1) Renumber Beam in X and Z Renumbering done as per VC.

Not
direction. done properly
2) Make a word file with lift load Calculations of Lift Load, Staircase
consideration details, staircase load
Load and Time Period are written
calculation and Time period below the compliance table. Same
calculation. Also apply the same Value of load applied in the Staad
value of load in Staad model Model.
No calculation provided for steps
load, slab load. Only values are
written.
3) Apply same parapet load value in We have considered full height wall
balcony portion. in balcony for future extension.

4) Check all load definition and Done


Application of load before email

5) Check Structure Checks. Done

6) Make an Excel sheet for Noted and Attached in Email.


Foundation design and Grouping A
discuss in VC
7) Make Comment Compliance in Done
Table form

8) Recheck release specification and We didn’t understand this


relocate comment. Please help in this
comment. Indicate in Comment do
the same.

9) Apply Master slave command as During previous EQ session, Master


discuss. Slave was not taught. Please explain
it. Take help from Group B.

10) Update EQ seismic definition As per the calculation of Time


Period in X & Z direction, Reduction
factor and Soil type EQ definition is
updated.

11) change soil parameter medium As we have considered Medium


soil Instead of hard soil Type of soil, Factor is changed to
“2”

12) Check and update lift load Height of 2.5m extended above
application terrace level for lift room and Water
tank and load applied on each
column using point load for Lift load
and as floor load for water tank
loading. No need to extend 2.5m
on water tank area.
13) Check and update reduction Response Reduction factor is 5 as
factor as per IS:1893 we have considered RC building
frame with special moment
resisting frame (SMRF)

Figure-1 : Rock and soil site factor and type of structure.


Source-
https://docs.bentley.com/LiveContent/web/STAAD.Pro%20P
hysical%20Modeler-v12/en/stx_Seismic_Definition.html
Figure-2 : Response Reduction Factor (IS 1893 part 1- 2016)
CALCULATIONS:
1) Lift load – (Reference File attached in Email)
Capacity – 750 Kg
Load – 750 * 9.81 = 7357.5 N
Four Column = 1839.375 = 1.84 kN on each column
2) Staircase Load –
Inclined Length – 5.2m
Width of step – 2m
Riser – 0.15m
Tread – 0.3m
No of Step – 10
DL – 1.5
LL – 3
Waist slab thickness – 0.15
Steps Load – 11.25
Waist slab load – 86.13
One flight load on beam – 13.88 kN/m
Two Flight load on beam – 27.75 kN/m
3) Time period calculation – Cl 7.6.1
Period in X direction – 0.09 * h /Sqrt (d) = 0.52
Period in Z direction – 0.09 * h /Sqrt (d) = 0.68
Response reduction factor – 5
Rock and soil site factor – 2 (Medium Soil)
Figure-3: Updated Seismic Parameters