MAKING MODERN LIVING POSSIBLE

Technical brochure

Programmable controller LCX06C

Danfoss’ range of universal MCX


programmable controllers offers the
functionality and reliability you need to get
the best out of your heating, ventilation,
air-conditioning and refrigeration (HVAC/R)
equipment. With the MCX range, Danfoss is
widening the concept of programmability
and applying it to as many environments as
possible

LCX06C is the new low-end programmable


controller in the 32x74 mm standard size.
It also provides options for Modbus RS485
serial communication interface and Real
Time Clock

Features LCX06C yy 4 analog and 6 digital inputs yy Modbus RS485 serial interface
yy 2 analog and 6 digital outputs yy Display LED with 3½ digits and 8 icons for
yy Power supply 20/30 Vdc - 24 Vac showing the desired information in one screen
yy TTL serial interface for software upload yy Dimensions 33x75mm
yy RTC clock for weekly time programs and data yy Panel mounting
logging information

MYK connection Modbus RS485

485

www.danfoss.com/mcx
LCX06C

General features

FEATURES DESCRIPTION

20÷30 Vdc and 24 Vac ±15% 50/60 Hz.


Power supply There is NO insulation between power supply and extra-low voltage
Maximum power consumption: 5 W, 9 VA
Self extinguishing V0 according to IEC 60695-11-10 and glowing/hot wire test at
Plastic housing
960 °C according to IEC60695-2-12
Ball test 125 °C according to IEC 60730-1. Leakage current: ≥ 250 V according to IEC 60112
Operating conditions CE: -20T60, 90% RH non-condensing
Storage conditions -30T80, 90% RH non-condensing
Integration In Class I and/or II appliances
Index of protection IP64 ~ NEMA3R only on the front cover
Period of electric stress
Long
across insulating parts
Resistance to heat and fire Category D
Immunity against voltage
Category I
surges
Software class and
Class A
structure
CE compliance:
This product is designed to comply with the following EU standards:
-- Low voltage guideline: 73/23/EEC
-- Electromagnetic compatibility EMC: 89/336/EEC and with the following norms:
Approvals • EN61000-6-1, EN61000-6-3
(immunity for residential, commercial and light-industrial environments)
• EN61000-6-2, EN61000-6-4
(immunity and emission standard for industrial environments)
• EN60730 (Automatic electrical controls for household and similar use)

Produced by Danfoss A/S (AC-SMC/az) | 11 - 2011 DKRCC.PD.RK0.A1.02 / 520H5763 2


LCX06C

Inputs/outputs

I/O TYPE NUM SPECIFICATIONS

Analog NTC 2 AI1, AI2


inputs PT1000 Analog inputs selectable via software between:
ON/OFF -- NTC and PT1000 temperature probes
0/1 V -- ON/OFF
0/5 V -- 0/1 V, 0/5 V, 0/10 V
0/10 V
NTC 2 AI3, AI4
PT1000 Analog inputs selectable via software between:
ON/OFF -- NTC and PT1000 temperature probes
0/1 V -- ON/OFF
0/5 V, -- 0/1 V, 0/5 V, 0/10 V
0/10 V -- 0/20 mA, 4/20 mA
0/20 mA, 12 V+ Power supply: min 12 Vdc max 18 Vdc, 50 mA max for 4/20 mA transmitter
4/20 mA 5 V+ Power supply: 5 Vdc ±2%, 50 mA max for 0/5 V transmitter
Digital Voltage 6 DI1, DI2, DI3, DI4, DI5, DI6
input free Current consumption: min 10 mA
contact
Analog 0/10 V 2 AO1, AO2
outputs PWM Analog output selectable via software between:
PPM -- pulsing output, synchronous with the line, at modulation of impulse position
(PPM) or modulation of impulse width (PWM):
• open circuit voltage: 5 V
• minimum load: 1 kΩ, for cutting phase speed regulators
-- 0/10 Vdc non optoinsulated output, referred to the ground
• 10 mA maximum loads
Digital Relay 6 C1-NO1, C2-NO2, C3-NO3, C4-NO4, C5-NO5, C6-NO6
output Insulation between relays: (common lines internally connected)
Insulation between relays and the extra-low voltage parts: reinforced
Relay 5 A
Normally open contact relays:
-- contact characteristics:
• contact rating (resistive) 5 A 30 Vdc/250 Vac - 100.000 cycles

Produced by Danfoss A/S (AC-SMC/az) | 11 - 2011 DKRCC.PD.RK0.A1.02 / 520H5763 3


LCX06C

Network diagram
Connection diagram

Serial lines cable layout


SERIAL LINES

N/-
L/+
POWER SUPPLY INPUT/OUTPUT
WHITE 12V+ 5V+ VIOLET 0/10 V 0/10 V
Analog Analog
output PWM A0 2 A0 1 PWM output
N1

