Professional Documents
Culture Documents
Axial Fans: Technical Submittals
Axial Fans: Technical Submittals
AXIAL FANS
___________________________
Technical Submittals
Rev. 00
TECHNICAL DATA SUMMARY
1 - 2 Wall Mounted Propeller Fan (Direct Drive) 14700 - 2.20 460/3/60 WMF-P-22-D
2 - 1 Wall Mounted Propeller Fan (Direct Drive) 4840 - 0.37 460/3/60 WMF-P-16-D
3 - 1 Wall Mounted Propeller Fan (Direct Drive) 14829 - 2.20 460/3/60 WMF-P-22-D
4 - 2 Wall Mounted Propeller Fan (Direct Drive) 9000 - 0.75 460/3/60 WMF-P-20-D
5 - 1 Wall Mounted Propeller Fan (Direct Drive) 2510 - 0.37 460/3/60 WMF-P-12-D
6 - 1 Roof Top Ventilator Propeller Fan (Direct Drive) 1600 - 0.37 460/3/60 REF-IMP-12-D
7 - 1 Roof Top Ventilator Propeller Fan (Direct Drive) 18000 - 2.20 460/3/60 REF-IMP-24-D
WMF-P-24-D C/W
8 - 4 Wall Mounted Propeller Fan (Direct Drive) 21500 125 5.50 460/3/60
Weather Hood
WMF-P-24-D C/W
9 - 3 Wall Mounted Propeller Fan (Direct Drive) 21000 125 5.50 460/3/60
Weather Hood
10 - 2 Roof Top Ventilator Propeller Fan (Direct Drive) 43000 122 11.00 460/3/60 REF-IMP-30-D
11 - 2 Roof Top Ventilator Propeller Fan (Direct Drive) 43000 122 11.00 460/3/60 REF-IMP-30-D
12 - 1 Wall Mounted Propeller Fan (Direct Drive) 12300 125 2.20 460/3/60 WMF-P-22-D
Item Q TSP Motor Installed
Designation Qty Description Model Name
No. CMH PA kW Vo/Ph/Hz
13 - 1 Wall Mounted Propeller Fan (Direct Drive) 3702 118 0.37 460/3/60 WMF-P-16-D
14 - 2 Wall Mounted Propeller Fan (Direct Drive) 45605 112 15.00 460/3/60 WMF-P-30-D
B
(TYP.)
A
(SQUARE)
ITEM 1
250
200
150
100
14700CMH
50
0
0 5k 10k 15k 20k
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 5k 10k 15k 20k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
13.0% 1.85 kW 2.2 kW 1750 rpm
SIZE 16"
A 508.0
B 254.0
C 418.0 ITEM 2: 4,840 CMH
B
(TYP.)
A
(SQUARE)
ITEM 2
200
150
100
4840CMH
50
0
0 1000 2000 3000 4000 5000 6000 7000
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 1000 2000 3000 4000 5000 6000 7000
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
26.0% 0.31 kW 0.37 kW 1750 rpm
SIZE 22"
A 716.0
B 358.0
C 570.0 ITEM 3: 14,829 CMH
B
(TYP.)
A
(SQUARE)
ITEM 3
250
200
150
100
14829CMH
50
0
0 5k 10k 15k 20k
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 5k 10k 15k 20k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
13.0% 1.85 kW 2.2 kW 1750 rpm
SIZE 20"
A 644.0
B 322.0
C 520.0 ITEM 4: 9,000 CMH
B
(TYP.)
A
(SQUARE)
ITEM 4
200
150
100
9000CMH
50
0
0 2000 4000 6000 8000 10000 12000
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 2000 4000 6000 8000 10000 12000
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
23.0% 0.64 kW 0.75 kW 1750 rpm
SIZE 12"
A 354.0
B 177.0
C 367.0 ITEM 5: 2510 CMH
B
(TYP.)
A
(SQUARE)
ITEM 5
100
80
60 2510CMH
40
20
0
0 1000 2000 3000 4000
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 1000 2000 3000 4000
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
31.0% 0.14 kW 0.37 kW 1750 rpm
SIZE 12"
A 584.0
B
C
484.0
160.0
ITEM 6: 1600 CMH
D 304.0
E 464.0 F (square)
F 561.0
B (square)
A (square)
ITEM 6
120
90
60 1600CMH
30
0
0 500 1000 1500 2000 2500 3000
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 500 1000 1500 2000 2500 3000
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
39.0% 0.07 kW 0.37 kW 1750 rpm
SIZE 24"
A
B
872.0
772.0
ITEM 7: 18,000 CMH
C 232.0
D 354.0
E 586.0 F (square)
F 1086.0
B (square)
A (square)
ITEM 7
300
200
100
18000CMH
0
0 5k 10k 15k 20k 25k 30k
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 5k 10k 15k 20k 25k 30k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
16.0% 1.93 kW 2.2 kW 1750 rpm
ITEM 8: 21,500 CMH @ 125 PA
676.0
768.0
(SQUARE) 309.0
N OTES
1. PROPELLER FAN AS SHOWN VARIES DEPENDING UPON
THE REQUIREMENT OF THE CUSTOMER
2. DIMENSIONS IN ( ) VARIES DEPENDING UPON THE SIZE OF
MOTOR TO BE USED.
