Best Practices in Technology – Case Study for Residential complex

S.no. Particulars Details


1. Site & Name of town STP,Mangalaghat,Puri
2. Name of State Odisha
3. Population 256533
2011 Census
Current Population
4. Population covered by 102613 persons approx.
STP
5. Capacity of STP 15ML/day
6. Year of Commissioning 2014
7. Time taken in 3 year.
Construction
8. Land area required 16.86 Square kilometres Approx.
9. Cost of the Project INR 80.45 crore
10. O&M arrangement WATCO ( Puja and Ureka (PSSO))
In house/Out sourced
11. O&M cost (per KL) INR 5.3 per KL
12. Recycle & Reuse of Gardening, Horticulture and Under
Treated water congratulations Site, Road sweeping.
13. Reuse of Treated Sludge Can be used as manure, removed on monthly
bases.
14. Description of Sedimentation separation followed by Anaerobic
Technology contact media, Aerobic attached growth process,
second sedimentation & disinfection.
15. Inlet Parameters (BOD, BOD: 95ppm, COD: 220ppm, TSS 180ppm
COD, TSS etc)
16. Outlet Parameters BOD: 14ppm, COD:50ppm, TSS:30PPM
(BOD, COD, TSS etc)
17. Skill requirement for Product works automatically; Common service
O&M person was given desired training to maintain the
plant.
18. Mode of collection of Existing local Sewage network
Sewage from Household
to the Treatment Facility
19. Unit Sizing- (including 11.29MX 2.4M
layout map)
20. Description on technical Design MLSS - 2500-3000ppm (attached growth
details process)
(A) Design F/M ratio TBD- F/M ratio, SRT & SOTE
B) Design MLSS
C) HRT HRT- Sedimentation Separation: 3.278hours
D) SRT Anaerobic chamber: 5.60 hours
E) Design SOTE Aeration chamber: 6 hours
Second sedimentation chamber:2.42 hours
Disinfection chamber: 0.18hours

21. Remarks