Comments For Groupa
Comments For Groupa
Not
direction. done properly
2) Make a word file with lift load Calculations of Lift Load, Staircase
consideration details, staircase load
Load and Time Period are written
calculation and Time period below the compliance table. Same
calculation. Also apply the same Value of load applied in the Staad
value of load in Staad model Model.
No calculation provided for steps
load, slab load. Only values are
written.
3) Apply same parapet load value in We have considered full height wall
balcony portion. in balcony for future extension.
12) Check and update lift load Height of 2.5m extended above
application terrace level for lift room and Water
tank and load applied on each
column using point load for Lift load
and as floor load for water tank
loading. No need to extend 2.5m
on water tank area.
13) Check and update reduction Response Reduction factor is 5 as
factor as per IS:1893 we have considered RC building
frame with special moment
resisting frame (SMRF)