Commercial SPD Catalog

Surge Protective Devices

2016 usa.siemens.com/spd
SPD Product Catalog | Introduction

Siemens full line of


Surge Protective Devices

UL 1449 4th Edition In today’s electronic world, home and business mechanical reinforcing taping resulting in a design
electrical systems aren’t complete unless they that ensured the highest possible electrical system
incorporate surge protection. This is best protection and reliability.
accomplished by Stopping Surges Before They Get
In through the application of hard-wired surge Our next generation UL 1449 4th Edition TPS3
protective devices (SPDs) at key surge entry paths SPDs carry on this same legacy by maintaining
located within an electrical system. the highest degree of safety while delivering
the industry’s best performance ratings – lowest
Locating SPD installation points is a relatively Voltage Protection Ratings (VPRs), Type 1 and 20 kA
easy step in developing a surge protection plan. I nominal ratings nearly across the board, and surge
Selecting and sizing surge protective devices is not current ratings from 50 kA to 1000 kA. This safety
as simple, but Siemens has solutions for virtually and performance “know-how” is infused within
all applications. every Siemens TPS.

Even at their inception over 18 years ago, our Electrical disturbances will always occur, but they
Transient Protection System (TPS) family of don’t have to cause surge protectors to fail in an
surge protectors included a number of industry unsafe manner. Safer surge protection means
SPD safety control firsts including the patented uncompromised electrical system protection,
Ceramgard and TranSafe circuitry, coordinated safety, and reliability.
fusing and thermal cutouts, dielectric isolation,

Internal External
SPD Product Catalog | Table of Contents

Table of Contents

SPD Sizing Chart 4

External SPDs (5-20)


TPS3 03 5
TPS3 03 DC 7
TPS3 09 9
TPS3 11 11
TPS3 12 13
TPS3 L12 (10-mode SPD) 15
TPS3 15 17
TPS3 L15 (10-mode SPD) 19

Internal SPDs (21-32)


TPS3 01 21
TPS3 L1 (10-mode SPD) 23
TPS3 02 25
TPS3 L2 (10-mode SPD) 27
TPS3 05 29
TPS3 L5 (10-mode SPD) 31
TPS3 06 33
TPS3 L6 (10-mode SPD) 35

Frequently Asked Questions 37

Services & Support 38


Sizing Chart
Surge Protective Devices

Service Entrance Greater than 2000A


Exposure Level kA per phase Model
High Exposure 300 kA TPS3_1230
Medium Exposure 200 kA TPS3_1220
Low Exposure 150 kA TPS3_1215
TPS3 03
Lowest Exposure 100 kA TPS3_1110

Service Entrance 1200A - 2000A


Exposure Level kA per phase Model
High Exposure 250 kA TPS3_1225
Medium Exposure 200 kA TPS3_1220
Low Exposure 150 kA TPS3_1215
Lowest Exposure 100 kA TPS3_0910

Service Entrance 800A - 1200A TPS3 09


Exposure Level kA per phase Model
High Exposure 200 kA TPS3_1120
Medium Exposure 150 kA TPS3_1115
Low Exposure 100 kA TPS3_0910
Lowest Exposure 50 kA TPS3_0305

Distribution/Branch Panel 800A - 1200A


Exposure Level kA per phase Model
High Exposure 200 kA TPS3_1120 TPS3 11
Medium Exposure 150 kA TPS3_1115
Low Exposure 100 kA TPS3_0910
Lowest Exposure 50 kA TPS3_0305

Distribution/Branch Panel Less than 800A


Exposure Level kA per phase Model
High Exposure 150 kA TPS3_1115
Medium Exposure 100 kA TPS3_1110
Low Exposure 100 kA TPS3_0910
Lowest Exposure 50 kA TPS3_0305
TPS3 12

4
Pricing & Product information - Phone: 888.333.3545 or visit usa.siemens.com/spd
TPS3 03
Type 1 Surge Protective Device (SPD)
Mounts External to Electrical Distribution
Equipment
Features: • SPD Specifications • Standard Configuration
• UL 1449 4th Edition Listed Type 1, • Surge Current Rating Per Phase • Standard NEMA 4X polycarbonate
CSA 22.2 No. 269.1 Per Phase L-N (L-G: Delta) enclosure (UL 746C (f1), UL 94-5VA)
50 kA 50 kA • Wire size: Prewired with 3’ (91.4 cm)
• Type 1 SPD • 100% monitoring
• Mounts external to electrical of #10 AWG
(Every MOV is monitored)
distribution equipment • Standard size: 3.25” x 3.25” x 3.3”
• Individually fused and thermally
• Recommended for Line Side or Load (82.6 mm x 82.6 mm x 83.8 mm)
protected MOVs
Side Applications • Standard weight: 2 lb. (0.9 kg)
• Solid state bi-directional operation
• Bracket included for multiple mounting • Repetitive impulse: 5000 - 3kA - 8 x
options • SPD Monitoring
20µs; 1000 - 10kA - 8 x 20µs
• Large-block 34 mm square MOVs • LED indicators
• Less than 1 nanosecond response
• 20 kA In (most models) time
• Options
• 200 kA SCCR (most models) • Relative humidity range:
• N-G protection
• All UL required OCP & safety 0-95% non-condensing
• Dry Contact & Audible Alarm
coordination included • Operating frequency: 47-63 Hz
(Dry Contact connection leads exit
• Type 1 SPDs intended for Line or • Peak Operating temperature:
through nipple via #18 AWG)
Load side of Main Disconnect +85°C (185°F)
• UL96A Lightning Protection Master • Operating temperature:
Label compliant (@20kA In) -40°C (-40°F) to +60°C (140°F)
• Designed, manufactured and tested
consistent with:
• ANSI/IEEE C62.41.1-2002, C62.41.2-
2002, C62.45-2002, C62.62-2010,
C62.72-2007 & CSA C22.2 No. 269.1
• 1992/2000 NEMA LS-1
• NEC Article 285
• IEC 61643, CE
• 5 year warranty

usa.siemens.com/spd
5
Ordering Information

TPS3 o 03 oo oo
Voltage Code Surge Current (kA) Options

N = Adds N-G
A = 120/240V, 1Ø, 3W (Fig 1) 05 = 50 kA per phase
Protection
B = 120/240V, 3Ø, 4W (Fig 3)
0 = No N-G
C = 120/208V, 3Ø, 4W (Fig 2)
Protection
D = 240V, 3Ø, 3W (Fig 4)
(Default)
E = 277/480V, 3Ø, 4W (Fig 2)
F = 480V, 3Ø, 3W (Fig 4)
D = Dry contact &
G = 600V, 3Ø, 3W (Fig 4)
audible alarm
K = 380/220V, 3Ø, 4W (Fig 2)
L = 600/347V, 3Ø, 4W (Fig 2)

Example: TPS3C0305D0 = Type 1 SPD for a 208/120V application with a surge current capacity Available Accessories:
of 50 kA per phase, in a standard NEMA 4X enclosure with dry contacts and audible alarm option Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE = Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G* N-G* L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 600 1000* 600* 100 20 kA 200kA 150
B 120/240V, 3Ø, 4W (Fig 3) 600/1200 1000/1500* 600* 100/1500 20 kA 200 kA 150/320
C 120/208V, 3Ø, 4W (Fig 2) 600 1000* 600* 1000 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200* — 1500 20 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1800* 1000* 2000 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800* — 3000 10 kA 200kA 550
G 600V, 3Ø, 3W (Fig 4) — 1200* — 1500 20 kA 200kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1800* 1000* 2000 20 kA 200kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 2500* 1200* 2500 20 kA 200kA 420
*with optional N-G protection

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Figure 1 Figure 2 Figure 3 Figure 4


Split Wye Hi-Leg Delta (B High) Delta & HRG Wye
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd
1 Neu, 1 Grnd

Siemens Industry, Inc.


5400 Triangle Parkway
Norcross, GA 30092
888-333-3545
info.us@siemens.com
Order No. RPFL-S303C-0916
Printed in USA
All Rights Reserved.
©2016 Siemens Industry, Inc.
09.07.16 RevA
6
TPS3 03 DC
For DC Photovoltaic Applications
TPS3 03 DC is available in 300VDC, Diagram Tri-Mount Installation
600VDC and 1000VDC versions, which Mounting Kit Included
DC+ DC-
are designed to protect photovoltaic
red wire black wire
electrical systems. Typical PV installation 8AWG 8AWG
would be on the DC solar panel side
and also on the AC side of the inverter/
converter. AC voltage TPS3 03’s are also
available. SPDs are highly recommended
when lightning activity is present to
Std. 3/4”-14 Nipple DIN-rail Mount
protect sensitive electrical photovoltaic (rail not incl.)
components.

TPS3 03 DC is designed as a stand alone


device in a NEMA 4X polycarbonate
enclosure. Large block, thermally
protected 50 kA MOVs are utilized. A
green LED illuminates for diagnostic Ground
green / yellow wire Bracket Mount for Flat Surfaces
monitoring. TPS3 03 DC comes standard
6 AWG
with a Tri-Mount installation kit3.26”
which
allows it to be Nipple, DIN-rail or Bracket
mounted.
(0.73 kg)
Weight: 1.60 lbs

3.31” 3.57”
Dimensions
3.57”

3/4”-14

Sized for std 35mm DIN-rail

4.13” Weight: 1.60 lbs


(0.73 kg)
3.31”

1.15”

3.26”
4.13”

3.26”
3.26”

3/4”-14

1.15”

Sized for std 35mm DIN-rail


Weight:
1.60 lbs (0.73kg)

usa.siemens.com/spd
7
Performance Data
Siemens Part Number TPS3M0305 TPS3R0305 TPS3P0305
Modes of Protection DC+ – DC- , DC+ – Ground, DC- – Ground
Nominal Network Voltage Un 300VDC 600VDC 1000VDC
Technology Large Block, Thermally Protected 50kA MOVs
Maximum Continuous Operating Voltage DC Uc 425VDC 760VDC 1180VDC
Maximum Surge Current (8/20 µs) Imax 50kA 50kA 50kA
Nominal Discharge Current (8/20 µs) In 20kA 20kA 10kA
Voltage Protection Level (3kA 8/20µs) Up <600V <1800V <2500V
Operating Temperature -40C + 65C
Response Time tA <1ns
Installation mounting method DIN Rail, Nipple or Bracket
Enclosure Material NEMA 4X Polycarbonate
Wiring (red = + , black = - , green / yellow = gnd) Pre-wired w/3’(~1m) of 8AWG + 6AWG Ground Conductor
Diagnostic circuit Low Consumption LED Indicator
Safety Disconnectors Thermal/Overcurrent Protection; Arc-Breaking Slide Gate
UL Listing UL 1449 Listed as Type 1 SPD as a DC SPD for PV and other types of DC applications
Warranty 5 Years

Siemens Industry, Inc.


