This document provides a hydraulic calculation report for the sprinkler system of the Epyllion Bonded Warehouse project in Bangladesh. It details the project specifications, including the hazard classification, design density, and number of sprinkler heads. It then lists the 20 operating sprinkler heads with their locations, sizes, flows, and pressures. Finally, it summarizes the hydraulically significant pipes in the system, including their sizes, lengths, elevations, flows, and pressure losses. The system is designed to provide adequate fire protection for the warehouse based on NFPA standards.
This document provides a hydraulic calculation report for the sprinkler system of the Epyllion Bonded Warehouse project in Bangladesh. It details the project specifications, including the hazard classification, design density, and number of sprinkler heads. It then lists the 20 operating sprinkler heads with their locations, sizes, flows, and pressures. Finally, it summarizes the hydraulically significant pipes in the system, including their sizes, lengths, elevations, flows, and pressure losses. The system is designed to provide adequate fire protection for the warehouse based on NFPA standards.
This document provides a hydraulic calculation report for the sprinkler system of the Epyllion Bonded Warehouse project in Bangladesh. It details the project specifications, including the hazard classification, design density, and number of sprinkler heads. It then lists the 20 operating sprinkler heads with their locations, sizes, flows, and pressures. Finally, it summarizes the hydraulically significant pipes in the system, including their sizes, lengths, elevations, flows, and pressure losses. The system is designed to provide adequate fire protection for the warehouse based on NFPA standards.
Submitted by FHC user number: 2104 Project: Epyllion Bonded Warehouse
SDS Global FZE Project Ref FP-XX-2021 Al Jazirah Al Hamra Area Ref: 150mm Combined Riser-01 Ras al Khaimah Inst. Number: 1 United Arab Emirates
Tel: Fax:
Project Data and Design Parameters
Project name : Epyllion Bonded Warehouse Area reference : 150mm Combined Riser-01 Address / location : Jangalipara (Banglabazar). Bhawal. Mirzapur Project number : FP-XX-2021 Installation number(s) : 1 Drawing number(s) : Fp-101 Issue no / date : 25.03.2022 Designers reference : SDS Global Limited Project Data File : SPRINKLER HYDRAULIC CALCULATION_BONDED WAREH Hazard classification : Ordinary Hazard Group-II Design authority : National Fire Protection Association Insurance company : N/A Specified density of discharge : 8.10 mm/min (l/min/m2) Assumed maximum area of operation : 0.00 m2 Number of operating sprinkler heads : 20 Maximum area covered per head : 0.00 m2 Highest head / nozzle above source : 22.65 m Number of pipes in system : 60 from 25 to 200 mm Pressure loss equation used : Hazen-Williams Fluid : Water Pipe Data Table : STD_PIPE.PDT Maximum fluid velocity : 7.51 m/s in pipe 370 380 Volume of pipework and fittings : 6.38 m3 Elbows are welded for : 65 mm and above Comment : --- Checked by & Date :
Source duty = 2284.1 l/min @ 5.402 bar at node no 100
Canute FHC Ver: 1.8.6 Friday, March 25, 2022 - 15:08
www.canutesoft.com Page: 1/4 FHC - Hydraulic Calculation Report Submitted by user number: 2104 Project: Epyllion Bonded Warehouse SDS Global FZE Project Ref FP-XX-2021 Tel: Area Ref: 150mm Combined Riser-01 Fax: Inst. Number: 1