Professional Documents
Culture Documents
Experimental Thermal and Fluid Science
Experimental Thermal and Fluid Science
a r t i c l e i n f o a b s t r a c t
Article history: Heat transfer, friction factor, effectiveness and number of transfer units (NTU) were determined experi-
Received 18 December 2016 mentally for a Fe3O4 nanofluid flowing through the inner tube with longitudinal strip inserts of a double
Received in revised form 9 March 2017 pipe U-bend heat exchanger. Different concentrations of the Fe3O4 nanofluid, which is the hot fluid, were
Accepted 13 March 2017
used in the present study and cold water circulates in the annulus region of the double pipe heat exchan-
Available online 16 March 2017
ger. The heat transfer and friction factor experiments were conducted for the Reynolds number range
from 15,000 to 30,000 with the Fe3O4 nanofluid volume concentrations of 0.005%, 0.01%, 0.03% and
Keywords:
0.06%. The effect on heat transfer and friction factor of longitudinal strip inserts in the inner tube is stud-
Nanofluid
Heat transfer
ied for three different strip aspect ratios (AR) with the values of 1, 2 and 4, respectively. The results indi-
Friction factor cate the Nusselt number on the nanofluid side increases with increasing Reynolds number and particle
Longitudinal strip inserts concentration, and with decreasing aspect ratio of the longitudinal strip inserts. The Nusselt number
Effectiveness enhancement, compared to the water data, for the 0.06% volume concentration of the nanofluid is
14.7% and it further increases to 41.29% for the same 0.06% concentration with the longitudinal strip
insert with AR equal to 1 for the Reynolds number of 28,954. Compared to water data, the friction factor
for the 0.06% volume concentration of the nanofluid increases by 1.092-times and it further increases to
1.267-times for the same concentration with the longitudinal strip insert with AR equal to 1 for the
Reynolds number of 28,954. The overall performance of the double pipe heat exchanger with longitudinal
strip inserts in the nanofluid side is expressed in terms of effectiveness and number of transfer units
(NTU). New correlations for the Nusselt number and friction factor are reported and they are based on
the obtained experimental data.
Ó 2017 Elsevier Inc. All rights reserved.
1. Introduction ing their commonly used working fluids by high thermal conduc-
tivity fluids such as nanofluids, which yield increased convective
Double pipe heat exchangers are widely used in chemical, food, heat transfer. Nanofluids, nowadays, are well-established and their
oil and gas industries due to their low-cost, manufacturing simplic- preeminence owes much to the pioneering work of Choi [1] and his
ity and easy maintenance. In addition, an important advantage of team.
the double pipe heat exchanger is its wide operating temperature Zamzamian et al. [2] obtained heat transfer enhancement of
range, which has a particular niche in different processes such as 26% for 1.0% weight of Al2O3/EG and 37% for 1.0% weight of CuO/
pasteurizing, reheating, preheating, digester heating and effluent EG in double pipe heat exchanger, while for the plate heat exchan-
heating. In small scale industries these heat exchangers tend to ger the heat transfer enhancement was 38% and 49%, respectively.
be favored for their low capital and operating costs. They com- Rabienataj Darzi et al. [3] observed heat transfer enhancement of
monly use as working fluids, among others, water, ethylene glycol, 20% for 1.0% volume concentration of Al2O3/water flow in a double
propylene glycol, and engine oil. A topic of ongoing investigation is pipe heat exchanger under turbulent flow conditions. El-Maghlany
the performance enhancement of these heat exchangers by replac- et al. [4] experimentally studied the effectiveness and number of
transfer units (NTU) for a double-pipe horizontal counter-flow heat
⇑ Corresponding author. exchanger with the Cu/water nanofluid as one of the working flu-
E-mail addresses: sslingala@gmail.com (L.S. Sundar), mksingh@ua.pt ids. Arani et al. [5] observed Nusselt number enhancement by
(M.K. Singh).
http://dx.doi.org/10.1016/j.expthermflusci.2017.03.019
0894-1777/Ó 2017 Elsevier Inc. All rights reserved.
