primary air is cold
On a rise in space temperature above the unoccupied cooling setpoint, the VAV terminal unit
shall open to its maximum cfm and the parallel fan is turned off. As the space temperature falls
below the unoccupied cooling setpoint, the unit shall close the air valve. As the space
temperature continues to fall below the unoccupied heating setpoint, the unit shall turn on the
parallel fan and the heat at 100%. The air valve stays closed. As the space temperature rises
above the unoccupied heat setpoint, the parallel fan and the reheat turn off.
If the air handler has heat, it shall support daytime warm-up. As the space temperature falls below
the daytime warm-up initiate setpoint, the VAV AHU shall control the DAT to the discharge air
heating setpoint. As the space temperature rises above the daytime warm-up terminate setpoint,
the VAV AHU shall control the DAT to the discharge air cooling setpoint.
If the air handler has heat, it shall support morning warm-up. On the transition from Unoccupied
to Occupied, if the space temperature is below the morning warm-up initiate setpoint, the VAV AHU
shall control the DAT to the discharge air heating setpoint. As the space temperature rises above
the morning warm-up terminate setpoint, the VAV AHU shall control the DAT to the discharge air
cooling setpoint.
Unoccupied
As the space temperature rises above the unoccupied cooling setpoint, the VAV AHU shall turn on
the supply fan and use mechanical cooling and economizing, if possible, to control the discharge
air temperature (DAT) to the discharge air cooling setpoint. The duct static pressure shall be
controlled. As the space temperature falls below the unoccupied cooling setpoint, the VAV AHU
shall turn off the supply fan and the mechanical cooling and close the outdoor air damper.
As the space temperature falls below the unoccupied heating setpoint, the VAV AHU shall turn on
the supply fan and use heating to control the DAT to the discharge air heating setpoint. The duct
static pressure shall be controlled. As the space temperature rises above the unoccupied heating
setpoint, the VAV AHU shall turn off the supply fan and the heating.
If the VAV AHU does not control the duct static pressure, it shall report Max Heat.
• For those zones equipped with an occupancy sensor, the required outdoor airflow for the zone
shall be continuously determined based on whether people are present or not. When the
occupancy sensor indicates that people are present in the zone, the required outdoor airflow
shall equal the design outdoor airflow. When the occupancy sensor indicates that no people are
present in the zone, the required outdoor airflow shall equal the Occupied Standby outdoor
airflow.
• For those zones equipped with a CO2 sensor, the required outdoor airflow for the zone shall be
continuously calculated using the measured CO2 concentration as an indicator of the current
per-person ventilation rate.
The required outdoor-air fraction shall be continuously calculated for each VAV terminal zone.
Outdoor-air fraction is defined as the current required outdoor airflow for the zone divided by the
current primary airflow to the zone.
The BAS shall regularly determine the highest zone outdoor-air fraction, sum the outdoor airflow
requirements for all VAV zones, and sum the current primary airflows for all VAV zones to determine
the total system primary airflow. This information shall be used in Equation 6-1 of ASHRAE
Standard 62-2001 to calculate the minimum required outdoor airflow for the system. This
minimum outdoor airflow setpoint shall be recalculated every 15 minutes (adjustable).
BAS Technician(s)
Install
BAS Technician
an(s)
Program Air/
Ai r/Wa
r/Wate
Wa terr Balance
te B Contractor
Maintain
Installation
This section contains basic installation and connection guidelines. Detailed information is located
in the ship-with documents that came with the devices. References to those documents are
provided as appropriate.
Assumptions
When the following equipment is referred to in this section, these assumptions apply:
• The controller is factory-mounted on all VAV boxes.
• The air valve actuator is factory-mounted on all VAV boxes.
• Fan-powered VAV boxes have their fans mounted and wired at the factory.
• Electric heat in VAV boxes is installed and wired at the factory.
• There is 24 Vac or a single-point connection that provides 24 Vac.
Overview
Figure 4, p. 27 and Figure 5, p. 28 give a summary view of the devices that are typically wired to
the VV550/551 and UC400 controllers in a VAV application and their terminations on the controllers.
Following the figures are brief descriptions of the devices, how they are used, and, if applicable,
best practices for connecting them. For detailed information on wiring specifications, terminations,
and instructions, refer to the documents shipped with the devices.
Actuator wiring
AC-power wiring
24 Vac
Air valve open
24V (counter clockwise)
GND
Air valve close
24 Vac transformer
(clockwise)
HEAT 1
HEAT 2
HEAT 3
3
4
1
2
J1 1
J10
TB1_2
TB1_1
J8
J9
Chassis ACTUATOR J1
ground
TB2_1
TB2_2
TB2_3
TB2_4
TB2_5
TB2_6
TB3_1
TB3_2
TB3_3
TB3_5
TB3_6
TB4_2
TB4_1
J2-2
BI1
J2-1
Zone Sensor
11 24 Vac/Vdc
10 Ground *
9 *
8
7 Comm – *
6 Comm +
5 Heat Setpoint (HSP) *
4 SVS/Fan Mode (Mode) Primary air temperature (Supply)
3 Setpoint * or
Dry contacts
2 Signal Common (Common) Discharge air temperature
only 1 Zone Temperature (Zone Temp)
Kavlico Pressure
Sensor
AO1 AO2 UI1 UI2 AI1 AI2 AI3 AI4 AI5
BI4 BI5
P1 P2
24 Vac
IMC 24 24 24 IMC
+24
Vac Vac Vac
Vdc
XFMR BI1 BI2 BI3 LINK IMC
AO1 AO2
UI1 UI2 AI1 AI2 AI3 AI4 AI5
BI4 BI5
P1 P2
UC400
LINK IMC
TX
RX
SERVICE
SERVICE TOOL
ADDRESS
0 1 0 1 0 1
9 9 9
BO1 BO2 BO3 BO4 BO5 BO6 B07 B08 BO9
8
8
2
2
7
7
3
6 4 6 4 6 4
5 5 5
x100 x10 x1
24VAC – 240VAC
BO1: ECM Fan POWER SUPPLY
See footnote
BO4: Fan On/Off
See footnote
Footnote: If using a standard motorized fan, connect to the BO6: Stage 2 Heat
BO4 terminal and not BO1. If using an ECM motorized fan,
BO7: Stage 1 Heat
connect to BO1 and not BO4. For an ECM application, BO1
will be slaved to BO4 via software. Air Valve
8=Close, 9=Open
Zone Sensors
A zone sensor measures the temperature of the space served by the VAV box. A zone sensor with
an optional space setpoint input measures the temperature of the space and allows a user to
generate a request for a different setpoint at the sensor. Both sensor types have the same wire and
distance requirements, but are connected to different terminals on the VAV box controller. Three
basic types of zone sensors can be installed:
• A zone sensor (required unless the box is used for flow tracking (refer to p. 187) or ventilation
flow control (refer to p. 182))
• A zone sensor with setpoint (has a thumbwheel) (optional)
• A digital zone sensor with space temperature and setpoint (optional)
• A digital zone sensor with setpoint and On/Cancel buttons on the sensor
Note: The space setpoint thumbwheel zone sensor and the digital zone sensor are both available
with an optional communication RJ-11 jack on the board and Timed Override request and
cancel buttons.
Use 18-22 AWG, stranded, tinned-copper, unshielded, twisted-pair wire when installing zone
Best sensors.
Practice
An RJ-11 communication jack is an option available on all zone sensors. It permits access to the
communications link and all the controllers on that link from the floor level in the space.
Run power for the digital zone sensor from the VV550/551 or UC400 controller.
Best
Practice
Install the VAV discharge air sensor 1-2 feet downstream of the VAV box in the discharge air duct
(refer to Figure 6). The sensor provides feedback during auto-commissioning to verify the
operation of the hot water valve, electric heat, parallel fan, and series fan. It can also be used for
troubleshooting.
Figure 6. Discharge air sensor location (VAV box with series fan is shown)
From
AHU
To
Space
From Plenum
Communications
For detailed instructions on communication wiring, refer to latest version of Trane document
BAS-SVN03-EN, Unit Controller Wiring for Tracer SC Wiring Guide, the Tracer SC Installation guide,
or to the installation guide for the applicable building automation system.
Power Considerations
Establish Power to the VAV Boxes
Installing high voltage power is typically the responsibility of the electrical contractor, especially
if the VAV box is equipped with electric heat or a fan.
Important: If the VAV box is not equipped with electric heat or a fan, an alternate source of 24
Vac power is required.
Pull power from a near-by electric heat-equipped or fan-equipped VAV box, or centrally mount a
100 VA, 24 Vac step-down transformer (typically in a mechanical room for ease of access) and daisy-
chain the 24 Vac power to the VAV boxes as described in “Design Considerations,” p. 12.
Note: Refer to the most recent version of Trane document number 32703399, Installing the
Tracer™ VV551 VAV Controller for wiring best practices and information on installing and
wiring the VV551 controller.
Note: Refer to the most recent version of Trane document number X39641064, Tracer UC400
Programmable Controller Installation Sheet for information on installing and wiring the
UC400 controller.
Best practice
X
A Better Location
Implementing the fan static pressure optimization feature (refer to “Duct Static Pressure
Optimization,” p. 157) of the Tracer SC VAS allows the sensor to be located anywhere along the
length of the duct. This is possible because fan static pressure optimization resets the setpoint
based on real-time system demand.
Locate the duct static pressure sensor near the discharge of the fan in the supply duct.
Best
Practice
BAS Technician(s)
Install
BAS Technician(s)
Commis
Commission Building Operator
Order has been placed
BAS Technician
Operate
Maintain
Controller Setup
This section contains information on the proper sequence and best practices for configuring the
components, and some considerations specific to the Tracer SC VAS, including:
• Air handler checkout and configuring the air handler controller (AH540, MP580/581, LCI-R
Voyager/Precedent, LCI-I IntelliPak, BCI-I, BCI-R1)
• Configuring the VAV box controllers
The following subsections describe equipment and controller setup performed with the Rover
service tool or at the equipment user interface.
Pre-Configuration Checkout
Before setting up the controller, perform a physical inspection of the air handler to verify that it is
installed properly. Be sure to check the following items:
• Are the door handles closed and locked?
• Are the fire dampers open?
• Are there filters installed?
• Is the fan rotating in the correct direction?
• Are the safeties in place?
• Are the shipping bolts removed?
• Are the starter fuses installed?
• Are the access panels closed?
• Did you remove the hard-wired zone sensor?
Confirming the list above is typically the responsibility of the mechanical contractor, but the startup
technician should also verify these tasks.
Factory-Mounted
All Trane unitary products have a static pressure sensor factory-mounted in the AHU. In most cases,
the high pressure tubing connecting the sensor to the control panel is also factory-installed and no
field installation is required. However, there are some exceptions; for instance the high pressure
side of the static pressure sensor on Commercial Self Contained (CSC) units must be field-installed
to a pickup tube mounted in the discharge air plenum. Consult the equipment documentation for
more details on the static pressure installation. Before starting any AHU, make sure the static
pressure sensor and its associated tubing are present and properly installed.
Field-Mounted
Commission the static pressure sensor prior to starting the AHU. The most common field-mounted
static pressure sensors are 4-20 mA devices that read pressure from 0-5 inH20. The specific
information for the static pressure sensor being installed should be available on the device’s
product data sheet.
Verify that the VFD responds to signals before sending a start command. Once the VFD has been
checked out, start the drive in hand/manual at about 20 Hz to provide some airflow and static to the
transmitter. If the transmitter reads static pressure, release the drive to auto and verify that it is
being controlled to the static pressure setpoint.
General
Conduct a more comprehensive startup and checkout of the AHU including all temperature and
humidity sensors, as well as all damper and airflow monitors. Refer to the documentation shipped
with the air handler for more detailed information.
Naming Devices
It is common to have multiple air handlers on a single LonTalk communication link, so it is
important to have a naming convention that allows you to quickly and accurately identify an AHU
and the VAV boxes it serves.
Name the air handler based on the blueprint name. Using a number also helps to tie the air
Best handler and the VAV box together. This is useful when you are viewing devices in Tracer SC and
Practice when you perform air and water balancing using the Rover service tool, where devices are
sorted.
Example: You have two air handlers on the LonTalk link (one MP580 identified as AHU
1 on the blueprint and one IntelliPak rooftop unit identified as RTU 2 on the blueprint).
Name those air handlers AHU 01 MP580 and RTU 02 IPAK (refer to Table 3, p. 37).
Subsequently, name the VAV boxes served by the MP580 with base names of VAV 01
along with extensions identifying individual boxes (VAV 01-01, VAV 01-02, etc.). Base
names for VAV boxes served by the IntelliPak would be VAV 02 along with extensions
(VAV 02-01, VAV 02-02, etc.). Be sure to use a “0” to designate numbers less than 10 (e.g.,
01, 02, 03, etc.) or the items will not sort into correct numerical order if there are more than
10 devices on the link.
3. Select the LCI-R DAC Unit tab. (Make sure the Morning Warm-up Enable check box is selected.)
4. Select the Setpoints tab.
• Verify the Duct Static Setpoint value is correct (refer to the specifications for the project)
• The Economizer Minimum field in the IAQ Setpoints group should be at 15%. Make sure it
is not set to 0% or 100%
Note: The air balancer should specify a different Economizer Minimum value.
©2009 Trane. All Rights Reserved.
BAS-APG007-EN, 12/15/2009 PROPRIETARY INFORMATION OF TRANE. 37
MAY ONLY BE USED IN THE CONDUCT OF TRANE BUSINESS.
Controller Setup
5. Click Download to send the new configuration to the LCI-R DAC controller.
6. Click Save to save the configuration for the AHU using the device name as the configuration
file name. Configuration files have an “.rcf” extension after the file name.
Note: Create a subdirectory identifying the job name beneath the Rover/Config/ directory on
the hard drive (e.g., Rover/Config/”Job Name”/”Device Name.rcf”).
1. Configure the LCI-I controller as described in “Controller Setup (both LCI-I and BCI-I),” p. 38
using the IntelliPak’s local display.
2. Press Next to navigate to the Software Revision Number Report: settings (the number varies
depending on the number of boards installed), confirm that the latest software versions are
loaded. If not, flash download the software revision to the latest version you have available in
the Rover service tool.
a. Make sure you have the latest Rover service pack downloaded before moving to step b
below. Downloads are available at http://tranenetlax1/GCC_Downloads/Home/Downloads/
Rover.asp, or publicly at www.trane.com, at the site select: Commercial > US > Software
Downloads > Select GCC Downloads.
b. Look in the C:\program files\Rover\images directory for the latest LCI-I image (e.g., 0003_LCI-
I_Appl_1_13_5.img).
8. On the Setpoints tab (Figure 11), verify that the following information is correct:
• Default setpoints are the heating and cooling setpoints the VV550/551 uses as default values.
Refer to the Tracer VV550/551 VAV Controller Installation and Operation manual, CNT-
SVX17*-EN for a detailed explanation of how these setpoints are used by the controller.
• The Enable Auto Calibration check box is selected. This enables automatic calibration when
the power cycles or the operating mode changes to Unoccupied.
• The Enable Thumbwheel Setpoint and Enable Thumbwheel Star and Double Star Function
check boxes are not selected.
Note: It is possible to use the Enable Thumbwheel Star and Double Star function for air-
balancing without using the Rover air and water balancing tool, but it is easier to
use the tool, so Trane recommends using it.
9. Click the Unit tab.
a. Select Space Temperature in the Control Type group. Best practices dictate that the VV550/
551 is configured this way. If setting up a ventilation flow or a flow tracking system, refer to
“Special Applications,” p. 181 for detailed information.
b. In the Box Setup group, select the item that corresponds to the VAV box. If using a Trane F-
Style box, also select the size of the box from the drop-down list box.
c. Auto Changeover Setpoint — this setpoint determines the heat/cool action of the VAV box
based on a comparison between this setpoint and the temperature of the primary air in the
duct.
10. Click the Setup tab.
The ventilation setup fields define the Occupied and Standby Outside Air cfm setpoint
requirements for the VAV. This information is typically found on the job specification.
11. Click the Inputs tab.
Analog input 4 is configurable for a primary supply air sensor or discharge air sensor. The
best practice is to install and configure the sensor for discharge air.
12. Click the Outputs tab.
Use the Output Configuration Wizard to set up the heating options for the VV550/551.
©2009 Trane. All Rights Reserved.
BAS-APG007-EN, 12/15/2009 PROPRIETARY INFORMATION OF TRANE. 41
MAY ONLY BE USED IN THE CONDUCT OF TRANE BUSINESS.
Controller Setup
• The address for each device on a single BACnet link should be unique. However, even if
Best there are two BACnet links, define unique addresses for each device (for example, do not
Practice put a device 002 on BACnet link 1 and a device 002 on BACnet link 2).
• Keep a separate record that includes the name of the VAV box, its rotary switch setting (MAC
address or device ID), and the name of the controller.
5. Select Utilities > Controller > Controller Settings. The controller settings page appears
(refer to Figure 14).
a. Change the device name for the VAV box to match the naming conventions described for air
handlers (“Naming Devices,” p. 36).
b. Set the controller units (the units selected must match the Tracer SC system units).
c. Set the baud rate; the default is 76800. All devices on the link must have the same baud rate.
6. Click Save.
Figure 14. Controller Settings
7. Verify the setpoints. Select Utilities > Equipment > Setpoints to define the setpoints and
setpoint limits (refer to Figure 16).
8. Click Save.
Figure 15. Verifying setpoints
9. Configure the Setup Parameters. Select Utilities > Equipment > Parameters to define the
following parameters (refer to Figure 16, p. 46).
a. Click the Ventilation tab. Set the Occupied and Standby Ventilation Setpoints.
b. If performing ventilation control based on CO2, verify the space CO2 low and high limit
setpoints.
c. Click the Airflow Setup tab. Verify all of the airflow setpoints for the VAV box (as specified).
d. Verify that all other parameters were configured properly in Step Note:.
10. Click Save.
Figure 16. Setup Parameters
BAS Technician(s)
Install
BAS Technician(s)
Commis
Commission Building Operator
Order has been placed
BAS Technician
Operate
Maintain
Figure 17. Enabling a profile using the Rover service tool (DAC profile enabled is shown)
Enabling the appropriate profile causes the DAC or SCC tab to display in the Rover service tool
Configuration editor (Figure 18, p. 48). The tab contains the specific air handler configuration
parameters for the MP580/581.
1. Configure, the inputs, outputs, and variables needed on the MP580/581 controller. Refer to
Tracer MP580/581 Programmable Controller Programming guide, CNT-SVP01C-EN for detailed
instructions.
Note: If you are not using Pre-Packaged Solutions, use names that are meaningful, but do not
make specific reference to the air handler (i.e., use “Supply Air Temp” but not “AHU 1
Supply Air Temp”). This allows you to configure points on the first MP580/581, and save
the configuration as a template. This configuration file can be reused to configure
additional air handlers of the same type.
2. Save the configuration file.
Note: If working offline, save the configuration to your hard drive for downloading at a later
time.
3. Download the configuration file to the MP580/581 controller.
Created on SC
MP580/581 Variable Volume Constant Volume Programmable
Configuration Air Handler Air Handler Controller
SCC x
DAC x
Generic x
Important: If you change the MP580/581 point configuration, you must “replace” the device in
the Tracer SC before the new point configuration is recognized. To replace the
device:
1. Select Installation > Device from the left-hand navigation.
2. Select the device that you want to replace from the list.
3. Click actions... > replace device.
Tracer SC
Browser
Ethernet Link
SC SC SC
Equipment
VV550/551
VV550/551
VV550/551
MP580/581 VV550/551
Controller
Associated TGP
Program block
MP580/581
Tracer SC Controller
Table 6, p. 54 shows the relationship between the operating mode and the occupancy request and
heating cooling request for non-VAV air handlers and VAV air handlers.
The heating cooling request requires additional calculation in order to determine the behavior of
the equipment in certain operating modes.
Important: The heating cooling request calculations for all equipment (except VAV air handlers)
are made using values from the equipment:
• The Heating Cooling Mode Request is Morning Warm-up if the Space
Temperature Active is below the Space Temperature Setpoint BAS or if either
value is invalid.
• The Heating Cooling Mode Request is PreCool if the Space Temperature Active
is above or equal to the Space Temperature Setpoint BAS.
The heating cooling request calculations for all VAV air handlers are made using
values from the Tracer SC VAS:
• The Heating Cooling Mode Request is Morning Warm-up if the VAS Average
Space Temperature is below the VAV AHU Startup Setpoint or if either value is
invalid.
• The Heating Cooling Mode Request is PreCool if the VAS Average Space
Temperature is above or equal to the VAV AHU Startup Setpoint.
Table 6. Operating mode relationship to Occupancy Request and Heat Cool Mode Request for MP580/581
(a) Heat Cool Mode Request calculations are calculated using properties from the equipment:
Heating Cooling Mode Request is Morning Warm-up if the Space Temperature Active is below the Space Temperature Setpoint BAS or if either value is
invalid.
Heating Cooling Mode Request is PreCool if the Space Temperature Active is above or equal to the Space Temperature Setpoint BAS
(b) Heat Cool Mode Request Calculations are calculated by the VAS based on the following:
Heating Cooling Mode Request is Morning Warm-up if the VAS Average Space Temperature is below the VAV AHU Startup Setpoint or if either value is
invalid.
Heating Cooling Mode Request is PreCool if the VAS Average Space Temperature is above or equal to the VAV AHU Startup Setpoint
You can override any Tracer Variable on the MP580/581 controller from the Tracer SC MP580/581
Configuration page (refer to Figure 22, p. 55).
You can also create TGP2 programs on the Tracer SC that can read any value from the system,
which in turn controls a Tracer variable on the MP580/581 (refer to Figure 23, p. 56).
Figure 23. Example of how a point controls a Tracer variable on the MP580/581
Figure 24. TGP2 program to communicate the outdoor air flow setpoint to the MP580/581
If you cannot us a Pre-Packaged Solution, there are several TGP programs in the TGP\Library\AHU
- VAV Plus directory created specifically to interface with building automation systems using the
LonTalk communication protocol. The TGP programs ship with the Rover service tool software and
are saved into this directory when you install the Rover service tool. To download the latest
versions of these programs along with the service packs for the Rover service tool go to http://
tranenetlax1/GCC_Downloads/Home/Downloads/Rover.asp
These TGP programs are written specifically for VAV air handler operations (controlling the fan,
controlling the discharge air, etc.). Refer to the MP580/581 Programming Guide, CNT-SVP01C-EN
for detailed information on creating and modifying TGP.
Configure as many points as possible before modifying the TGP programs and installing the
Best MP580/581 in Tracer SC. This will allow you to work most efficiently.
