Professional Documents
Culture Documents
Paquete Foundation 25 Ton EAC300A
Paquete Foundation 25 Ton EAC300A
and Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
Copyright
WARNING
This document and the information in it are the property of
Follow EHS Policies! Trane, and may not be used or reproduced in whole or in
Failure to follow instructions below could result in part without written permission. Trane reserves the right
death or serious injury. to revise this publication at any time, and to make changes
• All Ingersoll Rand personnel must follow Ingersoll to its content without obligation to notify any person of
Rand Environmental, Health and Safety (EHS) such revision or change.
policies when performing work such as hot work,
electrical, fall protection, lockout/tagout, refrigerant Trademarks
handling, etc. All policies can be found on the BOS
site. Where local regulations are more stringent than All trademarks referenced in this document are the
these policies, those regulations supersede these trademarks of their respective owners.
policies.
• Non-Ingersoll Rand personnel should always follow Revision Summary
local regulations.
• Updated Title24 information
• Updated ‘General Information’ and ‘Installation’
WARNING Sections
NOTICE:
Water Damage!
Non-factory penetrations through the base of this unit
are not allowed. Any penetration in the base of the unit
may affect the water tight integrity of the unit and lead
to water leaks into the conditioned space. Failure to
follow instructions could result in equipment and
property damage.
Overview of Manual
Note: One copy of this document ships inside the control
panel of each unit and is customer property. It must
be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for air cooled systems.
By carefully reviewing the information within this manual
and following the instructions, the risk of improper
operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to
help assure trouble free operation. A maintenance
schedule is provided at the end of this manual.
Should equipment failure occur, contact a qualified
service organization with qualified, experienced HVAC
technicians to properly diagnose and repair this
equipment.
RT-SVX50D-EN 3
Table of Contents
Model Number Description . . . . . . . . . . . . . . . 5 Unit Economizer Control (ECA) . . . . . . . . . .29
General Information . . . . . . . . . . . . . . . . . . . . . 6 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . .30
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . 6 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Precautionary Measures . . . . . . . . . . . . . . . . 6 Central Air Conditioner . . . . . . . . . . . . . . . . .31
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit Description . . . . . . . . . . . . . . . . . . . . . . . 6
System Input Devices & Functions . . . . . . . 7
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Initiation of Operating Modes - JADE Control-
ler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Foundation . . . . . . . . . . . . . . . . . . . . . . 16
General Unit Requirements . . . . . . . . . . . . 16
Main Unit Power . . . . . . . . . . . . . . . . . . . . . 18
Factory-Mounted Unit Options . . . . . . . . . . . 21
Unit Disconnect (FIYUDC) . . . . . . . . . . . . . . 21
Pre Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Verifying Proper Air Flow (Units with Belt
Drive Indoor Fan) . . . . . . . . . . . . . . . . . . . . . 22
Electromechanical Controls
Test Procedure . . . . . . . . . . . . . . . . . . . . . . . 22
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Standard Economizer Start-Up . . . . . . . . . 23
LLE Controls Test Procedure . . . . . . . . . . . 23
Compressor Start-Up . . . . . . . . . . . . . . . . . 23
Heating Start-Up . . . . . . . . . . . . . . . . . . . . . 24
Final System Set Up . . . . . . . . . . . . . . . . . . 24
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Belt Adjustment—Belt Drive Units . . 25
Monthly Maintenance . . . . . . . . . . . . . . . . . 26
Final Process . . . . . . . . . . . . . . . . . . . . . . . . . 27
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 28
Standard Troubleshooting . . . . . . . . . . . . . 28
Low Leak Economizer
(LLE) Troubleshooting . . . . . . . . . . . . . . . . . 28
Resetting Cooling and Heating Lockouts . 29
4 RT-SVX50D-EN
Model Number Description
E A C 1 8 0 A 3 E G A 0 0
1 2 3 4 5 6 7 8 9 10 11 12 13
Digit 1 — Unit Type J = Low Leak Economizer, Dry Bulb 7. 10 hp oversized motor is factory
E = Packaged Cooling, Electric Heat w/o Barometric Relief4 installed only.