332 N.T. Ravi Kumar et al. / Experimental Thermal and Fluid Science 85 (2017) 331–343
Nomenclature
using the TiO2/water nanofluid in a horizontal double tube For pipe flow, higher heat transfer rates can be achieved by
counter-flow heat exchanger under fully developed turbulent flow. enhanced turbulence, and to this aim longitudinal strip inserts will
Khedkar et al. [6] obtained 16% heat transfer enhancement using a be used in this work. The original work on the concept of longitu-
3.0% volume concentration of Al2O3/water nanofluid in a concen- dinal strip inserts in a tube as turbulence enhancers was used by
tric tube heat exchanger. Goodarzi et al. [7] conducted heat trans- Liu [18] back in 1996 and he performed experiments in the fully
fer experiments for Reynolds numbers between 5000 and 15,000 developed turbulent flow region. Later, Hsieh and Wen [19], Hsieh
and observed heat transfer enhancement of 16.2% for 0.06% weight and Huang [20] conducted heat transfer experiments for water
fraction of nitrogen-doped graphene (NDG) nanofluids. Sarafraz flow in a tube with longitudinal strip inserts in the Reynolds num-
et al. [8] observed that the heat exchanger thermal performance ber range from 1700 to 4000 and they observed the occurrence of
in comparison with water was up by 44% for a 0.3% mass concen- heat transfer augmentation. Saha and Langille [21] also used longi-
tration of the CNT/water nanofluid used in a double pipe heat tudinal strip inserts for water flow in a tube and conducted heat
exchanger for a Reynolds number of 10,500. Duangthongsuk and transfer and pressure drop experiments in the laminar region.
Wongwises [9] reported a heat transfer enhancement of 11% for Based on this literature, the use longitudinal strip inserts for com-
0.2% volume concentration of TiO2/water nanofluid in a horizontal monly used fluids yields heat transfer enhancement.
double pipe counter flow heat exchanger under turbulent flow Longitudinal strips for nanofluids flowing in a tube were used
conditions. Sarafraz and Hormozi [10] determined a heat transfer by Sundar and Sharma [22]. They conducted heat transfer and fric-
enhancement of 67% for 1.0% volume concentration of 50:50% tion factor experiments with the Al2O3 nanofluid in a tube with
EG/W based silver nanofluids used in a double pipe heat exchan- longitudinal strip inserts and, for a 0.5% volume concentration of
ger. Sonawane et al. [11] observed a 16% overall heat transfer the Al2O3 nanofluid and a longitudinal strip insert with aspect ratio
enhancement for 3.0% volume concentration of Al2O3 nanofluids equal to 1, they observed heat transfer enhancement of 76.20% and
in a double pipe heat exchanger for a Reynolds number of 3992. 80.19%, as compared to water flowing in a plain tube, for Reynolds
Reddy et al. [12] reported that the heat transfer coefficient and fric- number values of 3000 and 22,000, respectively. Sundar et al. [23],
tion factor increase by 10.73% and 8.73%, respectively, for a 0.02% also using a 0.5% volume concentration of the Al2O3 nanofluid and
volume concentration of TiO2 water based nanofluid. Hemmat Esfe a longitudinal strip insert with aspect ratio equal to 1, reported
and Saedodin [13] conducted heat transfer experiments for MgO/ heat transfer enhancement of 32.12% and 14.50% for Reynolds
water nanofluid in a double pipe heat exchanger for particle con- number values of 700 and 2200, respectively. Prasad et al. [24],
centrations in the range from 0.005 to 0.02 and they also observed using a 0.03% volume concentration of the Al2O3 nanofluid in a
an increase in heat transfer rates. Aghayari et al. [14] observed heat double pipe heat exchanger and a longitudinal strip insert of aspect
transfer enhancement of 19% and Nusselt number enhancement of ratio equal to 1, observed heat transfer enhancement of 47.35%
24% for a 0.3% volume concentration of Al2O3/water nanofluid in a with a friction penalty of 1.21-times, as compared to water flowing
double pipe heat exchanger. Sudarmadji et al. [15] noted a Nusselt with no longitudinal strip insert. Sundar et al. [25] report a Nusselt
number increase of 40.5%, as compared to the water data, for the number enhancement for 0.3% volume concentration of MWCNT/
0.5% volume concentration of the Al2O3/water nanofluid in the Fe3O4 hybrid nanofluid flowing in a tube without inserts of
hot side of a double pipe heat exchanger. Demir et al. [16], by using 32.72% and with longitudinal strip inserts of aspect ratio equal to
a CFD analysis, numerically investigated the forced convection flow 1 of 50.99% for a Reynolds number of 22,000.