Practice
The following sections give a brief description of the TGP and the logic the programs use to allow
the MP580/581 to control the air handler as a DAC object. To access these programs:
1. In the Rover service tool, click Program Editor.
2. When the TGP editor appears, select File > Open... from the menu. The Open window appears.
3. Navigate to the C:\TGP\Library\AHU - VAV Plus directory and highlight the appropriate file.
4. Click Open.
When the appropriate TGP program displays in the editor, you will see the unmapped inputs,
outputs, and variables in the editor (red text). Map these to the corresponding inputs on the
MP580/581 for each of the programs. (Refer to the MP580/581 Installation and Programming guide
for specific information on mapping inputs to a network variable.)
BAS Technician(s)
Install
BAS Technician(s)
Commis
Commissio n Building Operator
Order has been placed
Optim
Optimiz
Optimize Service Technician
Maintain
Figure 26. Physical layout and Areas in the 1st Street Office Building
Common Spaces
By design VAV air handlers will still produce approximately 20% airflow to the system at their
minimum flow settings. To account for this, the VAS uses common space VAVs to prevent over-
pressurization of the ductwork when the central fan is delivering minimum airflow to the system.
By providing a place to put excess air, the common space VAVs allow the air handler to run when
it is asked to provide more airflow than the VAV boxes in an Area can deliver.
Example: At 4:15 PM, the Eastside Law Offices are Unoccupied (0 cfm) and the AAA Moving
Area VAV boxes are maintaining an airflow of 1975 cfm to the space. RTU-01 is operating at 22
Hz and delivering 2500 cfm (which is the minimum cfm the central fan can provide). Without
the common space VAV boxes, the excess air (525 cfm) would over-pressurize and potentially
damage the ductwork.
Common spaces do not need to be scheduled because the VAS controls the common space VAV
boxes to match the highest ranking operating mode of the non-common space VAV boxes (refer
to “How Area and VAS Interact,” p. 66). Where each tenant is defined by an Area and common
spaces are shared, the common spaces are managed by the VAS and do not have to be members
of either Area.
Important: When no clearly defined “common space” exists (i.e., a hallway, stairwell, etc.), or
there is a need for timed override of the space served by the common space VAV box,
then the common space VAV box should be a member of an Area. This is a new
feature associated with Tracer SC. Previously, Tracer Summit could not have
common space VAV boxes as members of an Area.
In Figure 26, p. 61, the two conference rooms, the bathrooms, and the hallways have been
designated as common spaces. Lobbies, hallways, rest rooms, and utility rooms are good
candidates for common space VAVs, because the excess airflow and any associated noise are less
noticeable by the tenants.
The number of VAV boxes in the smallest Area plus the number of common space VAV boxes
Best should add up to at least 20% of the total number of VAV boxes in the VAS.
Practice
Note: When selecting the VAV boxes make sure they can accommodate 20% of the total design
airflow.
Area: Area:
AAA Moving Eastside Law Offices
VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV
Note: In this example, common space VAV boxes cannot initiate timed overrides of the Areas and
there is no logical Area for them to be a member of, so they are not members of any Area.
Figure 28. 1st Street Office Building physical air system layout
The members of the VAS are the VAV air handler, all the VAV boxes served by the air handler
including the common space VAV boxes, and the exhaust fan (refer to Figure 29, p. 65).
AAA Moving VAV boxes 1-10 Eastside Law Offices VAV boxes 11-20
VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV
VAV AHU =
Tracer SC Application =
Common Space
VAV boxes 21-25
Note: There should only be one air handler as a member of the VAS.
Area: Area:
AAA Moving Eastside Law Offices
VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV
Members of both
Area and VAS
VAV AHU =
Common Space
VAVs
The VAS monitors the operating mode of its member VAV boxes, which are also members of an
Area, but it does not control them. The VAS only controls its member VAV boxes that are designated
as common space VAV boxes, VAV boxes or exhaust fans designated as ventilation members, and
its member VAV AHU.
Important: In a VAS, the operating mode of common space VAV boxes are only controlled by
the VAS. The operating mode of all other VAV boxes are controlled by the Areas they
serve. If a VAV box has been designated as a common space VAV box, its operating
mode cannot be controlled by an Area.
Area and VAS coordinate and control the operating modes of their members in the sequence
described below:
1. Area(s) controls the operating mode of its VAV box members.
2. The VAS detects the change in operating mode of the VAV boxes that are members of the VAS.
3. The VAS evaluates the operating mode of each non-common space VAV box.
4. The AHU Mode Request of the VAS is determined based on the operating mode of the VAV box
with the highest rank (lowest number)(refer to Table 8).
5. The VAS controls the AHU and common space VAV boxes to the same operating mode as
follows:
Start up (fan on)
• The VAS System Mode transitions from Off to StartupDelay.
• The operating mode of the common space VAV boxes are immediately controlled to match
the VAS “Common Space VAV Mode Request” property.
• The current value of the Startup Delay Time Remaining indicates the time left before the
System Mode transitions to On.
• The AHU operating mode does not change until after the Startup Time Delay expires. It is
then controlled to match the VAS “AHU Mode Request” property.
Shut down (fan off)
• The VAS System Mode transitions from On to ShutdownDelay.
• The operating mode of the air handler is immediately controlled to match the VAS “AHU
Mode Request” property.
• The current value of the Shutdown Delay Time Remaining indicates the time left before the
System Mode transitions to Off.
• The common space VAV boxes’ operating mode do not change until after the shutdown time
delay expires. They are then controlled to match the VAS “Common Space VAV Mode
Request” property.
Important: When multiple Areas exist, it is possible to have VAV boxes in the same VAS with
different operating modes. When this occurs, the desired AHU mode of the VAS
is determined as shown in Table 8 (Occupied having the highest rank and
Unoccupied having the lowest rank)
Example: Figure 31, p. 68 shows that AAA Moving is in the Unoccupied mode and Eastside
Law Offices is in the Unoccupied Heat/Cool mode. The VAV members of each Area are
controlled to the corresponding operating mode.
The VAS evaluates which non-common space VAV member operating mode has the highest
rank and uses that to determine its operating mode. In turn, the VAS controls the operating
mode of the common space VAV boxes to match the VAS “VAV Mode Request” property. The
AHU operating mode does not change until after the Startup Time Delay expires. It is then
controlled to match the VAS “AHU Mode Request” property.
Off
EF
RTU 01 VAS
Note: The operating mode of the common space VAV boxes and the AHU mimic the operating
mode of the non-common space VAV boxes with the highest ranking operating mode.
Time-Based Only
If the HVAC equipment is controlled using a schedule without an Area defined, the occupancy
of the equipment could only be controlled to Occupied between the hours of 6:30 AM and 5:00
PM and Unoccupied at all other times.
12 12
5:00 PM
6:30 AM
AM PM
Temperature-Based
By using both an HVAC Schedule (time-based) and an Area (temperature), the operating mode of
the equipment can be controlled to Optimal Start, Optimal Stop, Night Purge, and Unoccupied
Heating/Cooling in addition to Occupied and Unoccupied.
• Optimal Start allows the equipment to start in advance of normal operating hours to ensure the
space temperature is at the occupied temperature setpoint when employees arrive.
• Optimal Stop relaxes the occupied temperature setpoints up to two hours prior to the
employees leaving as an energy saving measure.
• Unoccupied Heating/Cooling allows the equipment to start during unoccupied periods when
the space temperature exceeds the unoccupied heating and cooling setpoints.
• During Unoccupied periods, Night Purge allows a warm interior space to be purged with cool,
dry outdoor air during Unoccupied hours to cool the space prior to building occupancy.
12 12
1:00 AM
Occupied
Night
Occupied Purge
9 3:00 AM 9 3
Unoccupied
Optimal
Stop
Optimal
Optimal
Start
Start 4:30 AM
5:00 PM
6:30 AM
AM PM
= Unoccupied heating/cooling is possible
Humidity-Based
Humidity Pulldown allows the equipment to start in advance of normal operating hours to ensure
the space humidity is at the occupied humidity setpoint when employees arrive.
Unoccupied Dehumidification allows the dehumidification members to start during unoccupied
periods when the space humidity rises above the unoccupied dehumidification setpoint.
Unoccupied Humidification allows the humidification members to start during unoccupied periods
when the space humidity falls below the unoccupied humidification setpoint.
12 12
Occupied
Unoccupied
Occupied
9 3 9 3
Unoccupied
Humidity
Optimal
Pulldown
Start 4:30 AM
5:00 PM
6:30 AM
AM PM
= Unoccupied dehumidification/humidification is possible
VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV VAV
VAV AHU =
Flow of control
que
(Sequence) VAV boxes &
EF Exhaust Fan =
RTU 01 VAS
Tracer SC Application =
Common Space
VAVs
Important: Schedules and Area work together to determine the operating mode of the Area VAV
box members. Those same VAV boxes are also members of the VAS. VAS gets its
operating mode from them and controls its own VAV box members, which, in turn,
it passes to the VAV AHU member. Therefore, the Schedule and Area ultimately
determine the VAV AHU operating mode.
BAS Technician(s)
Install
BAS Technician(s)
Commis
Commission Building Operator
Order has been placed
BAS Technician
Operate
Maintain
Before installing devices in Tracer SC, name equipment appropriately while commissioning the
Best equipment in the facility. For equipment on a LonTalk communication link, this is the location
Practice label, and for equipment installed on a BACnet communication link this is the object name.
Add a “0” to the sequential number assigned by Tracer SC so the VAV boxes sort in the proper
order (e.g., VAV 01-01, VAV 01-02, VAV 01-03, etc.)
Adding the type of space the VAV box serves to the object name, may be useful when selecting
common space VAV boxes in the VAS or assigning VAV members to Areas.
Examples: VAV 01-01 (Room 212), VAV 01-02 (Cafeteria), etc.
5. When the discovery status changes from “Discovery in Progress” to “Discovery Completed”,
click install devices. The Install Devices page appears.
6. Select the check box for each piece of equipment to be installed and click install selected
devices (Figure 38, p. 74). The Device Installation Complete page appears.
7. Confirm that the selected devices are installed.
Figure 38. Install Selected Devices
Set Up Areas
Areas play a vital role in VAV air systems, so it is very important they are set up correctly. Standard
operating modes that rely on Area include Optimal Start/Stop, Unoccupied Heating/Cooling, and
Night Purge. Refer to “Standard Operating Modes,” p. 118 for detailed information.
The basic steps for setting up an Area include:
1. Determine how many Areas are needed. (It is acceptable to have multiple Areas within a single
VAS. Refer to “Defining Areas and Selecting Area Members,” p. 62.)
2. Determine which VAV boxes go with which Area (refer to “Defining Areas and Selecting Area
Members,” p. 62).
3. Click create area on the Areas list page (refer to Figure 39).
Note: The drop-down list box contains seven possible choices for the economizing decision.
When an option is selected, a description of that choice appears in the Description box
to the right.
4. If Night Purge will be used, select the Supports Night Purge check box.
5. If any of the three humidity functions will be used, select the Supports Humidity Control and
the appropriate humidity function.
6. Click next.
Important: If you do not select a check box to support the Economizing Decision, Night Purge,
or Humidity Control, the setup for these functions will not be included in the wizard.
Additionally, those functions will be disabled within the Area you are creating. They
can be enabled at a later time if desired.
Note: The reverse is also true. If a function is enabled on this page of the wizard,
you cannot disable it on the Functions page of the wizard. You must either
come back to this page of the wizard and change the check box for the
function, or wait until the wizard is complete and then turn off the function
on the Area Configuration page.
Select Members
This page of the wizard allows you to select the equipment to be members of the Area you defined
on page one.
1. From the selection tree, click the appropriate link to view the available items of that type. When
the link is selected, all the available items of that type are presented in the available items
column. Use the check boxes to select the items you want to include in the Area as members
(refer to Figure 41, p. 77).
Important: VAV boxes, fan coil units, and water source heat pumps, appear under the spaces
link in the selection tree. Constant volume air handlers, variable volume air
handlers, and programmable controllers, appear under the equipment link in the
selection tree.
2. Click Add. The items move to the selected items column on the right.
3. Click next.
Leave most members as Heating/Cooling type members. Heating only and Cooling only
Best members are typically used for testing.
Practice
Configure Members
When this page of the wizard appears (refer to Figure 43), some of the check boxes will already be
selected based on the choices you made on the first page of the wizard. For instance, if you selected
the Supports Night Purge check box on the first page, all of the members will be selected here
as night purge members. This page is dynamic and changes based on your selections earlier in the
wizard.
Note: If you do not select a check box on page one (i.e., Supports Humidity Control), none of the
associated check boxes on this page of the wizard will appear (i.e., humidify or dehumidify).
The calculation check box indicates that the member (typically a VAV box) is included in the
calculations conducted by Area for Average Space Temperature, Average Min Space Temperature,
and Average Max Space Temperature. To exclude a member from Area calculations, deselect the
check box in this column (e.g., if a VAV box is located in a closet or utility room, it is undersized, it
may have a faulty space temperature sensor, etc., you may not want its input included in
temperature calculations for the rest of the space).
Configuration
The important task on this page of the wizard (refer to Figure 44, p. 80) is to reference the
temperature and humidity sensors for the Area. If the Area does not support humidity control
(determined by the check box on the first page of the wizard), then only the space temperature
sensor and the outdoor air temperature sensor need to be referenced.
Important: If the proper references to sensors are not set here, temperature and humidity
control strategies (i.e., Optimal Start, Optimal Stop, Night Heat/Cool, Humidity Pull-
down, etc.) will not work properly. Area will use constant values instead of the
dynamic data obtained from the sensors, which accurately reflects current
conditions.
Setup:
3. Click on the blue referencer icon ( ) behind the sensor value you want to reference.
4. The Reference window appears. Choose either the User pre-defined data source or Select
custom data source options from the Change Data Source frame.
Note: The concept of a pre-defined referencer is new in Tracer SC. The pre-defined data source
is typically the sensor or value that is used most often for the referencer. The only sensor
that does not have pre-defined referencers defined is the space humidity sensor. The
pre-defined defaults for each of the other sensors are listed below:
– Space temperature sensor = Area average space temperature (Area minimum space
temperature and maximum space temperature are also available for selection)
– Outdoor air humidity sensor = Facility outdoor air humidity
– Outdoor air temperature sensor = Facility outdoor air temperature
5. Verify that the selections in the Event Notifications frame for Timed Override Class and
Diagnostics Class meet the event routing needs for the facility.
6. Click Next.
Functions
The content of the Functions page depends on the selections you made on the Define Area page
of the wizard. If you determined that the Area would support Economizing Decision, Night Purge,
and Humidity Control, this page contains setup information that is critical to the proper operation
of those functions in the Area application (Figure 45). If the Area does not support any of those
functions, the Functions page will not appear in the wizard.
Functions - Economizing
This is a new function for the Area application. Area now has the ability to determine when to allow
Economizing. Area then controls the Economizer Enable point to Enabled or Disabled (it does not
actually control equipment). The Night Purge function can use this economizing decision for input
on its decision to perform Night Purge.
The economizing decision is based on the type of Economizing selected on the first page of the
wizard (refer to the bulleted list below) and the setpoints entered in the Start Condition and Stop
Condition fields on this page of the wizard (referencers can be used for these values, but these are
typically constants).
A box to the right of the condition fields explains how the economizing decision is made:
• Fixed Dry Bulb — The ”Economizer Enable” point will be Enabled when the outdoor air
temperature falls below the start condition. This point will be Disabled when the outdoor air
temperature rises above the stop condition.
• Differential Dry Bulb — The ”Economizer Enable” point will be Enabled whenever the
differential between the outdoor air temperature and space temperature is below the start
condition. This point will be Disabled when the differential between the outdoor air
temperature and space temperature is below the stop condition.
• Fixed Enthalpy — The ”Economizer Enable” point will be Enabled whenever the outdoor air
enthalpy is below the start condition. This point will be Disabled when the outdoor air enthalpy
rises above the stop condition.
• Differential Enthalpy — The ”Economizer Enable” point will be Enabled whenever the
differential between the outdoor air enthalpy and space enthalpy is below the start condition.
This point will be Disabled when the differential between the outdoor air temperature and
space temperature is below the stop condition.
Important: If Area is making an economizing decision based on enthalpy, the corresponding
temperature and humidity sensors must be referenced. Area uses the space
temperature and space humidity to calculate space enthalpy; and outdoor air
temperature and outdoor air humidity to calculate the outdoor air enthalpy and
dew point.
• OA Dew Point and OA Temperature — The “Economizer Enable” point will be Enabled when
the outdoor air temperature is below the start condition and the outdoor air dew point is below
the start condition 2. This point will be Disabled when either the outdoor air temperature falls
below the stop condition or the outdoor air dew point rises above the stop condition 2.
• Referenced — The ”Economizer Enable” point will follow the referenced point status.
Example: TAn Area is being served by four rooftop units. The Area is configured to support the
Economizing Decision using Fixed Enthalpy calculations. Using a referencer, each of the rooftop
units can be configured to base its decision to economize on the condition of the Economizer
Enable point in Area.
Setup
1. Support for economizing and the type of economizing decision have already been selected on
the Define Area page of the wizard.
2. Type in a value for the Start Condition. This value will vary depending on how Area is making
its economizing decision.
3. Type in a value for the Stop Condition. This value will vary depending on how Area is making
its economizing decision.
4. Click Next.
Functions - Night Purge
The Night Purge function and its setup are described in detail in the Standard Operating Modes
section (refer to “Night Purge (Night Economizing),” p. 129). Make the appropriate changes and
click Next.
Confirmation
The confirmation page is a summary of all the settings you defined in the wizard and allows you
to verify that they are as you expected them to be (refer to Figure 46).
5. To change any of the parameters, click the previous until you come to the page of the wizard
that allows you to change the parameter.
6. To confirm the settings for the Area and close the wizard, click finish.
Figure 46. Confirmation page
Area Optimization
After completing the wizard, optimize the Area to suit the needs of the facility. This includes
defining the setpoints and offsets, Unoccupied operations, Optimal Start/Stop operation, Binary
member operation, Setpoint Differentials, and Timed Override parameters.
Viewing an Area
Once you have created an Area with the wizard, view it to confirm your settings and make
additional changes. To view all Areas created on the Tracer SC:
1. Select systems > areas from the left-hand navigation. The Area list page appears.
2. Click on the Area you just created with the wizard, or click the check box and select view from
the actions list. The Status page for the Area you selected appears.
3. There are four pages associated with Area; they are: Status, Configuration, Functions, and
Members. When first entering Area, you see the Status page.
• The Status page displays general information about the Area, such as the current
conditions in the Area (i.e., temperature, humidity, setpoints, etc.), its occupancy, what its
members are doing, what functions are enabled, data logs, alarms and diagnostics, and who
is controlling the Area
• The Configuration page displays information about the the Area setup (name, sensor
values and references, heat/cool request, etc.), the Area operation (Unoccupied operation,
Optimal Start/Stop operation, Timed Override operation, etc.), and Event Notifications
• The Functions page allows you to manage the Economizing, Night Purge, and Humidity
Control functions
• The Member page allows you to add and delete equipment and points as members of the
Area and modify their attributes
Application Defaults
Application defaults are a set of parameters that can be defined once and then used each time a
new Area or VAS are created. You can change the defaults on your system permanently if you prefer
different values than those originally created for the program. You can use the same capability to
push changes to the parameters for existing Areas and VASs in a facility.
Viewing and Changing Application Defaults
To view and change the application defaults:
1. Select installation from the left-hand navigation. The Installation page appears.
2. Within the 2. Configure Facility Settings section, click on Application Defaults. The
Application Defaults page appears.
3. The page contains three sections: Alarming, Facility Defaults for Areas (Figure 47), and Facility
Defaults for Variable Air Systems. To change any of these parameters, click edit in the
appropriate section. The parameters in the section become editable.
Area Setpoints
Setpoints are not set up in the wizard so they have to be managed after the Area wizard is complete.
Area control uses six space temperature setpoints:
• Occupied Cooling Calculated using a single space
• Occupied Heating temperature setpoint and the
• Standby Cooling (used for Optimal Stop) occupied and standby offsets
• Standby Heating (used for Optimal Stop)
• Unoccupied Cooling
• Unoccupied Heating
Tracer SC calculates the Occupied and Standby Heating/Cooling setpoints using a single space
temperature setpoint with offsets. The operator has five values they need to define (refer to
Figure 49, p. 87) to make this strategy work properly, they are: Space Temperature Setpoint,
Standby Offset, Occupied Offset, Unoccupied Cooling, and Unoccupied Heating. The unoccupied
setpoints are not calculated, they are the absolute minimum and maximum temperatures that Area
must try to achieve during unoccupied times.
Example: Area calculates the active setpoint based on the space temperature, the occupancy
of the Area, and the current heating/cooling mode of the Area. For this example the Area is
Occupied and in the Heating mode, the Space Temperature Setpoint is 72°F (22.2°C), and the
Occupied Offset is 2°F (1.1°C). So the Occupied Heating setpoint is 70°F (22.2°C).
Area calculates the Occupied Heating setpoint by subtracting the Occupied Offset from the
Space Temperature Setpoint (72°F – 2°F = 70°F)(22.2°C – 1.1°C = 21.1°C), and Occupied Cooling
setpoint by adding the Occupied Offset to the Space Temperature Setpoint (72°F + 2°F =
74°F)(22.2°C + 1.1°C = 23.3°C).
Note: The Standby Cooling and Heating setpoints work the same as described above except
that the Standby Offset is used instead.
The Unoccupied Cooling and Heating setpoints are not calculated by Area. The values typed into
the fields (refer to Figure 49, p. 87) or referenced from another source are used as the setpoints.
All the equipment in a Tracer SC system also uses this same setpoint strategy, which allows Tracer
SC to send a single space temperature setpoint from Area to the equipment and the equipment
then calculates the heating and cooling setpoints based on the offsets defined for them.
Setup
1. Select systems > areas from the left-hand navigation.
2. Click on the Area that you just created in the wizard, or the Area you want to modify.
Note: You can also click the check box in front of the Area and select view from the actions
button list.
3. Review the space temperature setpoint, offsets, and unoccupied heating and cooling setpoints
of the Area. The default values provided are adequate for most applications.
4. To change any of the setpoints or offsets, click edit.
5. The setpoint and offset values become editable (Figure 49, p. 87). After making changes, click
save.
Controlling Setpoints
Figure 50 shows the three ways a setpoint can be controlled:
1. By directly entering a value in the field.
2. By overriding the setpoint directly with a static value.
3. By selecting a referencer that will control the point at the priority level of the Area.
Note: When you change the setpoint by directly entering a value in the field, you are actually
changing the default value for that setpoint.
Notice that not all the setpoints are editable directly (in this case only the Unoccupied
Heating Setpoint and the Unoccupied Cooling Setpoint). The other setpoints have a
referencer ( ) or an override ( ) available. The ability to override a point is prevalent
throughout the Tracer SC system. Referencers, however, are unique to the Area
application.
Clicking on the override icon ( ) allows you to override the value of a point or an existing
point override.This is a simple override. Refer to the Tracer SC online help for an in-depth
discussion on overrides. You must have edit access to Area to perform advanced
overrides on points created by the Area application. Advanced overrides allow you to
override point values at various priority levels. To access the advanced override screen:
4. Click the override icon ( ) in the actions column to the right of the point you want to override.
The Override page appears.
