Professional Documents
Culture Documents
A Study On Grid Connected PV System
A Study On Grid Connected PV System
Abstract—Photovoltaic (PV) energy has a fast growing II. IMPACTS OF CONNECTING PV SYSTEM TO THE GRID
annual rate and is quickly becoming an important part of the
If the PV penetration is really high Photovoltaic systems can
energy balance in most regions and power systems. This
subject the grid to several negative impacts. They are i) Reverse
paper aims to study the effects of connecting a PV system to
power flow, ii) Overvoltage along Distribution feeders, iii)
the grid through simulation of the system in RSCSD software
Voltage control difficulty, iv) Phase unbalance, v) Power Quality
in real time on the Real Time Digital Simulator (RTDS).
problems, vi) Increased Reactive power and vii) Islanding
Effect of variation of power factor of loads, variation of PV
detection difficulty. This paper considers the following three
penetration, introduction of harmonics into the system by the
impacts.
PV inverter and anti-islanding effect of the PV system are
studied. Finally, the Performance Ratio (PR) of a typical grid A. Power quality problems/Harmonics
connected PV system is evaluated to determine the reliability
and grid connectivity of the PV system. The inverter forms the core of the grid connected PV system
and is responsible for the quality of power injected into the grid.
Keywords—Grid connected PV, Harmonics, Anti-islanding, Inverters also introduce harmonics into the system in the presence
Performance Ratio (PR), RSCAD, RTDS. of non-linear loads, during DC to AC conversion. Harmonic
currents introduce voltage drop and result in distortion of supply
voltage. Harmonics can also cause resonance in the supply
I. INTRODUCTION system, resulting in malfunction, reduction in lifetime or
An important source of renewable energy is solar energy. In permanent damage of electrical equipment [3].
India, the average annual solar energy incident on land area alone, B. Increased Reactive Power
is about 5000 trillion kilowatt-hours, because India gets about 300
clear sunny days in a year. The solar energy output received in a Photovoltaic inverters usually operate at unity power factor.
year exceeds the possible energy output of all the fossil fuel The owners of small residential PV systems in an incentive based
reserves in India. From 10 MW of installed capacity in 2010 and program are levied based on their kilowatt-hour yield and not on
468.3 MW in 2011, the installed grid connected solar power their kilovolt-ampere hour yield. Hence they prefer to operate PV
capacity, as of 31st March 2016 in India is 6762.85MW and an inverters at unity power factor, maximizing the active power
additional 10,000 MW by 2017 and total of 100,000 MW by generation, and accordingly their returns. As a result the reactive
2022, is expected to be installed [1,2]. Some renewable energy power demand met by the PV system is minimal. Hence, the grid
projects are large scale, but renewable technologies are also suited is responsible for supplying majority of reactive power, and it
to rural and remote areas in developing countries, where energy makes the distribution transformer operate at a low power factor
is crucial to human development [3].
Grid connected PV systems in the world account for about 99% C. Islanding Detection
of the installed capacity compared to stand alone systems, which The condition when the solar system continues to supply to
use batteries. Battery-less grid connected PV are cost effective the load even though grid power from the utility is not present is
and require less maintenance. Batteries are not needed for grid called islanding. Islanding can be dangerous to utility workers,
connected PV, as the power generated is uploaded to the grid for who may not realize that a circuit is still energized while working
direct transmission, distribution and consumption. This eases the on repairs or maintenance. Hence, the solar inverter must detect
burden on other sources supplying power to the grid. islanding and disconnect the PV system when the grid is down.
In this paper, the impacts of connecting PV system to grid are This function of the PV system is known as ‘anti-islanding’ [4].
studied. Further, the Performance Ratio of a typical grid These impacts are dependent on the size and location of the
connected PV system in India is evaluated. PV system. According to the Solar America Board for Codes and
Standards (Solar ABCs) PV systems are classified into three
categories, based on the ratings of the system. Small-scale
systems are rated at 10kW or less; Medium-scale systems are
The PV array consists of modules. To arrive at a power output Temperature co-efficient of ISC 0.065% / 0C
of 4 MW, the number of modules considered in series and parallel Reference Temperature (Tref) 250C
are 1500 and 30. The detailed data considered for PV array in Reference solar intensity (Insref) 1000 W/m2
simulation is given in Table I.
PI
TR2 5 33/11
Section TR3, TR4, TR5 12.5 33/11
TR6, TR7, TR8 1.25 11/0.433
4MW peak output from the PV array and 80% loading of the I
distribution system at 0.8 pf, the harmonic current at the output of EPV
Eg
July
October
January
May
August
November
June
September
December
February
March
April
orientation of a PV plant and the incident solar irradiation on the
PV plant. Hence, the performance ratio can be used to compare
PV plants at different locations all over the world [9].