of water-based nanofluids with TiO2 and Al2O3 nanoparticles in a Data for Fe3O4 nanofluids flowing in an inner tube of a double
horizontal tube with constant wall temperature. Choi and Zhang pipe heat exchanger with longitudinal strip inserts is not available;
[17] investigated numerically by using a finite element method therefore, the present study is primarily focused on the estimation
the laminar forced convection heat transfer of the Al2O3/water of heat transfer, friction factor, effectiveness and number of trans-
nanofluid flowing in a pipe with a return bend and they observed fer units for a double pipe heat exchanger having a nanofluid flow-
Nusselt number enhancement with increasing Reynolds number ing through the inner tube with longitudinal strip inserts. The
and Prandtl number. Interestingly, in their majority the studies experiments were conducted for the Reynolds number range from
dealing with the use of nanofluids in double pipe heat exchangers 15,000 to 30,000, particle volume concentration from 0% to 0.06%
observed higher heat transfer rates with practically negligible fric- for the Fe3O4 nanofluid and longitudinal strip inserts of aspect
tion increase. ratios 1, 2 and 4. The thermal performance of heat exchanger is
N.T. Ravi Kumar et al. / Experimental Thermal and Fluid Science 85 (2017) 331–343 333
determined for different operating conditions and longitudinal W Fe3 O4 is the weight of the nanoparticles. Based on Eq. (1), the quan-
strip inserts. New Nusselt number and friction factor correlations tities of 4.364, 8.278, 26.19, 52.39 g of Fe3O4 nanoparticles were
are proposed based on the experimental data. used for the preparation of 0.005%, 0.01%, 0.03% and 0.06% volume
concentrations, respectively. The thermophysical properties of
2. Experimental section Fe3O4 nanoparticles and the distilled water were shown in Table 1.
The thermal properties of Fe3O4 nanofluids were taken from Sundar
2.1. Nanofluids preparation et al. [26] and the data shown in Table 2.
The magnetic nanoparticles (Fe3O4) were purchased from 2.2. Test section and experimental procedure
Sigma-Aldrich Chemicals, USA. The nanofluids were prepared by
dispersing Fe3O4 nanoparticles in distilled water for volume con- The schematic diagram of the experimental setup is depicted in
centrations of 0.005%, 0.01%, 0.03% and 0.06% in bulk quantities Fig. 2a and the actual view of the experimental setup is shown in
of 15 L. Cetyl Trimethyl Ammonium Bromide (CTAB) surfactant Fig. 2b, and the test section details are presented in Fig. 2c. The
was used for stability of the nanoparticles in the base fluid (water) experimental setup consists of: (i) two concentric tube heat
on a proportion of nearly 1/10th of weight of nanoparticles. CTAB exchangers, (ii) data logger along with a personal computer, (iii)
was added to 15 L of distilled water and then stirred with high cooling water tank and heating water tank, (iv) thermocouples,
speed stirrer; after full dispersion of surfactant in water the (v) flow meters (both on hot and cold sides), and (vi) U-tube
required quantity of nanoparticles were added and stirring was manometer. The test section contains the inner tube and the annu-
maintained for 24 h, as illustrated in the photo shown in Fig. 1. lus tube. The inner diameter (ID) and outer diameter (OD) of the
The particles required for a specified volume concentration per- stainless steel inner tube is 0.019 m and 0.025 m, respectively.
centage were calculated using the following relation: The inner diameter (ID) and outer diameter (OD) of the cast iron
2 3 annulus is 0.05 m and 0.056 m, respectively. The test section con-
W Fe
3 O4 tains two tube-side passes (Fig. 2c) in which the inner tube is bent
6 qFe3 O4 7
Volume concentration; / 100 ¼ 6
4 7
5 ð1Þ at a distance of 2.2 m with a radius of 0.160 m. The total length of
W Fe the inner tube is 5 m and the effective length of one pass is 2.2 m.
