Commercial SPD Catalog: Surge Protective Devices
Commercial SPD Catalog: Surge Protective Devices
2016 usa.siemens.com/spd
SPD Product Catalog | Introduction
UL 1449 4th Edition In today’s electronic world, home and business mechanical reinforcing taping resulting in a design
electrical systems aren’t complete unless they that ensured the highest possible electrical system
incorporate surge protection. This is best protection and reliability.
accomplished by Stopping Surges Before They Get
In through the application of hard-wired surge Our next generation UL 1449 4th Edition TPS3
protective devices (SPDs) at key surge entry paths SPDs carry on this same legacy by maintaining
located within an electrical system. the highest degree of safety while delivering
the industry’s best performance ratings – lowest
Locating SPD installation points is a relatively Voltage Protection Ratings (VPRs), Type 1 and 20 kA
easy step in developing a surge protection plan. I nominal ratings nearly across the board, and surge
Selecting and sizing surge protective devices is not current ratings from 50 kA to 1000 kA. This safety
as simple, but Siemens has solutions for virtually and performance “know-how” is infused within
all applications. every Siemens TPS.
Even at their inception over 18 years ago, our Electrical disturbances will always occur, but they
Transient Protection System (TPS) family of don’t have to cause surge protectors to fail in an
surge protectors included a number of industry unsafe manner. Safer surge protection means
SPD safety control firsts including the patented uncompromised electrical system protection,
Ceramgard and TranSafe circuitry, coordinated safety, and reliability.
fusing and thermal cutouts, dielectric isolation,
Internal External
SPD Product Catalog | Table of Contents
Table of Contents
4
Pricing & Product information - Phone: 888.333.3545 or visit usa.siemens.com/spd
TPS3 03
Type 1 Surge Protective Device (SPD)
Mounts External to Electrical Distribution
Equipment
Features: • SPD Specifications • Standard Configuration
• UL 1449 4th Edition Listed Type 1, • Surge Current Rating Per Phase • Standard NEMA 4X polycarbonate
CSA 22.2 No. 269.1 Per Phase L-N (L-G: Delta) enclosure (UL 746C (f1), UL 94-5VA)
50 kA 50 kA • Wire size: Prewired with 3’ (91.4 cm)
• Type 1 SPD • 100% monitoring
• Mounts external to electrical of #10 AWG
(Every MOV is monitored)
distribution equipment • Standard size: 3.25” x 3.25” x 3.3”
• Individually fused and thermally
• Recommended for Line Side or Load (82.6 mm x 82.6 mm x 83.8 mm)
protected MOVs
Side Applications • Standard weight: 2 lb. (0.9 kg)
• Solid state bi-directional operation
• Bracket included for multiple mounting • Repetitive impulse: 5000 - 3kA - 8 x
options • SPD Monitoring
20µs; 1000 - 10kA - 8 x 20µs
• Large-block 34 mm square MOVs • LED indicators
• Less than 1 nanosecond response
• 20 kA In (most models) time
• Options
• 200 kA SCCR (most models) • Relative humidity range:
• N-G protection
• All UL required OCP & safety 0-95% non-condensing
• Dry Contact & Audible Alarm
coordination included • Operating frequency: 47-63 Hz
(Dry Contact connection leads exit
• Type 1 SPDs intended for Line or • Peak Operating temperature:
through nipple via #18 AWG)
Load side of Main Disconnect +85°C (185°F)
• UL96A Lightning Protection Master • Operating temperature:
Label compliant (@20kA In) -40°C (-40°F) to +60°C (140°F)
• Designed, manufactured and tested
consistent with:
• ANSI/IEEE C62.41.1-2002, C62.41.2-
2002, C62.45-2002, C62.62-2010,
C62.72-2007 & CSA C22.2 No. 269.1
• 1992/2000 NEMA LS-1
• NEC Article 285
• IEC 61643, CE
• 5 year warranty
usa.siemens.com/spd
5