5400 Triangle Parkway
Norcross, GA 30092
888-333-3545
info.us@siemens.com
Order No. RPFL-S303DC-0716
Printed in USA
All Rights Reserved.
©2016 Siemens Industry, Inc.
06.03.16 Rev-
8
TPS3 09
Type 1 Surge Protective Device (SPD) • 100% monitoring (Every MOV is
monitored, incl. N-G)
Mounts External to Electrical Distribution • Individually fused and thermally
protected MOVs
Equipment or Internal to P1, P2 Lighting • Solid state bi-directional operation
• Repetitive impulse: 5,000 hits
Panelboards, P3 Power Panelboards and • Less than 1 nanosecond response
time
Busway Systems • Relative humidity range:
0-95% non-condensing
• Operating frequency: 47-63 Hz
Features: • Designed, manufactured and tested • Operating temperature:
• UL 1449 4th Edition Listed Type 1, CSA consistent with: -40°C (-40°F) to +85°C (185°F)
22.2 No. 269.1 • ANSI/IEEE C62.41.1-2002,
• Type 1 SPD C62.41.2-2002, C62.45-2002, • Standard Configuration
• Mounts external to electrical C62.62-2010, C62.72-2007 & CSA • Standard NEMA 4X polycarbonate
distribution equipment C22.2 No. 269.1 enclosure (UL 746C (f1), UL 94-5VA)
• Weatherproof hub included • 1992/2000 NEMA LS-1 • Wire size: Prewired with 3’ (91.4 cm)
• Mounts internal to P1 panelboards & • NEC Article 285 of #10 AWG
busway • IEC 61643, CE • Standard size: 8.3” x 3.6” x 3.0”
• P1 - Field retrofit or factory install • 10 year warranty (211 mm x 91 mm x 77 mm)
• P2 and P3 - Factory install only • Standard weight: 3 lb. (1.4 kg)
Consult factory for field retrofit • SPD Specifications
• SPD Monitoring
• Large block, individually fused, • Surge Current Rating Per Phase
Per Phase L-N L-G N-G • LED indicators
thermally protected, 50 kA MOVs
100 kA 50 kA 50 kA 50 kA
• 20 kA In (most models)
• 200 kA SCCR (most models)
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• UL96A Lightning Protection Master
Label compliant (@20kA In)

usa.siemens.com/spd
9
Ordering Information

TPS3 o 09 oo ooo
Voltage Code Surge Current (kA) Options

A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase


B = 120/240V, 3Ø, 4W (Fig 3)
C = 120/208V, 3Ø, 4W (Fig 2) E = Extended
D = 240V, 3Ø, 3W (Fig 4) indicator
E = 277/480V, 3Ø, 4W (Fig 2) light
F = 480V, 3Ø, 3W (Fig 4)
G = 600V, 3Ø, 3W (Fig 4) I = Internal mounting in
K = 380/220V, 3Ø, 4W (Fig 2) P1, P2 panelsŒ
L = 600/347V, 3Ø, 4W (Fig 2)
D = Dry contact & audible alarm
S = 400/230V, 3Ø, 4W (Fig 2)
Example: TPS3C0910D00 = Type 1 SPD for a 208/120V panelboard with a surge current capacity Available Accessories:
of 100 kA per phase with standard NEMA 4X enclosure, dry contacts and audible alarm option. Ordered Separately
Available for field retrofit in P1 panels
RMSIE = Remote monitor
XMFMKIT = Flush mount plate
When an option is not selected, include a zero (0) in the field TPS9IKITP1 = Mounting bracket for
installation in P1 panels
TPS9IKITP2 = Mounting bracket for
installation in P2 panels
(factory install only)

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 600 700 500 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 600/1200 700 /1200 500 1000/1000 20 kA 200 kA 150/320
C 120/208V, 3Ø, 4W (Fig 2) 600 700 500 1000 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 1200 20 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1000 1800 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 1800 10 kA 200 kA 552
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1000 1800 20 kA 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 10 kA 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1000 1800 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Figure 1 Figure 2 Figure 3 Figure 4 Siemens Industry, Inc.


Split Wye Hi-Leg Delta (B High) Delta & HRG Wye 5400 Triangle Parkway
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd Norcross, GA 30092
1 Neu, 1 Grnd
888-333-3545
info.us@siemens.com
Notes: Order No. RPFL-S309C-0916
ΠRequires TPS9IKITP1 or TPS9IKITP2 mounting bracket accessory, Printed in USA
see available Accessories. Prewired cables are extended from All Rights Reserved.
3 feet to 6 feet. ©2016 Siemens Industry, Inc.
09.07.16 RevA
10
TPS3 11
Type 1 / Type 2 Surge Protective Device
(SPD) Mounts External to Electrical
Distribution Equipment
Features: • SPD Specifications • Relative humidity range:
• UL 1449-4 Type 2 SPD, UL 1283 Listed, • Surge Current Rating Per Phase 0-95% non-condensing
CSA 22.2 No. 269.2 Per Phase L-N L-G N-G • Operating frequency: 47-63 Hz
100 kA 50 kA 50 kA 50 kA • Operating temperature:
• Optional UL 1449 4th Edition Listed 150 kA 100 kA 50 kA 50 kA
Type 1, CSA 22.2 No. 269.1 200 kA 100 kA 100 kA 100 kA -25°C (-15°F) to +60°C (140°F)
• Type 1 / Type 2 SPD • 100% monitoring (Every MOV is
• Mounts external to electrical monitored, incl. N-G) • Standard Configuration
distribution equipment • Individually fused and thermally • Standard NEMA 4X polycarbonate
protected MOVs enclosure (UL 746C (f1), UL 94-5VA)
• Large block, individually fused,
• Solid state bi-directional operation • Wire size: #8 AWG to #10 AWG
thermally protected, 50 kA MOVs
• EMI/RFI filtering: Active tracking up • Standard size: 6” x 6” x 4”
• 20 kA In (most models) to -50 db from 10 kHz to 100 MHz (152 mm x 152 mm x 102 mm)
• 200 kA SCCR (most models) (Type 2 option only, includes UL • Standard weight: 5 lb. (2.27 kg)
• All UL required OCP & safety 1283 Listing)
coordination included • Repetitive impulse: 5,000 hits • SPD Monitoring
• Type 1 SPDs intended for Line or • Less than 1 nanosecond response • LED indicators
Load side of Main Disconnect time
• Type 2 SPDs intended for Load side
of Main Disconnect
• UL96A Lightning Protection Master
Label compliant (@20kA In)
• Designed, manufactured and tested
consistent with:
• ANSI/IEEE C62.41.1-2002, C62.41.2-
2002, C62.45-2002,
C62.62-2010, C62.72-2007 & CSA
C22.2 No. 269.1 and .2
• 1992/2000 NEMA LS-1
• NEC Article 285
• IEC 61643, CE
• 10 year warranty

usa.siemens.com/spd
11
Ordering Information

TPS3 o 11 oo o 2
Voltage Code Surge Current (kA) Options

A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase 2 = Type 2 SPD (Default)


B = 120/240V, 3Ø, 4W (Fig 3) 15 = 150 kA per phase Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 20 = 200 kA per phase EMI/RFI Filters
D = 240V, 3Ø, 3W (Fig 4) 0 = Type 1 SPD
E = 277/480V, 3Ø, 4W (Fig 2)
F = 480V, 3Ø, 3W (Fig 4) D = Dry contact
G = 600V, 3Ø, 3W (Fig 4) Œ & audible alarm
K = 380/220V, 3Ø, 4W (Fig 2)
L = 600/347V, 3Ø, 4W (Fig 2)
S = 400/230V, 3Ø, 4W (Fig 2)
Example: TPS3C1110D2 = Type 2 SPD (Default) for a 208/120V application with a surge current Available Accessories:
capacity of 100 kA per phase, in a standard NEMA 4X enclosure with dry contacts and audible Ordered Separately
alarm option
RMSIE - Remote monitor
When option ‘D’ is NOT selected, include a zero (0) in the field. KITFMXF = Flush mount plate

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 600 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1200 700 /1200 600 1000 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 600 1000 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 2000 20 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 2000 10 kA 200 kA 552
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 10 kA 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Figure 1 Figure 2 Figure 3 Figure 4