The closer the PR value determined for a PV plant approaches
100 %, the more efficiently the respective PV plant is operating. Months
In real life, a value of 100 % cannot be achieved, as unavoidable
Fig. 5 Monthly Performance Ratio (PR)
losses always arise with the operation of the PV plant. High-
performance PV plants can however reach a performance ratio of
up to 80 %. PR is defined for a period of time (usually a month or The annual average PR% from Fig 5 is found to be 71.2%.
a year). Performance Ratio is also affected by ambient temperature.
Higher the temperature, lower is the PV output, and hence lowers
kWh
PR. As seen from Table VII and Fig.5, the month of December
Measured enrgy at PCC (
month
) has the highest PR%. This result tallies with the PR% of most PV
Monthly PR% =
kWh
Insolation ( 2 ) × Array area(m2 ) × 30 × ηmodule
systems across the world. The month of December receives a
m . day large number of sunshine hours and has relatively low ambient
(1) temperature.
Where PCC is Point of common coupling. To calculate the annual
PR%, replace month by year and 30 by 365 in (1). VI. CONCLUSION
Photovoltaic Systems have developed into a mature technology
TABLE VII. MONTHLY PR% AT STC used for mainstream electricity generation. However, they
introduce numerous negative impacts into the electrical networks.
Month Performance Ratio at STC (%)
Studies on three such impacts has been provided. A grid-
January 80.687
connected PV test system was considered and simulated in
February 73.669
RSCAD software. Harmonic content introduced by 4MW PV
March 66.789
system with a 3-phase, 2-level DC/AC inverter, at PCC was found
April 63.980
May 65.019
to be within the limits. Reactive power support with regards to
June 65.611 varying load power factor and varying PV penetration levels was
July 68.043 studied. Anti-islanding function of the PV system was studied and
August 69.560 found that the critical islanding time of the PV system for the
September 70.539 system considered is 125ms. Further, the Performance Ratio of a
October 74.381 typical grid connected system in India was calculated in order to
November 82.052 compare the performance of the PV system with other systems
December 83.628 throughout the world. The studies carried out will help PV power
generators and utilities the issues to be studied for a grid
The Monthly Performance Ratio was evaluated for a PV system connected PV system.
connected to grid at a typical location in India. The values are
tabulated in Table VII.
ACKNOWLEDGMENT
Additional data of PV array considered for calculating the PR%
is: Module efficiency (ηmodule) = 14.44%; Array area = 0.156 m x The authors would like to acknowledge the support of K.S.Meera
0.156m; Insolation data [10]; Number of sunshine hours per day and R.A Deshpande and wish to thank the authorities of CPRI for
data [10]. permitting to publish this paper.
REFERENCES
[1] "Physical Progress (Achievements)", Ministry of New and
Renewable Energy, Govt. of India. 31 January 2014.
Retrieved 21 February 2014.
[2] "State wise installed solar power capacity" (PDF), Ministry
of New and Renewable Energy, Govt. of India. 1 March
2016. Retrieved 24 March 2016.
[3] D. M. Tobnaghi, “A Review on Impacts of Grid-Connected
PV System on Distribution Network,” International Journal
of Electrical, Computer, Energetic, Electronic and
Communication Engg. , Vol. 10, No.1, 2016.
[4] “Grid Integration of Distributed Solar Photovoltaics (PV) in
India,” A Prayas (Energy Group) Report, July 2014.
[5] IEEE Standard 519-1992 – Recommended Practices and
Requirements for Harmonic Control in Electrical Power
Systems. Revision to IEEE 519-2014.
[6] M. V. Bakshi, U. A. Bakshi, Electrical Machines –III,
technical Publications, Jan 2009.
[7] B. K. Perera, P. Ciufo, S. Perera, “Point of Common
Coupling (PCC) voltage control of a grid-connected solar
Photovoltaic (PV) system,” 39th Annual Conference of the
IEEE Industrial Electronics Society (IECON 2013), 2013,
pp.7475-7480.
[8] P. Brucke, “Reactive Power Control in Utility-Scale PV,”
SOLARPRO magazine, Issue 7.4, Jun/Jul 2014.
[9] SMA Solar Technology AG, Performance Ratio, Technical
Information, Perfratio-UEN100810 (PDF).
[10] Gaisma.com, ‘Sunrise, Sunset, dawn and dusk times around
the World,’ 2005 [online]. Available:
http://www.gaisma.com/en/