Ordering Information
TPS3 o 03 oo oo
Voltage Code Surge Current (kA) Options
N = Adds N-G
A = 120/240V, 1Ø, 3W (Fig 1) 05 = 50 kA per phase
Protection
B = 120/240V, 3Ø, 4W (Fig 3)
0 = No N-G
C = 120/208V, 3Ø, 4W (Fig 2)
Protection
D = 240V, 3Ø, 3W (Fig 4)
(Default)
E = 277/480V, 3Ø, 4W (Fig 2)
F = 480V, 3Ø, 3W (Fig 4)
D = Dry contact &
G = 600V, 3Ø, 3W (Fig 4)
audible alarm
K = 380/220V, 3Ø, 4W (Fig 2)
L = 600/347V, 3Ø, 4W (Fig 2)
Example: TPS3C0305D0 = Type 1 SPD for a 208/120V application with a surge current capacity Available Accessories:
of 50 kA per phase, in a standard NEMA 4X enclosure with dry contacts and audible alarm option Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE = Remote monitor
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
3.31” 3.57”
Dimensions
3.57”
3/4”-14
1.15”
3.26”
4.13”
3.26”
3.26”
3/4”-14
1.15”
usa.siemens.com/spd
7
Performance Data
Siemens Part Number TPS3M0305 TPS3R0305 TPS3P0305
Modes of Protection DC+ – DC- , DC+ – Ground, DC- – Ground
Nominal Network Voltage Un 300VDC 600VDC 1000VDC
Technology Large Block, Thermally Protected 50kA MOVs
Maximum Continuous Operating Voltage DC Uc 425VDC 760VDC 1180VDC
Maximum Surge Current (8/20 µs) Imax 50kA 50kA 50kA
Nominal Discharge Current (8/20 µs) In 20kA 20kA 10kA
Voltage Protection Level (3kA 8/20µs) Up <600V <1800V <2500V
Operating Temperature -40C + 65C
Response Time tA <1ns
Installation mounting method DIN Rail, Nipple or Bracket
Enclosure Material NEMA 4X Polycarbonate
Wiring (red = + , black = - , green / yellow = gnd) Pre-wired w/3’(~1m) of 8AWG + 6AWG Ground Conductor
Diagnostic circuit Low Consumption LED Indicator
Safety Disconnectors Thermal/Overcurrent Protection; Arc-Breaking Slide Gate
UL Listing UL 1449 Listed as Type 1 SPD as a DC SPD for PV and other types of DC applications
Warranty 5 Years
usa.siemens.com/spd
9
Ordering Information
TPS3 o 09 oo ooo
Voltage Code Surge Current (kA) Options
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
usa.siemens.com/spd
11
Ordering Information
TPS3 o 11 oo o 2
Voltage Code Surge Current (kA) Options
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
usa.siemens.com/spd
13
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Internal rotary disconnect switch • Audible alarm with silence switch and test button
• Wire size: #8 AWG to 1/0 • Dry contacts
• Standard size: 12” x 12” x 7” • Surge counter
(305 mm x 305 mm x 178 mm) *
• Standard weight: 20 lb. (9.07 kg)*
*Internal disconnect options and other NEMA ratings may increase enclosure
size and weight
Ordering Information
TPS3 o 12 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase 0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 15 = 150 kA per phase V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 20 = 200 kA per phase S= NEMA 4X stainless steel EMI/RFI Filters
D = 240V, 3Ø, 3W (Fig 4) 25 = 250 kA per phase F= NEMA 1 flush mount 0 = Type 1 SPD
E = 277/480V, 3Ø, 4W (Fig 2) 30 = 300 kA per phase P= NEMA 1 screwcover pullbox
F = 480V, 3Ø, 3W (Fig 4) 40 = 400 kA per phase with extended display on 6ft D = Internal rotary disconnect
G = 600V, 3Ø, 3W (Fig 4) 50 = 500 kA per phase cable for line side mounting T = Thru-door disconnect
K = 380/220V, 3Ø, 4W (Fig 2) in SWBD/SWGR X = Surge counter
L = 600/347V, 3Ø, 4W (Fig 2) (Standard)
S = 400/230V, 3Ø, 4W (Fig 2)
Example: TPS3C12100XD2 = Type 2 SPD (Default) for a 208/120V application with a surge Available Accessories:
current capacity of 100kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge Ordered Separately
counter and internal rotary disconnect option
RMSIE - Remote monitor
When option ‘’X’, ‘T’, or ‘D’ are NOT selected, include a zero (0) in the field.