L = Low Leak Economizer, Reference
Digit 2 — Efficiency Enthalpy w/o Barometric Relief4
A = ASHRAE 90.1 - 2010 N = Low Leak Economizer,
Comparative Enthalpy w/o
Digit 3 — Airflow Configuration Barometric Relief4
C = Convertible
D = Downflow Only4 Digit 15 — Supply Fan/Drive
Type/Motor
Digit 4, 5, 6 — Nominal Gross
0 = Standard Motor
Cooling Capacity (MBh) 1 = Oversized Motor7
180 = 15 Tons 7 = Multi-Speed Standard Motor
210 = 17½ Tons 9 = Multi-Speed Oversized Motor
240 = 20 Tons
300 = 25 Tons Digit 17 — Condenser Coil
Protection
Digit 7 — Major Design
0 = Standard Coil
Sequence 4 = CompleteCoat™ Condenser Coil
A
Digit 18 — Through The Base
Digit 8 — Voltage Selection Provisions
3 = 208-230/60/3 0 = No Through The Base Provisions
4 = 460/60/3 A = Through The Base Electric
W = 575/60/3
K = 380/60/36 Digit 19 — Disconnect Switch
0 = No Disconnect
Digit 9 — Unit Controls
1 = Unit Mounted Non-Fused
E = Electromechanical Disconnect Switch2
Digit 10 — Heating Capacity Digit 25 - System Monitoring
0 = No Heat Controls
G = 18 kW Electric Heat
0 = No Monitoring Controls
N = 36 kW Electric Heat
A = Condensate Drain Pan Overflow
P = 54 kW Electric Heat
Switch
R = 72 kW Electric Heat
Digit 26
Digit 11 — Minor Design
B = Economizer Fault Detection
Sequence
and Diagnostics (FDD)5
Digit 12, 13 — Service Sequence
00 = None
Model Number Notes
Digit 14 — Fresh Air Selection3
0 = No Fresh Air 1. Some field set up required.
A = Manual Outside Air Damper
2. Must be ordered with Through-
0-25%
B = Motorized Outside Air Damper the-Base Electrical option.
0-50% 3. All Factory Installed Options are
C = Economizer, Dry Bulb 0-100%
without Barometric Relief4 Built-to-Order. Check order
D = Economizer, Dry Bulb 0-100% services for estimated production
with Barometric Relief1, 4 cycle.
E = Economizer, Reference Enthalpy
0-100% without Barometric 4. Factory installed economizers
Relief4 only available in downflow
F = Economizer, Reference Enthalpy configuration.
0-100% with Barometric Relief1, 4
G = Economizer, Comparative 5. Fault Detection and Diagnostics
Enthalpy 0-100% without (FDD) is available on Low Leak
Barometric Relief4 Economizers only.
H = Economizer, Comparative
Enthalpy 0-100% with Barometric 6. Unit will operate reliably at
Relief1, 4 400VAC.
RT-SVX50D-EN 5
General Information
Unit Inspection additional respiratory protection. Use the appropriate
NIOSH approved respiration in these situations.
As soon as the unit arrives at the job site:
First Aid Measures
• Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data). • Eye Contact - Flush eyes with water to remove dust. If
symptoms persist, seek medical attention.
• Verify that the power supply complies with the unit
nameplate specifications. • Skin Contact - Wash affected areas gently with soap
and warm water after handling.
• Visually inspect the exterior of the unit, including the
roof, for signs of shipping damage.
• Visually inspect the internal components for shipping
Storage
damage as soon as possible after delivery and before Take precautions to prevent condensate from forming
it is stored. Do not walk on the sheet metal base pans. inside the unit’s electrical compartments and motors if:
• If concealed damage is discovered, notify the carrier’s • The unit is stored before it is installed; or,
terminal of damage immediately by phone and by
• The unit is set on the roof curb, and temporary heat is
mail. Concealed damage must be reported within 15
provided in the building. Isolate all side panel service
days.
entrances and base pan openings (e.g., conduit holes,
– Request an immediate joint inspection of the S/A and R/ A openings, and flue openings) from the
damage by the carrier and the consignee. ambient air until the unit is ready for start-up.
– Do not remove damaged material from the Note: Do not use the unit’s heater for temporary heat
receiving location. without first completing the start-up procedure
– Take photos of the damage, if possible. The owner detailed under “Start Up,” p. 23.
must provide reasonable evidence that the damage The manufacturer will not assume any responsibility for
did not occur after delivery. equipment damage resulting from condensate
• Notify the appropriate sales representative before accumulation on the unit’s electrical and/or mechanical
installing or repairing a damaged unit. components.
RT-SVX50D-EN 7
General Information
On units with a low leak economizer, configure the JADE go to a LOW fan speed damper setting, while Y2 or W
controller by setting the following parameters: states will cause the controller to open the damper to the
HIGH fan speed damper setting). The Heating System
SETPOINTS Menu: mode requires an input to the AUX2-1 terminal from the
DCV SET = desired CO2 ppm to start DCV thermostat, and the Cooling System mode requires an
input to the Y2 IN and/or the Y1 IN terminals from the
VENTMAX = desired maximum position w/DCV &
thermostat.
occupied status (2-speed applications require LO & HI
settings)
VENTMIN = desired minimum position w/DCV & occupied
status (2-speed applications require LO & HI settings)
ADVANCED SETUP Menu:
CO2 ZERO = set to detector's start level
CO2 SPAN = detector's max level minus start level
Attach the sensor to the CO2 and "R" terminals (at
customer connections).