5. If you have the proper access, the more options button is available at the bottom of the section.
Click more options. A more extensive Override Value section appears along with a Priority
Array section (Figure 51).
The Priority Array section shows who is currently controlling the point and a short list of what
has controlled or requested control of the point in the past. The Override Value section allows
you override the point at different priority levels. You will only be able to control a point at
priority levels defined by your user profile.
6. Set the override as required and click apply.
Figure 51 also shows the priority array and user (user, referencer, or function) trying to control the
Space Temperature Setpoint. The figure shows that the user named “Trane” tried to perform a
simple override to control the point at priority level 13. Because Area is controlling the point at a
higher priority level, user Trane had to perform an advanced override at a higher priority level than
Area to override the point to the desired temperature.
Synchronize Setpoints
The Tracer SC allows you to quickly send the five Area default setpoints to all the members of the
Area with one action. The setpoints involved are the Space Temperature Setpoint, Standby Offset,
Occupied Offset, Unoccupied Cooling, and Unoccupied Heating setpoints. To synchronize the
setpoints:
1. Click actions... from the Status section of the Area Status page.
2. Select synchronize all from the list.
This is not a selective process at this time. Synchronizing the setpoints pushes ALL the default
setpoints (5 total) to EVERY member of the Area. If any of these setpoints has an override applied,
at the member level, the override will remain in place. However, the default of the unit will be
changed to match the synchronized value. When the override ends, the member will use the default
value synchronized during this process.
Area Configuration—Setup
Heat/Cool Request
The Heat/Cool Request for Area is typically configured as Auto. This means that Area uses the
Space Temperature Setpoint and the Occupied Cooling and Occupied Heating setpoints plus and
minus 1°F (0.56°C) to determine whether to request Cooling or Heating. Other options are to use
a referencer, or one of the other selections available in the drop-down list box.
Leave the Heat Cool Request set to Auto in the Area Configuration Setup section.
Best
Practice
Example: Area monitors the space temperature. When it rises to 1°F (0.56°C) above the Occupied
Cooling setpoint, Area requests cooling. When the space temperature falls to 1°F (0.56°C) below
the Occupied Heating setpoint, Area requests heating.
If you select the arrow on the list box, there are many options available for defining the Heat Cool
Request (Optimal Cooling, Economizing, etc.). Regardless of which is selected, Area evaluates the
option and decides which of these to implement: heating, cooling, or auto. For instance, if Optimal
Cooling is selected as the Heat Cool Request option, Area sends that request to its members during
Optimal Start; however, it is still a cooling decision. Therefore, the Area active heat/cool status is
Cooling (refer to Table 10, p. 90).
Area Configuration—Operations
Figure 53 shows the operations that can be Enabled and Disabled in the Operations section.
Unoccupied Operations
Enable this operation if you want Area to heat or cool during unoccupied periods. If Enabled, you
can also set the differential value that defines how far below the Unoccupied Cooling setpoint the
temperature must fall before Area stops cooling, and how far above the Unoccupied Heating
setpoint the temperature must rise before Area stops heating.
Optimal Start/Stop
This allows you to Enable or Disable Outdoor Air Temperature Compensation in the Area thermal
ramp rate calculation. If Enabled, Area correlates the Optimal Start/Stop rates with the outdoor air
temperature and adjusts the start/stop times if a drastic temperature change occurs from one day
to the next.
Timed Override
If you want people in the building to be able to request a timed override, this operation must be
Enabled. Timed Override is typically initiated from a zone temperature sensor in the space, which
has an override button. This zone temperature sensor must be attached to a VAV box that is a
member of the Area and is also defined as an override member on the Member Configuration page.
You can set the duration for any overrides in this section as well. You can also use an Optional Input
to initiate timed override when there is no zone temperature sensor available. The Optional Input
is a multi-state value where 1 = TOV Auto, 2 = TOV On, 3 = TOV Cancel.
Binary Members
Binary members are non-equipment members of an Area. Therefore, Area can only control binary
outputs or binary value points On or Off.
Binary Control-Continuous Operation
If the binary control is set for Continuous, Area controls the binary output to On any time the Area
Heating/Cooling mode matches the binary member type (heating, cooling, or heating/cooling) and
the Area is in the Occupied operating mode.
Binary Control-Cycling Operation
For Cooling only binary members, Area controls the binary member to On any time the space
temperature rises above the Occupied Cooling Setpoint, the Heating/Cooling mode is Cooling, and
the Area is in the Occupied operating mode. Area controls the binary member to Off any time the
space temperature falls below the Occupied Cooling Setpoint minus the Binary Control Differential,
or the Area Heating/Cooling mode transitions to Heating, or the Area operating mode transitions
to Unoccupied (refer to Figure 54).
Example: An exhaust fan in a warehouse is used to vent hot air during the summer.
For Heating only binary members, Area controls the binary member to On any time the Area space
temperature falls below the Occupied Heating Setpoint, the Heating/Cooling mode is Heating, and
the Area is in the Occupied operating mode. Area controls the binary member to Off any time the
space temperature rises above the Occupied Heating Setpoint plus the Binary Control Differential,
or the Area Heating/Cooling mode transitions to Cooling, or the Area operating mode transitions
to Unoccupied (refer to Figure 55, p. 92).
Example: An unit heater in a warehouse is used to heat a space during the winter.
Heating/Cooling binary members operate as a composite of both the heating only and cooling only
operation (refer to Figure 56, p. 93)
Example: A third-party air handler is part of the system where Tracer SC only controls the Start/
Stop status.
Figure 54. Cycling operation (with differential) for a binary cooling-only member
Figure 55. Cycling operation (with differential) for a binary heating-only member
Figure 56. Cycling operation (with differential) for a binary heating/cooling member
Create a VAS
Before creating a VAS, determine whether the VAS you create needs to support any optimization
strategies (i.e., duct static pressure optimization or ventilation optimization).
1. To create a new VAS, select Systems > VAS from the left-hand navigation, then click on +
create variable air system on the list page (Figure 57).
2. The Create Variable Air System wizard launches.
3. There are also three check boxes and three editable fields in the Configuration Settings group.
Trane recommends leaving these in their default settings. These are available after the VAS is
created if you need to make changes.
Leave the check boxes selected for Allow VAVs to use auxiliary heat at night, Send source
Best temperature to VAV boxes, and Send drive max to VAV boxes.
Practice
4. If you are implementing Duct Static Pressure Optimization, select the Duct Static Pressure
Optimization check box in the Optimization Support section.
5. If you are implementing Ventilation Optimization, select the Ventilation Optimization check
box in the Optimization Support section.
6. Click Next.
Important: Ventilation Optimization requires that the air handler is equipped with Traq
dampers or outdoor air flow sensors.
Important: When commissioning VAV boxes, define the outdoor air requirements for each
VAV box using the Rover service tool or Tracer TU. You can see the values for
outdoor air requirements from Tracer SC, but they are not editable, so this must
be configured at the VAV box. The calculated values for each VAV box are
available on the schedule from the Design Engineer.
Uncheck the Allow VAVs to use auxiliary heat at night check box when:
Best • there is a heat source in the AHU and no local heat source in the VAV boxes, or
Practice • the local heat source isn't being used
Use the default setting (2 minutes) unless the drive times of the VAV boxes exceeds 90 seconds.
Best If the drive times of the VAV boxes are more than 90 seconds, increase the AHU Startup Delay
Practice time.
Set Up Functions
This page of the wizard (Figure 63, p. 102) only displays if one or both of the Supports Duct Static
Pressure Optimization or Supports Ventilation Optimization check boxes are selected on the
first page of the wizard. The initial values in each section are pulled from the application defaults
(refer to “VAS Application Defaults,” p. 104). When these applications are enabled, the Tracer SC
VAS calculates an optimized static pressure setpoint and an optimized minimum outdoor airflow
setpoint.
Important: Further setup is required. Selecting the check boxes, enabling both optimization
strategies, optimizes the setpoints but does not communicate them to the air
handler. Refer to “Optimization,” p. 157 for more detailed setup information.
Duct Static Pressure Optimization
Typical values for the duct static pressure setpoints are:
• Minimum Static Setpoint: 0.75 in(H20) (186.63 Pascal)
• Startup Static Setpoint: 1.00 in(H20) (248.84 Pascal)
• Maximum Static Setpoint: 1.50 in(H20) (373.26 Pascal)
Tracer SC offers a new feature for duct static pressure optimization. In previous products, the reset
up and reset down functions had the same increment value and time interval for both directions.
Now, reset up and reset down can be set independently from each other with different time
intervals and increment values.
Ventilation Optimization
The ventilation optimization section requires only one change to allow the function to operate
properly. The Startup Airflow Setpoint is zero, which is also the default, but the value must be
changed to the design airflow value for the air handler. The air handler’s design airflow is available
on the schedule/prints from the Design Engineer.
Important: When commissioning VAV boxes, define the outdoor air requirements for each VAV
box using the Rover service tool or Tracer TU. You can see the values for outdoor air
requirements from Tracer SC, but they are not editable, so this must be configured
at the VAV box. The calculated values for each VAV box are available on the schedule
from the Design Engineer.
Confirm Selections
The Confirm Selections page (refer to Figure 64, p. 103) allows you to see the settings you made
and to go back and make changes if necessary. The group just above the cancel, previous, and
finish buttons, shows which Tracer SC is the destination for the VAS (where it will be saved) when
you click finish.
Status Page
The VAS Status page is the first page to appear and provides detailed information for the selected
VAS. Each section on this page can be collapsed or expanded to view the contents by clicking the
arrow in the left most corner.
Access
From the Variable Air Systems page click on the name of the VAS you created in the wizard, or
select a VAS from the list and then select view from the actions button.
Content
The Status page appears by default; however, you can access the following pages for the VAS by
clicking the appropriate button at the top of the Status page.
• configure — Click to open the Configuration page for this VAS
• functions — Click to open the Functions page for this VAS
• members — Click to open the Members page for this VAS
Status Section. This section shows the conditions, current value, and status of the VAS. All
values within the table can be selected to create a data log.
• actions — Click this button to create data logs for the selected values
• more values — Click to open a list containing more VAS properties and current values
Members Section
This section contains status details for air handlers, VAV Boxes, and ventilation members, each
divided into separate tables. Each table shows the name of the VAS member and related status
details.
Graph Section
This section displays data logs that were automatically generated when the VAS was initially
created.
Configuration Page
The VAS Configuration page shows the configuration settings for the selected VAS. This is an
editable page in which you can make changes to most of the current configurations. The page is
divided into two sections — Setup and Operations.
Access
Click configure from the Variable Air System Status page, the Variable Air System
Functions page, or the Variable Air System Members page.
Content
The following pages for the VAS are available from the Configuration page by clicking the
appropriate button at the top of the page.
• status — Click to open the Status page for this VAS
• functions — Click to open the Functions page for this VAS
• members — Click to open the Members page for this VAS
Setup Section
This section shows basic settings for the VAS. To make changes, enter or select a value in the
corresponding property fields.
Name — Shows the display name of the VAS.
Description — Shows a brief description of the VAS (optional).
Air Handler Startup Delay — This shows the amount of time in which the VAS will wait before
starting the air handler unit.
VAV Box Shutdown Delay — This shows the time in which the VAS waits before shutting down
common space VAV boxes after the VAS enters the unoccupied mode.
VAV AHU Startup Temperature — When the VAS operating mode transitions to Optimal Start,
Unoccupied Heating/cooling, Unoccupied Humidify, Unoccupied Dehumidify, or Humidity
Pulldown, it compares the VAS average space temperature to the AHU Startup temperature. If the
average space temperature is warmer than the startup temperature, the VAS sends PreCool to the
VAV AHU heat/cool request. If the average space temperature is below or equal to the startup
temperature, the VAS sends Morning Warm-up to the VAV AHU heat/cool request.
Allow VAVs to use auxiliary heat at night — When unoccupied, which is typically at night, VAV
boxes use local heat to heat the space. Use the check box to enable or disable this setting.
Send source temperature to VAV boxes — Select this option to send the AHU discharge air
temperature to all VAV boxes.
Send drive max to VAV boxes — Select this option to drive all VAV boxes to maximum flow when
the AHU enters a constant volume mode.
Operations Section
This section shows the calibration and autocommissioning status for the VAS.
Calibration
This box shows the current calibration status. You can enable or disable calibration and change the
trigger value in this box. Refer to “VAV Calibration,” p. 116 for more information.
Autocommissioning
This box shows the current autocommissioning status. This is a defined operating sequence that
validates the proper operation of all inputs and outputs of VAV members. You can enable or disable
autocommissioning by clicking start/stop.
Important: cancel — Click to return to the previous page. Changes made on this page will not
be saved.
save — Click to save your changes.
Functions Page
This page shows the current functions and associated values for this VAS. To make changes, enter
new values and then click save.
Access
Click functions from the VAS Status page, the VAS Configuration page, or the VAS Members
page.
Content
The following pages for the VAS are available from the Functions page by clicking the appropriate
button at the top of the page.
• status — Click to open the Status page for this VAS.
• configure — Click to open the Configure page for this VAS.
• members — Click to open the Members page for this VAS.
Members Page
This page shows current members for the selected VAS. In addition, you can select to add more
members.
Access
Click Members from the VAS Status page, the VAS Configuration page, or the VAS Functions
page.
Content
The following pages for the VAS are available from the Functions page by clicking the appropriate
button at the top of the page.
• status — Click to open the Status page for this VAS
• configure — Click to open the Configure page for this VAS
• functions— Click to open the Functions page for this VAS
Ventilation Section
This section shows ventilation members for this VAS and the current occupancy for each.
• actions — Click or pause over this button to take action on a selected member
• + Air Handler — Click to open the Add Air Handler Member page
Do not include equipment in HVAC schedules if you plan to use Optimal Start/Stop, because
Best Optimal Start/Stop are functions of Area and typically only Areas are members of HVAC
Practice schedules.
An advantage to using HVAC schedules for Areas is that HVAC schedules use Trane’s
implementation of occupancy, which is Occupied, Unoccupied, Standby, and Bypass. Whereas,
multi-state schedules use actual values such as “1”, “2”, “3”, ...up to “20” instead of state text to
designate the state of the device (per the BACnet standard).
In this Tracer SC Air Systems Applications Guide, we will only be using HVAC schedules. For more
information on analog output, binary output, and multi-state schedules, refer to the Tracer SC
online help.
Analog Output Schedules
Analog output schedules are comparable to the Set Analog function in Tracer Summit. Keep in
mind that in Tracer Summit you can mix schedule types, where Tracer SC has BACnet compliant
schedules, which must be kept separate by data type. When you want to schedule an analog output
or an analog value to change, you can use an analog output schedule. Examples of when you might
use an analog output schedule:
• In a ventilation optimization scenario, you can schedule the outdoor air requirement airflow for
a space based on the expected occupancy. For instance if you know a classroom will be filled
with 20 people between 1 PM and 3 PM, you can schedule the outdoor air airflow rate to change
from 200 cfm to 400 cfm for that 2 hour duration. At 3 PM, after everyone has left the classroom,
you can schedule the rate to return to 200 cfm.
• It is also useful for scheduling changes to setpoint values. For instance, if you want the chilled
water temperature setpoint for your chiller plant at 40°F at 4 AM, and at 45°F at 10 AM, you could
use an analog output schedule to accomplish to make those changes.
Binary Output Schedules
Binary output schedules allow you to schedule On/Off events for binary outputs and binary values.
An example of when you might use a binary output schedule:
• This is a useful schedule to control lighting. For instance, you can control binary outputs to
parking lot lights with a binary output schedule.
• You can use a binary output schedule to control internal lighting in conjunction with HVAC
control. However, these are two different schedules in Tracer SC.
Multi-state Output Schedules
Multi-state output schedules are very similar to HVAC schedules and allow you to schedule multi-
state outputs and values. However, a multi-state schedule does not have the capability to perform
optimal start and stop functions. Each multi-state schedule contains 20 states. Each state is
identified by number and has no state text associated with it. Use multi-state schedules to control
equipment that does not require the optimal functions.
3. The Schedule Information page appears (Figure 67). Type in a name for the schedule.
4. Select the HVAC schedule option and click the Optimal Start/Stop check box.
5. Click next.
6. The Schedule Times page appears (Figure 68). The current date displays as the default Start
Date in the Specify Effective Dates group. Choose the Start Date and End Date for your HVAC
schedule.
Figure 68. Create Schedule - Schedule Times
7. Add the effective days and times for the schedule. Click + add event.
8. The Add event -HVAC window appears (Figure 69). Select the check boxes for Start Time, Stop
Time, and the days of the week you want to schedule. Set the Start Time and Stop Time. Click
add.
Figure 69. Create Schedule - Add Events
9. A vertical bar appears on each day you selected with the appropriate start and stop time
(Figure 68, p. 111). Click + add optimal window.
10. The Add Optimal Window appears (Figure 70). Select the check boxes for Start Time, Stop
Time, and the days of the week you want to schedule an optimal window. Set the Start Time
and Stop Time. Click add.
11. A darker vertical bar representing the optimal window appears behind the event bar on each
day with the appropriate start and stop times set (Figure 68, p. 111). Click next.
Important: The optimal window defines a period of time in which Optimal Start and Optimal
Stop can occur if the conditions are right. It does not define exactly when the
optimal events will start and stop. For detailed information on how Optimal Start
and Optimal Stop operate, refer to “Optimal Start (PreCool/Morning Warm-up,”
p. 122 and “Optimal Stop,” p. 127.
12. The Select Members page appears (Figure 71). Click on areas in the selection tree, highlight
the Areas available in the available items column, and click add >.
Important: Areas can be member of more than one HVAC schedule. However, the effective
dates and times of those schedules cannot overlap.
13. The appropriate Area moves to the selected items column. Click next.
14. The Summary page appears. This page is a summary of all the settings you defined in the
wizard and allows you to verify that they are as you expected them to be (refer to Figure 72,
p. 114).
15. To change any of the parameters, click previous until you come to the page of the wizard that
allows you to change the parameter.
16. To save the settings for the HVAC schedule and close the wizard, click finish.
17. The Confirmation page appears (Figure 73, p. 115). This page shows you the created schedule
and confirms that it has been created successfully.
VAV Calibration
During a VAV calibration, the controller:
1. Closes the damper.
2. Reads the voltage from the flow sensor at zero airflow.
To prevent duct over-pressurization, the SC divides the VAV boxes into 6 groups and
staggers the command to calibrate between these six groups. A new group of VAV boxes
calibrates every 15 minutes until finished.
3. Closes the water valve and zeros the valve position.
4. When calibration is complete, the VAV box resumes normal operation.
Auto-Calibration
One of the features of the Tracer VV550/551 and UC400 VAV controllers is auto-calibration. Auto-
calibration eliminates the need for scheduled calibration in most applications. A calibration
sequence is initiated after either a power cycle, or when the operating mode of the VAV box
transitions from Occupied to Unoccupied. Actual calibration of the VAV boxes begins after a fixed,
3-minute delay.
VAV boxes that are always Occupied (a hospital is a good example) can only be recalibrated by
Best scheduling calibration.
Practice
1. On the VAS Configure page, select the override icon for the calibration trigger.
2. The Override page appears, in the Override Value frame,
3. Change the Change Value To field to Recalibrate.
BAS Technician(s)
Install
BAS Technician(s)
Commis
Commissio n Building Operator
Order has been placed
Optim
Optimiz
Optimize Service Technician
Maintain
Unoccupied Heating/Cooling
The easiest way to reduce heating and cooling energy consumption and cost during unoccupied
periods is to expand the space temperature setpoints (sometimes referred to as night setback).
Unoccupied Heating/Cooling allows the temperature in a conditioned space to fall/rise to the
unoccupied setpoints before enabling the HVAC equipment.
Implementing Unoccupied Heating/Cooling requires both the Scheduling and Area functions in
Tracer SC.
1. On the Area page, set the unoccupied heating and cooling setpoints to temperature limits that
will protect the building.
2. Create a schedule for each area (refer to “Add the Area to an HVAC Schedule,” p. 108).
3. Assign the areas as members of the appropriate HVAC schedule.
4. Unoccupy the areas by creating an HVAC schedule with an unoccupied event.
When Unoccupied Heating/Cooling begins, the area occupancy is controlled to Unoccupied by the
HVAC schedule. In turn area controls the operating mode of the area members to unoccupied and,
consequently, the VAS controls the operating mode of the air handler and common space VAV
boxes to unoccupied.
While Unoccupied, the Area monitors the space temperature continuously. If the space
temperature reaches the unoccupied heating setpoint (Unoccupied Heat) or the unoccupied
cooling setpoint (Unoccupied Cool), the Area controls the operating mode of the VAV members to
Unoccupied Heating/Cooling. The VAS then controls the operating mode of the air handler and
common space VAV boxes to Unoccupied Heating/Cooling.
The operating mode of the VAV boxes remain in Unoccupied until the Area space temperature:
• Rises above the Unoccupied Heating setpoint plus the Unoccupied differential, or
• Falls below the Unoccupied Cooling setpoint minus the Unoccupied differential
Note: The Area occupancy remains Unoccupied until Scheduling controls it to Optimal Start or
Occupied.
Unoccupied Heating
When an Area space temperature sensor value falls below the unoccupied heating setpoint (refer
to Figure 76 note), the Area operating mode transitions to Unoccupied Heating/Cooling. The Area
application controls the operating mode of each Heating Only, and Heating/Cooling VAV member
to Unoccupied Heating/Cooling. VAS detects this transition, which causes the VAS operating mode
transition to Unoccupied Heating/Cooling, which enables the VAV air handler. Ventilation members
and Cooling Only members remain Unoccupied or Off.
Unoccupied heating stops when the Area's inside space temperature rises above the unoccupied
heating setpoint plus the unoccupied differential (Area > Configuration page).
Use the default value for the unoccupied differential, which is 4.0°F (2.2°C).
Best
Practice
Unoccupied Heat
Space Ends
Temperature
64° F
Unoccupied Differential
is locked out
60° F
Unoccupied
Unoccupied Heat Heating
Starts setpoint
Note: Area occupancy remains Unoccupied until an HVAC Schedule controls it to Optimal Start or
Occupied.
Important: To disable the reheat in the VAV boxes when their operating mode is Unoccupied,
Unoccupied Heating/Cooling, Night Purge, or Optimal Start, uncheck the Allow VAV
Aux Heat at Night check box in the VAS editor (Setup tab) as shown in Table 11.
Heating with central heat only VAS editor (Setup tab) Gas heat in the air handler
Applies when it is most cost effective Disable local heat. and electric heat in the VAV
to heat the spaces using only the boxes
heat source in the air handler during The air handler is enabled
unoccupied periods. and uses its heat to
maintain the discharge air
heating setpoint.
Local heat at the VAV boxes
is disabled.
