Professional Documents
Culture Documents
Water Supply Hydraulics Calculation: Transmission Pipeline
Water Supply Hydraulics Calculation: Transmission Pipeline
Hydraulics Calculation
Design Guidelines
1 MWA Design Guidelines
2 PUAS Design Guidelines
3 B.S. 534
4 Relevant Standards
HGL
SWP
Rp
Source
point
Supply
point
Design Criteria
Pipe's material = C.L.M.S.
Hazen-williams coefficient C = 100
Total planar length of pipeline L 15,000 m
Tapping Point
Safe Water Pressure at tapping source SWP = 60.00 m ODL
Supply Point
Platform Level @ source point PL = 37.00 m ODL
Note: Supply point is at Suction Tank
within development site
hence
Required Supply Level (min) @ supply point RSL = TWL+Rp
= 50 m ODL
Water Demand
Ultimate Demand Qa = 441,000 CuM/day
= 98.00 Mgd
From Hazen-Williams
Major frictional loss Hf = [10.6*Qd^1.85]
C^1.85*Di^4.87
Rp Residual Pressure
PL Platform Level
TWL Top Water Level
BWL Bottom Water Level
SWP Safe Water Pressure
HGL
SWP
60.00
mODL
Rp
11.86 m 51.86
Level (PL) m ODL
37.00 37.00 Level
mODL (ODL) 40.00
mOLD
Datum
Hydraulics Diagram