Note: When using any 0-10 Vdc CO2 sensor with the JADE
you will need to set CO2 ZERO to 400 ppm and the
CO2 SPAN to 1600 ppm in the ADVANCED SETUP
menu.
Occupancy Sensor
A customer-supplied occupancy sensor can also be added
to provide damper control based on occupied/unoccupied
conditions.
Low Leak Economizer Units
To configure the JADE controller, set:
SYSTEM SETUP menu: OCC = INPUT
Attach the occupancy sensor to the OCC SENSOR wire and
"R" terminal (at customer connections). The occupancy
sensor must utilize a normally open contact for proper
operation.
If an occupancy sensor is not used, another option to
controlling occupied and unoccupied status is to use the
'G' input (fan is running). Connect the G input to the OCC
SENSOR wire (at customer connections). The controller
will then operate in the occupied mode every time the
indoor fan is running.
8 RT-SVX50D-EN
Dimensional Data
Figure 1, p. 12 illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged
unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may
result in condenser coil starvation, “short-circuiting” of
exhaust and economizer airflows, or recirculation of hot
condenser air.
Figure 1. Typical installation clearance for single and multiple unit applications
5' 8"
5' 0"
RT-SVX50D-EN 9
Dimensional Data
Figure 3. Cooling with optional electrical units — front & side views — 15–25 tons standard efficiency
10 RT-SVX50D-EN
Dimensional Data
Figure 4. Cooling with optional electrical heat units — plan view — 15–25 tons standard efficiency
Figure 5. Foundation units — back view (horizontal configuration) — 15–25 tons standard efficiency
RT-SVX50D-EN 11
Dimensional Data
Notes:
9 • Duct flanges mount 7-7/16” down inside the
curb on the 1-1½” curb flanges.
• Roofcurb is intended for downflow use only.
1”
25.4 MM
CURB FLANGE
LONG SIDES
SHORT SIDES
12 RT-SVX50D-EN
Dimensional Data
MOTORIZED DAMPER
(
FOR LOW LEAK)
RT-SVX50D-EN 13
Dimensional Data
14 RT-SVX50D-EN
Unit Weights
Table 1. Maximum unit & corner weights (lb) and center of gravity dimensions (in.)
Weights (lb)(a), (b) Corner Weights(c) Center of Gravity (in.)
Unit
Tons Model No. Shipping Net A B C D Length Width
15 EAC180A 2020 1700 568 402 338 392 54” 37”
17½ EAC210A 2074 1755 578 418 358 400 55” 38”
20 EAC240A 2163 1844 632 438 357 416 54” 37”
25 EAC300A 2208 1888 664 457 345 422 53” 35”
(a) Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
(b)Weights do not include additional factory or field installed options/accessories.
(c) Corner weights are given for information only. 15–25 ton models must be supported continuously by a curb or equivalent frame support.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in unit dropping and
possibly crushing operator/technician which could
result in death or serious injury and possible equipment
or property-only damage.
RT-SVX50D-EN 15
Installation
Unit Foundation When attaching the ductwork to the unit, provide a water-
tight flexible connector at the unit to prevent operating
sounds from transmitting through the ductwork.
WARNING All outdoor ductwork between the unit and the structure
should be weather proofed after installation is completed.
Risk of Roof Collapsing!
Note: For sound consideration, cut only the holes in the
Confirm with a structural engineer that the roof
structure is strong enough to support the combined roof deck for the ductwork penetrations. Do not cut
weight of the roofcurb and the unit. Refer to “Unit out the entire roof deck within the curb perimeter.
Weights,” p. 15 for typical unit and curb weights. Failure If a Curb Accessory Kit is not used:
to ensure proper structural roof support could cause the
roof to collapse, which could result in death or serious a. The ductwork can be attached directly to the
injury and property damage. factory-provided flanges around the unit’s supply
and return air openings. Be sure to use flexible duct
connections at the unit.
NOTICE: b. For “built-up” curbs supplied by others, gaskets
Water Damage! must be installed around the curb perimeter flange
and the supply and return air opening flanges.
Non-factory penetrations through the base of this unit
are not allowed. Any penetration in the base of the unit
may affect the water tight integrity of the unit and lead General Unit Requirements
to water leaks into the conditioned space. Failure to
follow instructions could result in equipment and
property damage. WARNING
Horizontal Units Proper Field Wiring and Grounding
Required!
Notes: All field wiring MUST be performed by qualified
• For complete step by step instructions on how to install personnel. Improperly installed and grounded field
a Horizontal Conversion Kit, please refer to ACC- wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
SVN159*-EN.
field wiring installation and grounding as described in
• For units with optional Condensate Overflow Switch NEC and your local/state electrical codes. Failure to
(COF), the switch will not work properly if unit is not follow code could result in death or serious injury.
level or slightly sloped toward switch.