3 O4
qFe3 O4 þ W water
qwater
The heat loss from the test section is minimized by wrapping the
annulus tube with asbestos rope material. The four thermocouples
where / is the percentage of volume concentration (%),
are of the resistance temperature detectors (RTD) type and they
qFe3 O4 = 5810 kg/m3, qwater = 998.5 kg/m3, Wwater = 15,000 g and
were installed to measure the inlet and outlet temperatures of
hot fluid (water or nanofluid) and cold fluid (water). Thermocouple
needles are connected to the data acquisition system and the read-
ings were recorded in the computer for further processing. Before
using the thermocouples in the test section, they are calibrated
and the obtained resolution is ±0.1 °C. The flow in the test section
is assumed to be hydrodynamically developed considering that l/d
is equal to 263 (l: length; d: diameter).
Two flow meters were used to measure the flow rates of cold
fluid and hot fluid (nanofluid). The hot fluid was supplied through
the inner tube, while the cold fluid, which circulates through the
annulus, is used as the cooling medium. The counter flow arrange-
ment was adopted for the present work. The temperature of the
cold water (annulus side) was maintained around 29 °C with a con-
stant flow rate of 8 LPM (0.133 kg/s). The hot Fe3O4 nanofluid (tube
side) with constant inlet temperature of 60 °C from the hot fluid
tank was supplied through the inner tube at different mass flow
rates of 8, 10, 12 and 14 LPM. The experiments were conducted
for different particle concentrations of 0.005%, 0.01%, 0.03% and
0.06%. The temperatures of the nanofluid and water were only
recorded after steady state is reached. The test section was cali-
brated with water as the hot working fluid, before using the
Fe3O4 nanofluid. For each and every nanofluid experiment the test
section is thoroughly cleaned with pure water. The thermophysical
properties of the nanofluid were calculated at mean temperature,
and the formulas used for Nusselt number determination are
reported in section 3. The pressure drop across the inner tube of
the test section was measured by placing a mercury (Hg) filled
U-tube manometer between both ends of the tube. To this purpose,
Fig. 1. Preparation of bulk Fe3O4 nanofluid.
4-mm holes, which were drilled at both ends of the inner tube, are
connected using flexible tubing to the U-tube manometer; the Hg
Table 1
Thermophysical property of Fe3O4 nanoparticles and distilled water at 20 °C.
Particle/water Mean diameter Density (kg/m3) Thermal conductivity (W/m K) Specific heat (kJ/kg K) Viscosity (mPas)
Fe3O4 36 nm 5810 80.4 670 –
Water – 998.5 0.6024 4182 0.79
334 N.T. Ravi Kumar et al. / Experimental Thermal and Fluid Science 85 (2017) 331–343
Table 2
Thermophysical properties of base fluid and Fe3O4 nanofluid [26].
relative height is recorded as a function of the mass flow rate. The inserts is calculated based on the hydraulic diameter. The hydrau-
system requires approximately two hours of operation to reach lic diameter (dh) is defined as follows:
steady state, and only then the readings of the four thermocouples
are recorded and used for the heat transfer calculations. The heat 4A
dh ¼ ð2Þ
transfer and friction factor experiments were repeated three times p
at a particular mass flow rates (8, 10, 12, and 14 LPM) and the aver- where p is the perimeter, and A the cross-sectional area.
age values (temperatures of thermocouples) were used for Nusselt The heat conducted by the longitudinal strip inserts is neglected
number, effectiveness and friction factor calculations. The inner in the heat transfer calculations.
tube heat transfer coefficient for the nanofluid is calculated based
on the logarithmic mean temperature difference method.
3. Calculated parameters
2
f ¼ ð1:58 lnðReÞ 3:82Þ ; 2300 < Re < 106 ; 0:5 < Pr < 2000
4A
Dh ¼ ¼ Do Di ð9Þ
P
where A is the flow area and determined as A ¼ p4 ðD2o D2i Þ.
The Nusselt number value obtained from Eq. (8) is used to cal-
culate the annulus heat transfer coefficient (ho) using the hydraulic
diameter (Dh) and thermal conductivity of annulus fluid at mean
temperature and the equation is given as:
Fig. 2b. Photograph of an experimental setup. Nuo ko
ho ¼ ð10Þ
Dh
Rate of heat flow ðannulus-side fluidÞ; The value of ho, which is determined from Eq. (10), is substi-
Qc ¼ m_ c C c ðT c;o T c;i Þ ð4Þ tuted in Eq. (7) to obtain the inner tube-side heat transfer coeffi-
cient (hi or hnf); the Nusselt number of nanofluid (Nunf) can be
Overall heat transfer coefficient ðtube-sideÞ; determined as:
Q av g hnf Di
Ui ¼ 0 1 ð5Þ Nunf ¼ ð11Þ
knf
Ai @DT1 DT2 A
ln
DT 1 The Reynolds number is based on the flow rate at the inlet of
DT 2
the tube.