Split Wye Hi-Leg Delta (B High) Delta & HRG Wye
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd
1 Neu, 1 Grnd
Siemens Industry, Inc.
5400 Triangle Parkway
Norcross, GA 30092
888-333-3545
info.us@siemens.com
Order No. RPFL-S311C-0716
Printed in USA
Notes: All Rights Reserved.
Œ Available in 100 kA per phase only ©2016 Siemens Industry, Inc.
06.03.16 Rev-
12
TPS3 12
Type 1 / Type 2
Surge Protective Device (SPD) For Line
Side or Load Side Applications
Features: • Designed, manufactured and tested • 100% monitoring (Every MOV is
• UL 1449-4 Type 2 SPD, UL 1283 Listed, consistent with: monitored, incl. N-G)
CSA 22.2 No. 269.2 • ANSI/IEEE C62.41.1-2002, C62.41.2- • Individually fused and thermally
• Optional UL 1449 4th Edition Listed 2002, C62.45-2002, protected MOVs
Type 1, CSA 22.2 No. 269.1 C62.62-2010, C62.72-2007 & CSA • Solid state bi-directional operation
C22.2 No. 269.1 and .2 • EMI/RFI filtering: Active tracking up
• Type 1 / Type 2 SPD
• 1992/2000 NEMA LS-1 to -50 db from 10 kHz to 100 MHz
• Mounts external to electrical
• NEC Article 285 (Type 2 option only, includes UL
distribution equipment 1283 Listing)
• IEC 61643, CE
• Recommended for line side or load • Repetitive impulse: 5,000 hits
• 10 year warranty
side applications • Less than 1 nanosecond response
• Large block, individually fused, time
• SPD Specifications
thermally protected, 50 kA MOVs • Relative humidity range:
• Surge Current Rating Per Phase
• 20 kA In (most models) Per Phase L-N L-G N-G 0 -95% non-condensing
• 200 kA SCCR (most models) 100 kA 50 kA 50 kA 50 kA • Operating frequency: 47-63 Hz
• Provides redundant replaceable 150 kA 100 kA 50 kA 50 kA • Operating temperature:
200 kA 100 kA 100 kA 100 kA
module protection for low to high 250 kA 150 kA 100 kA 100 kA
-25°C (-15°F) to +60°C (140°F)
exposure applications 300 kA 150 kA 150 kA 150 kA
• All UL required OCP & safety 400 kA 200 kA 200 kA 200 kA
500 kA 250 kA 250 kA 250 kA
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect
• UL96A Lightning Protection Master
Label compliant (@20kA In)

usa.siemens.com/spd
13
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Internal rotary disconnect switch • Audible alarm with silence switch and test button
• Wire size: #8 AWG to 1/0 • Dry contacts
• Standard size: 12” x 12” x 7” • Surge counter
(305 mm x 305 mm x 178 mm) *
• Standard weight: 20 lb. (9.07 kg)*
*Internal disconnect options and other NEMA ratings may increase enclosure
size and weight

Ordering Information

TPS3 o 12 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options

A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase 0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 15 = 150 kA per phase V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 20 = 200 kA per phase S= NEMA 4X stainless steel EMI/RFI Filters
D = 240V, 3Ø, 3W (Fig 4) 25 = 250 kA per phase F= NEMA 1 flush mount 0 = Type 1 SPD
E = 277/480V, 3Ø, 4W (Fig 2) 30 = 300 kA per phase P= NEMA 1 screwcover pullbox
F = 480V, 3Ø, 3W (Fig 4) 40 = 400 kA per phase with extended display on 6ft D = Internal rotary disconnect
G = 600V, 3Ø, 3W (Fig 4)Ž 50 = 500 kA per phase cable for line side mounting T = Thru-door disconnect
K = 380/220V, 3Ø, 4W (Fig 2) in SWBD/SWGRŒ X = Surge counter
L = 600/347V, 3Ø, 4W (Fig 2) (Standard)
S = 400/230V, 3Ø, 4W (Fig 2)

Example: TPS3C12100XD2 = Type 2 SPD (Default) for a 208/120V application with a surge Available Accessories:
current capacity of 100kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge Ordered Separately
counter and internal rotary disconnect option
RMSIE - Remote monitor
When option ‘’X’, ‘T’, or ‘D’ are NOT selected, include a zero (0) in the field.

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1200 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1200 700 /1200 700 1800/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1200 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 1200 20 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 1800 20 kA 200 kA 552
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 20 kA 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Siemens Industry, Inc.


5400 Triangle Parkway
Norcross, GA 30092
Figure 1 Figure 2 Figure 3 Figure 4
Split Wye Hi-Leg Delta (B High) Delta & HRG Wye 888-333-3545
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd info.us@siemens.com
1 Neu, 1 Grnd
Notes: Order No. RPFL-S312C-0716
ŒFor line side mounting in SWBD/SWGR ŽAvailable in 100kA, 150kA, 200kA & Printed in USA
Not available in 500kA 250 kA only All Rights Reserved.
VPR may increase when disconnect ©2016 Siemens Industry, Inc.
switch is added; VPR may decrease for 06.03.16 Rev-
14
products 400 & 500kA per phase
TPS3 L12
True 10 Mode Protection

Type 1 / Type 2 • SPD Specifications


• Directly connected discrete
Surge Protective Device (SPD) For Line protection elements between all
possible modes providing true
Side or Load Side Applications 10 mode protection
• Surge Current Rating Per Phase
Per Phase L-N L-G L-L N-G
150 kA 50 kA 50 kA 50 kA 50 kA
Features: • Designed, manufactured and tested 300 kA 100 kA 100 kA 100 kA 100 kA
• UL 1449-4 Type 2 SPD, UL 1283 Listed, consistent with: 450 kA 150 kA 150 kA 150 kA 150 kA

CSA 22.2 No. 269.2 • ANSI/IEEE C62.41.1-2002, C62.41.2- • 100% monitoring (Every MOV is
• Optional UL 1449 4th Edition Listed 2002, C62.45-2002, monitored, incl. N-G)
C62.62-2010, C62.72-2007 & CSA • Individually fused and thermally
Type 1, CSA 22.2 No. 269.1
C22.2 No. 269.1 and .2 protected MOVs
• Type 1 / Type 2 SPD
• 1992/2000 NEMA LS-1 • Solid state bi-directional operation
• Mounts external to electrical
• NEC Article 285 • EMI/RFI filtering: Active tracking up
distribution equipment to -50 db from 10 kHz to 100 MHz
• IEC 61643, CE
• Recommended for line side or load (Type 2 option only, includes UL
• 10 year warranty
side applications 1283 Listing)
• Large block, individually fused, • Repetitive impulse: 5,000 hits
thermally protected, 50 kA MOVs • Less than 1 nanosecond response
• 20 kA In (most models) time
• 200 kA SCCR (most models) • Relative humidity range:
• Single TPS1 style replaceable modules 0 -95% non-condensing
• Provides replaceable module protection • Operating frequency: 47-63 Hz
for low to high exposure applications • Operating temperature:
• All UL required OCP & safety -25°C (-15°F) to +60°C (140°F)
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect
• UL96A Lightning Protection Master
Label compliant (@20kA In)

usa.siemens.com/spd
15
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Wire size: #8 AWG to 1/0 • Audible alarm with silence switch and test button
• Standard size: 12” x 12” x 7” • Dry contacts
(305 mm x 305 mm x 178 mm) * • Surge counter
• Standard weight: 20 lb. (9.07 kg) *
*Internal disconnect options and other NEMA ratings may increase enclosure
size and weight

Ordering Information

TPS3 o L12 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options

A = 120/240V, 1Ø, 3W (Fig 1) 15 = 150 kA per phase 0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 30 = 300 kA per phase V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 45 = 450 kA per phase S= NEMA 4X stainless steel EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) F= NEMA 1 flush mount 0 = Type 1 SPD
K = 380/220V, 3Ø, 4W (Fig 2) P= NEMA 1 screwcover pullbox
S = 400/230V, 3Ø, 4W (Fig 2) with extended display on 6ft D = Internal rotary disconnect
cable for line side mounting T = Thru-door disconnect
in SWBD/SWGRŒ
X = Surge counter
(Standard)

Example: TPS3CL12150XD2 = 10 Mode, Type 2 SPD (Default) for a 208/120V application with a Available Accessories:
surge current capacity of 150kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge Ordered Separately
counter and internal rotary disconnect option
RMSIE - Remote monitor
When an option is not selected, include a zero (0) in the field

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 800 /1500 700 /1200 700 1800/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1000 20 kA 200 kA 150
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320

Hot (BLK) Phase A (BLK) Phase A (BLK)


}V A B Phase B (BLK) Phase B (ORNG)
}V Neutral (WHT)
N
Neutral (WHT) }V

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)

Figure 1 Figure 2 Figure 3 Siemens Industry, Inc.


Split Wye Hi-Leg Delta (B High)
5400 Triangle Parkway
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), Norcross, GA 30092
1 Neu, 1 Grnd
888-333-3545
info.us@siemens.com
Order No. RPFL-S3L12-0716
Notes: Printed in USA
ΠFor line side mounting in SWBD/SWGR All Rights Reserved.
 VPR may decrease for 450kA per phase ©2016 Siemens Industry, Inc.
06.03.16 Rev-
16
TPS3 15
Type 1 / Type 2
Surge Protective Device (SPD) For Line
Side or Load Side Applications
Features: • UL96A Lightning Protection Master • 100% monitoring (Every MOV is
• UL 1449-4 Type 2 SPD, UL 1283 Listed, Label compliant (@20kA In) monitored, incl. N-G)
CSA 22.2 No. 269.2 • Designed, manufactured and tested • Individually fused and thermally
• Optional UL 1449 4th Edition Listed consistent with: protected MOVs
Type 1, CSA 22.2 No. 269.1 • ANSI/IEEE C62.41.1-2002, C62.41.2- • Solid state bi-directional operation
• Type 1 / Type 2 SPD 2002, C62.45-2002, • EMI/RFI filtering: Active tracking up
C62.62-2010, C62.72-2007 & CSA to -50 db from 10 kHz to 100 MHz
• Mounts external to electrical
C22.2 No. 269.1 and .2 (Type 2 option only, includes UL
distribution equipment
• 1992/2000 NEMA LS-1 1283 Listing)
• Recommended for line side or load
• NEC Article 285 • Repetitive impulse: 5,000 hits
side applications
• IEC 61643, CE • Less than 1 nanosecond response
• When “P” option is selected, TPS3 15, time
• 10 year warranty
Type 1 SPD mounts internal to: • Relative humidity range:
SB1, SB3 and Type RCS switchboards, 0 -95% non-condensing
• SPD Specifications
Type WL low voltage switchgear and • Operating frequency: 47-63 Hz
• Surge Current Rating Per Phase
TIASTAR motor control centers • Operating temperature:
Per Phase L-N L-G N-G
• Large block, individually fused, -25°C (-15°F) to +60°C (140°F)
600 kA 300 kA 300 kA 300 kA
thermally protected, 50 kA MOVs 800 kA 400 kA 400 kA 400 kA
• Internal rotary disconnect switch 1000 kA 500 kA 500 kA 500 kA
• 20 kA In (most models)
• 200 kA SCCR (most models)
• Provides redundant replaceable
module protection for low to high
exposure applications
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect

usa.siemens.com/spd
17
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Internal rotary disconnect switch • Audible alarm with silence switch and test button
• Wire size: #8 AWG to 1/0 • Dry contacts
• Standard size: 20” x 20” x 7” • Surge counter
(508 mm x 508 mm x 178 mm) *
• Standard weight: 64 lb. (29 kg) *
*Other NEMA ratings may increase enclosure size and weight