The checklist listed below is a summary of the steps
• To assure proper condensate flow during operation the
required to successfully install a commercial unit. This
unit and the curb must be level.
checklist is intended to acquaint the installing personnel
If the unit is installed at ground level, elevate it above the with what is required in the installation process. It does not
snow line. Provide concrete footings at each support replace the detailed instructions called out in the
location with a “full perimeter” support structure or a slab applicable sections of this manual.
foundation for support. Refer to Table 1, p. 15 for the unit’s
• Check the unit for shipping damage and material
operating and point loading weights when constructing a
shortage; file a freight claim and notify appropriate
footing foundation.
sales representative.
If anchoring is required, anchor the unit to the slab using
• Verify correct model, options and voltage from
hold down bolts or isolators. Isolators should be installed
nameplate.
to minimize the transmission of vibrations into the
building. • Verify that the installation location of the unit will
provide the required clearance for proper operation.
For rooftop applications, if anchoring is required, anchor
the unit to the roof with hold-down bolts or isolators. • Assemble and install the roof curb (if applicable). Refer
to the latest edition of the curb installers guide that
Check with a roofing contractor for proper waterproofing
ships with each curb kit.
procedures.
• Fabricate and install ductwork; secure ductwork to
Ductwork curb.
Elbows with turning vanes or splitters are recommended • Rigging the unit.
to minimize air noise due to turbulence and to reduce static • Set the unit onto the curb; check for levelness.
pressure.
16 RT-SVX50D-EN
Installation
• Ensure unit-to-curb seal is tight and without buckles or A condensate trap must be installed at the unit due to the
cracks. drain connection being on the “negative pressure” side of
• Install and connect a condensate drain line to the the fan.
evaporator drain connection. A condensate drain line must be connected to the P-Trap.
Pitch the drain lines at least ½-inch for every 10 feet of
Factory Installed Economizer horizontal run to assure proper condensate flow. Do not
• Ensure the economizer has been pulled out into the allow the horizontal run to sag causing a possible double-
operating position. Refer to the standard or low leak trap condition which could result in condensate backup
economizer Installation Instructions for proper due to “air lock”.
position and setup.
Filter Installation
• Install all access panels.
Each unit ships with 2-inch filters installed. The quantity of
Controller Wiring Schematic - LLE filters is determined by unit size. Access to the filters is
obtained by removing the filter access panel.
For additional information, go to the Installation
Instructions ACC-SVN178*-EN. Refer to the unit Service Facts (shipped with each unit) for
filter requirements.
Main Electrical Power Requirements Note: Do not operate the unit without filters.
• Verify that the power supply complies with the unit
Field Installed Power Wiring
nameplate specifications.
• Inspect all control panel components; tighten any An overall dimensional layout for the standard field
loose connections. installed wiring entrance into the unit is illustrated in “Unit
Dimensions,” p. 12. To insure that the unit’s supply power
• Connect properly sized and protected power supply wiring is properly sized and installed, follow the guidelines
wiring to a field-supplied/ installed disconnect switch outlined below.
and to the main power terminal block (HTB1) in the unit
control panel. Note: All field installed wiring must conform to NEC
guidelines as well as state and Local codes.
• Install proper grounding wires to an earth ground.
Verify that the power supply available is compatible with
Note: All field-installed wiring must comply with NEC the unit’s nameplate ratings. The available supply power
and applicable local codes. must be within 10 percent of the rated voltage stamped on
the nameplate. Use only copper conductors to connect the
Electric Heat Requirements power supply to the unit.
• Verify that the power supply complies with the electric
heater specifications on the unit and heater nameplate. NOTICE:
• Inspect the heater junction box and control panel; Use Copper Conductors Only!
tighten any loose connections. Unit terminals are not designed to accept other types of
• Check electric heat circuits for continuity. conductors. Failure to use copper conductors could
result in equipment damage.
• Low Voltage Wiring (AC and DC) Requirements
• Install the zone thermostat, with or without switching Note: If the unit is not equipped with an optional factory
subbase. installed nonfused disconnect switch or circuit
breaker, a field supplied disconnect switch must be
• Connect properly sized control wiring to the proper installed at or near the unit in accordance with the
termination points between the zone thermostat and National Electrical Code (NEC latest edition).
the unit control panel.
RT-SVX50D-EN 17
Installation
Standard Wiring
The electrical service must be protected from over current
and short circuit conditions in accordance with NEC
requirements.
Protection devices must be sized according to the
electrical data on the nameplate.
• If the unit is not equipped with an optional factory
installed nonfused disconnect switch, a field supplied
disconnect switch must be installed at or near the unit
in accordance with the National Electrical Code (NEC
latest edition).