Overall heat transfer coefficient ðannulus sideÞ; qv d i
Renf ¼ ð12Þ
Q av g
l nf
Uo ¼ 0 1 ð6Þ
The Prandtl number is calculated based on the nanofluid speci-
Ao @DT1 DT2 A fic heat, thermal conductivity, and viscosity, which are determined
DT 1
ln DT 2 at the nanofluid mean temperature.
where Q av g ¼ Q h þQ ; DT 1 ¼ T h;i T c;o ; DT 2 ¼ T h;o T c;i .
lC P
2
c
Prnf ¼ ð13Þ
For double pipe heat exchangers by neglecting fouling, the rela-
k nf
experiments. The heat exchange between the hot and cold streams
was estimated by both Eqs. (3) and (4); the observed deviation was
±2.5%, which indicates the eventual heat losses can be neglected.
As already stated, the tube-side heat transfer coefficient ðhi Þ was
calculated based on the annulus side heat transfer coefficient
ðho Þ. Eq. (8) of Gnielinski [27] is used to estimate the Nusselt num-
ber of annulus fluid and then calculate the annulus fluid ho based
on the hydraulic diameter ðDh Þ and thermal conductivity of the
annulus side fluid at mean temperature. The value of ho deter-
mined from Eq. (10) is substituted in Eq. (7) for the estimation of
the tube-side heat transfer coefficient ðhi Þ and then the Nusselt
number ðNuÞ is calculated using Eq. (11), which involves hi , inner
tube diameter ðdÞ and thermal conductivity ðkÞ at bulk mean tem-
perature. The estimated tube-side Nusselt number is reported in
Fig. 3 along with values obtained from Eq. (19) of Dittus-Boelter
[28], namely:
Table 3
Dimensions of longitudinal strip inserts.
Longitudinal strip inserts Aspect ratio (AR) = w=h wðmÞ hðmÞ dh ðmÞ dh =di
AR = 1 0.012 0.012 0.005183 0.2727
AR = 2 0.012 0.006 0.008839 0.4652
AR = 4 0.012 0.003 0.011032 0.5806
N.T. Ravi Kumar et al. / Experimental Thermal and Fluid Science 85 (2017) 331–343 337
Fig. 3. Comparison of the experimental tubeside Nusselt number for hot water Fig. 5. Experimental Nusselt number of hot Fe3O4 nanofluid is compared with the
against the values predicted by the Dittus–Boelter relation [28]. data of Sajadi and Kezmi [30] and Xuan and Li [29].
4.2. Nusselt number of water and nanofluid flow in an inner tube with
longitudinal strip inserts
0:14 0:74
lb Dh
Nu ¼ 1:233ðGzÞ0:38 ðAR þ 1Þ0:41 ð22Þ
lw Di
Fig. 4. Experimental Nusselt number of hot Fe3O4 nanofluid for different values of Hsieh and Huang [20] conducted the experiments in the lami-
particle concentration and Reynolds number. nar regime; whereas in the present study, the experiments are
for the turbulent regime. For water flowing in the inner tube, it
and
Sajadi and Kazemi [30] for TiO2 nanofluid:
15; 000 < Re < 30000; 0 < / < 0:06%; 2:84 < Pr < 3:155;
Fig. 7c. Experimental Nusselt number of 0.06% nanofluid flowing through an inner
0 < AR < 4 tube with and without longitudinal strip inserts.
