CURRENT TRANSFORMERS
MINIATURES
TYPE TCW PAGE 2-4
TYPE TFW PAGE 5-7
TYPE TCB PAGE 8-11
TYPE TAB PAGE 12-15
INTERMEDIATE
TYPE AB WINDOW PAGE 16-18
TYPE AB WINDOW EXTENDED RANGE PAGE 16
TYPE AB BAR PAGE 19-25
TYPE AB BAR EXTENDED RANGE PAGE 19
PAD MOUNT
TYPE AP PAGE 26-27
TYPE AP EXTENDED RANGE PAGE 26-27
LARGE
TYPE I AD PAGE 28-31
TYPE I AD EXTENDED RANGE PAGE 28
TYPE II ACL PAGE 32-34
VOLTAGE TRANSFORMERS
TYPE DB 500 VOLT AMPERES PAGE 35-36
TYPE DA 750 VOLT AMPERES PAGE 35-36
TYPE DF 300 VOLT AMPERES PAGE 37-38
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover.
Retained shorting device.
Certified test record with each transformer.
Meets ANSI, NEMA and EEI standards.
4
GEC Durham Industries, Inc.
TYPE TFW
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS MINIATURE
WINDOW TYPE
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Includes clear sealable secondary terminal cover
Includes a retained shorting device
Includes certified test record with each transformer
7
GEC Durham Industries, Inc.
TYPE TCB
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS MINIATURE BAR TYPE
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Includes clear sealable secondary terminal cover
Clear sealable secondary terminal cover
Retained shorting device
#6-14 Potential terminal
Tinned plated copper bus bar
Certified test record with each transformer
Meets ANSI, NEMA AND EEI standards
10
TYPE TCB
11
GEC Durham Industries, Inc.
TYPE TAB
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS MINIATURE BAR TYPE
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover
Retained shorting device
#6-14 Potential terminal
Tinned plated copper bus bar
Certified test record with each transformer
Meet ANSI, NEMA AND EEI standards
14
TYPE TAB
15
GEC Durham Industries, Inc.
TYPE AB
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS INTERMEDIATE
WINDOW TYPE
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover
Retained shorting device
Certified test record with each transformer
Meet ANSI, NEMA AND EEI standards
DUAL RATIO
AB2/4 200/400 110K 0.5/0.5 4.0/2.0 3.0/1.5 2 11lbs.
AB3/6 300/600 111K 0.5/0.5 2.0/2.0 1.5/1.5 5 7lbs.
AB4/8 400/800 112K 0.5/0.5 2.0/2.0 1.5/1.5 5 7lbs.
18
GEC Durham Industries, Inc.
TYPE AB
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS LARGE TYPE II
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover
Retained shorting device
Tin plated copper removable bus bar
#6-14 Potential terminal
Certified test record with each transformer
Meet ANSI, NEMA AND EEI standards
TYPE AB WITH REMOVABLE BUS BAR WITH STUD TYPE SECONDARY TERMINALS
Aluminum Low Mounting Base Included
BURDEN 30C 55C
PRIMARY CATALOG 0.3 ACCURACY RATING RATING
MODEL AMPS NUMBER CLASS FACTOR FACTOR FIGURE WEIGHT
AB11 100 124K 0.1 4.0 4.0 2 11lbs.
AB11 100 122K 0.2 4.0 4.0 1 15lbs.
AB21 200 105K 0.5 4.0 4.0 2 13lbs.
AB31 300 106K 0.5 2.0 1.5 2 13lbs.
AB41 400 107K 0.5 4.0 3.0 5 11lbs.
AB61 600 108K 0.5 2.0 1.5 5 10lbs.
AB81 800 109K 0.5 2.0 1.5 5 10lbs.
AB101 1000 134K 0.5 2.0 1.5 6 10lbs.
AB121 1200 135K 1.8 1.5 1.1 6 10lbs.
AB151 1500 136K 1.8 1.5 1.1 9 12lbs.
AB201 2000 137K 1.8 1.5 1.1 10 18lbs.
AB301 3000 138K 1.8 1.33 1.0 13 20lbs.
AB401 4000 139K 1.8 1.0 0.7 13 21lbs.
DUAL RATIO
AB2/41 200/400 113K 0.5/0.5 4.0/2.0 3.0/1.5 2 13lbs.