• Location of the applicable electrical service entrance is
illustrated in “Unit Dimensions,” p. 12. Complete the
unit’s power wiring connections onto either; the main
terminal block HTB1 inside the unit control panel, the
factory mounted nonfused disconnect switch (UCD), or
the electric heat terminal block. Refer to the customer
connection diagram that shipped with the unit for
specific termination points.
Control Power Transformer
• Provide proper grounding for the unit in accordance
with local and national codes. The 24-volt control power transformers are to be used only
with the accessories called out in this manual.
Transformers rated greater than 50 Vac are equipped with
internal circuit breakers. If a circuit breaker trips, turn “Off”
all power to the unit before attempting to reset it.
The transformer is located in the control panel. The circuit
breaker is located on the left side of the transformer and
can be reset by pressing in on the black reset button.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of
conductors. Failure to use copper conductors could
result in equipment damage.
18 RT-SVX50D-EN
Installation
51 - 75 feet 18 gauge
• V1, V2, V3 = Line Voltage Readings
15.5 - 22.9 m .75 m2
• VD = Line Voltage reading that deviates the farthest
76 - 125 feet 16 gauge
from the average voltage.
23.1 - 38.1 m 1.3 m2
Example: If the voltage readings of the supply power
126 - 200 feet 14 gauge
measured 221, 230, and 227, the average volts would be:
38.4 - 60.9 m 2.0 m2
221 + 230 + 227
= 226 Avg.
3
Figure 14. Conventional thermostat field wiring
diagram • VD (reading farthest from average) = 221
• The percentage of Imbalance equals:
RT-SVX50D-EN 19
Installation
WARNING WARNING
Live Electrical Components! Hazardous Voltage!
During installation, testing, servicing and
Disconnect all electric power, including remote
troubleshooting of this product, it may be necessary to
disconnects before servicing. Follow proper lockout/
work with live electrical components. Have a qualified
tagout procedures to ensure the power can not be
licensed electrician or other individual who has been
inadvertently energized. Failure to disconnect power
properly trained in handling live electrical components
before servicing could result in death or serious injury.
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury. • Check all electrical connections for tightness and
“point of termination” accuracy.
• Observe the ABC and CBA phase indicator lights on the • Verify that the condenser airflow is unobstructed.
face of the sequencer. The ABC indicator light will glow
• Verify that the condenser fan and indoor blower turn
if the phase is ABC. If the CBA indicator light glows,
freely without rubbing and are properly tightened on
open the disconnect switch or circuit protection switch
the shafts.
and reverse any two power wires.
• Check the supply fan belts for proper tension and the
• Restore the main electrical power and recheck the
fan bearings for sufficient lubrication. If the belts
phasing. If the phasing is correct, open the disconnect
require adjustment, or if the bearings need lubricating,
switch or circuit protection switch and remove the
refer to the maintenance section of this manual for
phase sequence indicator.
instructions.
Compressor Crankcase Heaters • Verify that a condensate trap is installed and the piping
is properly sized and pitched.
NOTICE: • Verify that the correct size and number of filters are in
place.
Compressors Failure!
• Inspect the interior of the unit for tools and debris and
Unit must be powered and crankcase heaters energized install all panels in preparation for starting the unit.
at least 8 hours BEFORE compressors are started. This
will protect the compressors from premature failure.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
RT-SVX50D-EN 21
Pre Start
Verifying Proper Air Flow (Units
with Belt Drive Indoor Fan)
Much of the systems performance and reliability is closely
associated with, and dependent upon having the proper
airflow supplied both to the space that is being
conditioned and across the evaporator coil.
The indoor fan speed is changed by opening or closing the
adjustable motor sheave.
Before starting the SERVICE TEST, set the minimum
position setpoint for the economizer to 0% using the
setpoint potentiometer located on the Economizer Control
(ECA), if applicable.
Electromechanical Controls
Test Procedure
See unit schematic for correct wire numbers.
Fan Test and Minimum Ventilation. Connect red
thermostat wire (R) to black thermostat wire (G).
Economizer Cooling. Connect a jumper wire across
OAT on Economizer Control (ECA).
Connect red thermostat (R) wire to yellow thermostat wire
(Y1).
Cool 1. Connect red thermostat wire (R) to yellow
thermostat wire (Y1).
Cool 2. Connect red thermostat wire (R) to yellow
thermostat wire (Y2).
Heat 1. Connect red thermostat wire (R) to brown
thermostat wire (W1).
Heat 2. Connect red thermostat wire (R) to brown
thermostat wire (W2).
22 RT-SVX50D-EN
Start Up
Standard Economizer Start-Up mode and all components removed or failed will alarm
in the operation mode.
1. Set the minimum position setpoint for the economizer • Upon power up (or after a power outage or brownout),
to the required percentage of minimum ventilation the JADE controller module begins a 5 minute power
using the setpoint potentiometer located on the up delay before enabling mechanical cooling.
Economizer Control (ECA).