The values determined using Eq. (24) is shown in Fig. 9 along The observed deviation between the experimental friction fac-
with the experimental values. The above equation also predicts tor data and the values determined using Eq. (25) of Blasius [31]
the Nusselt number for water by making the volume particle con- and Eq. (26) of Petukov [32] is ±2.5%. Fig. 11 reports on friction fac-
centration equal to zero (/ = 0). tor values determined using Eq. (14) for different volume concen-
trations of the Fe3O4 nanofluid. The friction factor of the Fe3O4
4.3. Friction factor for water and nanofluids nanofluid increases with increasing values of particle volume con-
centration and Reynolds number. The viscosity of the nanofluid
The experimental friction factor for water and nanofluid flowing and the mass flow rate are the main contributors to the friction fac-
in the heat exchanger inner tube is calculated based on the pres- tor level. For a particle concentration of 0.005%, with Reynolds
sure difference measured by the U-tube manometer between the number values of 16,545 and 28,954 the friction factor increases
entrance and exit of the inner tube. As already stated, the pressure by 1.018-times and 1.01-times, respectively, compared to water
drop across the bend region is neglected. The experimental friction data. Similarly, for a particle concentration of 0.06%, with the same
factor data using Eq. (14) is reported in Fig. 10 along with the fric- Reynolds number values the friction factor increases by 1.079-
tion factors values obtained with Blasius [31], Eq. (25), and Petu- times and 1.092-times, respectively, also compared to water data.
khov [32], Eq. (26), equations for single phase fluid, namely: The benefit associated with the sizeable heat transfer enhance-
ment makes the friction factor penalty practically negligible.
f ¼ 4 0:0791Re0:25 ð25Þ
3000 < Re < 105 4.4. Friction factor of water and nanofluids in tube flow with
longitudinal strip inserts
2
f ¼ ð0:790 ln Re 1:64Þ ð26Þ
Further experiments were conducted for water and Fe3O4 nano-
fluid flowing in the inner tube of the double pipe heat exchanger
3000 < Re < 5 106
with longitudinal strip inserts. The experimental procedure was
performed for strips with aspect ratios of 1, 2, and 4, respectively.
Eq. (14) is used to estimate the experimental friction factor of
water flowing in the inner tube with longitudinal strip inserts
and the data is presented in Fig. 12 along with the data of Hsieh
and Huang [20] for the purpose of validation. The correlation pro-
posed by Hsieh and Huang [20] for single phase fluid flow in a tube
with longitudinal strip inserts is given as:
1:18
Dh
f ¼ 49:96ðReÞ0:44 ðARÞ1:53 ð27Þ
Di
Hsieh and Huang [20] conducted their experiments for the lam-
inar regime; whereas in the present study, the friction factor is
determined for the turbulent regime. In Fig. 12 can be noticed that
the friction factor increase for water flow in the presence of the
insert with AR = 1 is 1.079-times when compared to water flow
without inserts for a Reynolds number of 28,970.
The experimental friction factor data for the nanofluid with dif-
ferent concentrations (0.01%, 0.03% and 0.06%) flowing with inserts
having AR equal to 1, 2 and 4 are reported in Figs. 13a, 13b and 13c,
Fig. 9. Experimental and correlated Nusselt number values.
Fig. 10. Experimental friction factor of tubeside hot water is compared with the Fig. 11. Experimental friction factor of different volume concentrations of hot
values of Blasius [31] and Petukov [32]. nanofluid flow in an inner tube of double pipe heat exchanger.
340 N.T. Ravi Kumar et al. / Experimental Thermal and Fluid Science 85 (2017) 331–343
Fig. 13c. Experimental friction factor of 0.06% nanofluid flow in an inner tube and
Fig. 12. Experimental friction factor of water flow in the inner tube of the double
with longitudinal strip inserts.
pipe heat exchanger with longitudinal strip inserts along with Hsieh and Huang
[20] data.
respectively. For the three insert aspect ratios tested (AR = 1, 2 and
4), AR = 1 has the highest increase in friction factor because this
insert yields the largest reduction in flow area. Fig. 13a indicates
that the friction factor with a Reynolds number of 28,970 for the
0.01% nanofluid and AR = 1 increases by 1.129-times in comparison
with the same nanofluid without inserts; when compared to water
without inserts and the same Reynolds number, the friction factor
increase is 1.159-times. Similarly, from Fig. 13b it can be noticed
that the friction factor with a Reynolds number of 28,970 for the
0.03% nanofluid and AR = 1 increases by 1.137-times in comparison
with the same nanofluid without inserts; when compared to water
without inserts and the same Reynolds number, the friction factor
increase is 1.214-times. The trend noted in the previous figures is
also noted in Fig. 13c, where the friction factor with a Reynolds
number of 28,970 for the 0.06% nanofluid and AR = 1 increases by
1.16-times in comparison with the same nanofluid without inserts;
when compared to water without inserts and the same Reynolds
number, the friction factor increase is 1.267-times. Sundar and
Sharma [22], developed friction factor correlation for Al2O3
nanofluids flow in a tube with longitudinal strip inserts and the
Fig. 13a. Experimental friction factor of 0.01% nanofluid flow in an inner tube and expression is given below:
with longitudinal strip inserts.
