FIRE AND LIFE SAFETY zSYSTEM


READINESS – LUSAIL STADIUM

By WSP
Date 12/02/2022
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Objective
The aim of this report is to have a general understanding of
readiness of Life safety system installed in Lusail stadium in view
of proposed tournament to be taken place in the month of march
2022.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

SITE WISE OBSERVATIONS


The present Report highlight the observation that required attention in order to enter in
Tournament mode and are related to the following systems:

Architectural

Electrical

Mechanical
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

ARCHITECTURAL

Master Door Schedule & Door Key Plan not finalized, pending contractor revised submittal to
SC. Most door installation IRWs not approved. Door type including fire rated category,
hardware and accessories required to be verified at site to comply with the SC approved
Master Door Schedule & Door Key Plan, which still pending re-submission from contractor.

Exit Directional Signage completed installed but IRWs not approved. The signage type, location
and direction required to be verified at site to comply with QCDD approved Life and Safety
drawings. However, this could only be done if all areas at site are accessible, with all doors not
locked.

Evacuation Layout Plan (Zone Chart) completed installed but not inspected and no IRW raised.
The installation required to be verified at site to comply with QCDD approved Life and Safety
drawings.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)
CORE 18 CORE 17
LEVEL 0

CORE 23 CORE 12

CORE 26 CORE 9

CORE 1 CORE 6

CORE 3 CORE 4
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

LEVEL 1

CORE 23 CORE 12

CORE 26 CORE 9
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

LEVEL 2

CORE 23 CORE 12

CORE 26 CORE 9
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

LEVEL 3

CORE 1 CORE 6
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)
CORE 18 CORE 17

LEVEL 4

CORE 1 CORE 6
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

LEVEL 6

CORE 23 CORE 12

CORE 26 CORE 9

CORE 3 CORE 4
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)
CORE 18 CORE 17

LEVEL 8

CORE 3 CORE 4
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)
ELECTRICAL SYSTEM
LIFE SAFETY GENERATORS
Details of last preventive maintenance done to be collected, including the details of Oil
change, Filter change, etc. to ensure readiness of generator for continuous operation.

Final verification of earth connection to be done.

Tournament generators are not available, operation of related EMDB & Load transfer time
not verified
CENTRAL BATTERY SYSTEM

Correctness of “Exit” light directions still need to be verified and confirmed.

Emergency lights in areas other than egress routes are not verified and to be
done.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

FIRE ALARM SYSTEM

Fire alarm system consists of 10 FACP panels and all panels are functional.

Interfacing of fire alarm systems with firefighting and other life safety systems are done,
verified at site and found in line with QCDD approved cause and effect matrix.

Dedicated PAVA system is operational for notification, along with sounder and strobes
connected to fire alarm system

( copy of approved Cause and Effect matrix can be provided)


SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

MECHANICAL SYSTEM
SPRINKLER There is NCR about Skybox rooms (Insufficient coverage of sprinklers), also there are 17 IRWs about Sprinklers'
installation is noncompliance with NFPA 13
There are cases, where the sprinkles installation has not been provided. There are
potential issues with obstructions or sprinkler coverage that required to be verified.

STAIRCASE PRESSURIZATION No Action from JV


The testing for the staircases have been carried out and passed without completing the
installation of the gratitude wall (signature wall), and currently all the walls are installed.
So, the addition of the walls will increase the pressure resistances for the fans, which will
result in failure of the system. Contractor needs to perform the test again, and here are
the affected core walls : 15, 17, 18, and 20

DIESEL GENERATOR & FIRE DIESEL PUMP No Action from JV regarding Fire diesel pump
The installation, testing and commissioning for the fuel system are not yet completely
approved. Diesel pump, needs to be maintained as per manufacturer’s
recommendations/requirements prior tournament.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

DUCT SMOKE DETECTORS Closed


It is a device used to detect the presence of smoke in the airstream of ductwork sections of the HVAC air
handling systems. There are cases where the installation is not in compliance with the manufacturer’s
installation manual as level 4 Zone 1, plant room # 92, plant room # Zone 5 level 6, plant room # Zone 5 level
zero.

DUCTWORK AT EGRESS ROUTE (FIRE LOBBY) Closed


Ductwork is installed in egress route (fire lobby), which is not in compliance with QCDD and NFPA. (Location:
level 4, zone 1E)

INCOMPLETE INSTALLATION OF MSFDs Work is still going on


MFSD are designed to be installed in HVAC ductwork at locations that are designated as fire barrier or fire &
smoke barrier. The installation of MSFDs are incomplete in following rooms:
For all MV and Transformer rooms (level 0, zone 4E, 2E, 5E,8F, 8G & 8H, 3E, 4H, 2G&2F, 5 J&H, 7E), (level 2,
zone 7D&2B, 1F, ), (level 6, zone 5E&5F, 7c&7D), (level 1, zone 5F), (level 3, zone 4B, 7D, 1F), (level 5, zone 5E),

FOAM SYSTEM Closed


It is used to protect the flammable liquid hazards, such as the Standby generator rooms. Contractor has
shifted the equipment assigned to Phase 2, sub-zone 3F, which has already tested and approved by QCDD, to
phase 4, and a new equipment was installed instead of. There was no test done for the same.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation, Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs to
be verified in several
areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Note: Compliance to
Installation,
Coverage
obstruction issues of
Fire Sprinklers as
commented in IRWs
to be verified in
several areas.
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

Risk Assessment
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)
SC Classification:RESTRICTED\Personally Indentifiable Information(PII)

GENERAL CONCERNS
• There are around 3300 rooms have been snagged,
and so many critical issues, that are related to the fire
life safety, were found from the mechanical and
electrical side. De-snagging has not started yet for
addressing the same.