The economizer will drive to its minimum position Compressor Start-Up
setpoint, exhaust fans (if applicable) may start at
random, and the supply fan will start when the 1. Attach a set of service gauges onto the suction and
SERVICE TEST is initiated. discharge gauge ports for each circuit. Refer to the
refrigerant circuit illustration in the Service Facts.
The Exhaust Fan will start anytime the economizer
damper position is equal to or greater than the exhaust Using the Service Test Guide, perform the proper test
fan setpoint. mode connections.
2. Verify that the dampers stroked to the minimum Scroll Compressors
position. a. Once each compressor has started, verify that the
3. Verify that the dampers stroked to the full open rotation is correct. If wired correctly the suction
position. pressure should drop and the discharge pressure
should rise. If a scroll compressor is rotating
4. To stop the SERVICE TEST, turn the main power backwards, it will not pump and a loud rattling
disconnect switch to the “Off” position or proceed to sound can be observed.
the next component start-up procedure. Remove
electro mechanical test mode connections (if b. If the electrical phasing is correct, before
applicable). condemning a compressor, interchange any two
leads (at the compressor Terminal block) to check
the internal phasing. Refer to the following
LLE Controls Test Procedure illustration for the compressor terminal/phase
See unit schematic for correct wire numbers. identification. Do not allow the compressor to
operate backwards for more than 5 seconds.
Use the CHECKOUT menu in the Installation Instructions Operation for a period of time longer than this will
(ACC-SVN178*-EN) to test the damper operation and any result in compressor damage. Copeland (Alliance)
configured outputs. Only items that are configured are will experience failure also. If the compressor runs
shown in the Checkout menu. backward for an extended period, the motor
To Perform Checkout Tests: winding can overheat and cause the motor winding
thermostat to open.
1. Scroll to the desired test in the checkout menu using
the and buttons. Figure 16. Compressor terminal box
2. Press the button to select the item.
3. “RUN?” is displayed.
4. Press to start the test.
5. The unit pauses and then displays “IN PROGRESS”.
6. When the test is complete, “DONE” appears.
7. When all parameters have been tested, press
(Menu Up) to end the test (e.g. turn off the relay).
Notes:
• The checkout tests can all be performed at the time of
installation or any time during the operation of the
system.
• JADE will be in "set up" mode for the first 60 minutes
after powered. If OA sensor or Sylk Bus device (sensor
or actuator) is disconnected during the set up mode,
Note: The Copeland SSA scroll compressors for R-410A
the JADE will not alarm that failure. The MA sensor is
units use Trane OIL00094. The correct Oil for Trane
a system "critical" sensor, if the MA sensor is removed
CSHD is Trane OIL00079 or OIL00080. Compressor
during the set up mode, the JADE will alarm. After 60
minutes the JADE controller will change to operation
RT-SVX50D-EN 23
Start Up
types are listed in Table 3, p. 24. The appropriate oil • Program the Night Setback (NSB) panel (if applicable)
charge is listed in Table 4, p. 24. for proper unoccupied operation. Refer to the
programming instructions for the specific panel.
Table 3. Compressor types
• Verify that the Remote panel “System” selection
Tonnage C1 C2 switch, “Fan” selection switch, and “Zone
EA*180 SSA083 SSA076 Temperature” settings for automatic operation are
EA*210 SSA091 SSA083 correct.
EA*240 CSHD142 SSA083 • Inspect the unit for misplaced tools, hardware, and
EA*300 CSHD155 SSA083 debris.
• Verify that all exterior panels including the control
Table 4. POE Oil recharge amount (fl. oz.) panel doors and condenser grilles are secured in place.
• Close the main disconnect switch or circuit protector
C1 C2 switch that provides the supply power to the unit’s
Model 25mm 25mm
terminal block or the unit mounted disconnect switch.
EA*180 56 56
EA*210 56 56
EA*240 112 56
EA*300 112 56
Heating Start-Up
1. Clamp an amp meter around one of 1st stage heater
power wires at the heater contactor.
2. Verify that the heater stage is operating properly.
3. Clamp an amp meter around one of 2nd stage heater
power wires at the heater contactor (if applicable).
4. Verify that the heater stage is operating properly.
5. To stop the SERVICE TEST, turn the main power
disconnect switch to the “Off” position or proceed to
the next component start-up procedure. Remove
electro mechanical test mode connections.
24 RT-SVX50D-EN
Maintenance
Make sure all personnel are standing clear of the unit 6. Compare the “force” scale reading (Step 5) with the
before proceeding. The system components will start appropriate “force” value listed in Table 5, p. 25. If the
when the power is applied. “force” reading is outside the range, readjust the belt
tension.
Fan Belt Adjustment—Belt Drive Note: Actual belt deflection “force” must not exceed the
maximum “force” value shown in Table 5, p. 25.