Heating with local heat and a Area editor There is no heat in the AHU
central fan The unoccupied heating setpoint of the Area and shutoff VAV boxes with
Applies when the air handler has no is 60.0°F (15.6°C) reheat. The central fan
heat or insufficient heat, or the VAV must run for heat.
The unoccupied differential of the Area is
boxes are equipped with reheat but 4.0°F (2.2°C).
have no fan.
VAV editor
The central fan is used to:
The VAV box unoccupied heating setpoint
• provide air flow allowing VAV should be less than the Area unoccupied
boxes to use their local heat. heating setpoint (VAV editor, Configuration
• circulate air between interior and tab). This prevents the VAV box from using
exterior zones to facilitate the its local heat when its operating mode is
warm-up process. unoccupied.
The VAV box controls local heat to
its occupied setpoints when its VAS editor (Setup tab)
mode is warm-up. Enable local heat.
Heating with local heat only Area editor Parallel fan-powered VAV
(central fan not used during The Area unoccupied heating setpoint boxes with reheat located
unoccupied heating) (Setup tab) should be set to a very low value around the perimeter of
Applies when the air handler is not (e.g., 40°F (4.4°C)). the building.
equipped with heat and the central Note: Do this so the Area never controls
fan will not be used during unoccu- the VAV boxes during unoccupied heating.
pied heating.
The VAV box manages all the heat- VAV editor
ing during unoccupied periods by The unoccupied heating setpoint of the VAV
using its local heat and/or enabling box is 60.0°F (15.6°C).
its remote (perimeter) heat. The The unoccupied differential of the VAV box is
VAV boxes will remain in the unoc- +/- 1.5°F (0.9°C).
cupied mode and use their unoccu-
• Local heat is enabled at 58.5°F (14.7°C)
pied heating setpoints.
• Local heat is disabled at 61.5°F (16.4°C)
Note: A series or parallel fan is
required if the heat is in the VAV
box. VAS editor (Setup tab)
Enable local heat.
Unoccupied Cooling
When an Area space temperature sensor value rises above the unoccupied cooling setpoint (refer
to Figure 77 note), the Area operating mode transitions to Unoccupied Heating/Cooling. The Area
application controls the operating mode of each Cooling Only, and Heating/Cooling VAV member
to Unoccupied Heating/Cooling. VAS detects this transition, which causes the VAS operating mode
to transition to Unoccupied Heating/Cooling, which enables the VAV air handler. Ventilation
members and Heating Only members remain Unoccupied or Off.
Unoccupied Cooling stops when the Area's inside space temperature falls below the unoccupied
cooling setpoint minus the unoccupied differential (System > Area > Configuration page).
Use the default value for the unoccupied differential, which is 4.0°F (2.2°C).
Best
Practice
Unoccupied
Unoccupied Cooling Cooling
Starts setpoint
85° F
Unoccupied Differential
is locked out
81° F
Note: The Area occupancy remains Unoccupied until Scheduling controls it to Optimal Start or
Occupied.
• The Area operating mode for cooling only and heating/cooling members transitions to
Optimal Start.
Example:
Initial space temperature = 79°F (26.1°C)
Cooling Optimal Start rate = 8 min/°F (14.54min/°C)(learned by Area)
Occupied start time = 8:00 AM
Optimal Start window = 6:00 to 8:00 AM
Occupied cooling setpoint = 75°F (23.9°C)
Area calculates the optimal start time as follows:
(79°F - 75°F) x 8 min/°F = 32 minutes
or
(26.1°C - 23.9°C) x 14.54 min/°C = 32 minutes
Cooling
Begins Space
Temperature Occupied
Cooling
is locked out
setpoint
75° F
7:28 AM 8:00 AM
Optimal Start
Calculated Optimal Start Time Ends
70° F
Occupied
Heating
setpoint
Space
is locked out
Unoccupied Occupied
7:10 AM 8:00 AM
Setup
Create an HVAC Schedule with an optimal window defined and an Area added as a member.
Heating with central heat only Scheduling editor Gas heat in the air handler
Applies when it is most cost effec- Create an HVAC Schedule with an optimal and electric heat in the
tive to heat the spaces using only window defined with an 8:00 AM start. Add VAV boxes
the heat source in the air handler. the Area as a member of this schedule. Area initiates Optimal
VAS editor (Setup tab) Start at 7:10 AM
Disable the local heat. The air handler is enabled
and uses its heat to main-
tain the discharge air heat-
ing setpoint.
Local heat at the VAV
boxes is disabled.
Heating with local heat and a Schedule editor The Area's space tempera-
central fan Create an HVAC Schedule with an optimal ture is 65°F (18.3°C) and
Applies when the air handler has window defined with an 8:00 AM start. Add you want to warm it up so
no heat or if its heat is disabled the Area as a member of this schedule. that it gets to 70°F (21.1°C)
during unoccupied periods, and VAS editor (Setup tab) just as the building is
the VAV boxes are equipped with occupied at 8:00 AM. So
Enable the local heat.
reheat but have no fan. warm-up begins at 7:10
AM. The air handler has
The central fan is used to:
no heat and the VAV boxes
• Provide air flow allowing VAV are configured with hot
boxes to use their local heat water reheat.
• Circulate air between interior and
exterior zones to facilitate the
warm-up process
The VAV box controls local heat to
its occupied setpoints when its
mode is Warm-up.
Sequence
Area implements Humidity Pulldown as follows:
1. Area determines the actual time to control the operating mode of VAV boxes to Humidity Pull
Down based on the Area inside humidity sensor, the occupied humidity setpoint, and the
associated humidity pull down start rate.
2. When the calculated start time falls within the optimal window defined in the HVAC Schedule:
• The Area operating mode transitions to Humidity Pull Down.
• The operating mode of the Area cooling only and heating/cooling members transitions to
Humidity Pull Down.
Example:
Initial space humidity = 55%
Humidity pull down rate = 8 min/% RH (learned by Area)
Occupied start time = 8:00 AM
Optimal window = 6:00 to 8:00 AM
Occupied humidity setpoint = 50%
Area calculates the humidity pull down time as follows:
(55% - 50%) x 8 min/% RH = 40 minutes
setpoint
50%
7:20 AM 8:00 AM
Daytime Warm-up
Important: Daytime Warm-up is a function of the AHU controller. Specific setpoints and
deadbands may vary between AHU controllers.
Daytime Warm-up occurs during occupied periods. When the air handler’s space temperature is
colder than its “Daytime Warm-up Setpoint”, the air handler supplies hot air to the system. When
the space becomes too cold again, Daytime Warm-up runs again.
Follow the best practices defined in “Controller Setup,” p. 33 and sending the VAS Average Space
Temperature calculated in the VAS to the VAV air handler space temperature point (Figure 82). Use
Tracer TU to create this TGP2 program and download it to the Tracer SC controlling the VAV air
handler.
Optimal Stop
Optimal stop is an energy saving feature managed by the HVAC Schedule and Area applications.
During optimal stop the zone temperature is allowed to rise above the Occupied cooling setpoint
or fall below the Occupied heating setpoint. The VAV boxes control to their Occupied Standby
setpoints. The air handler behaves as it does when it’s in the Occupied mode.
Occupied
Cooling
Space setpoint
is locked out
Temperature
74° F
Unoccupied
73.5° F
Initial
Space
Temperature
4:25 PM 5:00 PM
Occupied
Calculated Optimal Stop Time
Heating
setpoint
71° F
Initial
Space Space Temperature
Temperature
70.6° F
is locked out
Optimal Stop
Ends
69° F
Unoccupied
4:36 PM 5:00 PM
Setup
Create an HVAC Schedule with an optimal window defined and an Area added as a member. The
stop event must occur within the defined optimal window.
For normal AHU systems, outside dampers are open and return air dampers are closed. All exhaust
fans operate at full speed.
All night purge VAV members of the Area control to their occupied cooling setpoint.
Night purge ends when any of the following is true:
• The current time is outside the scheduled time to night purge.
• The night purge input is disabled.
• The outdoor temperature is above the space temperature.
• The Area transitions to a heating mode.
• The space temperature falls below its occupied cooling setpoint minus the binary control
differential (1°F (.56°C)).
The Night Purge window (on the Area Function page) should be scheduled to occur during the
Best coolest time of the early morning, typically just before sunrise. For example, if sunrise is at 6
Practice AM or later, schedule Night Purge from 4 to 6 AM.
Setup
Setup for Night Purge occurs in the Area function page for the selected Area.
1. Enable Night Purge.
2. Click the referencer icon for Economizing decision.
3. The Referencer page appears, select the pre-defined referencer for the Area Economizing
decision.
Note: If desired, a binary point may be referenced to the Economizing decision input. This
input allows additional criteria, such as unit economizing decisions to be used.
The Area Economizing decision should be enabled. The referencer for the Night Purge
Best Economizing decision should be set to look at the Area Economizing decision.
Practice
Example: A building has been unoccupied over the weekend and the internal temperature has
been maintained at 82°F (27.8°C) by the Area Unoccupied Heating/Cooling function. A Night
Purge event will occur at 4 AM Monday morning under the following conditions.
• Night Purge is enabled.
• The Night Purge Economizing decision is enabled.
• The outdoor/space temperature differential is set to 15° (8.3°C)
• A Night Purge window is configured to occur between 4 AM and 6 AM.
• The Area occupied cooling setpoint is 75°F (23.9°C).
Night Purge will exchange the 82°F (27.8°C) air from inside the building with the cooler outdoor
air.
Night Initial
Purge Space
Begins Temperature
82° F
Space
Temperature Occupied
Cooling
is locked out
Night setpoint
Purge
Ends
75° F
74° F
4:00 AM 6:00 AM
Unoccupied Humidification
Unoccupied Humidification is the process of the HVAC Schedule and Area functions working
together to increase the humidity in a building during unoccupied times to maintain a minimum
humidity level within the space.
Note: The air handler may keep the outdoor air damper closed during Unoccupied Humidification
because it occurs during Unoccupied periods. The Area occupancy request remains
Unoccupied by the HVAC Schedule; the Area occupancy status transitions to Occupied.
Important: Humidification members are air handlers with humidifiers, or binary outputs
controlling humidifiers that are also a member of the Area. Insure that these
members are configured as humidification members when adding them to the Area.
Sequence
Area implements Unoccupied Humidification as follows:
1. When the Area is Unoccupied and Unoccupied Humidification is Enabled, Area compares the
space humidity with the Enable Humidification Setpoint. When the space humidity falls below
the Enable Humidification Setpoint, the Area operating mode transitions to Unoccupied
Humidification. When this transition occurs:
• All humidification members of the Area transition to Unoccupied Humidify.
• All members of the Area not designated as humidification members remain Unoccupied or
Off.
2. When the space humidity rises above the Disable Humidification Setpoint, the Area operating
mode transitions to Unoccupied. When this transition occurs:
• All humidification members of the Area transition to Unoccupied or Off.
• All members of the Area not designated as humidification members remain Unoccupied or
Off.
Example:
Initial space humidity = 26%
Enable Humidification Setpoint = 20%
Disable Humidification Setpoint = 25%
Humidification
Space Ends
Humidification
25%
is locked out
20%
Humidification Enable
Starts Humidification
setpoint
Note: Area occupancy request, remains Unoccupied until an HVAC Schedule controls it to
Occupied; the occupancy status will transition to Occupied during this mode.
Unoccupied Dehumidification
Unoccupied Dehumidification is the process of the HVAC Schedule and Area functions working
together to decrease the humidity in a building during unoccupied times to maintain a maximum
humidity level within the space.
Note: The air handler may keep the outdoor air damper closed during Unoccupied
Dehumidification because it occurs during Unoccupied periods. The Area occupancy
request remains Unoccupied by the HVAC Schedule; the Area occupancy status transitions
to Occupied.
Sequence
Area implements Unoccupied Dehumidification as follows:
1. When the Area is Unoccupied and Unoccupied Dehumidification is Enabled, Area compares the
space humidity with the Enable Dehumidification Setpoint. When the space humidity rises
above the Enable Humidification Setpoint, the Area operating mode transitions to Unoccupied
Dehumidification. When this transition occurs:
• All dehumidification members of the Area transition to Unoccupied Dehumidify.
• All members of the Area not designated as dehumidification members remain Unoccupied
or Off.
2. When the space humidity falls below the Disable Dehumidification Setpoint, the Area operating
mode transitions to Unoccupied. When this transition occurs:
• All dehumidification members of the Area transition to Unoccupied or Off.
• All members of the Area not designated as dehumidification members remain Unoccupied
or Off.
Example:
Initial space humidity = 54%
Enable Dehumidification Setpoint = 60%
Disable Dehumidification Setpoint = 55%
Enable
Dehumidification Dehumidification
Starts setpoint
60%
is locked out
55%
Space Dehumidification
Humidity Ends
Note: Area occupancy request remains Unoccupied until an HVAC Schedule controls it to
Occupied; the occupancy status will transition to Occupied during this mode.
Timed Override
During unoccupied periods, a Timed Override request (typically initiated by pressing the On button
at a zone sensor attached to a VAV box) controls the Area occupancy request to Standby at a higher
priority than the Schedule for a specified duration.
Timed override ends when the time defined in the Duration field expires for the temporary override,
or the Cancel button on a zone sensor in the Area is pressed. When Timed Override ends, the
schedule regains control of the Area occupancy request.
Setup
Figure 91 details specific settings used to make Timed Override work properly.
Figure 91. Timed override setup. Area configuration page, operations frame
General Settings
These settings are considered best practices for each of these Standard Operating modes.
VAV Configuration
• Configure the VAV boxes prior to installing into Tracer SC.
• The Heat/Cool Request field is set to Auto.
Area Configuration
Configure page - Setup
• Area Heat/Cool Request: = Auto (Configuration page)
• Reference the Space Temperature Sensor (Configuration page, Setup) to the pre-defined
referencer for the Area Average Space Temperature.
• Reference the Outdoor Air Temperature Sensor (Configuration page, Setup) to the pre-defined
referencer for the Facility Outdoor Air Temperature.
• If Economizing with Enthalpy or Dew Point, reference the Space Humidity sensor and the
Outdoor Air Humidity sensor (not shown as referenced in Figure 93).
Members configuration
• Each VAV box is a Heat/Cool member of the Area. (select Add or Edit Members on the Members
page).
• The Calculations, Override, and Night Purge check boxes are selected for each VAV member
(Members Configuration page). If performing humidification or dehumidification, those check
boxes must also be selected.
VAS Configuration
• All of the VAV boxes, which are part of the VAV system, should be defined as members of the
VAS.
• Select the Allow VAVs to use auxiliary heat at night check box.
• Select the Send source temperature to VAV boxes check box.
• Select the Send drive max to VAV boxes check box.
• Air Handler Startup Delay = 2 min.
• VAV Box Shutdown Delay = 5 min.
• The VAV AHU Startup Setpoint is set to 72.0°F (22.2°C).
• Calibration Trigger is set to Normal.
Scheduling Configuration
• Each Area must be a member of either an HVAC Schedule or a Multi-State Schedule
Note: Optimal functions are only available when the Area is a member of an HVAC Schedule.
BAS Tec
ch
hni
n ci
cian
an(s
an (s))
(s
Install
BAS Technician(s)
Operate
O perate BAS Technician
B
Maintain
Commissioning
This section discusses the commissioning process of a variable air system. The intended audience
is the field startup technician with the last section devoted to air balancing. It is important to note
that the LonTalk VAV system commissioning process differs dramatically from previous air
systems due to the unique ability of the VV550/551 controllers to perform auto-commissioning.
Consequently, new best practices are now being recommended.
90
High
85
Measured Resistance (Ohms)
80
75
Low
70
65
60
55
50
45
40
35
0 500 1000 1500 2000 2500 3000 3500 4000 4500
If the measured resistance does not fall within the expected values, most of the time it is possible
to determine the nature of the problem from the resistance readings. Table 13 shows some typical
resistance readings for communications links when various problems occur along with the effects
and what to look for when these problems exist. The most common communication link issues are
shorts, open links, or the wrong number of resistors installed on the link. Most of these problems
can be found quickly using a multi-meter to check for link resistance. This can be done with or
without the devices powered up.
Finding a Short
Shorts are the most common issue related to communication links. If a short occurs anywhere in
the communications link, a resistance reading between 0 Ω and 10 Ω is typically seen. The easiest
way to determine where the short occurs is to use the divide and conquer technique. This technique
is the fastest way to locate most communications issues and does not require a computer or a
service tool. On a link of 60 devices the problem can typically be found in no more than six steps.
The first step after a problem is detected is to select a device that is approximately in the middle
of the link. At the middle device remove one side of the communication link, which effectively splits
the link into two separate links (refer to Figure 99). The resistance is then read on each of the two
links from the split back to the termination resistors located at each end of the link. One of the two
links will read a short and is the link that contains the problem. The other link reading should be
reading the termination resistor plus the resistance of the wire. Reconnect the communication link
and select a device that represents half the length from the previously tested device and the end
of the link which showed the short. Using the same procedure, measure the resistance of each link.
This procedure is repeated until the wiring problem is located.
Ω
VAV 03-03
VAV 03-02
VAV 03-05
Ω
Reading too high a resistance on the link indicates that one of the termination resistors is missing
or the link has a break somewhere between the two termination resistors. Verify that both resistors
are installed and read the resistance of the link at each device where the resistor is installed. If the
resistance at both ends of the link are approximately equal to the resistor plus some resistance of
the communication wire then it is safe to assume that the communication link has a break
somewhere between the two end devices.
Rover is helpful in determining where the break is located. The installation contractor should
provide as-built documents that show how the communication link was actually installed. Use
Rover to discover the devices on the link and the as-built documents to determine how many
devices should be on the link. It should be possible to find the approximate location of the break
in the link.
Using Figure 99 as an example, Rover should find three devices when connected to one end of the
communication link or two devices when connected to the other end of the communication link.
The as-built document should indicate that there are five devices on the link.
Devise an address scheme for all the devices on the BACnet link and then make sure both the
Best installer and BAS technician adhere to that scheme.
Practice
Other things to consider during installation of the devices that will make commissioning and
troubleshooting the link much easier:
• Make sure the devices are wired properly (proper terminations and polarity).
• Label the communication wiring “IN” from the Tracer SC and “OUT” to the next device at each
device. This makes troubleshooting the link much easier. It helps you to know you have
included or excluded the device when splitting the link without trial and error.
The most useful tool for troubleshooting the BACnet link is the Tracer SC itself. All of the issues
below can be discovered by using divide-and-conquer methods. If any BACnet device on the link
is powered up, a digital volt meter will not provide useful information when troubleshooting a
BACnet communication link. The most frequently encountered problems on an MS/TP BACnet link
are:
• An open circuit
• A short circuit
• A duplicate MAC address (duplicate rotary address on the UC)
• UCs that are not addressed (0,0,0 on the UC’s rotary switches)
Before troubleshooting the link, you should have a valid set of prints for the project that show you
how the devices are wired on the link along with their addresses.
The following steps define the general troubleshooting tasks for BACnet links.
1. From the Tracer SC, verify the following:
a. Verify the rotary address setting on the SC (make sure it’s rotary switches match the
submittal documents). If you change the rotary switches, verify the Tracer SC BACnet
configuration using the Tracer SC (Installation > Identification and Communication >
BACnet Configuration)
b. Verify the shield wires are properly terminated per the wiring diagrams.
c. Verify the communication wiring terminal is fully seated on the controller.
d. Verify the polarity of the comm link.
e. Verify that both the in and out are properly terminated on the terminal by performing a tug
test on each wire.
2. Verify that a Tracer BACnet Terminator is properly installed on each end of the comm link.
3. Go to the middle of the link and check the following items. If you find any of these items to be
improperly installed, correct the problem and rediscover using the Tracer SC (Step 4):
a. Verify the rotary address setting on the UC (make sure it’s rotary switches match the
submittal documents). If you find switches set incorrectly, you must change the rotary
address and then cycle power on the UC.
b. Verify the shield wires are properly terminated per the wiring diagrams (and per wiring
guidelines).
c. Verify the communication wiring terminal is fully seated on the controller.
d. Verify the polarity of the comm link.
e. Verify that both the in and out wires are properly terminated on the terminal by performing
a tug test on each wire.
4. Using Tracer SC, discover the link.
5. If all devices are discovered, the problem exists on the outward side (away from the Tracer SC)
of the broken link.
a. Reconnect the link and move half-way farther out on the link and break the link there.
b. Discover the link with Tracer SC.
c. Repeat step 3 until the trouble is isolated.
6. If not all the devices are discovered, the issue with the BACnet link is on the inward side of the
broken link.
a. Reconnect the link and move half-way back toward the Tracer SC and break the link there.
b. Discover the link with Tracer SC.
c. Repeat step 3 until the trouble is isolated.
Troubleshooting Scenario
The following example shows a typical troubleshooting scenario. The example uses a limited
number of UC devices to help illustrate the procedure. Most installations have many more UCs
installed. A link of 30 devices should take no more than five steps to isolate a problem using the
divide-and-conquer method.
Important: To communicate properly, the baud rate for all devices must be the same when they
reside on the MS/TP link. The factory default setting for the baud rate on the UC400
is 76,800. The factory default setting for the baud rate on the Tracer SC is Disabled.
Therefore, you have to configure the baud rate on the Tracer SC to match the UC400.
The installation for this example (as shown in Figure 100) has a single Tracer SC with six BACnet
devices connected on the communication link and is terminated on each end of the link with a
Tracer BACnet Terminator.
Figure 100.BACnet Link Troubleshooting Scenario
– +
LINK 1
Tracer – +
UC-006 UC-005 UC-000 UC-003 UC-002 UC-001 LINK 1
BACnet
Terminator Tracer
Tracer SC-101
BACnet
Terminator
The BACnet device in the fourth position (UC-004) has been installed on the project without it’s
rotary switches being properly set (they were left at 0,0,0, which is the factory setting).
Important: The Tracer SC and the UC400 are shipped from the factory with their rotary switches
set at (0,0,0). The Tracer SC always uses a MAC address of (0). The UC400 determines
it’s MAC address from its rotary switches. Therefore, when UC400s are installed on
a project, the rotary switches need to be reset to a specific and unique address (from
1-127). If the UC400 factory setting is not changed, the UC400 ends up with the same
MAC address as the Tracer SC (which is 0). When this happens, the token is lost on
the MasterSlave/TokenPassing (MS/TP) link.
Since there are two MAC addresses on the BACnet link that are the same, the Tracer SC will typically
discover no devices on the link. The technician should follow this process to isolate and find the
problem:
1. Per step 1 in the preliminary checkout procedure above, the technician should do the following
at the Tracer SC.
a. Check the rotary address setting on the SC.
b. Check the shield wire terminations.
c. Check the seating of the communication wiring terminal on the controller.
d. Check the polarity of the comm link.
e. Perform a tug test on each wire.
©2009 Trane. All Rights Reserved.
146 PROPRIETARY INFORMATION OF TRANE. BAS-APG007-EN, 12/15/2009
MAY ONLY BE USED IN THE CONDUCT OF TRANE BUSINESS.