Ordering Information

TPS3 o 15 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options

A = 120/240V, 1Ø, 3W (Fig 1) 40 = 400 kA per phase  0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 50 = 500 kA per phase  V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 60 = 600 kA per phase S= NEMA 4X stainless steel EMI/RFI Filters
D = 240V, 3Ø, 3W (Fig 4)Ž 80 = 800 kA per phase F= NEMA 1 flush mount 0 = Type 1 SPD
E = 277/480V, 3Ø, 4W (Fig 2) 1K = 1000 kA per phase P= NEMA 1 screwcover pullbox
F = 480V, 3Ø, 3W (Fig 4)Ž with extended display on 6ft T = Thru-door disconnect
G = 600V, 3Ø, 3W (Fig 4) cable for line side mounting
K = 380/220V, 3Ø, 4W (Fig 2) in SWBD/SWGRŒ X = Surge counter
L = 600/347V, 3Ø, 4W (Fig 2) (Standard)
S = 400/230V, 3Ø, 4W (Fig 2)

Example: TPS3C1560SX02 = Type 2 SPD (Default) for a 208/120V application with a surge Available Accessories:
current capacity of 600 kA per phase, in a NEMA 4X stainless steel enclosure with a surge Ordered Separately
counter and standard disconnect switch
RMSIE - Remote monitor
When an option is not selected, include a zero (0) in the field

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1200 700 /1200 700/1000 1000/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1000 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 1200 20 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 1800 20 kA 200 kA 550
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 20 kA 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Siemens Industry, Inc.


5400 Triangle Parkway
Figure 1 Figure 2 Figure 3 Figure 4 Norcross, GA 30092
Split Wye Hi-Leg Delta (B High) Delta & HRG Wye
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd 888-333-3545
1 Neu, 1 Grnd info.us@siemens.com
Order No. RPFL-S315C-0716
Notes: Printed in USA
ŒFor line side mounting in SWBD/SWGR ŽAvailable in 600 kA & 800 kA only All Rights Reserved.
Available in G voltage code only Available in 400 kA & 500 kA only ©2016 Siemens Industry, Inc.
06.03.16 Rev-
18
TPS3 L15
True 10 Mode Protection

Type 1 / Type 2 • SPD Specifications


• Surge Current Rating Per Phase
Surge Protective Device (SPD) For Line Per Phase L-N
600 kA
L-G L-L N-G
200 kA 200 kA 200kA 200kA
900 kA 300 kA 300 kA 300 kA 300 kA
Side or Load Side Applications • 100% monitoring (Every MOV is
monitored, incl. N-G)
• Individually fused and thermally
Features: • Type 2 SPDs intended for Load side protected MOVs
• UL 1449-4 Type 2 SPD, UL 1283 Listed, of Main Disconnect
• Solid state bi-directional operation
CSA 22.2 No. 269.2 • UL96A Lightning Protection Master • EMI/RFI filtering: Active tracking up
• Optional UL 1449 4th Edition Listed Label compliant (@20kA In) to -50 db from 10 kHz to 100 MHz
Type 1, CSA 22.2 No. 269.1 • Designed, manufactured and tested (Type 2 option only, includes UL
• Type 1 / Type 2 SPD consistent with: 1283 Listing)
• Mounts external to electrical • ANSI/IEEE C62.41.1-2002, • Repetitive impulse: 5,000 hits
distribution equipment C62.41.2-2002, C62.45-2002, • Less than 1 nanosecond response
• Recommended for line side or load C62.62-2010, C62.72-2007 & CSA time
side applications C22.2 No. 269.1 and .2 • Relative humidity range:
• When “P” option is selected, TPS3 15, • 1992/2000 NEMA LS-1 0 -95% non-condensing
• NEC Article 285 • Operating frequency: 47-63 Hz
Type 1 SPD mounts internal to: SB1, SB3
• IEC 61643, CE • Operating temperature:
and Type RCS switchboards, Type WL low
• 10 year warranty -25°C (-15°F) to +60°C (140°F)
voltage switchgear and TIASTAR motor
control centers
• Large block, individually fused,
thermally protected, 50 kA MOVs
• 20 kA In (most models)
• 200 kA SCCR (most models)
• Single TPS6 style replaceable modules
• Provides redundant replaceable
module protection for medium to high
exposure applications
• Internal rotary disconnect switch
included
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect

usa.siemens.com/spd
19
• Standard Configuration • SPD Monitoring
• Standard NEMA 1/12/3R/04 ANSI 61 steel enclosure • LED indicators
• Internal rotary disconnect switch • Audible alarm with silence switch and test button
• Wire size: #8 AWG to 1/0 • Dry contacts
• Standard size: 20” x 20” x 7” • Surge counter
(508 mm x 508 mm x 178 mm) *
• Standard weight: 64 lb. (29 kg) *
*Other NEMA ratings may increase enclosure size and weight

Ordering Information

TPS3 o L15 oo o X o2
Voltage Code Surge Current (kA) Enclosure Options

A = 120/240V, 1Ø, 3W (Fig 1) 60 = 600 kA per phase 0= Standard NEMA 1/12/3R/4 Steel 2 = Type 2 SPD (Default)
B = 120/240V, 3Ø, 4W (Fig 3) 90 = 900 kA per phase V= NEMA 4X non-metallic Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) S= NEMA 4X stainless steel EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) F= NEMA 1 flush mount 0 = Type 1 SPD
K = 380/220V, 3Ø, 4W (Fig 2) P= NEMA 1 screwcover pullbox
S = 400/230V, 3Ø, 4W (Fig 2) with extended display on 6ft T = Thru-door disconnect
cable for line side mounting
in SWBD/SWGR X = Surge counter
(Standard)

Example: TPS3CL15600X02 = 10 Mode, Type 2 SPD (Default) for a 208/120V application with a Available Accessories:
surge current capacity of 600 kA per phase, in a standard NEMA 1/12/3R/4 enclosure with a surge Ordered Separately
counter
RMSIE - Remote monitor
When an option is not selected, include a zero (0) in the field

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1200 700 /1200 700/1000 1000/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1000 20 kA 200 kA 150
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320

Hot (BLK) Phase A (BLK) Phase A (BLK)


}V A B Phase B (BLK) Phase B (ORNG)
}V Neutral (WHT)
N
Neutral (WHT) }V

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)

Siemens Industry, Inc.


Figure 1 Figure 2 Figure 3
5400 Triangle Parkway
Split Wye Hi-Leg Delta (B High)
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), Norcross, GA 30092
1 Neu, 1 Grnd
888-333-3545
info.us@siemens.com
Order No. RPFL-S3L15-0716
Printed in USA
All Rights Reserved.
©2016 Siemens Industry, Inc.
06.03.16 Rev-
20
TPS3 01
Type 1 / 2 Surge Protection Device (SPD) • 100% monitoring (Every MOV is
monitored, incl. N-G)
for P1, P2 Lighting Panelboards and P3 • EMI/RFI filtering: Active tracking up
to -50 db from 10 kHz to 100 MHz
Power Distribution Panelboards, Motor (Type 2 option only, includes UL
1283 Listing)
Control Centers and Busway Systems • Repetitive impulse: 5,000 hits
• Less than ½ nanosecond response
time
Features: • Designed, manufactured and tested • Relative humidity range:
• Mounts internal to: consistent with: 1-95% non-condensing
• P1, P2 and P3 panels • ANSI/IEEE C62.41.1-2002, • Operating frequency: 47-63 Hz
• TIASTAR motor control centers - C62.41.2-2002, C62.45-2002, • Operating temperature:
standard 6” bucket C62.62-2010, C62.72-2007 & CSA -25°C (-15°F) to +60°C (140°F)
• STP series busplug on SX series busway C22.2 No. 269.1 and .2
• Consult factory for field retrofit in P1 • 1992/2000 NEMA LS-1
panels • NEC Article 285
• UL 1449-4 Type 2 SPD, UL 1283 Listed, • IEC 61643, CE
CSA 22.2 No. 269.2 • 10 year warranty
• Optional UL 1449 4th Edition
Recognized Type 1, CSA 22.2 No. 269.1 • SPD Specifications
• Surge Current Rating Per Phase
• Type 1 / Type 2 SPD
Per Phase L-N L-G N-G
• Large block, individually fused, 100 kA 50 kA 50 kA 50 kA
thermally protected, 50 kA MOVs 150 kA 100 kA 50 kA 50 kA
200 kA 100 kA 100 kA 100 kA
• 20 kA In (most models) 250 kA 150 kA 100 kA 100 kA
• 200 kA SCCR (most models) 300 kA 150 kA 150 kA 150 kA

• Direct bus connected or can be wired


to a circuit breaker (include W option)
• UL96A Lightning Protection Master
Label compliant (@20kA In)
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect

usa.siemens.com/spd
21
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 100kA/phase • Dry contacts
• Inc. redundancy use: 200kA/phase • Surge counter
• Max. redundancy use: 300kA/phase

Ordering Information

TPS3 o 01 oo X oo2
Voltage Code Surge Current (kA) Options

A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase


B = 120/240V, 3Ø, 4W (Fig 3) 15 = 150 kA per phase W = Terminal lug
2 = Type 2 SPD (Default)
C = 120/208V, 3Ø, 4W (Fig 2) 20 = 200 kA per phase
Includes UL 1283
D = 240V, 3Ø, 3W (Fig 4) 25 = 250 kA per phase
EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) 30 = 300 kA per phase
0 = Type 1 SPD
F = 480V, 3Ø, 3W (Fig 4)
G = 600V, 3Ø, 3W (Fig 4)Œ
K = 380/220V, 3Ø, 4W (Fig 2) X = Surge counter
L = 600/347V, 3Ø, 4W (Fig 2) (Standard) B = Busway application
S = 400/230V, 3Ø, 4W (Fig 2) M = MCC application

Example: TPS3C0120X002 = Type 2 SPD (Default) for a 208/120V panelboard with a surge Available Accessories:
current capacity of 200 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In Type SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1200 20 kA Type 4 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1200 700 /1200 700 1800/1800 20 kA Type 4 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1200 20 kA Type 4 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 1200 10 kA Type 4 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA Type 4 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 1800 10 kA Type 4 200 kA 550
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA Type 4 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA Type 4 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 10 kA Type 4 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA Type 4 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Siemens Industry, Inc.


5400 Triangle Parkway
Figure 1 Figure 2 Figure 3 Figure 4 Norcross, GA 30092
Split Wye Hi-Leg Delta (B High) Delta & HRG Wye 888-333-3545
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd
1 Neu, 1 Grnd info.us@siemens.com
Order No. RPFL-S301C-0716
Printed in USA
Notes: All Rights Reserved.
Œ Available 100 kA & 150 kA only ©2016 Siemens Industry, Inc.
06.03.16 Rev-
22
TPS3 L1
True 10 Mode Protection • 100% monitoring (Every MOV is
monitored, incl. N-G)
• EMI/RFI filtering: Active tracking up
to -50 db from 10 kHz to 100 MHz
(Type 2 option only, includes UL
Type 1 / 2 Surge Protection Device (SPD) 1283 Listing)
• Repetitive impulse: 5,000 hits
for P1, P2 Lighting and P3 Power • Less than ½ nanosecond response
time
Distribution Panelboards, Motor Control • Relative humidity range:
1-95% non-condensing
Centers and Busway Systems • Operating frequency: 47-63 Hz
• Operating temperature:
-25°C (-15°F) to +60°C (140°F)
Features: • Designed, manufactured and tested
• Mounts internal to: consistent with:
• P1, P2 and P3 panels • ANSI/IEEE C62.41.1-2002,
• TIASTAR motor control centers - C62.41.2-2002, C62.45-2002,
standard 6” bucket C62.62-2010, C62.72-2007 & CSA
• STP series busplug on SX series busway C22.2 No. 269.1 and .2
• Consult factory for field retrofit in P1 • 1992/2000 NEMA LS-1
panels • NEC Article 285
• UL 1449-4 Type 2 SPD, UL 1283 Listed, • IEC 61643, CE
CSA 22.2 No. 269.2 • 10 year warranty
• Optional UL 1449 4th Edition
Recognized Type 1, CSA 22.2 No. 269.1 • SPD Specifications
• Directly connected discrete
• Type 1 / Type 2 SPD
protection elements between
• Large block, individually fused,
all possible modes providing true 10
thermally protected, 50 kA MOVs mode protection
• 20 kA In (most models) • Surge Current Rating Per Phase
• 200 kA SCCR (most models) Per Phase L-N L-G L-L N-G
• Direct bus connected or can be wired 150 kA 50 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA 100 kA
to a circuit breaker (include W option)
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect

usa.siemens.com/spd
23
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 150kA/phase • Dry contacts
• Max. redundancy use: 300kA/phase • Surge counter

Ordering Information

TPS3 o L1 oo X oo2
Voltage Code Surge Current (kA) Options

A = 120/240V, 1Ø, 3W (Fig 1) 15 = 150 kA per phase


B = 120/240V, 3Ø, 4W (Fig 3) 30 = 300 kA per phase W = Terminal lug
2 = Type 2 SPD (Default)
C = 120/208V, 3Ø, 4W (Fig 2)
Includes UL 1283
E = 277/480V, 3Ø, 4W (Fig 2)
EMI/RFI Filters
K = 380/220V, 3Ø, 4W (Fig 2)
0 = Type 1 SPD
S = 400/230V, 3Ø, 4W (Fig 2)

X = Surge counter B = Busway application


(Standard) M = MCC application

Example: TPS3CL130X002 = 10 Mode Type 2 SPD (Default) for a 208/120V panelboard with a Available Accessories:
surge current capacity of 300 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 800 /1500 700 /1200 700 1800/1800 20 kA 200 kA 150/320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1000 20 kA 200 kA 150
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320

Hot (BLK) Phase A (BLK) Phase A (BLK)


}V A B Phase B (BLK) Phase B (ORNG)
}V Neutral (WHT)
N
Neutral (WHT) }V

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)

Figure 1 Figure 2 Figure 3


Split Wye Hi-Leg Delta (B High)
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), Siemens Industry, Inc.
1 Neu, 1 Grnd 5400 Triangle Parkway
Norcross, GA 30092
888-333-3545
info.us@siemens.com
Order No. RPFL-S3L1C-0716
Printed in USA
All Rights Reserved.
©2016 Siemens Industry, Inc.
06.03.16 Rev-
24
TPS3 02
Type 1 / 2 Surge Protection Device (SPD)
for Revised P1 Lighting Panelboards
Features: • Designed, manufactured and tested • Repetitive impulse: 5,000 hits
• Mounts internal to: consistent with: • Less than ½ nanosecond response
• Revised P1 Lighting Panelboards • ANSI/IEEE C62.41.1-2002, time
• Consult factory for field retrofit in C62.41.2-2002, C62.45-2002, • Relative humidity range:
Revised P1 Lighting Panelboards C62.62-2010, C62.72-2007 & CSA 1-95% non-condensing
• UL 1449-4 Type 2 SPD, UL 1283 Listed, C22.2 No. 269.1 and .2 • Operating frequency: 47-63 Hz
• 1992/2000 NEMA LS-1 • Operating temperature:
CSA 22.2 No. 269.2
• NEC Article 285 -25°C (-15°F) to +60°C (140°F)
• Optional UL 1449 4th Edition
• IEC 61643, CE
Recognized Type 1, CSA 22.2 No. 269.1
• 10 year warranty
• Type 1 / Type 2 SPD
• Large block, individually fused,
• SPD Specifications
thermally protected, 50 kA MOVs • Surge Current Rating Per Phase
• 20 kA In (most models) Per Phase L-N L-G N-G
• 200 kA SCCR (most models) 100 kA 50 kA 50 kA 50 kA
150 kA 100 kA 50 kA 50 kA
• Direct bus connected 200 kA 100 kA 100 kA 100 kA
• Can be wired to a circuit breaker 250 kA 150 kA 100 kA 100 kA
300 kA 150 kA 150 kA 150 kA
(consult factory at time of order or see • 100% monitoring (Every MOV is
installation manual for retrofit) monitored, incl. N-G)
• UL96A Lightning Protection Master • EMI/RFI filtering: Active tracking up
Label compliant (@20kA In) to -50 db from 10 kHz to 100 MHz
• All UL required OCP & safety (Type 2 option only, includes UL
coordination included 1283 Listing)
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect

usa.siemens.com/spd
25
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 100kA/phase • Dry contacts
• Inc. redundancy use: 200kA/phase • Surge counter
• Max. redundancy use: 300kA/phase

Ordering Information

TPS3 o 02 oo X 2
Voltage Code Surge Current (kA) Option

A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase 2 = Type 2 SPD (Default)


B = 120/240V, 3Ø, 4W (Fig 3) 15 = 150 kA per phase Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 20 = 200 kA per phase EMI/RFI Filters
D = 240V, 3Ø, 3W (Fig 4) 25 = 250 kA per phase 0 = Type 1 SPD
E = 277/480V, 3Ø, 4W (Fig 2) 30 = 300 kA per phase
F = 480V, 3Ø, 3W (Fig 4)
G = 600V, 3Ø, 3W (Fig 4)Œ
X = Surge counter
K = 380/220V, 3Ø, 4W (Fig 2)
(Standard)
L = 600/347V, 3Ø, 4W (Fig 2)
S = 400/230V, 3Ø, 4W (Fig 2)

Example: TPS3C0220X2 = Type 2 SPD (Default) for a 208/120V panelboard with a surge current Available Accessories:
capacity of 200 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1200 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1200 700 /1200 700 1800/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1200 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 1200 10 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 1800 10 kA 200 kA 550
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 10 kA 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Siemens Industry, Inc.