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
CSA 22.2 No. 269.2 • ANSI/IEEE C62.41.1-2002, C62.41.2- • 100% monitoring (Every MOV is
• Optional UL 1449 4th Edition Listed 2002, C62.45-2002, monitored, incl. N-G)
C62.62-2010, C62.72-2007 & CSA • Individually fused and thermally
Type 1, CSA 22.2 No. 269.1
C22.2 No. 269.1 and .2 protected MOVs
• Type 1 / Type 2 SPD
• 1992/2000 NEMA LS-1 • Solid state bi-directional operation
• Mounts external to electrical
• NEC Article 285 • EMI/RFI filtering: Active tracking up
distribution equipment to -50 db from 10 kHz to 100 MHz
• IEC 61643, CE
• Recommended for line side or load (Type 2 option only, includes UL
• 10 year warranty
side applications 1283 Listing)
• Large block, individually fused, • Repetitive impulse: 5,000 hits
thermally protected, 50 kA MOVs • Less than 1 nanosecond response
• 20 kA In (most models) time
• 200 kA SCCR (most models) • Relative humidity range:
• Single TPS1 style replaceable modules 0 -95% non-condensing
• Provides replaceable module protection • Operating frequency: 47-63 Hz
for low to high exposure applications • Operating temperature:
• All UL required OCP & safety -25°C (-15°F) to +60°C (140°F)
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect
• UL96A Lightning Protection Master
Label compliant (@20kA In)
usa.siemens.com/spd
15
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Wire size: #8 AWG to 1/0 • Audible alarm with silence switch and test button
• Standard size: 12” x 12” x 7” • Dry contacts
(305 mm x 305 mm x 178 mm) * • Surge counter
• Standard weight: 20 lb. (9.07 kg) *
*Internal disconnect options and other NEMA ratings may increase enclosure
size and weight
Ordering Information
TPS3 o L12 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1Ø, 3W (Fig 1) 15 = 150 kA per phase 0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 30 = 300 kA per phase V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 45 = 450 kA per phase S= NEMA 4X stainless steel EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) F= NEMA 1 flush mount 0 = Type 1 SPD
K = 380/220V, 3Ø, 4W (Fig 2) P= NEMA 1 screwcover pullbox
S = 400/230V, 3Ø, 4W (Fig 2) with extended display on 6ft D = Internal rotary disconnect
cable for line side mounting T = Thru-door disconnect
in SWBD/SWGR
X = Surge counter
(Standard)
Example: TPS3CL12150XD2 = 10 Mode, Type 2 SPD (Default) for a 208/120V application with a Available Accessories:
surge current capacity of 150kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge Ordered Separately
counter and internal rotary disconnect option
RMSIE - Remote monitor
When an option is not selected, include a zero (0) in the field
}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)
usa.siemens.com/spd
17
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Internal rotary disconnect switch • Audible alarm with silence switch and test button
• Wire size: #8 AWG to 1/0 • Dry contacts
• Standard size: 20” x 20” x 7” • Surge counter
(508 mm x 508 mm x 178 mm) *
• Standard weight: 64 lb. (29 kg) *
*Other NEMA ratings may increase enclosure size and weight
Ordering Information
TPS3 o 15 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1Ø, 3W (Fig 1) 40 = 400 kA per phase 0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 50 = 500 kA per phase V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 60 = 600 kA per phase S= NEMA 4X stainless steel EMI/RFI Filters
D = 240V, 3Ø, 3W (Fig 4) 80 = 800 kA per phase F= NEMA 1 flush mount 0 = Type 1 SPD
E = 277/480V, 3Ø, 4W (Fig 2) 1K = 1000 kA per phase P= NEMA 1 screwcover pullbox
F = 480V, 3Ø, 3W (Fig 4) with extended display on 6ft T = Thru-door disconnect
G = 600V, 3Ø, 3W (Fig 4) cable for line side mounting
K = 380/220V, 3Ø, 4W (Fig 2) in SWBD/SWGR X = Surge counter
L = 600/347V, 3Ø, 4W (Fig 2) (Standard)
S = 400/230V, 3Ø, 4W (Fig 2)
Example: TPS3C1560SX02 = Type 2 SPD (Default) for a 208/120V application with a surge Available Accessories:
current capacity of 600 kA per phase, in a NEMA 4X stainless steel enclosure with a surge Ordered Separately
counter and standard disconnect switch
RMSIE - Remote monitor
When an option is not selected, include a zero (0) in the field
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
usa.siemens.com/spd
19
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Internal rotary disconnect switch • Audible alarm with silence switch and test button
• Wire size: #8 AWG to 1/0 • Dry contacts
• Standard size: 20” x 20” x 7” • Surge counter
(508 mm x 508 mm x 178 mm) *
• Standard weight: 64 lb. (29 kg) *
*Other NEMA ratings may increase enclosure size and weight
Ordering Information
TPS3 o L15 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options
A = 120/240V, 1Ø, 3W (Fig 1) 60 = 600 kA per phase 0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 90 = 900 kA per phase V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) S= NEMA 4X stainless steel EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) F= NEMA 1 flush mount 0 = Type 1 SPD
K = 380/220V, 3Ø, 4W (Fig 2) P= NEMA 1 screwcover pullbox
S = 400/230V, 3Ø, 4W (Fig 2) with extended display on 6ft T = Thru-door disconnect
cable for line side mounting
