Compact Performance: Pneumatics Manual CPV CPV Valve Terminal Type CPV... - VI
Compact Performance: Pneumatics Manual CPV CPV Valve Terminal Type CPV... - VI
Compact Performance: Pneumatics Manual CPV CPV Valve Terminal Type CPV... - VI
Pneumatics
Manual CPV
Manual
165 200
en 0005e
Contents and general instructions
Author . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M. Simons
Original . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . de
Typesetting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DUCOM
Edition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . en 0005e
Title . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Manual-EN
Designation . . . . . . . . . . . . . . . . . . . . . . . . . . P.BE-CPV-EN
Contents
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
Notes on these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IX
Index of abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XI
2. Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
3. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
4. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
C. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Intended use
– as intended
– in original condition
Please comply with national and local safety laws and regula-
tions.
Warrning
If used as an explosion-protected operating media, do not
disconnect when under tension!
Target group
Service
Information on Information on
electrics/electronics: electrics/electronics:
in this manual see leaflet supplied with
product
Information on Information on
electrics/electronics: electrics/electronics:
see manual ”CP system, see leaflet supplied with
installation and commis- product
sioning”
Information on
electrics/electronics:
see the manual ”CPV
valve terminal with direct
connection” for the
relevant field bus.
User “CP field bus node, “CPV valve terminal, “CP modules, elec-
manual programming and di- pneumatics” or “CPA tronics”
agnosis” valve terminal, pneu- Type P.BE-CPEA-...
Type P.BE-CP-FB... matics”
or P.BE-VIFB...-10... Type P.BE-CPV-...
or P.BE-CPA-...
b b b b
node used.
Danger categories
This manual contains instructions on the dangers which may
occur if the product is not used correctly. These instructions
are marked with a heading (Warning, Caution, etc.), printed
on a shaded background and accompanied by a pictogram.
Warning
... This means that there is a danger of serious injury to
human beings and damage to property if these instruc-
tions are not observed.
Caution
... This means that there is a danger of human injury and
damage to property if these instructions are not observed.
Please note
... This means that there is a danger of damage to property
if these instructions are not observed.
Pictograms
Information:
Recommendations, tips and references to other sources of
information.
Accessories:
Information on necessary or useful accessories for the Festo
product.
Text markings
Index of abbreviations
Term Meaning
5/3G valve actuator Actuator with two delockable non-return valves. With this actuator
and in conjunction with valve plate Ident. code G, the valve func-
tion “5/3-way blocked in mid-position” can be implemented on
the CPV 10/14 valve terminals.
AS-i AS-interface
AS-i connection CPV valve terminal variant with serial connections which enable
the CPV valve terminal to be connected to the AS-i bus.
Blanking plate Plate without valve function for occupying empty positions
Components Common term for sub-bases, end plates, relay plates, blanking
plates, separator plates, valve plates, vacuum generator plates
and pneumatic multipin.
Connecting the tubing Connecting the supply tubing (hoses) to the CPV valve terminal
CP Compact Performance
CP connection CPV valve terminal variant with plug and socket which enables the
CPV valve terminal to be connected to a field bus node and further
CP modules.
CP modules Common term for the various modules which can be incorporated
in a CP system
CPV valve terminal CPV valve terminal (type 10) for field bus systems or with IC, MP,
DI or AS-i connection
Term Meaning
DI connection CPV valve terminal variant with plug and socket which can be con-
nected directly to the field bus and, depending on the type, with
further CP modules.
End plate Blanking plate at the left and right-hand ends of the CPV valve
terminal with channels or connections for supplying the valves
with compressed air and for conducting the exhaust air.
IC connection (individual con- CPV valve terminal variant on which each valve solenoid coil is
nection) connected individually by means of a special CP cable.
MP connection (multipin con- CPV valve terminal variant with sub-D plug by means of which all
nection) the valve solenoid coils are connected centrally.