AB3/61 300/600 114K 0.5/0.5 2.0/2.0 1.5/1.5 5 11lbs.
AB4/81 400/800 115K 0.5/0.5 2.0/2.0 1.5/1.5 5 11lbs.
AB10/201 1000/2000 143K 0.5/1.8 2.0/1.5 1.5/1.1 10 18lbs.
AB15/301 1500/3000 144K 1.8/1.8 1.5/1.33 1.1/1.0 13 21lbs.
AB20/401 2000/4000 145K 1.8/1.8 1.5/1.0 1.1/0.7 13 21lbs.
DUAL RATIO
AB2/41 200/400 113KH 0.5/0.5 4.0/2.0 3.0/1.5 4 13lbs.
AB3/61 300/600 114KH 0.5/0.5 2.0/2.0 1.5/1.5 7 11lbs.
AB4/81 400/800 115KH 0.5/0.5 2.0/2.0 1.5/1.5 7 11lbs.
AB10/201 1000/2000 143KH 0.5/1.8 2.0/1.5 1.5/1.1 12 18lbs.
AB15/301 1500/3000 144KH 1.8/1.8 1.5/1.33 1.1/1.0 14 21lbs.
AB20/401 2000/4000 145KH 1.8/1.8 1.5/1.0 1.1/0.7 14 21lbs.
TYPE AB WITH REMOVABLE BUS BAR WITH PRESSURE TYPE SECONDARY TERMINALS
Aluminum Low Mounting Base Included
BURDEN 30C 55C
PRIMARY CATALOG 0.3 ACCURACY RATING RATING
MODEL AMPS NUMBER CLASS FACTOR FACTOR FIGURE WEIGHT
AB11 100 124KP 0.1 4.0 4.0 2 11lbs.
AB11 100 122KP 0.2 4.0 4.0 1 15lbs.
AB21 200 105KP 0.5 4.0 4.0 2 13lbs.
AB31 300 106KP 0.5 2.0 1.5 2 13lbs.
AB41 400 107KP 0.5 4.0 3.0 5 11lbs.
AB61 600 108KP 0.5 2.0 1.5 5 10lbs.
AB81 800 109KP 0.5 2.0 1.5 5 10lbs.
AB101 1000 134KP 0.5 2.0 1.5 6 10lbs.
AB121 1200 135KP 1.8 1.5 1.1 6 10lbs.
AB151 1500 136KP 1.8 1.5 1.1 9 12lbs.
AB201 2000 137KP 1.8 1.5 1.1 10 18lbs.
AB301 3000 138KP 1.8 1.33 1.0 13 20lbs.
AB401 4000 139KP 1.8 1.0 0.7 13 21lbs.
DUAL RATIO
AB2/41 200/400 113KP 0.5/0.5 4.0/2.0 3.0/1.5 2 13lbs.
AB3/61 300/600 114KP 0.5/0.5 2.0/2.0 1.5/1.5 5 11lbs.
AB4/81 400/800 115KP 0.5/0.5 2.0/2.0 1.5/1.5 5 11lbs.
AB10/201 1000/2000 143KP 0.5/1.8 2.0/1.5 1.5/1.1 10 18lbs.
AB15/301 1500/3000 144KP 1.8/1.8 1.5/1.33 1.1/1.0 13 21lbs.
AB20/401 2000/4000 145KP 1.8/1.8 1.5/1.0 1.1/0.7 13 21lbs.
Specifications Subject to Change Without Notice.
20
TYPE AB WITH REMOVABLE BUS BAR WITH STUD TYPE SECONDARY TERMINALS
Aluminum 1'' High Mounting Base Included
BURDEN 30C 55C
PRIMARY CATALOG 0.3 ACCURACY RATING RATING
MODEL AMPS NUMBER CLASS FACTOR FACTOR FIGURE WEIGHT
AB11 100 124KHP 0.1 4.0 4.0 4 11lbs.
AB11 100 122KHP 0.2 4.0 4.0 3 15lbs.
AB21 200 105KHP 0.5 4.0 4.0 4 13lbs.
AB31 300 106KHP 0.5 2.0 1.5 4 13lbs.
AB41 400 107KHP 0.5 4.0 3.0 7 11lbs.