Commissioning
2. Make sure there is a Tracer BACnet Terminator at each end of the link, and that the wiring is
terminated properly.
3. Go to the middle of the link (UC-003) and check the following items. If any of these items are
improperly installed, correct the problem and rediscover using the Tracer SC (step 4 below and
refer to Figure 101):
a. Verify the rotary address setting on the UC400 (make sure it’s rotary switches match the
submittal documents—in this case UC-003). If you find switches set incorrectly, you must
change the rotary address and then cycle power on the UC.
b. Check that the shield wires are properly terminated per the wiring diagrams (and per wiring
guidelines).
c. Check the seating of the communication wiring terminal on the controller.
d. Check the polarity of the comm link.
e. Perform a tug test on each wire.
– +
LINK 1
Tracer – +
UC-006 UC-005 UC-000 UC-003 UC-002 UC-001 LINK 1
BACnet (address: 0,0,6) (address: 0,0,5) (address: 0,0,0) (address: 0,0,3) (address: 0,0,2) (address: 0,0,1)
Terminator Tracer
Tracer SC-101
BACnet
Terminator
UC400
4. Using Tracer SC, discover the link. In this scenario, all devices should be discovered, this means
the problem exists on the outward side (away from the Tracer SC) of UC-003.
5. Reconnect the link and move half-way farther out on the link from where it was broken in the
first jump and break the link (at UC-005)(refer to Figure 102, p. 148).
6. Per step 1 in the preliminary checkout procedure above, the technician should do the following:
a. Verify the rotary address setting on the UC400 (make sure it’s rotary switches match the
submittal documents—in this case UC-005). If you find switches set incorrectly, you must
change the rotary address and then cycle power on the UC.
b. Check that the shield wires are properly terminated per the wiring diagrams (and per wiring
guidelines).
c. Check the seating of the communication wiring terminal on the controller.
– +
LINK 1
Tracer – +
UC-006 UC-005 UC-000 UC-003 UC-002 UC-001 LINK 1
BACnet (address: 0,0,6) (address: 0,0,5) (address: 0,0,0) (address: 0,0,3) (address: 0,0,2) (address: 0,0,1)
Terminator Tracer
Tracer SC-101
BACnet
Terminator
UC400
8. Per step 1 in the preliminary checkout procedure above, the technician should do the following:
a. Verify the rotary address setting on the UC400 (make sure it’s rotary switches match the
submittal documents—in this case UC-004). In this scenario, the switches are still at their
factory default setting of (0,0,0) so they need to be changed to (0,0,4).
b. Cycle power on the UC (refer to Figure 103, p. 149).
– +
LINK 1
Tracer – +
UC-006 UC-005 UC-000 UC-003 UC-002 UC-001 LINK 1
BACnet (address: 0,0,6) (address: 0,0,5) (address: 0,0,0) (address: 0,0,3) (address: 0,0,2) (address: 0,0,1)
Terminator Tracer
Tracer SC-101
BACnet
Terminator
UC400
For each VAV box, install an auxiliary temperature sensor, configured as a discharge air sensor,
Best in the discharge air stream to allow the most complete auto-commissioning of the VAV box.
Practice
This sequence is initiated via a command from Tracer SC’s VAS or VAV Configuration pages or from
a Trane service tool. When the auto-commissioning command is initiated from the VAV
Configuration page or a service tool, you can only initiate auto-commission on one VAV at a time.
Tracer SC’s VAS editor can auto-commission all the VAVs in the VAS at once (but staggered). The
results are stored locally in the controller. Access the results using either Tracer SC, the Rover
service tool, or Tracer TU.
Have the air handler making cold air under static pressure control and have hot water available
Best at the VAV box if a hot water valve is present.
Practice
If duct static pressure optimization is used, the system may not respond in time to satisfy the
Best short term high demand of the VAV during the auto-commissioning phase. Disable the duct
Practice static pressure optimization feature in the VAS editor during the auto-commissioning process.
5. Once started the auto-commissioning function goes to each VAV box and runs it through some
operation performance tests (refer to Table Note:, p. 154) and records the results (refer to
Figure 108, p. 155). How long it takes for each VAV box depends on the configuration of the box.
VAV boxes configured with fans and heat take longer than those that do not. Auto-
commissioning follows this sequence:
a. The SC divides its VAV members into six groups (common space members are distributed
as evenly as possible among these groups).
b. The SC then staggers the command to auto-commission each VAV group by 15 minutes. The
first group begins immediately; the second group 15 minutes later; the third group 15
minutes after that, and so on. The last group begins auto-commissioning 75 minutes after
initiating the auto-commissioning command. When a particular VAV box gets the command
to auto-commission, it calibrates and then runs through a sequence of operation
performance tasks as described in Table 14
Note: The data generated during the auto-commissioning sequence is stored on the
controller. Tracer SC harvests this data to populate the auto-commissioning report.
New data overwrites existing data on the controller each time auto-commissioning
occurs.
The auto-commissioning report contains the following information about the VAS air system:
• The VAV box name.
• Whether there are alarms present.
• The zone temperature and its setpoint.
• Active airflow (in cfm).
• When the VAV box was tested as part of the report.
• The air valve position when the VAV box reaches 40% of Maximum cooling setpoint.
• The air valve position when the VAV box reaches 100% of Maximum cooling setpoint.
• The discharge air temperature of the VAV box when the fan is off.
• The discharge air temperature of the VAV box when the fan is on.
• The discharge air temperature of the VAV box when the hot water heat is on (if applicable).
• If the box is equipped with electric heat, the report shows temperatures measured when one
stage of heat is turned on, when two are turned on, and when three are turned on.
maximum flow and with the fan off. It then turns the fan on and drives the air valve closed. If the
fan runs, it draws warm plenum air in through the box and out past the discharge air temperature
sensor. A rise in the discharge air temperature indicates that the fan is operating. No change in
temperature indicates that the fan did not start.
Note: The plenum air should be warmer than the primary air source.
BAS Technician(s)
Install
BAS Technician(s)
Maintain
M i t i
Optimization
The Tracer SC VAS has two standard features designed to minimize overall energy consumption
of the VAV air system:
• Duct static pressure optimization
• Ventilation optimization
Install a duct static pressure sensor at the discharge of the fan. (refer to “Static Pressure Sensor
Best Location,” p. 32 for more information)
Practice
Figure 109. Setup for duct pressure optimization in the VAS editor
Minimum operating pressure
4. Validate the maximum duct pressure setpoint with the air balancer. The default duct pressure
setpoint is the duct pressure an AHU must maintain in order for all VAVs to supply their design
airflow at peak capacity.
5. Verify that the Enable Duct Pressure Optimization check box is selected.
Figure 110 shows the relation between the airflow and the position of the air valve in the
VAV box. The graph shows that as the air valve begins to open and as it approaches 100%
open, the airflow only increases in small increments. Most of the airflow variation occurs
when the air valve is between 20% and 80% open. In this area of the graph, airflow
increases roughly 2% for every 1% of modulation by the air valve. In order to implement
the optimization routine most effectively, it is important to select limits that are still within
the “dynamic range” of the damper.
Figure 110. Best practices for VAV air valve position limits
Recommended settings:
High limit = 75%
Flow increases 2% for every 1% Low limit = 65%
of damper movement
Maximum
Airflow
Dynamic range
0
20% 80% 100%
Ventilation Optimization
Ventilation optimization is a tool that calculates the system outdoor air requirement based on “real
time” conditions in the spaces (i.e., number of occupants, CO2 levels, etc.) minimizing the amount
of unconditioned outdoor air that must be brought into the building. The benefit is reduced
operating costs because less outdoor air must be conditioned (heated, cooled, humidified, or
dehumidified) by the air handler while insuring that ventilation air reaches the zones where it is
needed.
Ventilation optimization can be divided into two areas: zone level action which takes place at the
VAV box, and system level action that takes place at the air handler.
When the occupancy mode of the VAV is Occupied Standby (the building is occupied but the zone
is unoccupied), the zone only requires the building component of the ventilation rate. Under these
conditions, the VAV uses the “Occupied Standby Ventilation” setpoint
Important: Occupied Standby Ventilation setpoint. The Occupied Standby Ventilation
setpoint is the amount of outdoor air required to ventilate a zone during Occupied
hours when no people are present (i.e., an empty conference room). Refer to
ASHRAE 62.1 for detailed information.
Refer to the previous example for details on calculating the setpoints.
Occupied
Ventilation Setpoint
Outdoor Air
Occupied Standby
Ventilation Setpoint
Minimum ventilation
for building only
CO2 Level
This ventilation strategy requires a communicated CO2 input to the Tracer controller from either
a local binding (e.g., nviSpaceCO2), or from Tracer SC. When using Tracer SC, create a TGP2
program (using the Tracer TU service tool) that will read the Space CO2 Concentration from another
source (such as an MP580 universal input) and then write it to the VAV Space CO2 Concentration
BAS point (refer to “Tracer SC Setup for VAV boxes with communicated CO2 values,” p. 163).
Trane’s CO2-based, demand-controlled ventilation strategy is cost effective for the customer
because it only places CO2 sensors in locations with widely varying occupancy patterns and
population densities (i.e., conference rooms, break rooms, classrooms, cafeterias, etc.).
The values used to determine the CO2 setpoint are configured using either Tracer SC or the Rover
service tool (refer to Figure 114, p. 163).
6. Using Tracer TU, create a TGP2 program that reads the value from the actual CO2 sensor being
used and writes it to this point (refer to Figure 116). This TGP2 program must be set to run no
less than every 5 minutes. In this example TGP2 program, the Analog Value would be replaced
by the point that contains the actual CO2 value (which may be wired to an MP580 or some other
device).
7. Once created, download this program into the Tracer SC.
Important: The UC400 controller also supports a hardwired CO2 sensor. When using a
hardwired sensor, it is not necessary to place the Space CO2 Concentration BAS
point in service or in the TGP2 program described above.
Ventilation_Calc.tgp
This program (refer to Figure 118) calculates a minimum outdoor air requirement given the number
of occupants in a space and the cfm per person.
Note: The values in this TGP2 program are for this example only. Modify the program to meet the
specific needs of your building.
Considerations for using scheduled ventilation:
1. One multi-state schedule and one multi-state value are required for each zone using scheduled
ventilation.
2. The multi-state schedule(s) must be updated when times or the number of people change.
3. CO2-based demand controlled ventilation may be a better solution.
Conditioning outdoor air is expensive. To reduce costs, Trane has developed a strategy to minimize
the amount of unconditioned outdoor air brought into the building while still meeting ASHRAE
ventilation requirements. By reducing the amount of unconditioned outdoor air, the cost to
ventilate the zones is minimized both at the air handler and in reheat at the VAV boxes. This strategy
is known as ventilation optimization.
The ventilation optimization program in the Tracer SC VAS continually calculates the corrected
outdoor airflow. This is defined as the minimum amount of outdoor air the AHU needs to deliver
to the system as defined in ASHRAE 62.1 for single-path VAV systems.
To calculate the corrected outdoor airflow, VAS must obtain several pieces of flow data from its VAV
members.
• Measured primary airflow. The VAV property associated with this value is the “Nominal
Airflow Status” point.
• Effective ventilation setpoint. The VAV property associated with this value is the
“Ventilation Setpoint” point.
• Ventilation ratio. The VAV property associated with this value is the “Ventilation Ratio” point.
Note: Because some of this flow data can only be provided by the controllers, the ventilation
optimization strategy requires the use of Trane controllers.
The example on the following pages describes how the ventilation optimization program works.
Figure 119. Effective ventilation setpoints for each VAV box (shown in IP units)
Exhaust
AHU
Unconditioned
Outdoor Air
Return Air
zone 1
Supply Air
zone 2
zone 3
Figure 119 shows a scenario where an air handler supplies airflow to three zones, each equipped
with a Trane-controlled VAV box. Each VAV box must supply a minimum amount of ventilation air,
which is determined by the selected zone-level ventilation strategy discussed earlier in this section.
Zone 1 needs 200 cfm(94.39 L/s), zone 2 needs 300 cfm(141.60 L/s), and zone 3 needs 200 cfm (94.39
L/s). The Tracer SC VAS determines the minimum outdoor air requirements for the system based
on the needs of each of the zones.
Note: The ventilation optimization program ignores a VAV’s active ventilation setpoint at times
even when it is a non-zero value (i.e., when the Heat/Cool Mode Status mode is Test,
Calibration, Max Heat, or Off). The controller goes into test mode under a variety of
situations, but most commonly during air valve overrides and during auto-commissioning.
Figure 120. Measured primary airflow required for each zone (shown in IP units)
Exhaust
AHU
Unconditioned
Outdoor Air
Return Air
zone 1
zone 2
zone 3
Figure 120 shows the measured primary airflow for each zone. This is the amount of air required
to satisfy the temperature setpoints. In the example, zone 1 is delivering 400 cfm (188.80 L/s), zone
2 is delivering 900 cfm (424.80 L/s), and zone 3 is delivering 1000 cfm (471.90 L/s).
Exhaust
AHU
Unconditioned
Outdoor Air
Critical Zone
200 cfm
Supply Air = 2300 cfm
VAV = .5 (50%)
400 cfm
Return Air
zone 1
300 cfm
VAV = .33 (33%)
900 cfm
zone 2
200 cfm
VAV = .2 (20%)
1000 cfm
zone 3
The controller calculates a ventilation ratio for each zone by dividing the effective ventilation
setpoint by the measured primary airflow (refer to Figure 121). Zone 1 needs 50% outdoor air, zone
2 needs 33% outdoor air, and zone 3 needs 20% outdoor air.
Because zone 1 requires a larger percentage of outdoor air than zones 2 or 3, it becomes the critical
zone. As a result, the outdoor air dampers could be controlled to maintain a mixture of 50% outdoor
air (1150 cfm (542.70 L/s)) in the supply (refer to Figure 122).
Exhaust
AHU
Unconditioned
Outdoor Air
1150 cfm
All three zones are now adequately ventilated; however, it supplies more outdoor air than is
required by ASHRAE 62.1. The reason for this is that zones 2 and 3 are both receiving 50% outdoor
air, which is more than they require.
The ASHRAE 62.1 standard includes equations to calculate the amount of unconditioned outdoor
air required (Vot) by accounting for the unused outdoor air in the return:
Vot = Vou / (1 + Xs – Zd)
where:
Vot = the outdoor airflow required at the system intake.
Vou = the “uncorrected” outdoor air intake flow.
Xs = the average fraction of outdoor air required.
Zd = the critical zone ventilation ratio.
Using the example above, the results would be:
(with IP units) (with SI units)
Vou = 200 + 300 + 200 = 700 cfm Vou = 94.4 + 141.6 + 94.4 = 330.4 L/s
Xs = (200 + 300 + 200) / (400 + 900 + 1000) Xs = (94.4 + 141.6 + 94.4) / (188.8 + 424.8 + 471.9)
or Xs = 0.304 or Xs = 0.304
Zd = 0.50 Zd = 0.50
Vot = 700 / (1 + 0.304 – 0.50) Vot = 330.4 / (1 + 0.304 – 0.50)
or Vot = 870 cfm or Vot = 410.9 L/s
As a result, the required amount of outdoor air obtained through the outdoor air dampers is
reduced to 870 cfm(410.9 L/s)(Figure 123).
Exhaust
AHU
Unconditioned
Outdoor Air
870 cfm
Once the ventilation optimization program calculates the corrected outdoor airflow value, it must
be communicated as the minimum flow setpoint to the VAV air handler.
Figure 124. VAS writing to the outdoor air minimum flow setpoint at priority level 14
If using an MP580/581 on the air handler with Traq dampers or outdoor air flow
monitoring:
• Tracer SC VAS calculates the corrected outdoor air flow setpoint and writes the value to the
analog value point “VentOptOaSetpointCorrected|VAS-1”.
• The MP580/581 DAC profile does not support the nviMinOAFlowSP LonTalk variable; therefore,
you must communicate the outdoor air minimum flow setpoint using a Tracer Summit analog
variable in the MP580/581.
• Use the small TGP2 program in the Tracer SC (refer to Figure 126, p. 172) to read the
VentOptOaSetpointCorrected|VAS-1 value in Tracer SC and write to the Tracer Analog Variable
“Outdoor Airflow Setpoint” in the MP580/581 (refer to Figure 125).
Figure 125. Data flow for OA flow setpoint from Tracer SC VAS to the MP580/581
Tracer SC MP580/581
TGP2
Setup
1. Program the MP580/581 using a DAC profile.
Important:All VAV air handlers controlled using MP580/581 controllers must be programmed
using a DAC profile.
2. Program the MP580/581 to use a “Tracer Summit Analog Variable” for the Minimum OA Flow
Setpoint.
3. Install the MP580/581 in the Tracer SC.
4. Create the VAS in the Tracer SC
5. Add the MP580/581 to the VAS as an air handler member.
6. Create and download the outdoor air flow TGP2 program on the Tracer SC (using Tracer TU).
Figure 126. TGP2 program for OA air flow setpoint when using an MP580/581
While this field limits the percentage of outdoor air the VAS requests from the air handler, it does
not prevent the VAV boxes from asking for a greater percentage of outdoor air than the system can
deliver (refer to “Ventilation Ratio Limit for each VAV” below).
High
Low
25% 50% 60% 75%
% of Ventilation Air
Note: As the percentage of outdoor air decreases, the VAV box must increase the total airflow to
the space to maintain the ventilation ratio. This increase in airflow leads to over-cooling and,
consequently, the need for reheat.
Based on energy analysis simulations, to minimize total system energy consumption, Trane
Best recommends that the amount of outdoor air supplied to the critical zone be between 50% and
Practice 60% of the total airflow. The default value is 60%.
Exhaust
AHU
Unconditioned
Outdoor Air
1387 cfm
zone 1
Supply Air = 2750 cfm
Return Air
300 cfm
VAV = .75 (75%)
400 cfm
zone 2
200 cfm
VAV = .2 (20%)
1000 cfm
zone 3
Min OA Requirement
Total Air Flow Required for the zone
Problem: If the critical zone is allowed to request 75% outdoor air, two things will occur:
1. The energy consumed by the VAV system will be higher than necessary because it will now be
operating outside the optimal energy consumption range as shown in Figure 129 on page 174.
2. The zone will be under-ventilated, because the corrected outdoor air requirement of 1387
cfm(654.6 L/s) (50% of the total airflow) exceeds the Ventilation Ratio Limit of the AHU value,
which is set at 40%. As discussed earlier in this section, the Ventilation Ratio Limit of the AHU
restricts the amount of outdoor air the air handler can provide in the total supply airflow.
Solution: Set the Ventilation Ratio Limit of each VAV to 60% (default), which will do the following:
• prevent the system from operating outside the optimal energy consumption range (refer to
Minimizing energy consumption on p. 173).
• limit the ventilation ratio of the critical zone to a maximum value.
How the Ventilation Ratio Limit of each VAV is applied
1. Initially, each VAV box calculates the ventilation ratio and the VAS uses this information to
determine the critical zone. In example 1, the ventilation ratio of 75% establishes zone 2 as the
critical zone.
zone 1
Supply Air = 2750 cfm
Return Air
300 cfm
VAV = .75 (75%)
400 cfm
zone 2
200 cfm
VAV = .2 (20%)
1000 cfm
zone 3
Min OA Requirement
Total Air Flow Required for the zone
Although the ventilation ratio of 0.75 is used to establish the critical zone, it cannot be
used to determine the corrected percentage of outdoor air in the system supply (refer to
the equations on p. 170) because the value exceeds the Ventilation Ratio Limit for each
VAV (0.60).
When the critical zone requests a higher ventilation ratio than the Ventilation Ratio Limit
for each VAV allows, the value for the Ventilation Ratio Limit for each VAV (60%= 0.60)
replaces the ventilation ratio (0.75) of the critical zone.
2. The VAV box recalculates the total airflow required for the zone in order to satisfy the Minimum
OA Requirement of the critical zone. Refer to “Zone Level Action,” p. 160 for details on
calculating the ventilation requirement.
Return Air
300 cfm
VAV = 0.60
??? cfm
zone 2
To satisfy the equation, the VAV box must increase the total airflow delivered to the Zone because
the value for the Min OA Requirement cannot change.
(with IP units) (with SI units)
0.60 = 300 cfm/Total Airflow Delivered to Zone 0.60 = 141.60 L/s per Total Airflow Delivered to Zone
Total Airflow Delivered to Zone = 300 cfm/0.60 Total Airflow Delivered to Zone = 141.60 cfm/0.60
Total Airflow Delivered to Zone = 500 cfm Total Airflow Delivered to Zone = 236.00 L/s
Exhaust
AHU
Unconditioned
Outdoor Air
1084 cfm
200 cfm
Supply Air = 2850 cfm
300 cfm
VAV = .60 (60%)
500 cfm
zone 2
200 cfm
VAV = .2 (20%)
1000 cfm
zone 3
Min OA Requirement
Total Air Flow Required for the zone
Using the equations discussed on p. 170, the corrected outdoor airflow at the air handler is now
1084 cfm (511.6 L/s), which is 38% of the total airflow and the zone is now properly ventilated with
supply air containing a lower concentration of outdoor air.
Default Ventilation
The startup airflow setpoint is used during the initial air handler startup allowing time for the air
system to stabilize.
The length of time the system uses this value is called the transitional delay, which is twice the value
specified in the Reset Interval: field (refer to Step 4). When the Reset Interval expires, the system
uses the corrected outdoor airflow setpoint (refer to “System Level Action,” p. 166 for a discussion
on how the system calculates this value).
ASHRAE 62.1 specifies an outdoor air rate of 0.06 cfm/ft2 (0.35 L/s per m2) for most spaces.
Best To calculate the startup airflow setpoint, multiply the (total square footage of the zone(s) being
Practice
served by the air handler) x 0.06 cfm/ft2 (0.35 L/s per m2).
The ventilation ratio limit for the AHU is fixed at 25% when the outdoor air temperature is below
0°F or above 75°F, and fixed at 40% when the outdoor air temperature is between 50°F and 65°F
(Figure 136). The ventilation ratio limit modulates from 25% to 40% between 0°F and 50°F and 65°F
and 75°F.
Figure 136. FG_Ventilation ratio limit reset curve
20% Differential
40%
AHU Limit
25%
The Ventilation Ratio Limit of each VAV should be set 20% higher than the Ventilation Ratio Limit
Best of the AHU.
Practice
Setup
1. Create two analog output points in Tracer SC.
2. Reference the first analog output from the Ventilation Ratio Limit of the AHU: field in the VAS
editor.
3. Reference the second analog output from the Ventilation Ratio Limit for each VAV: field in the
VAS editor.
4. Control the operating mode of the analog outputs using the custom program
Vent_Ratio_Limits (refer to p. 180).