in SWBD/SWGR X = Surge counter
(Standard)
Example: TPS3CL15600X02 = 10 Mode, Type 2 SPD (Default) for a 208/120V application with a Available Accessories:
surge current capacity of 600 kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge Ordered Separately
counter
RMSIE - Remote monitor
When an option is not selected, include a zero (0) in the field
}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)
usa.siemens.com/spd
21
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 100kA/phase • Dry contacts
• Inc. redundancy use: 200kA/phase • Surge counter
• Max. redundancy use: 300kA/phase
Ordering Information
TPS3 o 01 oo X oo2
Voltage Code Surge Current (kA) Options
Example: TPS3C0120X002 = Type 2 SPD (Default) for a 208/120V panelboard with a surge Available Accessories:
current capacity of 200 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
usa.siemens.com/spd
23
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 150kA/phase • Dry contacts
• Max. redundancy use: 300kA/phase • Surge counter
Ordering Information
TPS3 o L1 oo X oo2
Voltage Code Surge Current (kA) Options
Example: TPS3CL130X002 = 10 Mode Type 2 SPD (Default) for a 208/120V panelboard with a Available Accessories:
surge current capacity of 300 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor
}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)
usa.siemens.com/spd
25
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 100kA/phase • Dry contacts
• Inc. redundancy use: 200kA/phase • Surge counter
• Max. redundancy use: 300kA/phase
Ordering Information
TPS3 o 02 oo X 2
Voltage Code Surge Current (kA) Option
Example: TPS3C0220X2 = Type 2 SPD (Default) for a 208/120V panelboard with a surge current Available Accessories:
capacity of 200 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
usa.siemens.com/spd
27
• Applications • Standard Monitoring
• Provides main service or downstream protection for • LED indicators
sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Standard redundancy use: 150 kA per phase • Dry contacts
• Maximum redundancy use: 300 kA per phase • Surge counter
Ordering Information
TPS3 o L2 oo X 2
Voltage Code Surge Current (kA) Option
Example: TPS3CL230X2 = 10 Mode Type 2 SPD (Default) for a 208/120V panelboard with a surge Available Accessories:
current capacity of 300 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor
}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)
usa.siemens.com/spd
29
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 100kA/phase • Dry contacts
• Inc. redundancy use: 200kA/phase • Surge counter
• Max. redundancy use: 300kA/phase • Internal rotary disconnect switch
Ordering Information
TPS3 o 05 oo X 2
Voltage Code Surge Current (kA) Option
Example: TPS3C0530X2 = Type 2 SPD (Default) for a 208/120V power panel with a surge current Available Accessories:
capacity of 300 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
usa.siemens.com/spd
31
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 150kA/phase • Dry contacts
• Max. redundancy use: 300kA/phase • Surge counter
• Rotary disconnect switch
Ordering Information
TPS3 o L5 oo X 2
Voltage Code Surge Current (kA) Options
Example: TPS3CL530X2 = 10 mode Type 2 SPD (Default) for a 208/120V Power Panel with a Available Accessories:
surge current capacity of 300kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor
}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)
usa.siemens.com/spd
33
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 300kA/phase • Dry contacts
• Inc. redundancy use: 450kA/phase • Surge counter
• Max. redundancy use: 500kA/phase • Rotary disconnect switch
Ordering Information
TPS3 o 06 oo X o2
Voltage Code Surge Current (kA) Options
Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
• SPD Specifications
Type 1 / 2 Surge Protection Device (SPD) • Directly connected discrete
usa.siemens.com/spd
35
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 300kA/phase • Dry contacts
• Max. redundancy use: 450kA/phase • Surge counter
• Rotary disconnect switch
Ordering Information
TPS3 o L6 oo X o2
Voltage Code Surge Current (kA) Options
X = Surge counter
(Standard)
Example: TPS3CL645X02 = 10 mode Type 2 SPD (Default) for a 208/120V switchboard with a Available Accessories:
surge current capacity of 450 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor
}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)
37
SPD Product Catalog | Team Services and Support
38
Thank you...
for choosing Siemens for your
surge protection needs.
usa.siemens.com/spd
39
Siemens Industry, Inc.
5400 Triangle Parkway
Norcross, GA 30092
For more information, please contact our Customer Support Center.
Phone: +1 888 333 3545
Fax: +1 727 539 8955
E–mail: info.us@siemens.com
Web: usa.siemens.com/spd
Article-No. RPCA-SPDCA-1216
Printed in USA
All rights reserved
© 2016, Siemens Industry, Inc.
The information provided in this manual contains merely general
descriptions of characteristics of performance which in case of actual use
do not always apply as described or which may change as a result of
further development of the product. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract.