Appendix Vii Typical Fouling Resistance Coefficients: Unit Select Resistance ft2 H°f / Btu
Appendix Vii Typical Fouling Resistance Coefficients: Unit Select Resistance ft2 H°f / Btu
Unit Select Resistance ft2 h°F / Btu Resistance ft2 h°F / Btu
Boiler Blowdown 2.00E-03 2.00E-03 2.00E-03 2.00E-03
Boiler Feed (Treated) 1.00E-03 5.00E-04 1.00E-03 1.00E-03
Brackish Water 2.00E-03 1.00E-03 3.00E-03 2.00E-03
City Water 1.00E-03 1.00E-03 2.00E-03 2.00E-03
Condensate 5.00E-04 5.00E-04 5.00E-04 5.00E-04
Treated MakeUp 1.00E-03 1.00E-03 2.00E-03 2.00E-03
Cooling Tower
Untreated MakeUp 3.00E-03 3.00E-03 5.00E-03 4.00E-03
Distilled Water 5.00E-04 5.00E-04 5.00E-04 5.00E-04
Engine Jacket (Closed System) 1.00E-03 1.00E-03 1.00E-03 1.00E-03
Hard Water (Over 15 Grains/Gal) 3.00E-03 3.00E-03 5.00E-03 5.00E-03
Muddy Or Silty Water 3.00E-03 2.00E-03 4.00E-03 3.00E-03
Minimum 2.00E-03 1.00E-03 3.00E-03 2.00E-03
River Water
Average 3.00E-03 2.00E-03 4.00E-03 3.00E-03
Sea Water 5.00E-04 5.00E-04 1.00E-03 1.00E-03
Treated MakeUp 1.00E-03 1.00E-03 2.00E-03 2.00E-03
Spray Pond
Untreated MakeUp 3.00E-03 3.00E-03 5.00E-03 4.00E-03
PAGE 25 OF 30
MNL 032A Issued 29 August 08, Prepared by J.E.Edwards of P & I Design Ltd, Teesside, UK www.pidesign.co.uk