5. Modify the CPL program Vent_Ratio_Limits to use the objects in your database.
PROGRAM Vent_Ratio_Limits
This routine calculates the ventilation ratio limit of the AHU and the ventilation ratio limit for each
VAV based on the outdoor air temperature and air handler capacity. The ventilation ratio limit for
the AHU ranges from a minimum of 25% to a maximum of 40% and is limited if the outdoor air
temperature falls below 50°F or rises about 65°F. The corresponding ventilation ratio limit for each
VAV is then calculated to be 20% higher than the ventilation ratio limit of the AHU.
Figure 137. Vent_Ratio_Limits.TGP2
BAS Technician(s)
Install
BAS Technician(s)
Commissio
Commiis n Building Operator
Order has been placed
BAS Technician
Operate
Maintain
Special Applications
This section describes enhancements to the basic VAS system to accommodate situations where
more specific control is beneficial or required.
• Dedicated ventilation systems. A separate outdoor air handling unit supplies ventilation air
to the building with VAV boxes controlling the ventilation airflow into various parts of the
building. This section describes how to set up a basic dedicated ventilation system, including
setting up the VAV box as a ventilation flow controller.
• Flow tracking. Maintains a positive or negative space pressure by controlling the airflow into
and out of the space. This section describes how to set up a pair of VAV boxes to work together
in a flow tracking application.
100% AHU
Outdoor Air 100% Outdoor Air Unit
mechanical
room VAS 5 common
( )
(16) space
VAS 6 VFC AHU VAV VAV
(1) (4)
CSC (w/LCI-I)
Floor 5
mechanical
room VAS 4 common
( )
(16) space
VFC boxes
In a dedicated ventilation system, the VAV boxes are configured for ventilation flow control (VFC
boxes) one of three applications supported by the Tracer VV550/551 and the UC400 controller
(Space Temperature Control and Flow Tracking Control are the other two). Use the Rover or Tracer
TU service tool to configure the VAV controllers for VFC.
Figure 139, p. 183 shows the typical components installed on a VAV box with a VV550/551 or UC400
controller configured as a VFC box in a dedicated ventilation system.
Outdoor Air
from AHU VFC Box To Floor VAS
Do not define any common spaces for a dedicated ventilation air system. If additional boxes are
Best required to handle the minimum airflow of the supply fan, use TGP2 to override an additional
Practice VFC box.
common
space
Floor 5
VFC VAS VAV VAV
(1) (16) (4)
VAS 6
AHU not shown
AHU not shown
common
space
Floor 4
VFC Area VAV VAV
(1) (16) (4)
AHU not shown
common
space
Floor 3
VFC VAS VAV VAV
(1) (16) (4)
Steps “b” and “c” make the VFC boxes behave like other VAV boxes in the system, which makes
Best air balancing easier.
Practice
The value for both the Occupied Ventilation setpoint and the Occupied Standby Ventilation
setpoint should have been determined by the project engineer and filled in on the Controller
Flow Settings Worksheet (refer to “Appendix A: Controller Flow Settings Worksheet,” p. 239).
d. If the VFC boxes are equipped with electric reheat, select the Configuration tab. Verify the
Auxiliary Heat Control field is set to Enabled. Do not reference this field to another property.
9. Create Areas
Create Areas and add VAV boxes.
a. Create five Areas (one Area for each floor of the building). Refer to “Set Up Areas,” p. 75.
b. For each floor Area, assign the 16 VAV boxes in the tenant space as "Heating/Cooling"
members.
Flow Tracking
Flow tracking, commonly applied in hospitals and labs, is used to maintain a positive or negative
pressure in a space relative to adjoining spaces. Space pressure is maintained by controlling
airflow into and out of a space using two VAV boxes (a space temperature control box on the inlet
and a flow tracking box on the outlet).
Inlet Outlet
Flow is
300 cfm Flow is
200 cfm
Space Temp
Sensor
Inlet Outlet
Flow is
200 cfm Flow is
300 cfm
Space Temp
Sensor
How to Set It Up
Setup for a flow tracking system is the same as setting up a standard VAV air system (refer to
“Tracer SC Application Setup for Variable Air Systems,” p. 72 for detailed information). The space
temperature control box on the inlet to the room is just like a normal VAV box described throughout
this manual. The only difference is the setup required for the additional VAV boxes in each
temperature-controlled space that track the incoming airflow.
Binding
nvoAirFlow nviAirFlowSetpt
This binding communicates the airflow through the space temperature control VAV box
to the flow tracking VAV box.
1. Set the Tracking Offset
• positive value for negative room pressure
• negative value for positive room pressure
2. Set the cooling maximum and minimum airflow setpoints as follows:
Positive room pressure (Negative Flow Tracking Offset)
• Maximum Air Flow Setpoint = Main Box Max Flow - Tracking Offset value
• Minimum Air Flow Setpoint = Main Box Min Flow - Tracking Offset value
Negative room pressure (Positive Flow Tracking Offset)
• Maximum Air Flow Setpoint = Main Box Max Flow + Tracking Offset value
• Minimum Air Flow Setpoint = Main Box Min Flow + Tracking Offset value
Note: The Rover service tool will not allow the setpoints to be less than 10% of nominal flow
because the transducer used to measure the air flow requires a nominal flow greater than
10% of the design airflow.
3. In the Application Selection section, select Flow Tracking in the Profile list box.
4. In the Equipment Options section, select the appropriate Box Size and Air Damper Opens
parameters for the VAV box being configured.
5. Click Save.
6. Click the 2. Setup Parameters tab.
UC400 on a UC400 on a
Space Temperature Control Tracer SC
Flow Tracking VAV Box
VAV Box
BAS Technician(s)
Install
BAS Technician(s)
Commission
n Building Operator
Order has been placed
BAS Technician
BA
Operate
Maintain
Maintenance
This section gives some ideas on:
• How to use auto-commissioning. Using the auto-commissioning tool to generate a report
and isolate non-performing or under-performing VAV boxes, which can save time in
troubleshooting and can give the customer some indication of the overall condition of their
system.
• Manual output testing.
Auto-commissioning
Important: Detailed information on initiating and using auto-commissioning is available in the
section titled “Preliminary Checkout for BACnet Communication Links,” p. 144.
Auto-commissioning provides a means to quickly evaluate the condition of the VAV air system by
putting each VAV box through a special operating sequence as part of a routine maintenance
program. Figure 147 presents an example of an auto-commissioning report.
BAS Technician(s)
Install
BAS Technician(s)
Commissio
Commiis n Building Operator
Order has been placed
BAS Technician
Operate
Maintain
Troubleshooting
This section provides information for troubleshooting the system after installation and during
routine maintenance, which includes:
• Scenarios outlining the proper sequence of operation for the system under specific conditions.
• How to isolate problem VAV boxes and remove them from the VAS until they’re fixed.
• Charts for both the VAV box and air handler equipment showing the input received from the
SC, the output sent over the network, and the expected result at the device.
Make sure to follow the best practices outlined in previous sections as you find and fix problems
in the VAV Air System.
Note: While the SC supports other manufacturers equipment, the sequences in this section are
written for Trane equipment only.
General Assumptions
For the following scenarios to work properly, the assumption is the system is set up a certain way
and some basic best practices have been followed. The following list summarizes those general
settings and best practices. Where there are assumptions specific to a scenario, they are listed at
the beginning of that particular scenario.
Scheduling
Each Area is a member of an HVAC schedule.
Area
• Area Heat/Cool Input: = Auto
• Each VAV box should be defined as a Heating/Cooling Member Type (regardless of whether the
VAV box has the capability to provide heat).
• Each VAV box should have the desired functions enabled on the Member Configuration page.
VAV box
All of these items are configured using the service tool (either TU or Rover).
• Configured for space temperature control.
• Auto calibrate is enabled (check box IS selected)(applies to VV550/551 controllers only).
• Star and double star (*/**) is not enabled (check box is NOT selected)(applies to VV550/551
controllers only).
• auto changeover setpoint = 80°F.
VAS
• All of the VAV boxes are members—both normal and common space VAVs.
• A variable volume air handler is the AHU member.
• AHU Startup Delay = 2 min.
• Common space shutdown delay = 5 min.
• On the VAV Box Configure Members page, select which functions each VAV box will participate
in and whether the VAV box is a common space VAV box.
AHU Object
• Create a TGP routine to read the VAS average space temperature and send it to the air handler’s
space temperature VAS.
Air Handler
• Configured as a VAV.
• The Space Temperature BAS, on the air handler’s Configuration page (Sensors sections), is in
service. To place this in service:
1. Select the Space Temperature BAS check box.
2. Click actions....
3. Select place in service from the menu.
Assumptions
This sequence of operation assumes the following settings are in place (beyond the general
assumptions stated at the beginning):
• Area Heat/Cool mode status = Cooling
• Area is part of an HVAC schedule and Optimal Stop/Start is enabled (check box is selected)
• An Optimal window is created in the HVAC schedule.
Sequence of Operation
The following steps occur in the order shown during Optimal Start mode in a cooling only scenario.
Area 2. Area decides how early to enable the system based on the Area setpoint for the
cooling mode (Calculated Occupied Cooling Setpoint), the space temperature
(Space Temperature Sensor), and the optimal cooling start rate
(startupcoolrate).
3. At the startup time determined in the previous step, controls the operating
mode of all cooling only and heating/cooling VAV members to Optimal Start at
the Area priority level.
4. Ventilation and heating members are Unoccupied or disabled.
Note: Refer to “Appendix E: Equipment Response to Operating Modes,” p. 245
VAV object 5. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (each VAV box Heat
Cool mode request is determined by comparing its space temperature to its
space temperature setpoint (the Space Temperature Setpoint BAS value is
located on the Configuration page (select equipment > configure)). If the
space temperature is above the setpoint, the SC sends PreCool. If the space
temperature is below the setpoint, the SC sends Morning Warm-up.)
Note: The local space temperature setpoint (thumbwheel) is not used to
determine the Heat Cool Mode Request for optimal start.
VAV box 6. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step 5).
7. The VAV box damper modulates to maintain the active space temperature
setpoint.
8. The VAV box heating or cooling minimum airflow is based on the heat or cool
control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto changeover
setpoint minus 10°F.
Note: When the AHU starts, the discharge air might be hot, but it should
cool as the AHU ramps up.
9. Reheat and parallel fans are disabled if the VAV box is in Precool.
VAS 10. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of common space VAV members to Optimal
Start at the VAS priority level.
• controls the operating mode of the VAV air handler members to Optimal
Start at the VAS priority level (there is a time delay(a) in VAS to allow time for
the common space VAV boxes to open).
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat Cool
mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint (located on the Configuration
page of the VAS). If the space temperature is above the setpoint, the SC
sends PreCool. If the space temperature is below the setpoint, the SC sends
Morning Warm-up.
11. Ventilation functions are disabled.
AHU 12. The operating mode controls the following values to the AHU at the VAS
priority level:
object • Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step 10).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 13. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step 10).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
14. The AHU begins producing cool air(b).
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
(b) There may be a time delay here depending on the AHU type.
Assumptions
This sequence of operation assumes the following settings are in place:
• Area Heat/Cool mode status = Heating
• Area is part of an HVAC schedule and Optimal window is defined.
• An Optimal window is created in the HVAC schedule.
• The check box for “Allow VAVs to use auxiliary heat at night” is NOT selected on the Tracer SC
VAS configuration page.
Sequence of Operation
The following steps occur in the order shown during Optimal Start mode in a heating with central
heat and no local heat scenario.
Area 2. Area decides how early to enable the system based on the Area setpoint for the
heating mode (Calculated Occupied Heating Setpoint), the space temperature
(Space Temperature Sensor), and the optimal heating start rate
(startupheatrate).
3. At the startup time determined in the previous step, controls the operating
mode of all heating only and heating/cooling VAV members to Optimal Start at
the Area priority level.
4. Ventilation members are disabled.
Note: Refer to “Appendix E: Equipment Response to Operating Modes,” p. 245
VAV object 5. The operating mode controls the following values to the VAVs at the Area
priority level:
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat (each
VAV box Heat Cool mode request is determined by comparing its space
temperature to its Space Temperature Setpoint BAS value. If the space
temperature is above the setpoint, the SC sends PreCool. If the space
temperature is below the setpoint, the SC sends Morning Warm-up.)
Note: The local space temperature setpoint (thumbwheel) is not used to
determine the Heat Cool Mode Request for optimal start.
• The Heat Cool Mode Request is Max Heat if the AHU reports that it is in the
constant volume fan mode.
• Occupancy Request = Occupied
6. The VAS controls the Auxiliary Heat Control point to Disabled at the VAS priority
(refer to Step 12).
VAV Box 7. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat (based
on step 5).
8. If in Max Heat mode, the VAV object opens its damper to the Maximum Heat
Airflow setpoint.
9. If not in Max Heat, the VAV box damper modulates to maintain the active space
temperature setpoint. The VAV box heating or cooling minimum airflow is
based on the heat or cool control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto
changeover setpoint minus 10°F.
Note: When the AHU starts, the discharge air might be hot, but it should
cool as the AHU ramps up.
• Reheat and parallel fans are disabled if the VAV box is in Precool.
10. The VAV box also receives the following value from the VAS (refer to Step 5
above).
• Auxiliary Heating Enabled = Disable (refer to assumption 5 on p. 202).
VAS 11. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of the common space VAV members to Optimal
Start at the VAS priority level.
• controls the operating mode of the VAV air handler members to Optimal
Start at the VAS priority level (there is a time delay(a) in VAS to allow time for
the common space VAV boxes to open).
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat Cool
mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint (located on the Configuration
page of the VAS). If the space temperature is above the setpoint, the SC
sends PreCool. If the space temperature is below the setpoint, the SC sends
Morning Warm-up.
12. The VAS also controls the auxiliary heat at all the VAV boxes, including the
common space VAV boxes, by sending the following value to the VAV object:
• Auxiliary Heating Enabled = Disable (refer to assumption 5 on p. 202).
13. Ventilation functions are disabled.
AHU 14. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
object
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step 11).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 15. The AHU receives the following values from the AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool.
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
16. The AHU begins supplying hot or neutral air(b) based on the active space
temperature it receives from Tracer SC(c) and the VAS Startup Setpoint.
• Active space temperature is below the VAS Startup Setpoint then the AHU
supplies Hot air (if the air handler is running in the constant volume mode,
it will report Max Heat to the VAS. The VAS then controls the Heat/Cool Mode
Request of all the VAV members to Max Heat at the VAS control priority
level.)
• Active space temperature is above the VAS Startup Setpoint then the AHU
supplies Cold or Neutral air
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
(b) There may be a time delay here depending on the AHU type.
(c) There are several choices available for this value. The first choice is probably the VAS average space temperature with the second
choice being the VAS minimum space temperature.
Assumptions
This sequence of operation assumes the following settings are in place:
• Area Heat/Cool mode status = Heating
• Area is part of an HVAC schedule and Optimal window is defined.
• An Optimal window is created in the HVAC schedule.
• The check box for “Allow VAVs to use auxiliary heat at night” is selected on the Tracer SC VAS
configuration page.
Sequence of Operation
The following steps occur in the order shown during Optimal Start mode in a heating with local heat
and a central fan scenario.
Area 2. Area decides how early to enable the system based on the Area setpoint for the
heating mode (Calculated Occupied Heating Setpoint), the space temperature
(Space Temperature Sensor), and the optimal heating start rate (Optimal Start
Heating Rate).
3. At the startup time determined in the previous step, controls the operating
mode of all heating only and heating/cooling VAV members to Optimal Start at
the Area priority level.
VAV object 4. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat
• Morning Warm-up or PreCool is determined by comparing the space
temperature of the Area equipment members to the setpoint sent to the
unit by the Tracer SC Space Temperature Setpoint BAS point. If the space
temperature is above the setpoint, the Tracer SC sends PreCool. If the
space temperature is below the setpoint, the Tracer SC sends Morning
Warm-up.
• The Heat Cool Mode Request is Max Heat if the AHU reports that it is in the
constant volume fan mode.
VAV Box 5. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat (based
on Step 4).
6. If in Max Heat mode, the VAV object opens its damper to the Maximum Heat
Airflow setpoint.
7. If not in Max Heat, the VAV box damper modulates to maintain the active space
temperature setpoint. The VAV box heating or cooling minimum airflow is
based on the heat or cool control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto
changeover setpoint minus 10°F.
Note: When the AHU starts, the discharge air might be hot, but it should cool
as the AHU ramps up.
• Reheat and parallel fans are disabled if the VAV box is in Precool.
8. The VAV box also receives the following value from the VAS (refer to Step 10).
• Auxiliary Heating Enabled = Enable (value is 100)(refer to assumption 4 on
p. 205).
VAS 9. VAS detects that the operating mode of its VAV members and:
• controls the common space VAV members operating mode to Optimal Start
at the VAS priority level.
• controls the operating mode of the VAV air handler members to Optimal
Start at the VAS priority level (there is a time delay(a) in VAS to allow time for
the common space VAV boxes to open).
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat Cool
mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint (located on the Configuration
page of the VAS). If the space temperature is above the setpoint, the SC
sends PreCool. If the space temperature is below the setpoint, the SC sends
Morning Warm-up.
10. The VAS also controls the auxiliary heat at all the VAV boxes, including the
common space VAV boxes, by sending the following value to the VAV object:
• Auxiliary Heating Enabled = Enable (refer to assumption 4 on p. 205).
11. Ventilation functions are disabled.
Note: Refer to “Appendix E: Equipment Response to Operating Modes,” p. 245
AHU object 12. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step 9).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 13. The AHU receives the following values from the AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool.
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
14. The AHU begins supplying hot or neutral air(b) based on the heat/cool mode
request it receives from Tracer SC.
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
(b) There may be a time delay here depending on the AHU type.
Humidity Pull-down
The system goes into this mode when the Area space humidity is higher than the Area occupied
humidity setpoint, it is prior to the occupied start time, and there is an Optimal window defined in
Scheduling and it is within that time window.
Assumptions
This sequence of operation assumes the following settings are in place (beyond the general
assumptions stated at the beginning):
• Area Heat/Cool mode status = Cooling
• Area is part of an HVAC schedule and Humidity Pull-down is enabled (check box is selected)
• An early start limit must be set (greater than 0 minutes) that defines the earliest time that a
Humidity Pull-down event can occur.
• An Optimal window is created in the HVAC schedule.
Sequence of Operation
The following steps occur in the order shown during Humidity Pull-down mode in a cooling only
scenario.
Area 2. Area decides how early to enable the system based on the Area setpoint for the
cooling mode (Occupied Humidity Setpoint), the space humidity (Space
Humidity Sensor), and the humidity pull-down rate (Humidity Pulldown Rate).
3. At the startup time determined in the previous step, controls the operating
mode of all cooling only and heating/cooling VAV members to Humidity Pull-
down at the Area priority level (if they have dehumidification enabled).
4. Ventilation and heating members are Unoccupied or disabled.
Note: Refer to “Appendix E: Equipment Response to Operating Modes,” p. 245
VAV object 5. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (each VAV box Heat
Cool mode request is determined by comparing its space temperature to its
Space Temperature Setpoint BAS value (located on the Configuration page
of the equipment). If the space temperature is above the setpoint, the SC
sends PreCool. If the space temperature is below the setpoint, the SC sends
Morning Warm-up.)
Note: The local space temperature setpoint (thumbwheel) is not used to
determine the Heat Cool Mode Request for optimal start.
VAV box 6. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step 5).
7. The VAV box damper modulates to maintain the active space temperature
setpoint.
8. The VAV box heating or cooling minimum airflow is based on the heat or cool
control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto changeover
setpoint minus 10°F.
Note: When the AHU starts, the discharge air might be hot, but it should
cool as the AHU ramps up.
9. Reheat and parallel fans are disabled if the VAV box is in Precool.
VAS 10. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of the common space VAV members to
Humidity Pull-down at the VAS priority level.
• controls the operating mode of the VAV air handler members to Humidity
Pull-down at the VAS priority level (there is a time delay(a) in VAS to allow
time for the common space VAV boxes to open).
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat Cool
mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint (located on the Configuration
page). If the space temperature is above the setpoint, the SC sends PreCool.
If the space temperature is below the setpoint, the SC sends Morning Warm-
up.
11. Ventilation functions are disabled.
AHU 12. The operating mode controls the following values to the AHU at the VAS
priority level:
object
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step 10).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 13. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool.
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
14. The AHU begins producing cool air(b).
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
(b) There may be a time delay here depending on the AHU type.
Normal Start
The best practice is to use Optimal Start. However, if not using Optimal Start, the Normal Start
works as described here. The ventilation functions in both the VAV box and the air handler are
enabled during a Normal Start, which is the major difference between a Normal Start and an
Optimal Start, where ventilation functions in both the VAV box and the AHU are disabled.
Assumptions
This sequence of operation assumes the following settings are in place:
• There is no Optimal window defined in the HVAC schedule for this Area, or the current time has
reached the start of the schedule.
• The schedule must be an HVAC schedule.
Sequence of Operation.
The following steps occur in the order shown during Normal Start mode.
Area 2. Area controls the operating mode of all VAV members to Occupied at the Area
priority level.
VAV object 3. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
VAV Box 4. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
Note: The VAV box Heat/Cool mode is determined by the priority array, where
the highest level mode (lowest number) is applied when control is
released (e.g., a TGP program may also be controlling the Heat/Cool
mode).
VAS 5. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of the common space VAV members to
Occupied at the VAS priority level.
• controls the operating mode of the VAV air handler members to Occupied at
the VAS priority level (there is a time delay(a) in VAS to allow time for the
common space VAV boxes to open).
Note: Refer to “Appendix E: Equipment Response to Operating Modes,” p. 245
AHU object 6. The AHU receives the following values from the VAV AHU object (at the VAS
priority level):
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Release
AHU 7. The AHU receives the following values from the AHU object (at the VAS priority
level):
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Release
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
Optimal Stop
Optimal stop is a scheduled function, but it is also a temperature-based function of Area. Optimal
stop is the process of efficiently stopping the mechanical heating or cooling in advance of the space
going into an Unoccupied mode. Because this is an Occupied condition, the air handler and fan
continue to run and the outdoor air damper is set to allow minimum outdoor air into the air handler.
Assumptions
This sequence of operation assumes the following settings are in place:
• Area is part of an HVAC schedule and Optimal Stop/Start is enabled (check box is selected)
• An Optimal window is created in the HVAC schedule.
Sequence of Operation
The following steps occur in the order shown during Optimal Stop mode.
Area 2. Area determines the actual time to control the operating mode of VAV
boxes to Optimal Stop based on the space temperature sensor, the
occupied cooling/heating setpoint plus/minus 2°F (1.1°C), and the
associated optimal stop rate.
3. At the time determined in the previous step, Area controls the operating
mode of all VAV members to Optimal Stop at the Area priority level.
4. Ventilation members are enabled.
Note: Refer to “Appendix E: Equipment Response to Operating Modes,”
p. 245
VAV object 5. The operating mode controls the following values to the VAVs at the the
Area priority level:
• Occupancy Request = Standby
• Heat Cool Mode Request = Release
VAV Box 6. The VAV box receives the following values from the VAV object (at the VAS
priority level):
• Occupancy Request = Standby
• Heat Cool Mode Request = Release
7. The VAV box damper modulates to maintain the standby space
temperature setpoint.