Pneumatic multipin Plate for central tubing on the valve terminal (connections for
supply air, exhaust air and work air)
Relay plate Plate with relay coils for controlling two electrically isolated out-
puts
Separator plate Plate for dividing the valve terminal into two pressure zones
Vacuum generator plate Plate with generator for creating vacuum (with or without reject
pulse)
Valve manifold Basic unit with valve plates, vacuum generator plates, separator
plates, blanking plates, relay plates and end plates
Chapter 1
Contents
CPV valve terminal The CPV valve terminals are available with the following
variants electrical connections:
IC connection MP connection
CP direct connection
CPV valve terminal with The CPV valve terminal with IC connection is available with
IC connection 2 to 8 valve plates (also in uneven graduation). Electrical
connection is made individually on each valve solenoid coil.
CPV valve terminal with This CPV valve terminal is available with 4, 6 or 8 valve loca-
MP connection tions. Electrical connection of the valve solenoid coils is
made centrally via the multipin connection.
CPV valve terminal with The CPV valve terminal with CP connection is available with
CP connection 4, 6 or 8 valve locations. Connection to the higher-order field
bus node is made via specially manufactured CP cables.
CPV valve terminal with The CPV valve terminals with direct connection are available
DI connection for the following field bus systems in sizes CPV10/14/18:
– CANopen
– DeviceNet
– Honeywell SDS
CPV valve terminal with This CPV valve terminal is connected to the AS-i bus by
AS-i connection means of a special AS-i cable. Depending on the variant, it is
available with 2, 4,or 8 valve locations and with one of four
different types of electrical connections:
...5/3-way valve 1 2 -
Identification code
With the identification code (I.C.), you can ascertain the fit-
tings on your CPV valve terminal. The code is printed on the
front between manual override connections 12 and 14.
Valve plates
H Two 3/2-way valves, basic position control side 14 open, 110 closed
G CPV10/14: Two 3/2-way valves, basic position closed + 5/3G valve actuator
CPV18: 5/3-way valve, mid-position blocked
I Two 2/2-way valves, basic position control side 14 open, 112 closed
Separator plates
Blanking plate
Relay plate
– CPV-..-BS-GRZ-V-...
Separator plate
With the aid of the separator plates, you can divide the CPV
valve terminals into 2 to 4 pressure zones. Two types of sep-
arator plates are available:
Relay plate
CPV valve terminals with a holding current reduction can be
fitted with relay plates. This is the case with CPV valve ter-
minals with the following connections:
– CP connection
– AS-i connection
Each relay plate has two relays for controlling two electrically
isolated outputs.
Pneumatic multipin
The pneumatic multipin serves for common connections for
supply and work tubing. The CPV valve terminal is screwed to
the pneumatic multipin and sealed together with it. The pneu-
matic multipin permits speedy separation of the CPV valve
terminal from the supply and work tubing. Two types of pneu-
matic multipin are available:
1 1
1 Mounting holes
Fig. 1/2: Variants of the pneumatic multipin
Summary of components
4
6
5
1 Electric sub-base (only CPV valve ter- 4 Blanking plate or separator plate (with
minals with MP, AS-i, DI- or CP connec- blocked compressed air channels
tion) 1 and 11 and exhaust channel (3/5) or
only blocked compressed air channels
2 Right-hand end plate (designs see Ap- 1 and 11)
pendix B “Summary of end plates”)
3 Relay plate (only CPV10/14 valve ter- 5 Valve plates fitted with single-solenoid,
minals with CP connection) double-solenoid or vacuum valves
5 1
4 2
1 manual override cover and support for 4 support for hat rail fitting for
identification labels, not in conjunction CPV10/14 or CPV18
with relay plate
5 support for wall fitting for CPV10/14 or
2 pneumatic multipin CPV18
3 valve actuators (5/3G valve (only 6 support for wall fitting for CPV10/14
CPV10/14), flow control valve or one-
way flow control valve) 7 adapter plug with current reduction for
CPV valve terminals with IC connection
Fig. 1/4: Supplements to the CPV valve terminal
1 2 3 4
5
6
7 6 7
1 Identification labels for valve location 6 Supply connections (1, 11, 12/14), ex-
haust connections (3/5, 82/84):
2 Manual override cover and support for with individual tubing on the left
identification labels and/or right-hand end plate
with central tubing on the pneumatic
3 Manual override (per pilot solenoid, multipin
locking or non-locking)
7 Work connections (2, 4), per valve
4 Removing the manual override cover
8 Pneumatic multipin
5 Clip of the non-locking manual over-
ride
Fig. 1/5: Pneumatic connecting, display and operating elements on the CPV valve ter-
minal
6 1
5
4 2
1 Identification label (per cable socket) 5 Terminal lugs on pilot solenoid coil 12
2 Adapter plug with current reduction 6 Yellow LED, Signal status displays of
pilot solenoids (per cable socket)
3 Earth connection
7 Ready-to-use cable with socket for
4 Terminal lugs on pilot solenoid coil 14 individual connection (per pilot sole-
noid), can be turned 180°.
