Surge protective devices

Eaton SPD Series


For mounting external to electrical distribution equipment
Eaton SPD Series sidemount Applications In addition to externally Features
surge protective devices generated surge events, such
The increasing necessity for as lightning and grid switching,
• Uses thermally protected
facility-wide surge protection equipment is also susceptible to metal oxide varistor
Eaton sidemount versions (MOV) technology
damage by internally generated
of the SPD Series surge The ever-increasing use of
surges. In fact, the majority of • 20 kA nominal discharge
protective devices are the microprocessors and other
surges are generated internally current (In) rating (maximum
sensitive electronic equipment
latest and most advanced has increased the necessity for
by commonly used items, such rating assigned by UL)
ULT 1449 3rd Edition certified as fluorescent lighting ballasts,
facility-wide surge protection. • 50 through 400 kA surge
light dimmers, photocopiers, fax
surge protectors. Application These sensitive electronic current capacity ratings
machines and variable frequency
of SPD Series units throughout components are used within
drives. This further reinforces the • Three feature package options
many pieces of equipment,
a facility will ensure that necessity for facility-wide surge
including computers, • Factory-sealed assembly
equipment is protected with protection applied at all stages
programmable logic controllers, prevents arc flash and
of the electrical distribution
the safest and most reliable and other commonly used shock hazards
system, from the electrical
electrical and electronic
surge protective devices service entrance down to the • Contains no replaceable
equipment. Surges can wreak
available. Units are available single-phase loads. parts or items that require
havoc on equipment, causing
in all common voltages and catastrophic failures, process periodic maintenance
Standards
configurations, and also in interruptions and premature • Optional internal
and certifications
aging leading to failure. The disconnect available
a variety of surge current application of surge protective • UL 1449 3rd Edition
capacity ratings from 50 devices (SPDs) can mitigate • 200 kA short-circuit current
• Canadian Standards rating (SCCR)
through 400 kA. Three feature problems with sensitive
Association (CSAT)
package options are also electronic equipment, keeping • 10-year warranty (15 years
the equipment and the related with registration)
available to choose from. processes up and running reliably
without disruption or damage
due to surge-related events. The breadth of the SPD
Series’ features, options and
configurations ensures that the
correct unit is available for all
electrical applications, including
service entrances, distribution
switchboards, panelboards and
point-of-use applications.
The SPD Series makes surge items, further increases user 20 kA nominal discharge
suppression safer than ever safety, as contact with live current rating (In)
The SPD Series employs safety
electrical parts is neither
The entire SPD Series product
SPD Series unit
possible nor necessary.
and design features that make offering has a nominal discharge
surge protection safer than ever. Compact size current (In) of 20 kA, the highest
Unlike many surge protective achievable rating for this
devices, the SPD Series contains Sidemount versions of the important parameter. This is
no user-serviceable parts or SPD Series are compact in a new rating for SPDs that is
items that require periodic size, taking up less space in the included as part of UL 1449
maintenance, such as replaceable electrical room. Units housed 3rd Edition testing and certifi-
surge modules, replaceable in NEMAT 1 rated enclosures cation. This rating provides an
fuses, surge counter memory in the 50 kA through 200 kA indication of the SPD’s design
backup batteries or wire lugs surge current capacity range robustness and ability to handle
that require periodic retightening. are housed in a 74-square-inch a number of large-magnitude
Sidemount versions of the unit enclosure that is only 3.50 inches surges over a short period of
are factory-sealed, meaning no deep. Units housed in NEMA 1 time and remain operational
potential contact with harmful rated enclosures in the 250 kA within tested parameters.
voltages present within the unit through 400 kA surge current
capacity range are housed in a During In testing, the SPD is
is possible.
74-square-inch enclosure that is subjected to 15 surges of a
The SPD Series sidemount only 6.00 inches deep. current magnitude chosen by
series has also taken safety to the SPD’s manufacturer. Valid
the next level by using thermally Enhanced protection current magnitude choices for
protected MOVs as its core status indicators the test are 20 kA and 10 kA for
