Current Monitoring | Current Switches: Fixed Trip Point

HX00 SERIES Reliable Installation


On/Off Status Current Switches More reliable for status than relays flexibility
across auxiliary contacts
Removable mounting bracket
provides installation flexibility

Ideal for direct- Flexibility


drive units Bracket on H900 can be installed
in three different configurations
Ideal for direct-drive units, unit
vents, fan coil units, exhaust fans,
H800 and other fixed loads
H900

Low setpoint Quick installation


Minimum trip point as low as Split-core H300, H600 and H900
H300 0.15 A (H600)…avoids the need for for fast retrofit installation
multiple wraps of the conductor
through the sensor even on loads
as small as 1/5 HP
Maximize Reliability H600
Minimize Installed Cost

Hawkeye x00 on/off current switches provide a cost-effective solution APPLICATIONS


for monitoring status on unit vents, exhaust fans, recirculation pumps,
•  Electrical load status •  VFD output On/Off status
and other fixed loads where belt loss is not a concern.
•  Direct-drive units, exhaust •  Direct-Drive units, unit vents,
Veris has applied new technology to the H300, H600, and H800 models
fans, process motors, and other fan coil units, exhaust fans, and
to achieve impressive improvement in turn-on levels. The Hawkeye
fixed loads other fixed loads
H300 and H600 have the lowest turn-on current in the industry at a
mere 0.15 A! •  Lighting run times and status

SPECIFICATIONS

Sensor Power N.O models: Induced from monitored current; Terminal Block Wire Size
H800NC: 5 to 30 Vdc, permanently connected H600, H800, H900 24 to 14 AWG (0.2 to 2.1 mm2);
Insulation Class 600 Vac RMS (UL), 300 Vac RMS (CE) H300 22 to 16 AWG (0.3 to 1.3 mm2)

Frequency Range 50/60 Hz, On/Off status for Variable Frequency Drive Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m);
(VFD) outputs at 12 to 115 Hz (a) H600, H800, H900 7 in-lbs (0.8 N-m)
H300
Temperature Range:
H800NC, H300, H900 -15 to 60 °C (5 to 140 °F) WARRANTY
Limited Warranty 5 years
H600 -15 to 40 °C (5 to 104 °F) (to 200 A);
AGENCY APPROVALS
H800, H800HV -15 to 60 °C (5 to 140 °F) (to 150 A) Agency approvals UL 508 open device listing; CE: EN61010-1, CAT III,
-40 to 50 °C (-40 to 122 °F) (to 200 A); Pollution Degree 2, basic insulation
-40 to 75 °C (-40 to 167 °F) (to 100 A, and 0.25 A
status output)
Humidity Range 10 to 90% RH non-condensing
E150462
Off State Leakage 34 μA @ 5 Vdc, 200 μA @ 30 Vdc
(H800NC Only) Note: Do not use the LED status indicators as evidence of applied voltage.
On State Voltage Drop 1.9 Vdc (max.) @ 0.1 A (a) VFD systems generate fields that can disrupt electrical devices. Ensure that these
(H800NC Only) fields are minimized and are not affecting the sensor.

800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | veris.com HQ0001753.H 0521


Current Monitoring | Hx00 Series

H300 H600 UNIT VENT HEATER CONTROL


Dimensional Drawing Dimensional Drawing Wiring Diagram

Self-gripping Iris Removable Mounting Bracket


Removable Mounting Bracket BUILDING AUTOMATION
CONTROLLER
POWER
0.6" SOURCE
0.3” Digital
(16 mm) 1.2" Input
(8 mm)
1.6” 2.1" 0.7" (31 mm)
6 AWG max. (18 mm)
(40 mm) (54 mm) 2.5" * Digital
0.5" (64 mm) Input
(13 mm)

1.5”
(38 mm) 0.4” x 0.2”
Ø 0.18” (x2) (10 mm x 5 mm) 2.1" Self-gripping Iris
(5 mm) Slot (2x) (54 mm)

0.6” 1.0"
(15 mm) (26 mm) POWER
SOURCE

1.8” 2.9"
(46 mm) (74 mm) UNIT VENT HEATER
3.5"
(89 mm)

H800, H800HV, H800NC H900


Dimensional Drawing Dimensional Drawing

Removable/Adjustable Mounting Bracket Removable Mounting Bracket


1.0” Bracket can
0.9" (25 mm) be mounted
0 0.7" on three sides
(18 mm) (23 mm) 1.1” 0.8” for added
(26 mm) (21 mm) installation
3.1”** flexibility.
2.8" * (79 mm)
(71 mm)
Self-gripping Iris

2.8”
(70 mm)

1.7 1.4”*
Ø 0.3” (36 mm)
(43 mm) (8 mm)
0.4” x 0.2”
Slot (x2) 2.5”
1.1" * (64 mm)
(27 mm) 3.0”
(76 mm)

2.3"
(58 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
** Slide switch may extend up to 1/4” over the height dimensions shown.

ORDERING INFORMATION
1. Listed for use on 75°C
MODEL AMPERAGE RANGE STATUS OUTPUT TRIP LEAD
HOUSING UL CE insulated conductors.
@ 50/60 HZ ONLY (MAX.) POINT FREE 2. Product provides functional
H300 0.15 to 60 A N.O. 1.0 A @ 30 Vac/dc 0.15 A or less Split-core •2 • insulation only.
3. Listed for use on 90°C
H600 0.15 to 200 A N.O. 1.0 A @ 30 Vac/dc 0.15 A or less Split-core •1 • insulated conductors.
H800 0.25 to 200 A N.O. 1.0 A @ 30 Vac/dc 0.25 A or less Solid-core •1 •
H800NC 0.5 to 200 A N.C. 0.1 A @ 30 Vdc 0.5 A or less Solid-core •1 •
H800HV 0.75 to 200 A N.O. 0.5 A @ 250 Vac/dc 0.75 A or less Solid-core • 3

H900 1.5 to 200 A N.O. 1.0 A @ 30 Vac/dc 1.5 A or less Split-core • •

HQ0001753.H 0521 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | veris.com