8. Ventilation functions are enabled.
VAS 9. VAS detects that the operating mode of its VAV members has changed and:
• controls the operating mode of the common space VAV members to
Optimal Stop at the VAS priority level.
• controls the operating mode of the VAV air handler members to Optimal
Stop at the VAS priority level.
10. Ventilation functions are enabled.
AHU object 11. The AHU object sends the following values to the AHU (at the VAS priority
level):
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Release
AHU 12. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Release
13. The AHU behaves as it does when Occupied.
Unoccupied
Assumptions
This sequence of operation assumes the following settings are in place:
• An HVAC schedule is created, which defines Occupied and Unoccupied times.
Sequence of Operation
The following steps occur in the order shown during Unoccupied mode.
Area 2. Area controls the operating mode of all VAV members to Unoccupied at the
Area priority level.
3. Ventilation functions are disabled.
VAV object 4. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Release
VAV Box 5. The VAV box receives the following values from the VAV object (at the Area
priority level):
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Release
6. It auto-calibrates on the transition from Occupied to Unoccupied.
7. It uses its unoccupied setpoints(a).
8. Ventilation functions are disabled.
9. It disables local heat for all VAVs depending on the VAS settings.
VAS 10. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of the common space VAV members to
Unoccupied at the VAS priority level. (b)
• controls the operating mode of the VAV air handler members to
Unoccupied at the VAS priority level.
11. Ventilation functions are enabled.
12. The VAS also sends the following command to the VAV object.
• Auxiliary Heat Control Request = Enabled (value is 100) (The check box
for “Allow VAVs to use auxiliary heat at night” is selected on the Tracer
SC VAS Configuration page).
AHU object 13. The AHU object sends the following values to the AHU (at the VAS priority
level):
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Off
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0
• Economizer Enable = Disabled
AHU 14. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Off
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Disabled
15. The AHU is Off.
(a) The best practice for this may vary depending on the VAV box/heat type.
(b) Does not occur until the shutdown delay expires.
Assumptions
This sequence of operation assumes the following settings are in place:
• The HVAC schedule is unoccupied
• The VAV box unoccupied cooling setpoint should be set higher than the Area unoccupied
cooling setpoint.
Sequence of Operation
The following steps occur in the order shown during Unoccupied Heating/Cooling mode when
cooling.
1 The industry sometimes refers to this function as the Night Setback mode
©2009 Trane. All Rights Reserved.
216 PROPRIETARY INFORMATION OF TRANE. BAS-APG007-EN, 12/15/2009
MAY ONLY BE USED IN THE CONDUCT OF TRANE BUSINESS.
Troubleshooting
VAV object 6. The operating mode controls the following values to the VAV boxes at the
Area priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up, PreCool, or Max Heat
(the Heat Cool mode request is determined by comparing the space
temperature of each of the Area equipment members to the Space
Temperature Setpoint BAS value sent to the unit by the Tracer SC. If the
space temperature is above the setpoint, the SC sends PreCool. If the
space temperature is below the setpoint, the SC sends Morning Warm-
up.)
• The Heat Cool Mode Request is Max Heat if the AHU reports that it is in
the constant volume fan mode.
VAV Box 7. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step
6).
8. The VAV box damper modulates to maintain the active space temperature
setpoint.
9. The VAV box heating or cooling minimum airflow is based on the heat or
cool control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto
changeover setpoint minus 10°F.
Note: When the AHU starts, the discharge air might be hot, but it should
cool as the AHU ramps up.
10. Reheat and parallel fans are disabled if the VAV box is in PreCool.
VAS 11. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of the common space VAV members to
Unoccupied Heating/Cooling at the VAS priority level.
• controls the operating mode of the VAV air handler members to
Unoccupied Heating/Cooling at the VAS priority level (there is a time
delay(a) in VAS to allow time for the common space VAV boxes to open).
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat
Cool mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint on the Configuration
page of the VAS. If the space temperature is above the setpoint, the SC
sends PreCool. If the space temperature is below the setpoint, the SC
sends Morning Warm-up.
12. Ventilation functions are disabled.
AHU object 13. The operating mode controls the following values to the AHU at the VAS
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step
11).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 14. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool.
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
15. The AHU begins producing cool air(b).
(a)The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler Startup Delay field.
(b)There may be a time delay here depending on the AHU type.
Assumptions
This sequence of operation assumes the following settings are in place:
• Area Heat/Cool mode status = Heating
• Area is part of an HVAC schedule.
• The check box for “Allow VAVs to use auxiliary heat at night” is NOT selected on the Tracer SC
VAS configuration page.
Sequence of Operation
The following steps occur in the order shown during Unoccupied Heating/Cooling mode in a
scenario where the system is heating with central heat and not using local heat.
VAV object 6. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat
– Morning Warm-up or PreCool is determined by comparing the
space temperature of each of the Area equipment members to the
Space Temperature Setpoint BAS of each member sent to the unit
by the Tracer SC. If the space temperature is above the setpoint,
the Tracer SC sends PreCool. If the space temperature is below the
setpoint, the Tracer SC sends Morning Warm-up.
• The Heat Cool Mode Request is Max Heat if the AHU reports that it is in
the constant volume fan mode.
7. The VAS controls the Auxiliary Heat Control point to Disabled (value of 0)
at the VAS priority (refer to Step 12).
VAV Box 8. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat
(based on Step 6).
9. If in Max Heat mode, the VAV object opens its damper to the Maximum
Heat Airflow setpoint.
10. If not in Max Heat, the VAV box damper modulates to maintain the active
space temperature setpoint. The VAV box heating or cooling minimum
airflow is based on the heat or cool control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto
changeover setpoint minus 10°F (5.6°C).
Note: When the AHU starts, the discharge air might be hot, but it
should cool as the AHU ramps up.
• Reheat and parallel fans are disabled if the VAV box is in Precool.
11. The VAV box also receives the following value from the VAS.
• Auxiliary Heating Enabled = Disable (refer to assumption 3 on p. 219).
VAS 12. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of the common space VAV members to
Unoccupied Heating/Cooling at the VAS priority level.
• controls the operating mode of the VAV air handler members to
Unoccupied Heating/Cooling at the VAS priority level (there is a time
delay(a) in VAS to allow time for the common space VAV boxes to open).
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat
Cool mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint (located on the
Configuration page of the VAS). If the space temperature is above the
setpoint, the SC sends PreCool. If the space temperature is below the
setpoint, the SC sends Morning Warm-up).
13. The VAS also controls the auxiliary heat at all the VAV boxes, including the
common space VAV boxes, by sending the following value to the VAV
object:
• Auxiliary Heating Enabled = Disable (refer to assumption 3 on p. 219).
14. Ventilation functions are disabled.
AHU object 15. The AHU object sends the following to the VAV AHU:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (If the VAS
Average Space Temperature is above the VAV AHU Startup
Temperature, the value is PreCool. If the VAS Average Space
Temperature is below or equal to the VAV AHU Startup Temperature, the
value is Morning Warm-up)(based on Step 12).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 16. The AHU receives the following values from the AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (If the VAS
Average Space Temperature is above the VAV AHU Startup
Temperature, the value is PreCool. If the VAS Average Space
Temperature is below or equal to the VAV AHU Startup Temperature, the
value is Morning Warm-up)(based on Step 12).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
17. The AHU begins supplying hot or neutral air(b) based on the active space
temperature it receives from Tracer SC(c) and the VAS Startup Setpoint.
• Active space temperature is below the VAS Startup Setpoint then the air
handler supplies Hot air (if the air handler is running in the constant
volume mode, it will report Max Heat to the VAS. The VAS then controls
the Heat/Cool Mode Request of all the VAV members to Max Heat at the
VAS control priority level.)
• Active space temperature is above the VAS Startup Setpoint then the air
handler supplies Cold or Neutral air
(a)The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler Startup Delay field.
(b)There may be a time delay here depending on the AHU type.
(c)There are several choices available for this value. The first choice is probably the VAS average space temperature with the second choice being the VAS minimum
space temperature.
Assumptions
This sequence of operation assumes the following settings are in place:
• Area Heat/Cool mode status = Heating
• Area is part of an HVAC schedule.
• The check box for “Allow VAVs to use auxiliary heat at night” is selected on the Tracer SC VAS
configuration page.
Sequence of Operation
The following steps occur in the order shown during Unoccupied Heating/Cooling mode in a
heating with local heat and a central fan scenario.
VAV object 6. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat
– Morning Warm-up or PreCool is determined by comparing the
space temperature of each of the Area equipment members to the
Space Temperature Setpoint BAS sent to the unit by the Tracer SC.
If the space temperature is above the setpoint, the Tracer SC sends
PreCool. If the space temperature is below the setpoint, the Tracer
SC sends Morning Warm-up.
• The Heat Cool Mode Request is Max Heat if the AHU reports that it is in
the constant volume fan mode.
VAV Box 7. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat
(based on Step 6).
8. If in Max Heat mode, the VAV box opens its damper to the Maximum Heat
Airflow setpoint.
9. If not in Max Heat, the VAV box damper modulates to maintain the active
space temperature setpoint. The VAV box heating or cooling minimum
airflow is based on the heat or cool control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto
changeover setpoint minus 10°F.
Note: When the AHU starts, the discharge air might be hot, but it
should cool as the AHU ramps up.
• Reheat and parallel fans are disabled if the VAV box is in Precool.
10. The VAV box also receives the following value from the VAS (refer to Step
11).
• Auxiliary Heating Enabled = Enable (refer to assumption 3 on p. 223).
VAS 11. VAS detects that the operating mode of its VAV members and:
• Controls the operating mode of the common space VAV members to
Unoccupied Heating/Cooling at the VAS priority level.
• VAS sends the following to all of its VAV members: Auxiliary Heating
Enabled = Enable (refer to assumption 3 on p. 223).
• Controls the operating mode of the VAV air handler members to
Unoccupied Heating/Cooling at the VAS priority level (there is a time
delay(a) in VAS to allow time for the common space VAV boxes to open).
• The VAS also controls the AHU Heat Cool Mode Request to Morning
Warm-up or PreCool (the Heat Cool mode request is determined by
comparing the VAS average space temperature to the VAV AHU Startup
Setpoint (located on the Configuration page of the VAS). If the space
temperature is above the setpoint, the Tracer SC sends PreCool. If the
space temperature is below the setpoint, the Tracer SC sends Morning
Warm-up.
12. Ventilation functions are disabled.
Note: Refer to “Appendix E: Equipment Response to Operating Modes,”
p. 245
AHU object 13. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on
Step 11).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 14. The AHU receives the following values from the AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on
Step 11).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
15. The AHU begins supplying air to the space.
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
Assumptions
This sequence of operation assumes the following settings are in place:
• The check box for “Allow VAVs to use auxiliary heat at night” is selected on the Tracer SC VAS
configuration page.
• The VAV box unoccupied heating setpoint is above the Area unoccupied heating setpoint.
Sequence of Operation
The following steps occur in the order shown during Unoccupied Heating/Cooling mode when
heating with local heat and there is no central fan for night heat.
VAV object 5. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Off
VAV Box 6. The VAV box receives the following values from the VAV object:
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Off.
7. The VAV box also receives the following value from the VAS (refer to Step 13 ).
• Auxiliary Heating Enabled = Enabled (refer to assumption 1 on p. 226).
8. The VAV box uses its unoccupied setpoints (specifically, its unoccupied heating
setpoint).
9. Ventilation functions are disabled.
10. Local heat is enabled.
11. The VAV box runs its local fan for heating.
12. The VAV box enables remote heat (perimeter heat).
VAS 13. VAS detects that the operating mode of its VAV members remains Unoccupied
and:
• controls the operating mode of the common space VAV members to
Unoccupied at the VAS priority level.
• controls the operating mode of the VAV air handler members to Unoccupied
at the VAS priority level.
• AHU Heat Cool Mode Request = Off
14. The VAS also controls the auxiliary heat at all the VAV boxes, including the
common space VAV boxes, by sending the following value to the VAV object:
• Auxiliary Heating Enabled = Enable (refer to assumption 1 on p. 226).
15. Ventilation functions are disabled.
16. The VAV box uses its local heat.
AHU object 17. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Off.
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Disabled
AHU 18. The AHU receives the following values from the AHU object:
• Occupancy Request = Unoccupied
• Heat Cool Mode Request = Off.
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Disabled
Night Purge
Typical scenarios:
• This scenario works best and is used most in drier climates (e.g., Los Angeles, Phoenix, etc.).
Assumptions
This sequence of operation assumes the following settings are in place:
• The VAV objects added as members to the Area are identified as Night Purge members.
• Area operating mode is Unoccupied
• Area must be in the cooling mode.
• Night Purge must be enabled in the Area function page.
• The Night Purge economizing decision must be true on the Area function page.
• The space temperature must be warmer than the outdoor air temperature by the Outdoor/
space Temperature Differential defined on the Area function page.
• The current time must fall within the time frame defined for Night Purge on the Area function
page.
Sequence of Operation
The following steps occur in the order shown during Night Purge mode.
Area 2. When the Area operating mode transitions from Unoccupied to Night
Purge (based on the conditions described above in Assumptions), it
controls the operating mode of all VAV members to Night Purge at the Area
priority level.
3. Ventilation and heating members are Unoccupied or disabled.
VAV object 4. The operating mode controls the following values to the VAV boxes at the
Area priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Night Purge
VAV Box 5. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Night Purge
6. The VAV box damper opens when the AHU goes into constant volume
mode.
7. Reheat and parallel fans are disabled if the VAV box is in PreCool.
VAS 8. VAS detects the operating mode of its VAV members are in Night Purge
mode and controls the following at the VAS priority level:
a. AHU object operating mode to Night Purge.
b. Common space VAV boxes to Night Purge.
AHU object 9. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Night Purge
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Enabled
AHU 10. The AHU receives the following values from the AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Night Purge
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Enabled
Unoccupied Humidify
This is not a recommended application for VAV air systems.
Unoccupied Dehumidify
Typical scenarios: This scenario works best and is used most in hot and humid climates (e.g.,
Miami, Houston, etc.).
Assumptions
This sequence of operation assumes the following settings are in place:
• The VAV objects added as members to the Area are identified as Dehumidifying members (not
limited to VAV objects, but can also include binary output objects.)
• Area operating mode is Unoccupied
• Unoccupied Dehumidification must be enabled in the Area function page.
• The Area space humidity must be above the Enable Dehumidification setpoint.
Sequence of Operation
The following steps occur in the order shown during Unoccupied Dehumidify mode
VAV object 6. The operating mode controls the following values to the VAV boxes at the
Area priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool or Max Heat
– Morning Warm-up or PreCool is determined by comparing the
space temperature of each of the Area equipment members to the
Space Temperature Setpoint BAS sent to the unit by the Tracer SC.
If the space temperature is above the setpoint, the Tracer SC sends
PreCool. If the space temperature is below the setpoint, the Tracer
SC sends Morning Warm-up.
• The Heat Cool Mode Request is Max Heat if the AHU reports that it is in
the constant volume fan mode.
VAV Box 7. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on
Step 6).
8. The VAV box damper modulates to maintain the active space temperature
setpoint.
9. The VAV box heating or cooling minimum airflow is based on the heat or
cool control action of the VAV box.
• Heating control action: If the source temperature is above the auto
changeover setpoint.
• Cooling control action: If the source temperature is below the auto
changeover setpoint minus 10°F (5.6°C).
Note: When the AHU starts, the discharge air might be hot, but it
should cool as the AHU ramps up.
10. Reheat and parallel fans are disabled if the VAV box is in PreCool.
VAS 11. VAS detects that the operating mode of its VAV members and:
• controls the common space VAV members operating mode to
Unoccupied Dehumidify at the VAS priority level.
• controls the operating mode of the VAV air handler members to
Unoccupied Dehumidify at the VAS priority level (there is a time delay(a)
in VAS to allow time for the common space VAV boxes to open).
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat
Cool mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint (located on the
Configuration page of the VAS). If the space temperature is above the
setpoint, the SC sends PreCool. If the space temperature is below the
setpoint, the SC sends Morning Warm-up.
12. Ventilation functions are disabled.
AHU object 13. The operating mode controls the following values to the AHU at the VAS
priority level:
• Occupancy Request = Occupied
• AHU Heat Cool Mode Request = Morning Warm-up or PreCool (the Heat
Cool mode request is determined by comparing the VAS average space
temperature to the VAV AHU Startup Setpoint. If the space temperature
is above the setpoint, the SC sends PreCool. If the space temperature is
below the setpoint, the SC sends Morning Warm-up (based on Step 11).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
AHU 14. The AHU receives the following values from the VAV AHU object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Morning Warm-up or PreCool (based on Step
13).
• Minimum OA Damper Position = 0%
• Outdoor Air Flow Setpoint = 0 (cfm or L/s)
• Economizer Enable = Release
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
Timed Override
Assumptions
This sequence of operation assumes the following settings are in place:
• The VAV boxes, with Timed Override capability, added as members of the Area and the override
check box is selected. This can be done using the Area creation wizard, or from the Member
Configuration screen (shown below).
• Timed override is enabled on the Area Configuration page (Operations section) and its duration
is defined.
Sequence of Operation
The following steps occur in the order shown during Timed Override mode.
VAV Box 2. The On button on the zone sensor is pushed and held (for 5 seconds) by
the tenant to initiate a timed override for the space.
Area 3. The Area monitors all of the members, designated as override, for a Timed
Override request from a zone sensor. When an override is detected the
following happens:
• The Area operating mode changes to Occupied
• The Area Occupancy Request is overridden to Bypass (at the Area
priority level)
• Area controls the operating mode of all of its members to Occupied
VAV object 4. The operating mode controls the following values to the VAVs at the Area
priority level:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release (at the Area priority level)
VAV Box 5. The VAV box receives the following values from the VAV object:
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release (at the Area priority level)
Note: The VAV box Heat/Cool mode is determined by the priority array,
where the highest level mode (lowest number) is applied when
control is released.
VAS 6. VAS detects that the operating mode of its VAV members and:
• controls the operating mode of the common space VAV members to
Occupied at the VAS priority level
• controls the operating mode of the VAV air handler members to
Occupied at the VAS priority level (there is a time delay(a) in VAS to allow
time for the common space VAV boxes to open)
Note: Refer to “Appendix E: Equipment Response to Operating Modes,”
p. 245
AHU object 7. The AHU receives the following values from the VAV AHU object (at the
VAS priority level):
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Release
AHU 8. The AHU receives the following values from the AHU object (at the VAS
priority level):
• Occupancy Request = Occupied
• Heat Cool Mode Request = Release
• Minimum OA Damper Position = Release
• Outdoor Air Flow Setpoint = Release
• Economizer Enable = Release
(a) The length of this delay is adjustable. This is located on the Systems > VAS > Configuration page. Set the time in the Air Handler
Startup Delay field.
Communications Loss
Typical scenarios:
• The SC is powered down for service (code update) and loses communications to the AHU,
VAVs, and Unit Controllers.
Assumptions
This sequence of operation assumes the following:
• The send/receive heartbeat settings are not altered.
• There is no space temperature sensor on the AHU
• There are discharge air sensors on the VAV boxes.
Sequence of Operation
The following steps occur in the order shown during Communication Loss mode.
All Controllers 1. Each unit controller uses its last communicated value from the Tracer SC
for 15 minutes (the receive heartbeat timer setting).
After 15 minutes
VAV Box 2. VAV boxes with LonTalk controllers revert to their local inputs and
setpoints.
3. For VAV boxes with BACnet controllers, their occupancy reverts to
Occupied and all communicated sensor values enter a fault state and the
controller reverts to local sensor values. All setpoints within the controller
remain in their last communicated state.
Note: If there is no hardwired zone sensor or no locally bound zone sensor
available, the VAV box generates a space temperature fail
diagnostic and puts the air valve at the cooling minimum airflow
setting. All heat will be off. A series fan will be on. A parallel fan will
be off.
AHU 4. AHUs with LonTalk controllers revert to their local inputs and setpoints.
5. For AHUs with BACnet controllers, their occupancy reverts to Occupied
and all communicated sensor values enter a fault state and the controller
reverts to local sensor values. All setpoints within the controller remain in
their last communicated state.
Best Practices for Determining the VV550/551 and UC400 Flow Settings
The numbers below correlate to the numbers shown in Figure 149. They provide general
guidelines for determining the values to use on the worksheet. The VV550/551 name is first and the
UC400 name is second.
1. Nominal Flow/Air Flow Nominal Status: This value is based on the size of the box. If using
Trane VAV boxes, select VariTrane™ F in Rover and the recommended nominal flow for the size
of the box should show up. For non-Trane boxes, measure the size of the box and select a
VariTrane F box of similar size to get the nominal flow value.
2. Minimum Airflow/Air Flow Setpoint Minimum: This value can be set to zero, or to greater
than 10% of the value used for nominal flow. It should be available from the job specs created
by the Consulting Engineer.
3. Maximum Airflow/Air Flow Setpoint Maximum: This value should be available from the
job specs created by the Consulting Engineer.
4. Standby Minimum Airflow/Air Flow Setpoint Minimum Standby: If this value is not
specified on the job specs, use the same value as the minimum airflow.
5. Heating Standby Minimum Airflow/Air Flow Setpoint Maximum Standby Heat: If this
value is not specified on the job specs, use the same value as the minimum airflow.
6. Heating Minimum Airflow/Air Flow Setpoint Minimum Heat: If this value is not specified
on the job specs, use the same value as the minimum airflow.
7. Heating Maximum Airflow/Air Flow Setpoint Maximum Heat: If this value is not
specified on the job specs, use the same value as the maximum airflow.
8. Local Heat Minimum Airflow/Air Flow Setpoint Minimum Local Heat: This value is
usually larger than the minimum airflow setting and is dependent on the reheat configuration
of the VAV box. Refer to the documentation supplied with the box to determine the minimum
airflow for the reheat option installed.
Table 18. Controller flow settings worksheet (bold indicates UC400 values)
Location Label
*From Specs
**If using Rover, these values are available in the Ventilation Setup group on the Setup tab.
Tracer SC MP580/581
SC Name SC Point SC Equipment Type LonTalk Network Variable Profile NV
Type Name Index
Occupancy Request Multistate Constant Volume Air Handler nviOccSchedule SCC 304
Output
Heat/Cool Request Multistate Constant Volume Air Handler nviApplicMode SCC 307
Output
Emergency Override Multistate Constant Volume Air Handler nviEmergOverride SCC 310
Output
Occupancy Request Multistate Variable Volume Air Handler nviOccSchedule DAC 315
Output
Heat/Cool Request Multistate Variable Volume Air Handler nviApplicMode DAC 317
Output
Emergency Override Multistate Variable Volume Air Handler nviEmergOverride DAC 318
Output
Occupancy Request Multistate Programmable Controller nviOccSchedule MP580 330
Output
VAS
Table 20 details the occupancy request only of VAS members for a given operating mode. The
operating mode of the air handler and common space VAV boxes will always follow the operating
mode of the VAS.