0:6420
Dh
f ¼ 1:184ðReÞ0:3840 ð0:001 þ ARÞ0:001 ð0:001 þ /Þ0:004593
Di
ð28Þ
Fig. 14 represents comparison between present experimental
friction factor of 0.06% volume concentration of Fe3O4 nanofluid
with the data of Sundar and Sharma [22] for Al2O3 nanofluids.
From the figure it is observed that the friction factor of present
study predicting more compared to Al2O3 nanofluids, but this
enhancement is very small.
The friction factor correlation is proposed in the similar lines of
Eq. (28) based on the present experimental data of Fe3O4 nanofluid
and is formulated by Eq. (29), which has an average deviation of
1.717% and standard deviation of 2.173%.
0:081
f Reg ¼ 0:2902Re0:2409 ð1 þ /Þ1:95 ð1 þ ARÞ0:0039 ðdh =di Þ ð29Þ
3000 < Re < 30; 000; 0 < / < 0:03%; 0 < AR < 12
Eq. (29) also predicts the friction factor for water by making the
volume particle concentration equal to zero (/ = 0). The values
Fig. 13b. Experimental Nusselt number of 0.03% nanofluid flow in an inner tube obtained by using Eq. (29) are presented in Fig. 15 along with
and with longitudinal strip inserts. the experimental values.
N.T. Ravi Kumar et al. / Experimental Thermal and Fluid Science 85 (2017) 331–343 341
Fig. 14. Friction factor comparison between the 0.06% nanofluid experimental Fig. 16a. Number of transfer units of 0.03% nanofluid flowing in the inner tube with
values of the present study and the values of Sundar and Sharma [22]. and without longitudinal strip inserts.
Fig. 17a. Effectiveness of 0.03% nanofluid flowing in the inner tube with and
Fig. 15. Correlated and experimental friction factor values. without longitudinal strip inserts.
342 N.T. Ravi Kumar et al. / Experimental Thermal and Fluid Science 85 (2017) 331–343
Appendix A
Fig. 17b. Effectiveness of 0.06% nanofluid flowing in the inner tube with and
DQ h
without longitudinal strip inserts. _ h C h ðDTÞh )
Qh ¼ m
Qh
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
2 2 2
Dm _h DC h DT
¼ þ þ ðA1Þ
m _h Ch T h
AR = 1 and Reynolds number values of 16,514 and 28,901, effec-
tiveness takes the values of 0.307 and 0.340, respectively, with (b) Rate of heat flow (annulus-side) (Qc)
the 0.03% nanofluid; similarly, with AR = 1 and Reynolds number
values of 16,478 and 28,970, effectiveness takes the values of DQ c
0.306 and 0.348, respectively, with the 0.06% nanofluid. The effec- _ c C c ðDTÞc )
Qc ¼ m
Qc
tiveness values, using longitudinal strip inserts, also increase with sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
2 2 2ffi
increasing values of Reynolds number. Dm _c DC c DT
¼ þ þ ðA2Þ
The NTU and e parameters are enhanced by the addition of the mc_ Cc T c
nanoparticles in the base fluid (water), because the overall heat
transfer coefficient is also enhanced. It should be mentioned that (c) Nusselt number (Nu)
the heat exchanger performance enhancement is also accompanied sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
2 2
by a penalty associated with pumping power. However, when this hd DNu Dh Dk
penalty is compared to the heat transfer enhancement is practi- Nu ¼ ) ¼ þ ðA3Þ
k Nu h k
cally negligible; a similar finding is reported by El-Maghlany [4]
using the Cu-water nanofluid flowing in the inner tube of a hori- (d) Friction factor (f)
zontal double tube heat exchanger. sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
2 2 2
DP Df Dp Dq 2Dv
f ¼ 2 ) ¼ þ þ ðA4Þ
5. Conclusions Li
2qv f p q v
Di
Table 4
Range and accuracy of the measuring instruments.