Units
7. Recheck the belt tension at least twice during the first
2 to 3 days of operation. Belt tension may decrease
WARNING until the new belts are “run in”.
Refer to Table 5, p. 25. 13.3–16.0 13.3 20.0 17.2 24.5 14.5 17.8
16.9–21.4 15.6 22.2 20.0 27.8 16.7 21.1
5. Remove the belt tension gauge. The small O-ring now A
indicates a number other than zero on the plunger’s 22.0–31.1 17.8 24.5 22.2 30.6 18.9 23.4
force scale. This number represents the force (in 15.1–18.7 17.8 24.5 25.6 35.6 20.0 24.5
pounds) required to give the needed deflection. 19.6–24.9 22.8 31.7 28.9 40.6 25.6 32.3
B
25.8–39.1 28.4 38.9 32.8 45.0 31.1 38.9
RT-SVX50D-EN 25
Maintenance
26 RT-SVX50D-EN
Maintenance
Due to the soft material and thin walls of the MCHE coils, (2) Unit Serial Number:
the traditional field maintenance method recommended _____________________________________________________
for Round Tube Plate Fin (RTPF) coils does not apply to
microchannel coils. (3) Wiring Diagram Numbers (from unit control panel)
Moreover, chemical cleaners are a risk factor to MCHE due — schematic(s)
to the material of the coil. The manufacturer does not _____________________________________________________
recommend the use of chemical cleaners to clean _____________________________________________________
microchannel coils. Using chemical cleaners could lead to — connection(s)
warranty claims being further evaluated for validity and
_____________________________________________________
failure analysis.
____________________________________________________
The recommended cleaning method for microchannel
condenser coils is pressurized water or air with a non-
pinpoint nozzle and an ECU of at least 180 with pressure no
greater than 600 psi. To minimize the risk of coil damage,
approach the cleaning of the coil with the pressure washer
aimed perpendicular to the face of the coil during cleaning.
Optimum clearance between the sprayer nozzle and the
microchannel coil is 1”–3”.
Final Process
For future reference, you may find it helpful to record the
unit data requested below in the blanks provided.
(1) Complete Unit Model Number:
_____________________________________________________
RT-SVX50D-EN 27
Troubleshooting
To Clear an Alarm
WARNING Once the alarm has been identified and the cause has been
Hazardous Service Procedures! removed (e.g. replaced faulty sensor), the alarm can be
The maintenance and troubleshooting procedures cleared from the display.
recommended in this section of the manual could result 1. Navigate to the desired alarm.
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings 2. Press .
provided throughout this manual concerning these 3. “ERASE?” is displayed.
procedures. Unless specified otherwise, disconnect all
electrical power including remote disconnect and 4. Press .
discharge all energy storing devices such as capacitors 5. “ALARM ERASED” is displayed.
before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be 6. Press (Menu Up) to complete the action and return
inadvertently energized. When necessary to work with to the previous menu.
live electrical components, have a qualified licensed Note: If an alarm still exists after you clear it, it re-displays
electrician or other individual who has been trained in within 5 seconds.
handling live electrical components perform these
tasks. Failure to follow all of the recommended safety Low Leak Economizer Fault Codes
warnings provided, could result in death or serious
injury. Low Leak Economizer Alarms:
• CO2 Sensor Error
Standard Troubleshooting • SYS Alarm
Failures • Actuator Undervoltage
• Actuator Overvoltage
Cooling Failure
• Actuator Stalled
1. Cooling and heating set point (slide pot) on the
thermostat has failed. The FDD system shall detect the following faults:
2. CC1 or CC2 24 VAC control circuit has opened. Check • Air temperature sensor failure/fault
CC1 & CC2 coils, and any of the controls below that • Not economizing when it should
apply to the unit (HPC1, HPC2, LPC1, LPC2, DLT1, DLT2,
• Economizing when it should not
Frostat™).
• Damper not modulating
Simultaneous Heat and Cool Failure
• Excess outdoor air
• Emergency Stop is activated.
The JADE controller is a certified FDD product (HJW10) by
California Title 24, Part 6. The FDD system is required for
Low Leak Economizer meeting California Energy Commission's Title 24
(LLE) Troubleshooting regulations. Table 7, p. 29 shows the various tests that can
be performed (rows) and the five faults that are defined by
1. The economizer controller provides alarm messages FDD (columns). The 'x' means that the test has to be
that display on the 2-line LCD. If one or more alarms are conducted to see if it is causing the fault to occur.
present and there has been no keypad activity for at
least 5 minutes, the Alarms menu displays and cycles
through the active alarms.
Note: You can also navigate to the Alarms menu at any
time.
2. Once the alarm has been identified and the cause has
been removed (e.g. replaced faulty sensor), the alarm
can be cleared from the display.
Note: If an alarm still exists after you clear it, it re-displays
within 5 seconds.