5400 Triangle Parkway
Figure 1 Figure 2 Figure 3 Figure 4 Norcross, GA 30092
Split Wye Hi-Leg Delta (B High) Delta & HRG Wye 888-333-3545
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd
1 Neu, 1 Grnd info.us@siemens.com
Order No. RPFL-S302C-0716
Printed in USA
Notes: All Rights Reserved.
Œ Available 100 kA & 150 kA only ©2016 Siemens Industry, Inc.
06.03.16 Rev-
26
TPS3 L2
True 10 Mode Protection

Type 1 / 2 Surge Protection Device (SPD)


for Revised P1 Lighting Panelboards
Features: • Designed, manufactured and tested • Repetitive impulse: 5,000 hits
• Mounts internal to: consistent with: • Less than ½ nanosecond response
• Revised P1 Lighting Panelboards • ANSI/IEEE C62.41.1-2002, time
• Consult factory for field retrofit in C62.41.2-2002, C62.45-2002, • Relative humidity range:
Revised P1 Lighting Panelboards C62.62-2010, C62.72-2007 & CSA 1-95% non-condensing
• UL 1449-4 Type 2 SPD, UL 1283 Listed, C22.2 No. 269.1 and .2 • Operating frequency: 47-63 Hz
• 1992/2000 NEMA LS-1 • Operating temperature:
CSA 22.2 No. 269.2
• NEC Article 285 -25°C (-15°F) to +60°C (140°F)
• Optional UL 1449 4th Edition
• IEC 61643, CE
Recognized Type 1, CSA 22.2 No. 269.1
• 10 year warranty
• Type 1 / Type 2 SPD
• Large block, individually fused,
• SPD Specifications
thermally protected, 50 kA MOVs • Surge Current Rating Per Phase
• 20 kA In (most models) Per Phase L-N L-G L-L N-G
• 200 kA SCCR (most models) 150 kA 50 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA 100 kA
• Direct bus connected • 100% monitoring (Every MOV is
• Can be wired to a circuit breaker monitored, incl. N-G)
(consult factory at time of order or see • EMI/RFI filtering: Active tracking up
installation manual for retrofit) to -50 db from 10 kHz to 100 MHz
• UL96A Lightning Protection Master (Type 2 option only, includes UL
Label compliant (@20kA In) 1283 Listing)
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect

usa.siemens.com/spd
27
• Applications • Standard Monitoring
• Provides main service or downstream protection for • LED indicators
sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Standard redundancy use: 150 kA per phase • Dry contacts
• Maximum redundancy use: 300 kA per phase • Surge counter

Ordering Information

TPS3 o L2 oo X 2
Voltage Code Surge Current (kA) Option

A = 120/240V, 1Ø, 3W (Fig 1) 15 = 150 kA per phase 2 = Type 2 SPD (Default)


B = 120/240V, 3Ø, 4W (Fig 3) 30 = 300 kA per phase Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) 0 = Type 1 SPD
K = 380/220V, 3Ø, 4W (Fig 2)
S = 400/230V, 3Ø, 4W (Fig 2) X = Surge counter
(Standard)

Example: TPS3CL230X2 = 10 Mode Type 2 SPD (Default) for a 208/120V panelboard with a surge Available Accessories:
current capacity of 300 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 800 /1500 700 /1200 700 1800/1800 20 kA 200 kA 150/320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1000 20 kA 200 kA 150
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320

Hot (BLK) Phase A (BLK) Phase A (BLK)


}V A B Phase B (BLK) Phase B (ORNG)
}V Neutral (WHT)
N
Neutral (WHT) }V

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)

Figure 1 Figure 2 Figure 3


Split Wye Hi-Leg Delta (B High)
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High),
1 Neu, 1 Grnd Siemens Industry, Inc.
5400 Triangle Parkway
Norcross, GA 30092
888-333-3545
info.us@siemens.com
Order No. RPFL-S3L2C-0716
Printed in USA
All Rights Reserved.
©2016 Siemens Industry, Inc.
06.03.16 Rev-
28
TPS3 05
Type 1 / 2 Surge Protection Device (SPD)
for P4 & P5 Panelboards and Distribution
Switchboards
Features: • Panelboard Features
• Mounts internal to: • Copper or aluminum bus
• P4 & P5 panelboards and distribution • MB or MLO
switchboards
• UL 1449-4 Type 2 SPD, UL 1283 Listed, • SPD Specifications
CSA 22.2 No. 269.2 • Surge Current Rating Per Phase
Per Phase L-N L-G N-G
• Optional UL 1449 4th Edition
100 kA 50 kA 50 kA 50 kA
Recognized Type 1, CSA 22.2 No. 269.1 150 kA 100 kA 50 kA 50 kA
200 kA 100 kA 100 kA 100 kA
• Type 1 / Type 2 SPD 250 kA 150 kA 100 kA 100 kA
• Large block, individually fused, 300 kA 150 kA 150 kA 150 kA
thermally protected, 50 kA MOVs • 100% monitoring (Every MOV is
• 20 kA In (most models) monitored, incl. N-G)
• 200 kA SCCR (most models) • EMI/RFI filtering: Active tracking up
to -50 db from 10 kHz to 100 MHz
• All UL required OCP & safety
(Type 2 option only, includes UL
coordination included
1283 Listing)
• Type 1 SPDs intended for Line or
• Repetitive impulse: 5,000 hits
Load side of Main Disconnect
• Less than ½ nanosecond response
• Type 2 SPDs intended for Load side
time
of Main Disconnect
• Relative humidity range:
• UL96A Lightning Protection Master 1-95% non-condensing
Label compliant (@20kA In) • Operating frequency: 47-63 Hz
• Designed, manufactured and tested • Operating temperature:
consistent with: -25°C (-15°F) to +60°C (140°F)
• ANSI/IEEE C62.41.1-2002,
C62.41.2-2002, C62.45-2002, • Switchboard Features
C62.62-2010, C62.72-2007 & CSA • Copper or aluminum bus
C22.2 No. 269.1 and .2 • 200% rated neutral bus for
• 1992/2000 NEMA LS-1 harmonic-rich applications
• NEC Article 285 • CSA, UL 891, UL 67 and NEMA PB-2
• IEC 61643, CE
• 10 year warranty

usa.siemens.com/spd
29
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 100kA/phase • Dry contacts
• Inc. redundancy use: 200kA/phase • Surge counter
• Max. redundancy use: 300kA/phase • Internal rotary disconnect switch

Ordering Information

TPS3 o 05 oo X 2
Voltage Code Surge Current (kA) Option

A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase 2 = Type 2 SPD (Default)


B = 120/240V, 3Ø, 4W (Fig 3) 15 = 150 kA per phase Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 20 = 200 kA per phase EMI/RFI Filters
D = 240V, 3Ø, 3W (Fig 4) 25 = 250 kA per phase 0 = Type 1 SPD
E = 277/480V, 3Ø, 4W (Fig 2) 30 = 300 kA per phase
F = 480V, 3Ø, 3W (Fig 4) X = Surge counter
G = 600V, 3Ø, 3W (Fig 4)Œ (Standard)
K = 380/220V, 3Ø, 4W (Fig 2)
L = 600/347V, 3Ø, 4W (Fig 2)
S = 400/230V, 3Ø, 4W (Fig 2)

Example: TPS3C0530X2 = Type 2 SPD (Default) for a 208/120V power panel with a surge current Available Accessories:
capacity of 300 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1200 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1500 700 /1200 700 1800/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1200 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 1500 20 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 1800 10 kA 200 kA 552
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1500 1200 1200 2500 20 kA 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 10 kA 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1500 1200 1200 2500 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Siemens Industry, Inc.


5400 Triangle Parkway
Figure 1 Figure 2 Figure 3 Figure 4 Norcross, GA 30092
Split Wye Hi-Leg Delta (B High) Delta & HRG Wye 888-333-3545
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd
1 Neu, 1 Grnd info.us@siemens.com
Order No. RPFL-S305C-0716
Printed in USA
Notes: All Rights Reserved.
Œ Available 100 kA & 150 kA only ©2016 Siemens Industry, Inc.
06.03.16 Rev-
30
TPS3 L5
True 10 Mode Protection

Type 1 / 2 Surge Protection Device (SPD) • Repetitive impulse: 5,000 hits


• Less than ½ nanosecond response
for P4 & P5 Panelboards and Distribution time
• Relative humidity range:
Switchboards 1-95% non-condensing
• Operating frequency: 47-63 Hz
• Operating temperature:
Features: • Designed, manufactured and tested -25°C (-15°F) to +60°C (140°F)
• Mounts internal to: consistent with:
• P4 & P5 panelboards and distribution • ANSI/IEEE C62.41.1-2002, • Switchboard Features
switchboards C62.41.2-2002, C62.45-2002, • Copper or aluminum bus
• UL 1449-4 Type 2 SPD, UL 1283 Listed, C62.62-2010, C62.72-2007 & CSA • 200% rated neutral bus for
CSA 22.2 No. 269.2 C22.2 No. 269.1 and .2 harmonic-rich applications
• 1992/2000 NEMA LS-1 • CSA, UL 891, UL 67 and NEMA PB-2
• Optional UL 1449 4th Edition
Recognized Type 1, CSA 22.2 No. 269.1 • NEC Article 285
• IEC 61643, CE
• Type 1 / Type 2 SPD
• 10 year warranty
• Large block, individually fused,
thermally protected, 50 kA MOVs
• Panelboard Features
• Direct bus connected or can be wired
• Copper or aluminum bus
to a circuit breaker (include W option)
• MB or MLO
• 20 kA In (most models)
• 200 kA SCCR (most models) • SPD Specifications
• All UL required OCP & safety • Directly connected discrete
coordination included protection elements between
• Type 1 SPDs intended for Line or all possible modes providing true 10
Load side of Main Disconnect mode protection
• Type 2 SPDs intended for Load side • Surge Current Rating Per Phase
of Main Disconnect Per Phase L-N L-G L-L N-G
• UL96A Lightning Protection Master 150 kA 50 kA 50 kA 50 kA 50 kA
300 kA 100 kA 100 kA 100 kA 100 kA
Label compliant (@20kA In) • 100% monitoring (Every MOV is
monitored, incl. N-G)
• EMI/RFI filtering: Active tracking up
to -50 db from 10 kHz to 100 MHz
(Type 2 option only, includes UL
1283 Listing)

usa.siemens.com/spd
31
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 150kA/phase • Dry contacts
• Max. redundancy use: 300kA/phase • Surge counter
• Rotary disconnect switch