AB61 600 108KHP 0.5 2.0 1.5 7 10lbs.
AB81 800 109KHP 0.5 2.0 1.5 7 10lbs.
AB101 1000 134KHP 0.5 2.0 1.5 8 10lbs.
AB121 1200 135KHP 1.8 1.5 1.1 8 10lbs.
AB151 1500 136KHP 1.8 1.5 1.1 11 12lbs.
AB201 2000 137KHP 1.8 1.5 1.1 12 18lbs.
AB301 3000 138KHP 1.8 1.33 1.0 14 20lbs.
AB401 4000 139KHP 1.8 1.0 0.7 14 21lbs.
DUAL RATIO
AB2/41 200/400 113KHP 0.5/0.5 4.0/2.0 3.0/1.5 4 13lbs.
AB3/61 300/600 114KHP 0.5/0.5 2.0/2.0 1.5/1.5 7 11lbs.
AB4/81 400/800 115KHP 0.5/0.5 2.0/2.0 1.5/1.5 7 11lbs.
AB10/201 1000/2000 143KHP 0.5/1.8 2.0/1.5 1.5/1.1 12 18lbs.
AB15/301 1500/3000 144KHP 1.8/1.8 1.5/1.33 1.1/1.0 14 21lbs.
AB20/401 2000/4000 145KHP 1.8/1.8 1.5/1.0 1.1/0.1 14 21lbs.
22
TYPE AB
1/2”
1/2”
23
TYPE AB
24
TYPE AB
25
GEC Durham Industries, Inc.
TYPE AP
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS FOR USE IN PAD MOUNTED
DISTRIBUTION TRANSFORMERS
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover
Retained shorting device
Pressure type secondary terminals
“Grabber” for stabilizing unit on a bus bar
Certified test record with each transformer
Meet ANSI, NEMA AND EEI standards
27
GEC Durham Industries, Inc.
TYPE AD
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS LARGE TYPE I
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover
Retained shorting device
Certified test record with each transformer
Meet ANSI, NEMA AND EEI standards
TYPE AD WITH STUD TYPE SECONDARY TERMINALS
Mounting Base Not Included
BURDEN 30C 55C
PRIMARY CATALOG 0.3 ACCURACY RATING RATING
MODEL AMPS NUMBER CLASS FACTOR FACTOR FIGURE WEIGHT
AD2 200 552E 0.2 4.0 4.0 1 17lbs.
AD4 400 554E 0.2 4.0 3.0 1 17lbs.
AD6 600 555E 0.5 3.0 2.4 1 17lbs.
AD8 800 556E 0.5 2.0 1.5 1 17lbs.
AD10 1000 562E 0.5 2.0 1.5 1 17lbs.
AD12 1200 557E 0.9 2.0 1.5 1 17lbs.
AD15 1500 558E 0.9 3.0 2.4 1 17lbs.
AD20 2000 559E 1.8 2.0 1.5 1 17lbs.
AD30 3000 560E 1.8 1.5 1.1 1 17lbs.
AD40 4000 561E 1.8 1.5 1.1 1 17lbs.
DUAL RATIO
AD6/12 600/1200 564E 0.5/0.9 3.0/2.0 2.4/1.5 1 17lbs.
AD8/16 800/1600 565E 0.5/0.9 2.0/2.0 1.5/1.5 1 17lbs.
AD10/20 1000/2000 571E 0.5/1.8 2.0/2.0 1.5/1.5 1 17lbs.
AD15/30 1500/3000 572E 0.9/1.8 2.0/1.5 1.5/1.0 1 17lbs.
AD20/40 2000/4000 573E 1.8/1.8 2.0/1.5 1.5/1.0 1 17lbs.
DUAL RATIO
AD6/12 600/1200 564M 0.5/0.9 3.0/2.0 2.4/1.5 2 17lbs.
AD8/16 800/1600 565M 0.5/0.9 2.0/2.0 1.5/1.5 2 17lbs.
AD10/20 1000/2000 571M 0.5/1.8 2.0/2.0 1.5/1.5 2 17lbs.
AD15/30 1500/3000 572M 0.9/1.8 2.0/1.5 1.5/1.0 2 17lbs.
AD20/40 2000/4000 573M 1.8/1.8 2.0/1.5 1.5/1.0 2 17lbs.