Fig. 1/6: Electrical connecting and display elements on the CPV valve terminal
with IC connection
3
4
1 SUB-D multipin plug (9-pin for ter- 3 Yellow LED, Signal status displays of
minals with 4 valves, 25-pin for ter- the pilot solenoids
minals with 6 or 8 valves)
4 Earth connection
2 Identification label
Fig. 1/7: Electrical connecting and display elements on the CPV valve terminal
with MP connection
1
2
3
8
5
7
Fig. 1/8: Electrical connecting and display elements on the CPV valve terminal with
CP connection
1
9
2
8 3
4
7 5
1 AS-i cable cap, (only CPV..-GE-ASI-.-Z) 5 Yellow LED, Status displays of the pilot
solenoids
2 Cable socket of additional supply with
black supply cable, 6 Earth connection
(only CPV..-GE-ASI-.-Z)
7 BUS-LED 1 (green),
3 Sensor cable with plug BUS-LED 2 (red),
(only CPV..-GE-ASI-...E..A-...) (only CPV..-GE-ASI-..E..A-...)
Chapter 2
Contents
2. Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Warning
Switch off the following before undertaking installation
and/or maintenance work:
S the compressed air supply
S the power supply for the valve solenoid coils
Fitting variants
The CPV valve terminal with individual tubing can be fitted
into a system or machine in one of the following methods:
Please note
If vibrations occur which exceed the following values:
– 0.15 mm path at 10-58 Hz
– 2 g acceleration at 58-150 Hz
use the wall or floor fittings for the CPV14 or CPV18 valve
terminals.
In order to fit the CPV valve terminal onto a wall, you will re-
quire the appropriate mounting kit depending on the type of
fitting. This is summarized in the table below.
Type of fitting
Proceed as follows:
Valve terminal Type of fitting from the rear Type of fitting from the front
self-boring screw tightening torque self-boring screw tightening torque
CPV18 M5 x 10 4 Nm – –
Type of fitting from the rear Type of fitting from the front
1 1 1
2 2
2
3
2
4 2
1 1
2 Additional self-boring screw with the 2 Self-boring screws for fastening the
CPV14/18 valve terminals profiles to the CPV valve terminal
Please note
The bore dimensions for fastening the CPV valve terminal
from the rear (fig. 2/3) do not apply to the CPV10/14 valve
terminals with direct connection for Interbus-Loop (type
CPV..-GE-IL-..) or AS-i connection with inputs/outputs (type
CPV..-GE-ASI..E/..A)
3 4 3
1
2
5
CPV10/14 CPV10/14 CPV18
narrow fastening profile broad fastening profile broad fastening profile
2 3 2
1 5
4
6
7
CPV10 CPV14
1 109.5 mm 109.5 mm
2 26 mm 10 mm
3 10 mm x number of plates 14 mm x number of plates
4 52 mm +3 20 mm +3
5 120 mm1 120 mm1
Valve terminal Type of fitting from the rear Type of fitting from the front
Diameter of Threaded holes Diameter of Threaded holes
fastening holes for: fastening holes for:
For fitting the CPV valve terminal onto a hat rail, you will re-
quire the following fitting kits:
– CPV10/14 valve terminal:
Fitting kit CPV10/14-VI-BG-NRH-35-
– CPV18 valve terminal:
Fitting kit CPV18-VI-BG-NRH-35
Both fitting kits consist of 2 brackets, 2 or 4 self-boring
M4x10 screws (CPV10/14) or M5x10 (CPV18) and 2 M4x10
screws with clamping elements and springs.