VAS Binary
VAS Equipment Members Members
Common Space
VAS Operating Mode Air Handler VAV Boxes Ventilation Ventilation
Occupied Occupied Occupied Occupied On
Unoccupied Unoccupied Unoccupied Unoccupied Off
Unoccupied Heating/
Occupied Occupied Unoccupied Off
Cooling
Night Purge Occupied Occupied Unoccupied Off
Optimal Start Occupied Occupied Unoccupied Off
Optimal Stop Occupied(a) Standby Occupied On
Unoccupied Humidify Occupied Occupied Unoccupied Off
Unoccupied Dehumidify Occupied Occupied Unoccupied Off
Humidity Pull Down Occupied Occupied Unoccupied Off
(a) VAV air handlers do not support the Standby mode for Occupancy.
Table 21. Area and VAS arbitration rank for operating modes.
Rank Operating Mode How Area Determines Operating Mode
1 Occupied All equipment will be occupied if the conditions for optimal stop are not true.
The Area can only enter the Optimal Stop mode under the following conditions:
• The Area is Occupied
2 Optimal Stop • The optimal window is active
• The Area determines there is sufficient capacity in the building to maintain
the space temperature within two degrees of the Occupied setpoints.
The area can only enter optimal start if the area is unoccupied, the optimal
3 Optimal Start
window is active and the optimal start early limit has been reached.
The area can only enter humidity pull down if the area is unoccupied, the
4 Humidity Pull Down optimal window is active and the humidity pull down early limit has been
reached. (only members checked as dehumidification members will respond)
The area can only enter night heat cool if the are is unoccupied, night heat cool
5 Unoccupied Heating/Cooling is enabled and the space temperature is above the unoccupied cooling setpoint
or below the unoccupied heating setpoint.
Night Dehumidify can occur if the dehumidify function is enabled, the area
6 Unoccupied Dehumidify space humidify rises above the unoccupied humidity setpoint. (only members
checked as dehumidification members will respond)
Night Humidity can occur if the humidify function is enabled, the area space
7 Unoccupied Humidify humidity falls below the unoccupied humidity setpoint. (only members checked
as humidification members will respond)
Night Purge can occur if:
• The Area must be unoccupied
• The Night Purge function must be enabled.
• The Night Purge/Economizing decision must be true.
8 Night Purge
• The space/outdoor air temperature differential must be satisfied.
• The space temperature must be at least one degree above the occupied
cooling setpoint.
• Only members checked as night purge members will respond.
9 Unoccupied All equipment will be unoccupied if none of the modes defined above are true.
(c) Heat Cool Mode Request Calculations are calculated by the VAS based on the following:
• Heating Cooling Mode Request is Morning Warm-up if the VAS Average Space Temperature is below the VAV AHU Startup Setpoint or
if either value is invalid.
• Heating Cooling Mode Request is PreCool if the VAS Average Space Temperature is above or equal to the VAV AHU Startup Setpoint
(d) Occupancy Request is controlled to Occupied as VAV air handlers do not support the Standby mode.
3 Miscellaneous ---
4 Miscellaneous ---
7 Miscellaneous ---
16 Miscellaneous ---
• VAV heat
CSC Any heat • Reports Morning Warm-up
• No ventilation
• VAV heat
AH540/541 Hydronic heat • Reports Morning Warm-up
• No ventilation
• VAV heat
AH540/541 Electric heat • Reports Morning Warm-up
• No ventilation
Note: Not all IntelliPak I air handlers report Max Heat during Optimal Start heating mode. To
ensure that the VAV box air valves are driven to max cfm setpoint, an additional TGP2
program is necessary. Refer to Figure 150, p. 248.
Air Valve Position Control Status false (0) = pressure independent control
true (1) = position control/pressure dependent
EngyWheelPreheatStatus 1 = Inactive
2 = Active
1 = Disabled
2 = Differential
Enthalpy Mode 3 = Fixed
4 = Differential Dry Bulb
5 = Fixed Dry Bulb
FinalFilterStatus 1 = Clean
2 = Dirty
3 = Not Present
IsoVlvStatus1 1 = Closed
2 = Open
3 = Not Present
IsoVlvStatus2 1 = Closed
2 = Open
3 = Not Present
Technical terms
Acronyms are listed according to the most common way to refer to them. In some cases, the
acronyms are the main entry, and in other cases, the full phrase is the main entry.
A
active mode. See Rover operating modes.
AH540/541 air-handler controller. See Tracer AH540/541 air-handler controller.
AIP. See analog input point.
air and water balance. A task usually performed by contractors to measure, calibrate, and
modulate the air and water flow through the system. Trane uses the Air and Water Balancing tool,
which is part of the Rover suite of software tools.
air valve. Sometimes also referred to as an air damper.
alarm. An audible or visual signal from a building automation system or controller that warns of
an abnormal, critical operating condition.
analog. Pertaining to a device or signal that constantly varies in strength or quantity. For example,
temperature, humidity, and flow rate have analog values.
analog input. A varying voltage, current, or resistive signal that can be converted to units of
temperature, pressure, humidity, and so on.
analog input point (AIP). 1. A location on a controller where the wiring for an analog input is
terminated.
analog output. A varying voltage or current signal used to change the position of an external
device, such as a valve damper, or temperature setpoint.
analog output point (AOP). 1. A location on a controller where the wiring for an analog output
is terminated.
AOP. See analog output point.
ASHRAE. American Society of Heating, Refrigerating, and Air-Conditioning Engineers.
An international organization that advances the science of heating, ventilation, air-conditioning,
and refrigeration (HVAC). It conducts research, writes standards, and promotes continuing
education in the HVAC industry.
auto-commissioning. The Tracer VV550/551 controller includes a special operating sequence
designed to validate the proper operation of all outputs and the ability to measure all inputs. The
purpose of this auto-commissioning sequence is to minimize the labor required to commission the
unit in the field.
B
BACnet Protocol. BACnet is a Data Communications Protocol for Building Automation and
Control Networks. It is an ASHRAE, ANSI, and ISO standard protocol.
BACnet attempts to encompass the full range of control devices by modeling them as objects, each
of which may have an assortment of properties. For example, a temperature sensor may be
considered an object of type Analog Input. Such an object will have many properties, such as
Present Value, Units, Resolution, and Status.
BAS. Building automation system. A combination of controllers and software products that
communicate with and control mechanical systems to manage buildings. The managed systems
can include HVAC systems, lighting systems, access control, and other systems. Also called
building management system (BMS).
binary. 1. A number system with only two digits, 0 and 1, in which each symbol represents a
decimal power of two. 2. Any system that has only two possible states or levels, such as a switch
that is either on or off. (On is 1 and off is 0.) 3. Represented in a computer circuit by the presence
of voltage (1) or absence of voltage (0).
binary input. A two-position signal indicating on/off status. Examples include flow switches,
limit switches, and other contacts.
binary input point (BIP). 1. A location on a controller where the wiring for a binary input is
terminated.
binary output. An on/off control from a microprocessor. Examples include controls to fans,
pumps, dampers, and other controlled outputs.
binary output point (BOP). 1. A location on a controller where the wiring for a binary output is
terminated.
binding. On LonTalk communication links, bindings allow two or more devices to share common
information, such as the same setpoint or zone temperature sensor. Bindings link a network
variable in one device with a network variable in another device. See also network variable.
BIP. See binary input point.
C
calibration. The process of standardizing a measuring instrument by determining the deviation
from a known value to find the proper correction factor. The Rover service tool can be used to
calibrate the space temperature and hard-wired setpoint from a zone sensor.
Climate Changer air handler. Trane’s brand of air handling units. Climate Changer air handlers
control the airflow and air temperature for an applied air handling system. Trane’s Modular Climate
Changer allows every air handler to be custom tailored to the specific requirements of a job.
Modular Climate Changers are currently available in sizes ranging from 3,000 to 100,000 cfm.
comm link. See communications link.
commissioning. The process of starting up and verifying correct operation of a building
automation system or device.
common space VAV. Common space VAVs are unique to the Tracer SC VAS. They are VAV boxes
that are not assigned to a specific Area and are controlled by the VAS application. They allow the
air handler to supply air to individual spaces without having to provide supply air to all spaces.
Common space VAVs do this by creating an outlet for excess airflow when the air handler is
operating at minimum flow settings, which would still provide too much airflow for the space
making the request.
communications link. The connection between devices that allows data transfer. Trane
communications links typically use twisted-pair wire.
constant-volume system. An air distribution system that supplies a constant volume of air
while varying temperature to maintain comfort.
control loop. The process that manages HVAC equipment. Control loops measure data using
sensors, and process the data at a controller to determine a control response, which results in an
action at the controlled equipment. See also DDC, PID loop.
controller. A microelectronic device that manages the operation of HVAC equipment. Controllers
that manage only one piece of equipment are called unit controllers or unit control modules
(UCMs). See also Tracer controllers.
D
DAC profile. Discharge Air Controller profile. A LonMark® functional profile for HVAC controllers
that provide variable airflow, such as air handlers and VAV rooftop units. The controlled element
is the discharge-air temperature rather than the space temperature. Compare SCC profile.
daisy-chain configuration. A wiring configuration used for LonTalk communications. All
devices are wired as shown below. Refer to “Installation,” p. 26 for more information on LonTalk
communication wiring.
SC
UC UC UC
Daytime Warm-up. Daytime Warm-up occurs during occupied periods. When the air handler’s
space temperature is colder than its “Daytime Warm-up Setpoint”, the air handler supplies hot air
to the system.
DDC. Direct digital control. A microprocessor-based control methodology that relies on software
to perform control logic. DDC is more flexible, easier to integrate with other systems, and more
effective than other control methodologies, such as pneumatic control. At Trane, DDC is often used
as synonym for PID control. Compare PID control.
DDC/VAV. A variable-air-volume (VAV) system that uses a controller on each VAV box to provide
temperature control and to interface with a building automation system.
demand controlled ventilation. A method of maintaining indoor air quality through intelligent
ventilation based on occupancy. The quantity of ventilation is controlled based on indoor CO2
levels, which correlate to occupancy levels. Demand controlled ventilation saves money by
reducing ventilation during periods of low occupancy.
depressurize. A control request sent to UCMs during smoke control. Used to coordinate supply
air and exhaust air to create a negative pressure in a space.
direct digital control (DDC). See DDC.
Discharge Air Controller (DAC) profile. See DAC profile.
E
economizer control. Opening an outdoor-air damper to cool a building with outdoor air, usually
when the outdoor air temperature is 40°F to 65°F (5°C to 18°C).
exhaust fan. A fan that removes excess air from a building to prevent over-pressurization and to
discharge unwanted air.
F
factory commissioning. The process of connecting and testing controllers in a factory.
Controllers are connected to the equipment and operated to verify their operating functionality in
detail. This reduces installation costs and helps ensure efficient, quiet, and accurate operation from
the first day through the life of the system. Factory mounting provides additional points not
available in field installations.
flow tracking. Flow tracking is a special application for controlling pressurization in a space. Flow
tracking uses two VAV boxes, one at the supply air inlet and one at the exhaust air outlet, set to
different cfm flow settings in order to maintain either a negative or positive airflow in the space.
G
graphical programming. A method of programming based on the assembly of graphically-
represented logical blocks. See also TGP.
graphical programming block. See TGP block.
H
heating, ventilation, and air-conditioning (HVAC). See HVAC.
human interface. See user interface.
HVAC. Heating, ventilation, and air-conditioning. Mechanical equipment, such as air handlers and
VAV boxes, that provides environmental comfort to building occupants.
I
IntelliPak rooftop unit (IPAK). A heating and cooling rooftop unit. The IntelliPak rooftop unit
can be configured to meet the requirements of most unitary system jobs and is currently available
in 20–130 ton sizes.
Internet Protocol (IP). See IP.
IP. Internet Protocol. The protocol within TCP/IP that governs the transmission of messages. It has
been adopted by ASHRAE as a means to communicate BACnet over a network. It allows BACnet
to pass through IP devices, such as IP system routers and over the Internet.
IP address. The 32-bit address defined by the Internet Protocol. The IP address is the unique
numerical code that is used by each device on a network. It is usually represented in dotted decimal
notation (for example, 159.112.138.173). Each of the four values can range from 0 through 255.
L
LCD. Liquid crystal display. A display screen used on some Trane products.
LCI. See Tracer LCI.
Level 4 wire. Used to specify a particular performance of communication wire (normally
associated with LonTalk). Trane recommends Level 4 wire for use with LonTalk installations.
liquid crystal display (LCD). See LCD.
LonMark® functional profiles. LonMark® standards that define standard network variable
types (SNVTs), standard configuration parameter types (SCPTs), and default and power-up
behaviors for compliant HVAC controllers. Many of the latest Tracer controllers use LonMark®
profiles, including the Space Comfort Controller (SCC) profile and the Discharge Air Controller
(DAC) profile. Compliance with LonMark® profiles is a part of Trane’s commitment to systems
integration. See also DAC profile, SCC profile, SCPT, SNVT.
LonMark® Interoperability Association. An association of organizations and individuals who
are committed to the development, manufacture, and use of interoperable LonWorks products and
networks. Products that conform to LonMark® guidelines can display the LonMark® logo.
LonTalk protocol. An interoperable protocol developed by the Echelon Corporation and named
as a standard by the Electronics Industries Alliance (EIA-709.1). It is packaged on a Neuron chip.
low-voltage. Common term for National Electrical Code Article 725 Class 2 wiring. Generally 24
Vac, 100 Vac, or less.
M
mode. See Rover operating modes.
morning warm-up. This functions the same as Daytime Warm-up, except it occurs during a
transition from Unoccupied to Occupied or Optimal Start.
N
network variable. An input or output data item from a controller. Network variables enable a
controller to exchange data with other devices on the network. Network variables are defined by
standard network variable types (SNVTs). See also SNVT.
Neuron ID. A unique identifying number assigned to each LonWorks controller. Neuron IDs
eliminate the need to set addresses with DIP switches.
Night Purge. Exchanging cool, dry outdoor air with warm inside air in preparation for an
Occupied condition.
night setback. Refer to Unoccupied Heating/Cooling.
noise. Electrical interference that creates abnormal characteristics and behaviors on an electrical
signal.
O
Optimal Start. The process of efficiently starting HVAC equipment so that the occupied setpoints
are achieved at the appropriate time. The equipment uses recirculated air to PreCool or pre-heat
a space as quickly as possible before it is Occupied. For example, the Tracer Summit system may
be programmed for Occupied temperature at 6:00 AM. With Optimal Start, the system may start at
5:15 AM to reach the setpoint by 6:00 AM.
Optimal Stop. Optimal stop is a scheduled event, but it is also a temperature-based function of
Area Control. Optimal stop is the process of efficiently stopping the mechanical heating or cooling
in advance of the space going into an Unoccupied mode. Because this is an occupied condition,
the air handler and fan continue to run and the outdoor air damper is set to allow minimum outdoor
air into the air handler.
output. See analog output, binary output.
P
passive mode. See Rover operating modes.
pressurize. A control request sent to UCMs during smoke control. Used to coordinate supply air
and exhaust air to create a positive pressure in a space.
profile. See LonMark® functional profile.
purge. In the HVAC industry, the act of bringing in outdoor air to cool a building. Purging during
Unoccupied hours allows the mechanical cooling equipment to operate less during Occupied
hours.
R
referencer. In Tracer SC software, allows the value of one property to be set equal to the value of
another property.
repeater. An electronic device used to regenerate, at full strength, signals that have weakened.
It is used with digital signals and ignores invalid voltages, such as noise.
resistor. An electronic circuit component which offers resistance to the flow of electric current for
the purpose of operation, protection, or control. The resistance is measured in ohms.
RJ-11 connector. A connector that attaches computers to LANs. It looks like a telephone
connector, but is larger.
rooftop unit (RTU). Roof-mounted packaged cooling and heating unit. Trane offers Voyager,
Precedent, and IntelliPak rooftops units in a range of sizes.
room sensor. See zone sensor.
Rover operating modes. The Rover LonTalk service tool can operate in one of three modes. In
the passive mode, Rover cannot manage networks. This is the safest (and default) mode of
operation. In this mode, Rover can configure controllers, but cannot create bindings or perform
flash downloads. On third-party networks, only the passive mode should be used. In the server-
connected mode, Rover can work on networks where another server, such as a SC or Tracker
controller, is on the link. In this mode, Rover can create bindings and perform flash downloads. In
the active mode, Rover can configure controllers on a Trane peer-to-peer network (a network
without a server). In this mode, Rover can create bindings, perform flash downloads, and clean up
communications links.
Rover LonTalk service tool . A software application for monitoring, configuring, and testing
Tracer controllers on LonTalk links. Rover is compatible with the EIA/CEA-860 standard for software
plug-ins for LonTalk devices. See also EIA/CEA-860 standard, plug-in.
S
SCC profile. Space Comfort Controller profile. A LonMark® functional profile for HVAC terminal
devices, such as WSHP, unit vents, blower coils, VAV boxes, and fan coils. SCC controllers control
to a space temperature setpoint. Many Tracer controllers use the SCC profile to support systems
integration. See also functional profile. Compare DAC profile.
schedules . Times assigned for defined actions to occur for components of the building
automation system. These include on/off commands.
sensor. A device used to read or monitor a physical property, such as temperature, pressure, or
humidity, for use by a controller or building automation system. See also zone sensor.
server-connected mode. See Rover operating modes.
service pin. A button on a Tracer controller that allows the installer to locate and identify it on the
network based on its Neuron ID. When pressed, the service pin sends its Neuron ID to Rover. See
also Neuron ID.
setpoint. A desired outcome, such as a room temperature, to be achieved and maintained by an
HVAC system. Setpoints can be communicated from a building automation system or set at a zone
sensor or touch screen.
smoke control. There are several forms of smoke control ranging from a simple shutdown in
response to a fire alarm up to zoned smoke control in a high-rise building. Smoke control is used
to keep smoke out of populated areas of a building and ventilate it to the outdoor.
SNVT. Standard network variable type. A definition of data objects in the LonTalk protocol. SNVTs
are organized into LonMark® functional profiles for specific applications. The acronym is
pronounced snivit.
Space Comfort Controller (SCC) profile. See SCC profile.
standard network variable type (SNVT). See SNVT.
start-up temperature . The start-up temperature is used during a transition from Unoccupied to
either Optimal Start or Unoccupied Heating/Cooling. It is used by the AHU when not referencing
the heat/cool input property. The AHU compares the space temperature to the start-up temperature
defined in the DAC editor. If the space temperature is below the start-up temperature, the system
will start heating. If the space temperature is above the start-up temperature, the system will start
cooling.
supply fan. A fan that moves air through an HVAC system to provide hot or cold air to an area.
T
terminal unit. HVAC equipment that provides comfort directly to a space. For example, fan coils
and unit ventilators. Air-handlers are not normally terminal units, but the VAV boxes that provide
conditioned air to a space are.
TGP. Tracer graphical programming. A programming language for HVAC applications that are
controlled by Tracer MP580/581 programmable controllers. TGP programs consist of logical blocks
assembled into a picture that describes the sequence of operation.
TGP2 block. A programming unit, such as OR and ON, used to assemble TGP2
programs. Examples include input and output blocks, constant blocks, function
blocks, logic blocks, and variable blocks.
Tracer AH540/541 air-handler controllers. Controllers that support air-
handling product configurations with analog modulating valves, economizer
dampers, and face and bypass dampers. Tracer AH540/541 controllers also support
constant-volume or variable-air volume supply fans. The Tracer AH540 is factory-mounted and the
Tracer AH541 is field-installed.
Tracer graphical programming. See TGP.
Tracer LCI. Tracer LonTalk communication interface. A device that allows a certain type of
controller to communicate using LonTalk. There are four LCIs. The Tracer LCI-V is for Voyager
rooftop controllers. The Tracer LCI-R is for ReliaTel controllers on Precedent rooftop units. The
Tracer LCI-I is for IntelliPak controllers. The Tracer LCI-C is for chiller controllers.
Tracer MP580/581 programmable controller. Programmable LonTalk controllers for a variety
of HVAC applications. The Tracer MP580/581 may be factory-mounted on Trane Modular and T-
Series Climate Changer air handlers. The Tracer MP581 is available for field installation. Tracer
MP580/581 controllers use the Tracer graphical programming (TGP) language. See also TGP.
U
UCM. Unit control module. A Trane term for a microelectronic circuit board that is used to control
HVAC equipment and link to an Integrated Comfort system.
unit control module (UCM). See UCM.
unit controller. A control device residing on a single piece of equipment. Unit controllers can be
attached to a system-level controller, such as a SC. Trane advocates use of the LonTalk protocol at
the unit level. Also called unit control module (UCM).
user interface (UI). A means for a user to interact with a computer. For example, a touch screen
or the part of a software program with which the user interacts.
V
variable air volume (VAV). See VAV.
VariTrane air terminal devices. Trane’s pressure-independent VAV terminal units. The
VariTrane product line is comprised of single-duct (cooling), dual-duct (cooling and heating), or fan-
©2009 Trane. All Rights Reserved.
BAS-APG007-EN, 12/15/2009 PROPRIETARY INFORMATION OF TRANE. 265
MAY ONLY BE USED IN THE CONDUCT OF TRANE BUSINESS.
Glossary
powered (parallel or series) units. Units may have electric or hydronic reheat. The VariTrane
product line offers an optional DDC/VAV UCM for greater control, accuracy, and integration into the
Trane Integrated Comfort system.
VAV. Variable air volume. An air distribution system that varies the volume of air supplied to a
space to maintain acceptable comfort conditions.
VFC box. Dedicated ventilation systems use single-duct VAV boxes for ventilation flow control
(called VFC boxes). These boxes are configured with either electric reheat or no reheat (shutoff
boxes).
Voyager rooftop air conditioner. Trane’s light commercial unitary rooftop air conditioner that
is available in sizes ranging from 3–50 tons of nominal cooling capacity. The Voyager rooftop comes
standard with microelectronic DDC unit controller that makes the unit an integral part of the Trane
Integrated Comfort system.
W
wink. In Rover Comm5 service tool, a procedure that matches a controller shown in the Rover
main window with the actual controller. When the wink command is initiated in Rover, the LED on
the controller winks for approximately 10 seconds.
XYZ
zone. The smallest area of control in an HVAC system. A zone is characterized by having a single
thermostat or zone temperature sensor. A room served by a single VAV box is a zone. Several
rooms served by the same VAV box also constitute a zone.
zone sensor. A device that measures the temperature in a space and
sends it to a controller by means of a variable resistance signal.
For more information, contact your local Trane Trane has a policy of continuous product and product data improvement and reserves the right to
office or e-mail us at comfort@trane.com change design and specifications without notice.