28 RT-SVX50D-EN
Troubleshooting
Method 1
To reset the system from the space, turn the “Mode”
selection switch at the thermostat to the “Off” position.
After approximately 30 seconds, turn the “Mode”
selection switch to the desired mode, i.e. Heat, Cool or
Auto.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch “Off” and then “On”.
RT-SVX50D-EN 29
Wiring Diagrams
Note: Wiring diagrams can be accessed via e-Library by
entering the diagram number in the literature order
number search field or by contacting technical
support.
Table 8. Wiring diagrams
Type of Schematic Diagram
Airflow Type Voltage Number Description
208-230/380(a) 2313-2202 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat
Power
460-575 2313-2204 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat
Control 208-575 2313-2207 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat
Constant
Volume Raceway
208-575 2313-2239 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat
Connection
Control Box 208-230/380(a) 2313-2230 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat
Connection 460-575 2313-2234 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat
208-230 2313-2225 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat w/VFD
Power
460-575 2313-2227 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat w/VFD
Control 208-575 2313-2209 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat w/VFD
Multi-Speed
Fans Raceway
208-575 2313-2240 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat w/VFD
Connection
Control Box 208-230 2313-2231 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat w/VFD
Connection 460-575 2313-2235 EAC180-300, EAD180-300, 60Hz, Cooling only / Electric Heat w/VFD
(a) Unit will operate reliably at 400VAC.
30 RT-SVX50D-EN
Warranty
Central Air Conditioner where the end purchaser uses the product for other than
personal, family or household purposes.
EAC, EAD (Parts Only) *A 5 year limited warranty is provided for the optional Low
Leak Economizer, including the JADE control system
Models Less than 20 Tons for Commercial (controller, actuator and sensors).
Use*
Models 20 Tons and Greater for Commercial
This warranty is extended by Trane, to the original
Use*
purchaser and to any succeeding owner of the real
property to which the Air Conditioner is originally affixed, The Company warrants for a period of 12 months from
and applies to products purchased and retained for use initial start-up or 18 months from date of shipment,
within the U.S.A. and Canada. There is no warranty against whichever is less, that the Company products covered by
corrosion, erosion or deterioration. this order (1) are free from defects in material and
If any part of your Air Conditioner fails because of a workmanship and (2) have the capacities and ratings set
manufacturing defect within one year from the date of the forth in the Company’s catalogs and bulletins, provided
original purchase, Warrantor will furnish without charge that no warranty is made against corrosion, erosion or
the required replacement part. deterioration.
In addition, if the sealed motor-compressor fails because
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth
of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will
year from the date of original purchase, Warrantor will furnish without charge the required replacement
furnish without charge the required replacement compressor
compressor.
Warrantor’s obligations and liabilities under this warranty The Company’s obligations and liabilities under this
are limited to furnishing F.O.B. Warrantor factory or warranty are limited to furnishing f.o.b. factory or
warehouse replacement parts for Warrantor’s products warehouse at Company designated shipping point, freight
covered under this warranty. allowed to Buyer’s city (or port of export for shipment
Warrantor shall not be obligated to pay for the cost of lost outside the conterminous United States) replacement
refrigerant. equipment (or at the option of the Company parts
No liability shall attach to Warrantor until products have therefore) for all Company products not conforming to this
been paid for and then liability shall be limited solely to the warranty and which have been returned to the
purchase price of the equipment under warranty shown to manufacturer.
be defective. The Company shall not be obligated to pay for the cost of
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE lost refrigerant.
IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, No liability whatsoever shall attach to the Company until
WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS said products have been paid for and then said liability
OR IMPLIED, IN LAW OR IN FACT, INCLUDING BUT NOT shall be limited to the purchase price of the equipment
SPECIFICALLY LIMITED TO IMPLIED WARRANTIES OF shown to be defective.
MERCHANTABILITY AND FITNESS FOR PARTICULAR The Company makes certain further warranty protection
USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE available on an optional extra-cost basis. Any further
FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. warranty must be in writing, signed by an officer of the
Company.
Some states do not allow limitations on how long an
The warranty and liability set forth herein are in lieu of all
implied warranty lasts or do not allow the exclusion or
other warranties and liabilities, whether in contract or in
limitation of incidental or consequential damages, so the
negligence, express or implied, in law or in fact, including
above limitation or exclusion may not apply to you. This
implied warranties of merchantability and fitness for
warranty gives you specific legal rights, and you may also
particular use.
have other rights which vary from state to state.
In no event shall the Company be liable for any incidental
Trane or consequential damages.
2701 Wilma Rudolph Blvd.
Clarksville, TN 37040-1008
Attention: Manager, Product Service
GW-602-4800
* This warranty is for commercial usage of said equipment
and not applicable when the equipment is used for a
residential application. Commercial use is any application
RT-SVX50D-EN 31
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient
environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and
Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.
ingersollrand.com
Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.