Proceed as follows:
Hat rail for CPV10/14 valve Hat rail for CPV18 valve
terminal terminal
Support rail DIN 50022 - 35x7.5 Support rail DIN 50022 - 35x7.5
(width 35 mm, height 7.5 mm) (width 35 mm, height 15 mm)
S Screw the two brackets onto the end plates with the
screws provided, as shown in the diagram below. In the
case of CPV10/14 valve terminals, make sure that the
fixing bolts grip into the groove in the CPV valve terminal.
CPV18 M5x10 4 Nm
S Hang the CPV valve terminal onto the hat rail. Fasten the
CPV valve terminal on both sides with the hat-rail clamp-
ing unit to prevent it from tilting or sliding.
In order to fit the CPV valve terminal onto the floor (fitting at
the level of work connections 2 and 4), you will require the
following fastening screws:
– 4 M4x45 socket head screws (CPV10)
– 4 M4x50 socket head screws (CPV14)
– 4 M6x65 socket head screws (CPV18)
Proceed as follows:
2 3 2
1 53 mm 66 mm 87 mm
2 4 mm 5 mm 8.1 mm
3 10 mm x number of 14 mm x number of 18 mm x number of
plates plates plates
1 M4 x 45 socket
head screws or
1 1
M4 x 50 or
M6 x 65
2 End plates 2
3 Fastening bracket 2
– IC connection
– 8 valve plates,
When the valve solenoid coils are fitted, their switching status
can be read on the relevant LED on the pneumatic interface
module.
Fitting
Proceed as follows:
1 2
1 M5 screws, at
least 60 mm long
(ISO 1207/
ISO 1580 - DIN 84 1
or DIN 912)
2 Centring pins
Fig. 2/9: Fitting the CPV valve terminal onto the Siemens SIMATIC ET200X
Please note
When removing the CPV valve terminal from the pneumatic
interface module,
S carefully pull the CPV valve terminal upwards without
tilting.
When refitting the CPV valve terminal on the pneumatic
interface module,
S replace the flat seals on the following CPV valve ter-
minals if they have been operated in a dirty environ-
ment.
- Type CPV10-GE-8
- Type CPV14-GE-8
Make sure that the fastening surface can support the pneu-
matic multipin and the CPV valve terminal. Make sure that
there is sufficient space for connecting the supply cables and
tubing, and that extra space is available for fitting CPV valve
terminals with surface silencers.
M4 M5 M6
CPV10/14 CPV18
1 1
8 4 8
7 7
3 2 2
5 6 5 5 6 5
Fig. 2/11: Dimensions of wall cut-out for pneumatic multipin (without step)
CPV10/14 CPV18
1 1
aB aB
7
aA 3 3 aA
2 6 2
aJ aJ
5 4
4
8 9 8 8 9 8
1 30 mm + 9 40 mm + 9 1 60 mm + 9
2 73 mm 89 mm 2 118 mm
3 R12 R14 3 R22
4 6.3 mm 9.0 mm 4 15 mm
5 — 4.7 mm 5 —
6 — 5.55 mm 6 —
7 — R8 7 —
8 21 mm 26 mm 8 35.5 mm
9 10 mm x number of 14 mm x number of 9 18 mm x number of plates
plates plates
aJ 21.5 mm 29.5 mm aJ 44 mm
aA 18.5 mm 29.5 mm aA 44 mm
aB Diameter 6.5 mm Diameter 6.5 mm aB Diameter 6.5 mm
Fig. 2/12: Dimensions of wall cut-out for pneumatic multipin (with step)
Dimensions 1
Number of CPV10 CPV14 CPV18
valve locations
2 62 mm 80 mm 107 mm
4 82 mm 108 mm 143 mm
Proceed as follows
S Lay the 3-part or 4-part seal for sealing the supply chan-
nels into the grooves in the left or right-hand end plate.