DUAL RATIO
AD6/12 600/1200 564EP 0.5/0.9 3.0/2.0 2.4/1.5 1 17lbs.
AD8/16 800/1600 565EP 0.5/0.9 2.0/2.0 1.5/1.5 1 17lbs.
AD10/20 1000/2000 571EP 0.5/1.8 2.0/2.0 1.5/1.5 1 17lbs.
AD15/30 1500/3000 572EP 0.9/1.8 2.0/1.5 1.5/1.0 1 17lbs.
AD20/40 2000/4000 573EP 1.8/1.8 2.0/1.5 1.5/1.0 1 17lbs.
Specifications Subject to Change Without Notice.
29
TYPE AD WITH PRESSURE TYPE SECONDARY TERMINALS
2-Piece Stainless Steel Mounting Base Included
BURDEN 30C 55C
PRIMARY CATALOG 0.3 ACCURACY RATING RATING
MODEL AMPS NUMBER CLASS FACTOR FACTOR FIGURE WEIGHT
AD2 200 552MP 0.2 4.0 4.0 2 17lbs.
AD4 400 554MP 0.2 4.0 3.0 2 17lbs.
AD6 600 555MP 0.5 3.0 2.4 2 17lbs.
AD8 800 556MP 0.5 2.0 1.5 2 17lbs.
AD10 1000 562MP 0.5 2.0 1.5 2 17lbs.
AD12 1200 557MP 0.9 2.0 1.5 2 17lbs.
AD15 1500 558MP 0.9 3.0 2.4 2 17lbs.
AD20 2000 559MP 1.8 2.0 1.5 2 17lbs.
AD30 3000 560MP 1.8 1.5 1.1 2 17lbs.
AD40 4000 561MP 1.8 1.5 1.1 2 17lbs.
DUAL RATIO
AD6/12 600/1200 564MP 0.5/0.9 3.0/2.0 2.4/1.5 2 17lbs.
AD8/16 800/1600 565MP 0.5/0.9 2.0/2.0 1.5/1.5 2 17lbs.
AD10/20 1000/2000 571MP 0.5/1.8 2.0/2.0 1.5/1.5 2 17lbs.
AD15/30 1500/3000 572MP 0.9/1.8 2.0/1.5 1.5/1.0 2 17lbs.
AD20/40 2000/4000 573MP 1.8/1.8 2.0/1.5 1.5/1.0 2 17lbs.
31
GEC Durham Industries, Inc.
TYPE ACL
INSTRUMENT CURRENT TRANSFORMER
600 VOLT CLASS LARGE TYPE II
STANDARD FEATURES:
34
GEC Durham Industries, Inc.
TYPE DB and DA
INSTRUMENT VOLTAGE TRANSFORMER
600 VOLT CLASS
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover
Pressure type secondary terminals
Certified test record with each transformer
Meet ANSI, NEMA AND EEI standards
TYPE DA
36
GEC Durham Industries, Inc.
TYPE DF
INSTRUMENT VOLTAGE TRANSFORMER
600 VOLT CLASS
STANDARD FEATURES:
60 Hertz, 600 VAC, 10KV Bil.
Clear sealable secondary terminal cover
Pressure type secondary terminals
Certified test record with each transformer
Meet ANSI, NEMA AND EEI standards
38
GEC Durham Industries, Inc.
Transformer Brackets
ALC - 27A
ALD - 21A
CHANNEL
TOP HAT Fig. 2
Fig. 1
ALT - 16A
ANGLE
Fig. 3
40
CURRENT TRANFORMERS VOLTAGE TRANSFORMERS
Ratio---------:5
Type Bar Ratio---------:1
Options
Conduit Box Furnished on unit
Voltage Transformers
Transformer
TYPE
Class Astra ABB Associated G.E. Schlumberger
300 Volt Amps DF PPW NA NA T5R
500 Volt Amps DB PPM CL-707 JVA-O T6R
750 Volt Amps DA PPI NA JVP-1 T7R5
45
GEC�Durham�Industries,�Inc.
www.gecdurham.com
ELIMINATOR
Extended�Range Transformers
Features:
Maintain�the�0.3% ANSI Accuracy�down�to�40%�instead�of�100%
Maintain�the�0.6% Accuracy�down�to�4%�instead�of�the ANSI�10%
Meter the�light�loads�with�greater accuracy
Eliminate�Billing�Multiplier errors
Eliminate�stocking�several�Ratio’s�of�CT’s�with�one�CT
All Astra Transformers�rated�for indoor or outdoor
NEW 200:5�CT’s!