GRASCO DRWN: DELOSREYES MODEL: WMF-P-24-D c/w Weather Hood CAD CODE: MAT'L: 1
ALLIED METALWORKS SPECIALIST INCORPORATED
WAREHOUSE 3A-A LA FILIPINA PROPERTY MANAGEMENT CORP., CHKD: APP TITLE: QTY.: 1 assy. SCALE:1:12.5 1
OLD NATIONAL HIGHWAY, BRGY. LANDAYAN,SAN PEDRO,LAGUNA WALL MOUNTED PROPELLER FAN (DIRECT DRIVE)
APPD: NAP DRWG. NO.: SHEET:
8-2000 EN-025 REV. 1
FAN PERFORMANCE CURVED
ITEM 8
400
300
200
21500CMH@125PA
100
0
0 5k 10k 15k 20k 25k 30k
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 5k 10k 15k 20k 25k 30k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
17.0% 4.28 kW 5.5 kW 1750 rpm
ITEM 9: 21,000 CMH @ 125 PA
676.0
768.0
(SQUARE) 309.0
N OTES
1. PROPELLER FAN AS SHOWN VARIES DEPENDING UPON
THE REQUIREMENT OF THE CUSTOMER
2. DIMENSIONS IN ( ) VARIES DEPENDING UPON THE SIZE OF
MOTOR TO BE USED.
GRASCO DRWN: DELOSREYES MODEL: WMF-P-24-D c/w Weather Hood CAD CODE: MAT'L: 1
ALLIED METALWORKS SPECIALIST INCORPORATED
WAREHOUSE 3A-A LA FILIPINA PROPERTY MANAGEMENT CORP., CHKD: APP TITLE: QTY.: 1 assy. SCALE:1:12.5 1
OLD NATIONAL HIGHWAY, BRGY. LANDAYAN,SAN PEDRO,LAGUNA WALL MOUNTED PROPELLER FAN (DIRECT DRIVE)
APPD: NAP DRWG. NO.: SHEET:
8-2000 EN-025 REV. 1
FAN PERFORMANCE CURVED
ITEM 9
400
300
200
21000CMH@125PA
100
0
0 5k 10k 15k 20k 25k 30k
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 5k 10k 15k 20k 25k 30k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
19.0% 3.90 kW 5.5 kW 1750 rpm
SIZE 30"
A 1034.0
B 934.0
ITEM 10 & 11: 43,000 CMH @ 122 PA
C 332.0
D 354.0
E 686.0 F (square)
F 1324.0
B (square)
A (square)
ITEM 10 & 11
600
400
200
43000CMH@122PA
0
0 10k 20k 30k 40k 50k
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 10k 20k 30k 40k 50k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
15.0% 9.88 kW 11 kW 1750 rpm
SIZE 22"
A 716.0
B 358.0
C 570.0 ITEM 12: 12,300 CMH @ 125 PA
B
(TYP.)
A
(SQUARE)
ITEM 12
250
200
150 12300CMH@125PA
100
50
0
0 5k 10k 15k 20k
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 5k 10k 15k 20k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
57.0% 1.58 kW 2.2 kW 1750 rpm
SIZE 16"
A 508.0
B 254.0
C 418.0 ITEM 13: 3,702 CMH @ 118 PA
B
(TYP.)
A
(SQUARE)
ITEM 13
200
150
3702CMH@118PA
100
50
0
0 1000 2000 3000 4000 5000 6000 7000
Air Volume in m3/h
Total Efficiency %
100
80
60
40
20
0
0 1000 2000 3000 4000 5000 6000 7000
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
42.0% 0.29 kW 0.37 kW 1750 rpm
SIZE 30"
A 923.0
B 461.5
C 778.0
ITEM 14: 45,605 CMH @ 112 PA
B
(TYP.)
A
(SQUARE)
ITEM 14
800
600
400
200 45605CMH@112PA
0
0 10k 20k 30k 40k 50k
Air Volume in m3/h
Fan Static Eff.% Fan Absorbed Power Motor Rating Installed Fan Speed
11.0% 12.35 kW 15 kW 1750 rpm