Fig. 2/14: Fitting the CPV valve terminal onto the pneumatic
multipin
Please note
– If the pneumatic multipin is used with assembly step,
the outer valve plates cannot be fitted with valve actua-
tors.
– The 5/3G valve actuator is intended for use with a work-
ing pressure for each valve plate, i.e. it must not be used
in two-pressure operation (different pressure at connec-
tions 1 and 11).
– If other valve plates are to be fitted onto the CPV valve
terminal in two-pressure mode, the valve plate fitted
with the 5/3G valve actuator must be separated from
compressed air channels 1 and 11 by means of a divid-
ing plate.
Proceed as follows
S Place the seals supplied with the product into the grooves
of the appropriate valve actuator.
Proceed as follows
S Clip the manual override cover into the groove in the left
and right-hand end plates (see diagram).
Chapter 3
Contents
3. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Caution
Dirty or incorrectly lubricated compressed air will reduce
the service life of the valve terminal.
– Please note that with non-lubricated compressed air,
only an oil content of max. 0.2 mg/m3 is permitted
(see ISO 8573-1 class 1-2).
– Note also the supplementary instructions on preparing
the auxiliary pilot air in the section “Auxiliary pilot air“.
Warning
Switch off the following before undertaking installation
and/or maintenance work:
S the compressed air supply
S the power supply for the valve solenoid coils
Please note
S Place a suitable sealing ring under each screw connector
or silencer in order to avoid leakage.
– If elbow screw connectors or multiple distributors are
used, the airflow will be reduced slightly.
Basic information
Connecting
1. Push the tubing as far as possible over or into the tube
connection of the screw connector.
Removing
1. Loosen the locking screw or locking ring of the screw con-
nector.
Connecting 1
Removing
Please note
S CPV valve terminal with two pressure zones Connect the
supply pressures to both sides of the end plates or the
pneumatic multipin.
Caution
Operate the CPV valve terminal only with the media de-
scribed below.
– If possible, use non-lubricated auxiliary pilot air (connec-
tions 12/14). Otherwise use hydraulic oil
DIN 51524-HLP32/ISO 6743-4. The oil content in the
auxiliary pilot air must not exceed 3 drops per 1000 l of
air used. This corresponds to 6 bar supply pressure and
a medium flow of approx. 1 drop every 4 minutes.
Please note also the remarks on special oil for service
units in the Festo Pneumatics Catalogue.
– With CPV valve terminals with internally branched auxili-
ary pilot air, the above mentioned remark also applies to
the supply air (connection 1/11).
CPV valve terminals with two pressure zones and exter-
nally branched auxiliary pilot air in the right-hand end
plate:
– Due to the internally branched auxiliary pilot air, the
pressure in the right-hand pressure zone must be
3 - 8 bar.
Please note
Using the CPV valve terminal with internal auxiliary pilot air
S Seal connection 12/14 with a blind plug.
Please note
S Use regulated auxiliary pilot air (3 to 8 bar). Reliable
faultless operation of the CPV valve terminal is then
possible.
S Please note that the regulated auxiliary pilot air need
only be supplied or branched at one position on all
CPV valve terminals if common tubing is used. This also
applies if the CPV valve terminal is operated with differ-
ent pressure zones (see diagram).
1 Separator plate 1
2 Blind plug
3 Pressure zone 2 2
4 Pressure zone 1
4 3
Please note
S Seal all connections not required for the functioning of
the CPV valve terminal with blind plugs
(see Appendix B.2).