Produced by Danfoss A/S (AC-SMC/az) | 11 - 2011


ORANGE D+ TTL-TX RED PPM PPM

RS485
24 Vac-Vdc
A-COM D-COM
BROWN D- TTL-RX GREEN L1

L
DI 2 DI 2 DI 1 DI 1
YELLOW GND GND YELLOW

24VAC
DI 4 DI 4 DI 3 DI 3

N
DI 6 DI 6 DI 5 DI 5

*NOTE: except 0/20 mA, 4/20 mA


to the AI 12V+ 5V+ to the AI
(50 mA max) (50 mA max)
A-COM A-COM

UNIVERSAL * AI 2 AI 1 UNIVERSAL *

UNIVERSAL AI 4 AI 3 UNIVERSAL

L
24VAC
LCX06C powered by dedicated transformer

N
D-
D+

DKRCC.PD.RK0.A1.02 / 520H5763
GND
RS485

L
SERIAL LINES

12V+ 5V+

N
C1 N0 1 5A

Standard kit connectors (part numbers 080G0189, 080G0190) not included


D+ TTL-TX
C2 N0 2 5A D- TTL-RX
C3 N0 3 5A
(if expected)

GND GND
TTL Serial Comm

EIA-485 (Modbus)

24VAC
TTL Max Lenght: 3 m

C4 N0 4 5A

C5 N0 5 5A

L
C6 N0 6 5A
LCX06C powered by a single transformer

N
DIGITAL OUTPUT
L
N

D-
D+
GND

LCX06C

4
LCX06C

Connection

CONNECTORS TYPE DESCRIPTION

Input and 18 way Molex Microfit type (43025-1800) -- Molex: (43030-0001) section cable AWG20-24
output crimping contact type (0.52-0.20 mm²)
connector -- Molex: (43030-0004) section cable AWG26-30
(0.13-0.05 mm²)
-- Instrument for the Molex crimp
code 69008-0982 (20-24 AWG)
-- Instrument for the Molex crimp
code 69008-0983 (26-30 AWG)
Serial Lines 8 way Cvilux type (CI0108SD000) crimping -- Cvilux: (CI01TD21PE0) section cable
connector contact type AWG22-28 (0,32-0,08 mm²)
-- Instrument for the Cvilux crimp cod.
CM07I01TD20
Power supply 2 way Molex KK type (09-50-8021) crimping -- Molex: (08-50-0105) section cable AWG18-24
connector contact type (0.82-0.20 mm²)
-- Molex: (08-50-0107) section cable AWG22-26
(0.32-0.13 mm²)
-- Instrument for the Molex crimp
code 69008-0953
Digital output 12 way Molex Minifit Jr. type (39-01-2125) -- Molex: (39-00-0077) section cable AWG16
1-6 connector crimping contact type (1.30 mm²)
-- Molex: (39-00-0038) section cable AWG18-24
(0.82-0.20 mm²)
-- Molex: (39-00-0046) section cable AWG22-28
(0.32-0.08 mm²)
-- Instrument for the Molex crimp
code 69008-0724

Dimensions

29
28
33

75 75 71
Drilling template
84 13 minimal thickness of panel 0.8 mm

Relays current carrying capability:


derating curve
6
5
4
3
2
1

-25 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C

Produced by Danfoss A/S (AC-SMC/az) | 11 - 2011 DKRCC.PD.RK0.A1.02 / 520H5763 5


LCX06C

User interface

TYPE FEATURES DESCRIPTION

LED Display LED 3½ digits + sign


display

Digits Green colour


Allarm/warning icons Red colour
Other icons Yellow/amber colour
Dimensions 45x17 mm
Keyboard Number of keys 4
Keys function Set by the application software

Ordering

DESCRIPTION CODE NR.

LCX06C, 24V, LED, S 080G0234


LCX06C, 24V, LED, RS485, RTC, S 080G0236
(S): Single Pack
Note: Single pack do not include standard kit connectors
Industrial pack codes are avaliable on request (these do not include standard kit connectors)

Accessories

DESCRIPTION CODE NR.

LCX06C CONNECTORS KIT 080G0177


ACCCNX, WIRED CONNECTORS KIT FOR LCX06C,
080G0189
1m CABLE
ACCCNX, WIRED CONNECTORS KIT FOR LCX06C,
080G0190
2m CABLE

Produced by Danfoss A/S (AC-SMC/az) | 11 - 2011 DKRCC.PD.RK0.A1.02 / 520H5763 6