surge suppression component. Type 1 SPDs. Valid choices for
These thermally protected The Eaton SPD Series has Type 2 SPDs are 20 kA, 10 kA,
MOVs operate in a safe elevated the features normally 5 kA and 3 kA. The 15 surges Eaton SPD Series sidemount
manner, even when subjected found within surge protective are then applied at the value unit mounted externally to an
to abnormal conditions, such devices to the next level. Unlike chosen by the manufacturer. Eaton panelboard.
as temporary overvoltages or many surge protectors that
may have only single-colored Prior to the start of In testing,
high fault current conditions.
indicators that simply indicate a preliminary voltage protection
When one of these conditions
whether power is applied to rating (VPR) is measured. The
exists, the thermally protected
the surge protective device, VPR is the measured let-through
MOVs are removed from the
each SPD Series unit includes voltage of the unit when a
circuit quickly and safely before
dual-colored protection status 6 kV, 3 kA surge is applied. This
a potentially unsafe condition
light emitting diodes (LEDs) value is documented and saved
can occur, with absolutely no
that indicate the true status of as a reference. After all surges
discharge of smoke or ionized
the protection. On three-phase have been applied, the VPR
gases. Using the latest in
units, if power is removed from is measured once again and
technology and surge protective
a phase, the unit’s protection compared to the value that was
device design, the SPD Series
status LEDs continue to indicate recorded prior to the 15-surge
provides safe, reliable, worry-
the status of the protection on sequence. In order to pass the
free surge protection.
that phase, not the status of In test, the SPD must survive all
15 surges, and the measured All SPD Series sidemount units
Prewired the power applied to the phase. come prewired and include a
This new feature ensures pre- and post-VPR values must
All SPD Series sidemount units be within ±10% of each other. factory-installed conduit
that the user is supplied with interface, making installation
are prewired at the factory and accurate information concerning
contain a factory-installed conduit Choosing an SPD with an In very easy.
the status of the protection the of 20 kA ensures that your
interface, making installation SPD is supplying on the phase,
very easy. Simply mount the unit, equipment is being protected
not the status of the power by a unit that will continue to
perform any required conduit applied to the phase.
runs, and land all required wires maintain a high level of surge
to the electrical assembly that All units that require a neutral protection performance, even
the unit is being interfaced with. wire connection also contain an after being subjected to multiple
No internal wiring connections additional set of dual-colored high-magnitude surges.
or access to the inside of the LEDs that report the status of the Industry standards for lightning
unit is required. protection in the neutral-ground protection systems require the
(N-G) protection mode. Like the installed SPDs to have a nominal
Factory-sealed phase protection status LEDs, discharge current of 20 kA.
the N-G protection status LEDs The 2008 Edition of National
All SPD Series sidemount
also report the true status of the Fire Protection Agency (NFPAT) All SPD Series units are factory-
units are factory-sealed. This
protection in the N-G mode. Standard 780, titled “Standard sealed, ensuring that the user/
preventive safety measure
for the Installation of Lightning installer has no potential of
eliminates potential arc flash Although most SPDs on the
Protection Systems,” states coming into contact with
and shock hazards, as the market contain N-G mode harmful voltages present
user/installer has no chance protection, they do not monitor the requirement in Section
4.18.3.1.2. The 2007 Edition inside the unit.
of coming into contact with and indicate the status of
energized electrical components the protection in that mode. of Underwriters Laboratories
within the unit. In addition, the Specifying the SPD Series’ (UL) Standard 96A, titled
unit contains no user-replaceable N-G protection mode status “Installation Requirements for
or serviceable items, such as indication feature will ensure Lightning Protection Systems,”
surge modules, fuses, backup that users are supplied states the requirement in
batteries for the surge counter’s with complete and accurate Section 13.1. Choosing an SPD
memory or wire lugs that information concerning the with an In of 20 kA will ensure
require periodic retightening. surge protective device’s that compliance with these
Factory-sealing all units, coupled protection status. standards can be achieved.
with the lack of replaceable