Ordering Information

TPS3 o L5 oo X 2
Voltage Code Surge Current (kA) Options

A = 120/240V, 1Ø, 3W (Fig 1) 15 = 150 kA per phase 2 = Type 2 SPD (Default)


B = 120/240V, 3Ø, 4W (Fig 3) 30 = 300 kA per phase Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) 0 = Type 1 SPD
K = 380/220V, 3Ø, 4W (Fig 2)
S = 400/230V, 3Ø, 4W (Fig 2) X = Surge counter
(Standard)

Example: TPS3CL530X2 = 10 mode Type 2 SPD (Default) for a 208/120V Power Panel with a Available Accessories:
surge current capacity of 300kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1200 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 800 /1500 700 /1200 700 1800/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1000 20 kA 200 kA 150
E 277/480V, 3Ø, 4W (Fig 2) 1500 1200 1200 1800 20 kA 200 kA 320
K 380/220V, 3Ø, 4W (Fig 2) 1500 1200 1200 1800 20 kA 200 kA 320
S 400/230V, 3Ø, 4W (Fig 2) 1500 1200 1200 1800 20 kA 200 kA 320

Hot (BLK) Phase A (BLK) Phase A (BLK)


}V A B Phase B (BLK) Phase B (ORNG)
}V Neutral (WHT)
N
Neutral (WHT) }V

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)

Figure 1 Figure 2 Figure 3


Split Wye Hi-Leg Delta (B High)
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High),
1 Neu, 1 Grnd Siemens Industry, Inc.
5400 Triangle Parkway
Norcross, GA 30092
888-333-3545
info.us@siemens.com
Order No. RPFL-S3L5C-0716
Printed in USA
All Rights Reserved.
©2016 Siemens Industry, Inc.
06.03.16 Rev-
32
TPS3 06
Type 1 / 2 Surge Protection Device (SPD) • SPD Specifications
• Surge Current Rating Per Phase
for Service Entrance Applications – Per Phase
100 kA
150 kA
L-N
50 kA
100 kA
L-G
50 kA
50 kA
N-G
50 kA
50 kA
SB1, SB2, SB3, Type RCS Switchboards, 200 kA
250 kA
100 kA
150 kA
100 kA
100 kA
100 kA
100 kA

Type WL Low Voltage Switchgear, Motor 300 kA


400 kA
150 kA
200 kA
150 kA
200 kA
150 kA
200 kA
500 kA 250 kA 250 kA 250 kA
Control Centers and Busway Systems • 100% monitoring (Every MOV is
monitored, incl. N-G)
• EMI/RFI filtering: Active tracking up
Features: • UL96A Lightning Protection Master to -50 db from 10 kHz to 100 MHz
• Mounts internal to: Label compliant (@20kA In) (Type 2 option only, includes UL
• SB1, SB2, SB3 & Type RCS • Designed, manufactured and tested 1283 Listing)
switchboards consistent with: • Repetitive impulse: 5,000 hits
• Type WL low voltage switchgear • ANSI/IEEE C62.41.1-2002, C62.41.2- • Less than ½ nanosecond response
• TIASTAR motor control centers - 2002, C62.45-2002, time
standard 12” bucket C62.62-2010, C62.72-2007 & CSA • Relative humidity range:
• STP series busplug on SX series C22.2 No. 269.1 and .2 1-95% non-condensing
busway • 1992/2000 NEMA LS-1 • Operating frequency: 47-63 Hz
• UL 1449-4 Type 2 SPD, UL 1283 Listed, • NEC Article 285 • Operating temperature:
CSA 22.2 No. 269.2 • IEC 61643, CE -25°C (-15°F) to +60°C (140°F)
• Optional UL 1449 4th Edition • 10 year warranty
Recognized Type 1, CSA 22.2
No. 269.1
• Type 1 / Type 2 SPD
• Large block, individually fused,
thermally protected, 50 kA MOVs
• 20 kA In (most models)
• 200 kA SCCR (most models)
• Rotary disconnect switch included
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect

usa.siemens.com/spd
33
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 300kA/phase • Dry contacts
• Inc. redundancy use: 450kA/phase • Surge counter
• Max. redundancy use: 500kA/phase • Rotary disconnect switch

Ordering Information

TPS3 o 06 oo X o2
Voltage Code Surge Current (kA) Options

A = 120/240V, 1Ø, 3W (Fig 1) 10 = 100 kA per phase


B = 120/240V, 3Ø, 4W (Fig 3) 15 = 150 kA per phase 2 = Type 2 SPD (Default)
X = Surge counter
C = 120/208V, 3Ø, 4W (Fig 2) 20 = 200 kA per phase Includes UL 1283
(Standard)
D = 240V, 3Ø, 3W (Fig 4) 25 = 250 kA per phase EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) 30 = 300 kA per phase 0 = Type 1 SPD
F = 480V, 3Ø, 3W (Fig 4) 40 = 400 kA per phase
G = 600V, 3Ø, 3W (Fig 4)Ž 50 = 500 kA per phase B = Busway applicationŒ
K = 380/220V, 3Ø, 4W (Fig 2) M = MCC applicationŒ
L = 600/347V, 3Ø, 4W (Fig 2)
S = 400/230V, 3Ø, 4W (Fig 2)
Available Accessories:
Example: TPS3C0640X002 = Type 2 SPD (Default) for a 208/120V switchboard with a surge
current capacity of 400 kA per phase and a surge counter
Ordered Separately
RMSIE - Remote monitor
When an option is not selected, include a zero (0) in the field WHXWDP120 = 10’ Display cable extension

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA)
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1200 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 700 /1200 700 /1200 700 1800/1800 20 kA 200 kA 150 / 320
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1200 20 kA 200 kA 150
D 240V, 3Ø, 3W (Fig 4) — 1200 — 1200 20 kA 200 kA 320
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
F 480V, 3Ø, 3W (Fig 4) — 1800 — 1800 20 kA 200 kA 550
G 600V, 3Ø, 3W (Fig 4) — 2500 — 2500 10 kA 200 kA 690
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320
L 600/347V, 3Ø, 4W (Fig 2) 1500 1500 1500 2500 20 kA 200 kA 420
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 2000 20 kA 200 kA 320

Phase A (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V

}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)

}
Hot (BLK) Phase C (BLK)
V Phase C (BLK)
Phase C (BLK) Neutral (WHT)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)

Figure 1 Figure 2 Figure 3 Figure 4 Siemens Industry, Inc.


Split Wye Hi-Leg Delta (B High) Delta & HRG Wye 5400 Triangle Parkway
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), 3 Hots, 1 Grnd Norcross, GA 30092
1 Neu, 1 Grnd
888-333-3545
Notes:
info.us@siemens.com
ΠG voltage code only available in 200 & 250 kA
 Not available in 500 kA Order No. RPFL-S306C-0716
Ž Available in 100 kA, 150 kA, 200 kA & 250 kA only Printed in USA
 VPR may increase when disconnect switch is added All Rights Reserved.
VPR may decrease for products 400 & 500 kA per phase ©2016 Siemens Industry, Inc.
 In rating for 100 - 300 kA per phase is 10 kA 06.03.16 Rev-
34
TPS3 L6
True 10 Mode Protection

• SPD Specifications
Type 1 / 2 Surge Protection Device (SPD) • Directly connected discrete

for Service Entrance Applications – protection elements between all


possible modes providing true

SB1, SB2, SB3, Type RCS Switchboards, 10 mode protection


• Surge Current Rating Per Phase

Type WL Low Voltage Switchgear, Motor Per Phase


150 kA
300 kA
L-N
50 kA
100 kA
L-G
50 kA
100 kA
L-L
50 kA
100 kA
N-G
50 kA
100 kA
Control Centers and Busway Systems 450 kA 150 kA 150 kA
• 100% monitoring (Every MOV is
150 kA 150 kA

monitored, incl. N-G)


Features: • Designed, manufactured and tested • EMI/RFI filtering: Active tracking up
• Mounts internal to: consistent with: to -50 db from 10 kHz to 100 MHz
• SB1, SB2, SB3 & Type RCS • ANSI/IEEE C62.41.1-2002, C62.41.2- (Type 2 option only, includes UL
switchboards 2002, C62.45-2002, 1283 Listing)
• Type WL low voltage switchgear C62.62-2010, C62.72-2007 & CSA • Repetitive impulse: 5,000 hits
• TIASTAR motor control centers - C22.2 No. 269.1 and .2 • Less than ½ nanosecond response
standard 12” bucket • 1992/2000 NEMA LS-1 time
• STP series busplug on SX series • NEC Article 285 • Relative humidity range:
busway • IEC 61643, CE 1-95% non-condensing
• UL 1449-4 Type 2 SPD, UL 1283 Listed, • 10 year warranty • Operating frequency: 47-63 Hz
• Operating temperature:
CSA 22.2 No. 269.2
-25°C (-15°F) to +60°C (140°F)
• Optional UL 1449 4th Edition Listed
Type 1, CSA 22.2 No. 269.1
• Type 1 / Type 2 SPD
• Large block, individually fused,
thermally protected, 50 kA MOVs
• 20 kA In (most models)
• 200 kA SCCR (most models)
• Rotary disconnect switch included
• All UL required OCP & safety
coordination included
• Type 1 SPDs intended for Line or
Load side of Main Disconnect
• Type 2 SPDs intended for Load side
of Main Disconnect
• UL96A Lightning Protection Master
Label compliant (@20kA In)

usa.siemens.com/spd
35
• Applications • SPD Monitoring
• Provides main service entrance or downstream protection • LED indicators
for sensitive computer and electronic loads • Audible alarm with silence switch and test button
• Std. redundancy use: 300kA/phase • Dry contacts
• Max. redundancy use: 450kA/phase • Surge counter
• Rotary disconnect switch