Billing�Multiplier
Standard�40�on�200:5’s
AB21Y AB2Y
0.6% 0.3%
Accuracy Accuracy Rating Rating Window
Catalog Rated Class Class Factor Factor Bar Secondary Drawing
Model Ratio Number Burden Amps. Amps. 30C 55C Type Terminals CT Base Fig.�#
AB2Y 200:5�������445YK��������0.2������������8-79��������80-800��������4.0������������3.0 Window������Stud����������Low������������1
AB2Y 200:5������445YKP 0.2������������8-79��������80-800��������4.0������������3.0 Window���Pressure�������Low������������1
AB2Y 200:5�����445YKH�������0.2������������8-79��������80-800��������4.0������������3.0 Window������Stud���������High������������2
AB2Y 200:5����445YKHP 0.2������������8-79��������80-800��������4.0������������3.0 Window���Pressure������High������������2
AB21Y 200:5�������446YK��������0.2������������8-79��������80-800��������4.0������������3.0 Slotted�Bar Stud����������Low�������������4
AB21Y 200:5������446YKP 0.2������������8-79��������80-800��������4.0������������3.0 Slotted�Bar Pressure������Low 4
AB21Y 200:5�����446YKH�������0.2������������8-79��������80-800��������4.0������������3.0 Slotted�Bar Stud����������High������������5
AB21Y 200:5�����446KHP 0.2������������8-79��������80-800��������4.0������������3.0 Slotted�Bar Pressure������High������������5
AB5Y 500:5������120YKP 0.5����������20-199����200-2000������4.0������������3.0 Window����Pressure������Low�������������3
AB51Y 500:5������276YKP 0.5����������20-199����200-2000������4.0������������3.0 Slotted�Bar Pressure������Low 6
AB51Y 500:5�����121YKP 0.5���������20-199����200-2000������4.0������������3.0 4�Hole�Bar Pressure�����Low�������������7
46 Specifications�subject�to�change�without�notice
GEC�Durham�Industries,�Inc.
www.gecdurham.com
Padmount
Extended�Range Transformers
NEW 400:5�EXTENDED�RANGE�PADMOUNT CT
Our Standard�200:5,�300:5,�400:5,�500:5,�600:5,�1000:5,�1200:5,
1500:5,�2000:5,�3000:5�and�4000:5�units�retain�their Rating�Factors
at�the�High Temperatures�of�85�C
(1)�500:5 Astra�Padmount
Extended�Range�CT
Can�Eliminate
Stocking�Several�Standard�Padmount�CT’s
Features:
Maintain�the�0.3% ANSI Accuracy�from�40%�to�400%�at�30C.
Maintain�the�0.6% Accuracy�down�to�4%�instead�of�the ANSI�10%
Meter the�light�loads�with�greater accuracy
Eliminate�Billing�Multiplier errors
Eliminate�stocking�several�Ratio’s�of�CT’s�with�one�CT
All Astra Transformers�rated�for indoor or outdoor
Large Type�1 Window
Extended�Range Transformers AD10Y
0.3% 0.6%
Accuracy Accuracy Rating Rating
Catalog Rated Class Class Factor Factor Secondary Window Drawing
Model Ratio Number Burden Amps. Amps. 30C 55C Terminals Size Fig.�#
AD10Y 1000:5�����562YMP 0.5���������400-4000�����40-399����������4.0��������������3.0����������Pressure�������5�5/8”������������9
AD10Y 1000:5������562YM����������0.5���������400-4000�����40-399����������4.0��������������3.0������������Stud�����������5�5/8”������������9
Specifications�subject�to�change�without�notice 47
GEC�Durham�Industries,�Inc.
www.gecdurham.com
Window Type
Figure�1 Figure�2
Figure�3
Bar Type
Figure�4 Figure�5
48
GEC�Durham�Industries,�Inc.
www.gecdurham.com
Bar Type
Figure�6 Figure�7
Large Type�1
Padmount Type
Figure�8
Figure�9 49