2 EATON CORPORATION  Surge protective devices 


Feature package options Basic feature package Standard feature package Standard with surge
counter feature package
The SPD Series provides users The basic feature package is The standard feature package
with the option of selecting perfect for applications where includes all of the features found The standard with surge
between three feature packages. basic, cost-effective, safe and in the basic feature package, counter feature package includes
These feature packages are the reliable surge protection is plus an audible alarm with all of the features found in the
basic, standard and standard required but budgets don’t silence button, EMI/RFI filtering, standard feature package plus
with surge counter. The proper allow for extra, additional and a Form C relay contact a six-digit surge counter with a
feature package can be selected features. Rather than sacrifice that can be used for remote reset button. The surge counter
based on the requirements of the performance or safety due to annunciation of the SPD’s status. indicates the ongoing count of
application or the specification. cost, SPD Series units with the The audible alarm activates the number of surges the unit
basic feature package provide and the Form C relay contact has been exposed to and stores
you with high-performing surge changes state when any loss of them in nonvolatile memory.
protection without sacrificing protection is detected or a fault Should power to the SPD Series
safety or reliability. The basic condition exists with the unit. unit be completely interrupted,
feature package provides the Should such a condition occur, the surge counter will recall and
same level of surge protection the audible alarm can be display the surge count prior to
and safety provided by the silenced by pressing the silence the interruption when power
standard package and the button. The EMI/RFI filter is restored. Unlike many surge
standard with surge counter provides up to 50 dB of noise protectors, the SPD Series’
feature package minus some of attenuation over the range of surge counter memory feature
the features found in them. The 10 kHz through 100 MHz. does not require a backup
package contains dual-colored battery that would require
protection status LEDs that periodic replacement in order to
report the true status of the achieve its memory functionality.
protection in each phase/mode.
All four-wire plus ground units
also contain an additional set of
dual-colored protection status
LEDs that report the status of
the protection in the N-G mode.

Side-by-side comparison of the SPD Series’ available feature packages


Standard with
Feature Package Comparison Basic Standard Surge Counter
Surge protection using thermally protected MOV technology n n n
Dual-colored protection status indicators for each phase n n n
Dual-colored protection status indicators for the N-G protection mode n n n
Audible alarm with silence button n n
Form C relay contact n n
EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz n n
Surge counter with reset button n

EATON CORPORATION  Surge protective devices  3


Specifications
Description Ratings
Surge current capacity per phase 50, 80, 100, 120, 160, 200, 250, 300 and 400 kA ratings available
Nominal discharge current (In) 20 kA
Short-circuit current rating (SCCR) 200 kA
SPD type Basic Feature Package = Type 1 (can also be used in Type 2 applications)
Standard and Standard with Surge Counter Feature Packages = Type 2
System voltages available (Vac)
Single split-phase (three-wire plus ground) 120/240
Three-phase wye (four-wire plus ground) 120/208, 127/220, 230/400, 277/480, 347/600
Three-phase delta (three-wire plus ground) 240, 480, 600
Three-phase high leg delta (four-wire plus ground) 120/240
Input power frequency 50/60 Hz
Protection modes
Single split-phase L-N, L-G, L-L, N-G
Three-phase wye L-N, L-G, L-L, N-G
Three-phase delta L-G, L-L
Three-phase high leg delta L-N, L-G, L-L, N-G
Operating temperature –40°C through 50°C (–40°F through 122°F)
Operating humidity 5% through 95%, noncondensing
Agency certifications and approvals UL 1449 3rd Edition listed device; CSA listed; UL 1283 (Type 2 SPDs only)
Warranty 10 years (15 years when registered on www.eaton.com/spd)

SPD Series catalog number configuration for units mounted external to electrical distribution equipment

SPD 250 480D 2 K

Series
kA Rating Application—Sidemount Units
SPD = Surge
Voltage Code Feature Package
protective 050 = 50 kA per phase K = NEMA 1 enclosure
device 080 = 80 kA per phase 240S = 120/240 single split-phase 1 = Basic L = NEMA 1 flushmount enclosure 2
100 = 100 kA per phase 208Y = 120/208 wye (4W + G) 2 = Standard M = NEMA 1 enclosure with internal disconnect
120 = 120 kA per phase 220Y = 127/220 wye (4W + G) 3 = Standard with N = NEMA 4 enclosure
160 = 160 kA per phase 400Y = 230/400 wye (4W + G) surge counter O = NEMA 4 enclosure with internal disconnect
200 = 200 kA per phase 480Y = 277/480 wye (4W + G) P = NEMA 4X enclosure (stainless steel)
250 = 250 kA per phase 600Y = 347/600 wye (4W + G) Q = NEMA 4X enclosure with internal disconnect
300 = 300 kA per phase 240D = 240 delta (3W + G) (stainless steel)
400 = 400 kA per phase 480D = 480 delta (3W + G)
600D = 600 delta (3W + G)
240H = 240 delta high leg (4W + G)
on 'B' phase 1

Example: SPD250480D2K = SPD Series, 250 kA per phase, 480D voltage, standard feature package, housed in NEMA 1 enclosure
A Please consult the factory for 240 delta high leg (4W + G) applications with high leg on ‘C’ phase.
B NEMA 1 flushmount units are available in 50–200 kA ratings only.