Ordering Information

TPS3 o L6 oo X o2
Voltage Code Surge Current (kA) Options

A = 120/240V, 1Ø, 3W (Fig 1) 15 = 150 kA per phase 2 = Type 2 SPD (Default)


B = 120/240V, 3Ø, 4W (Fig 3) 30 = 300 kA per phase Includes UL 1283
C = 120/208V, 3Ø, 4W (Fig 2) 45 = 450 kA per phase EMI/RFI Filters
E = 277/480V, 3Ø, 4W (Fig 2) 0 = Type 1 SPD
K = 380/220V, 3Ø, 4W (Fig 2)
S = 400/230V, 3Ø, 4W (Fig 2) B = Busway application
M = MCC application

X = Surge counter
(Standard)

Example: TPS3CL645X02 = 10 mode Type 2 SPD (Default) for a 208/120V switchboard with a Available Accessories:
surge current capacity of 450 kA per phase and a surge counter Ordered Separately
When an option is not selected, include a zero (0) in the field
RMSIE - Remote monitor

UL 1449 Fourth Edition - Test Data


Voltage Protection Rating (VPR - 6 kV, 3 kA) Œ
Voltage Code Service Voltage L-N L-G N-G L-L In SCCR MCOV
A 120/240V, 1Ø, 3W (Fig 1) 700 700 700 1000 20 kA 100 kA 150
B 120/240V, 3Ø, 4W (Fig 3) 800 /1500 700 /1200 700 1800/1800 20 kA 200 kA 150 / 275
C 120/208V, 3Ø, 4W (Fig 2) 700 700 700 1000 20 kA 200 kA 150
E 277/480V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
K 380/220V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320
S 400/230V, 3Ø, 4W (Fig 2) 1200 1200 1200 1800 20 kA 200 kA 320

Hot (BLK) Phase A (BLK) Phase A (BLK)


}V A B Phase B (BLK) Phase B (ORNG)
}V Neutral (WHT)
N
Neutral (WHT) }V

}
Hot (BLK) Phase C (BLK)
V
Phase C (BLK) Neutral (WHT)
Ground (GRN) C Ground (GRN)
Ground (GRN)

Siemens Industry, Inc.


Figure 1 Figure 2 Figure 3
5400 Triangle Parkway
Split Wye Hi-Leg Delta (B High)
2 Hots, 1 Neu, 1 Grnd 3 Hots, 1 Neu, 1 Grnd 3 Hots, (B High), Norcross, GA 30092
1 Neu, 1 Grnd
888-333-3545
info.us@siemens.com
Order No. RPFL-S3L6C-0716
Notes: Printed in USA
ΠVPR may increase when disconnect switch is added All Rights Reserved.
VPR may decrease for 450 kA per phase ©2016 Siemens Industry, Inc.
06.03.16 Rev-
36
SPD Product Catalog | FAQ

Frequently Asked Questions


What is a Surge Protective Device What is Surge Current Capacity? Safety: 1) the individual suppression
or SPD? circuit should be fused to clear an
Surge current capacity is the maximum inoperative MOV during an extreme
A Surge Protective Device is a device amount of surge current that a surge transient event, and 2) provide
that attenuates (reduces in magnitude) suppressor can pass for a single transient overcurrent protection for the surge
random, high energy, short duration event. This level is used to indicate the suppressor during a fault condition.
overvoltages caused by lightning, protection capacity of a particular surge
utilities, switching, etc. Such anomalies suppressor design, and when specifying What Surge Current Capacity is
occur in the form of voltage and current surge suppressors. For example, in a required?
spikes with a duration of less than half high exposure application with very
an AC voltage cycle. These high energy large transients present from lightning, a Surge current capacity is dependent
power spikes can damage sensitive higher level surge current capacity might on the application and the amount of
electronic equipment, such as computers, be desired. Be aware that surges have required protection. The selection of
instrumentation, and process controllers. natural limitations and that larger surge the proper surge suppressor is not an
current capacity tends to add redundancy exact science and cannot be scientifically
rather than the implied ability to handle
How do SPDs work? calculated from a standard algorithm.
an extremely large surge. For example, an
entire lightning strike cannot go through Questions to consider when specifying the
Surge Suppressors divert high energy
wire; it is much like trying to put the proper surge current capacity for a surge
power away from a load by providing
output from a fire hose through a soda suppressor include:
a lower impedance path to common
straw. Consequently, suppressors do
point earth ground. This is similar in
not need to be sized for entire lightning • What is the geographic location of the
concept to pressure relief valves that
strikes. There are valid reasons for facility and it’s susceptibility to
protect water heaters from overpressure.
adding excess surge current capacity for lightning? (For example, Florida is a
Surge suppressors used most often for high-lightning area; California is a
redundancy reasons.
protection of AC Power have metal oxide low lightning area.)
varistors (MOVs) connected in parallel. • Is the facility in a rural or urban setting?
What types of components • Is the facility the tallest building around?
Where are SPDs installed? make up a SPD? • Is the facility at the end of the utility grid?
• If it is an existing facility, what is its power
The device most commonly used in AC quality history?
AC voltage surge suppressors are typically
installed in these three areas: at a utility voltage surge suppressors are MOVs,
a solid-state device made of zinc oxide Based on the above information, and
service entrance for protection of an
materials. taking into account the cost of protection,
entire facility, in distribution panelboards
the following is a good rule of thumb:
and switchboards for protection of
MOVs are voltage sensitive a surge suppressor with a surge current
sensitive downstream loads; connected to
semiconductors, which change from capacity in the range of 100kA to
a wall outlet for individual protection of
high impedance to low impedance when 300kA would be used in conjunction
a specific piece of equipment, such as a
sensing an overvoltage condition. MOVs with a service entrance panelboard or
computer or solid-state controller.
are packaged for specific voltages and switchboard. A surge suppressor with
current handling capacities. a surge current capacity in the range
What is Clamping Voltage? of 100kA to 200kA would be used
Other devices (more typically found in in conjunction with a downstream
Clamping voltage, also referred to as panelboard.
DC applications) include single junction
peak let through or suppressed voltage
diodes and gas tubes that ionize at preset
rating, is the amount of voltage a surge
voltages.
suppressor permits to pass through it
to the attached load during a transient
event. Clamping voltage is a performance What features should be
measurement of a surge suppressor’s considered When selecting SPDs?
ability to attenuate a transient. For
example, a surge suppressor might limit a Two important areas to consider during
6,000V surge so that only 700V is ‘visible’ the selection of a surge suppressor are
to the load. The Voltage Protection Rating performance and safety, and include the
is 700V, commonly called Clamping following criteria:
Voltage. This performance value is
confirmed by Underwriters Laboratories Performance: 1) surge current capacity;
during tests conducted while evaluating a and 2) clamping voltage.
surge suppressor for listing.

37
SPD Product Catalog | Team Services and Support

Siemens SPD Team


Services and Support
Our Commitment to You

As our commitment Pre-Bid Support Post-Bid Support


to you, the Siemens
• Over 1000 jobs are downloaded per month Project Tracking to Conclusion
SPD Team is here to
from the Electronic Plan Rooms, which provides
assist you with all of us with complete take-offs, from drawings & Electrical Contractor Award Notification
your surge protection specs. • After bid day, we determine which Electrical
needs. Each region is • Notifications are sent to the Siemens Sales Contractor won the job.
Engineer and Siemens distributor, listing the • Electrical Contractor information is promptly
designated with a highly jobs bidding in your area. sent to the Siemens Sales Engineer and
trained representative to • Detailed quotes with product information Siemens Distributor to make sure they are the
provide you with the best are sent to the Siemens Sales Engineer and first to know.
Siemens distributor to enter into COMPAS or
support possible.
Industry Mall. Job Follow Up
• Prior Approval Packages (PAPs) are sent on any • Ensures that you are competitively priced to
jobs where Siemens Surge Protective Devices are win job.
not approved. • Shop Drawing Submittals are provided
1. Sending PAPs allow us to identify to Siemens Sales Engineer and Siemens
Consulting Engineers who specify Distributor.
Siemens gear but not Surge Protective • Engineering support is provided for any
Devices. This is done in an effort to gain rejections or questions from Consulting
approval. Engineers.
2. We have over 27 years of approval
history documented in our proprietary Ongoing Support
database.
• Customized Collaterals (i.e. flyers, handouts…)
• Design Guides
• Proper Product Selection Recommendations
• Competitor Product Comparison
• Specification Interpretation
• Webinars/Lunch & Learns
• On Site Visits
• Seminars at the Factory for CEU/PDH Credits
• 24/7 Online SPD Training via
usa.siemens.com/step
• Troubleshooting
• Product Forensics
• Returns

38
Thank you...
for choosing Siemens for your
surge protection needs.

Your technical support team is here to assist you.


(888) 333-3545

Learn more about our TPS3 Surge Protective Devices


(SPDs) by visiting: Step 2000 - Basics of Surge Protection at
usa.siemens.com/step.

usa.siemens.com/spd

39
Siemens Industry, Inc.
5400 Triangle Parkway
Norcross, GA 30092
For more information, please contact our Customer Support Center.
Phone: +1 888 333 3545
Fax: +1 727 539 8955
E–mail: info.us@siemens.com
Web: usa.siemens.com/spd
Article-No. RPCA-SPDCA-1216
Printed in USA
All rights reserved
© 2016, Siemens Industry, Inc.
The information provided in this manual contains merely general
descriptions of characteristics of performance which in case of actual use
do not always apply as described or which may change as a result of
further development of the product. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.
09.07.16 RevB