S In the case of valves which are not used, seal connec-
tions 2 and 4 with blind plugs.
S If you are using valve plates with Ident. code C (two
2/3-way valves in basic position blocked) with
CPV10/14 valve terminals and you wish to implement
the function “Closed in neutral position”, you will re-
quire the 5/3G valve actuator. This will be fitted onto the
above mentioned valve plate (see chapter 2.3 “Fitting
the valve actuator ”).
S Depending on the tool used, connect the work lines as
follows:
– Screw connector with hexagon socket head: any se-
quence is possible.
– Screw connector with external hexagon socket head:
connection must be made from left to right (space for
wrench).
1
1
3/5
12/14 82/84
11 3/5
82/84
2 11 2 11 12/14
Please note
With several systems with central ducted exhaust air:
use non-return valves in the common exhaust lines in
order to prevent functional impairment due to back pres-
sures.
2 Common 3/5
3 Common 82/84
4 CPV valve ter-
minal 2
5 Central 3/5
6 Central 82/84
2 6 5 3
Fig. 3/4: Common lines with non-return valves
Please note
The exhaust is passed through channels 3/5 and 82/84.
These connections must not be sealed with blind plugs.
Exhaust channels 3 and 5 are grouped together in the CPV
valve terminal. Separate exhaust restriction of channels 3
or 5 is not therefore possible.
Restriction of exhaust 3/5 on the vacuum generator plates
(Ident. codes A and E) is not permitted.
Please note
With CPV valve terminals with ducted supply air:
seal connections 11 and 12/14 with blind plugs
Please note
With CPV valve terminals with two pressure zones and ex-
ternally branched auxiliary pilot air in the right-hand end
plate:
Due to the internally branched auxiliary pilot air, the pres-
sure in the right-hand pressure zone must be 3 - 8 bar.
Vacuum/low-pressure operation
The CPV valve terminal can be operated with vacuum or low
pressure (<3 bar), if regulated auxiliary pilot air is applied
separately. A summary of the end plates required can be
found in Appendix B.2.
Please note
A high back pressure in exhaust channel 3/5 will impair
the functioning of the vacuum generator.
S Make sure that there is optimal exhausting
If the CPV valve terminal is fitted with valve plates and vac-
uum generator plates, the exhaust air from the valve plates
(in channel 3/5) can influence the vacuum generation.
S In this case, separate exhaust channel 3/5 between the
vacuum generator plates and the valve plates by means
of the separator plate with Ident. code S.
Warning
Use only power units which guarantee reliable isolation of
the operating voltages as per IEC 742/EN 60742/VDE 0551
with at least 4 kV isolation resistance (Protected Extra Low
Voltage PELV). Switch power packs are permitted, provid-
ing they guarantee reliable isolation in accordance with
EN 60950/VDE 0805.
Please note
Check within the framework of your EMERGENCY STOP
circuit, to ascertain the measures necessary for putting
your machine/system into a safe state in the event of an
EMERGENCY STOP (e.g. switching offthe operating voltage
for the valves and output modules, switching off the com-
pressed air).
1 Earth/ground
connection
Please note
Earth your CPV valve terminal
S Connect the earth connection on the left-hand end plate
(see fig. 2/5) with low impedance (short cable with large
cross-sectional area) to the earth potential.
S Tighten the earthing screw with max. 1 Nm.
In this way, you will avoid interference caused by electro-
magnetic influences.
Please note
S Use only ready-to-use connecting sockets KRP-1-24-...
from Festo for connecting current-consuming devices to
the relay outputs.
S Fit the second socket in the same way to the upper relay
output.
Please note
S Use only the following ready-to-use sockets from Festo
for connecting the valve solenoid coils:
– KMYZ-5-24-...-LED. There is an LED in each of the trans-
parent plugs of these connecting sockets. The LED indi-
cates the switching status of the valve solenoid coil.
– KMYZ-4-24-... This connecting socket is a low-cost alter-
native. It does not have an LED in the plug. It complies
with protection class IP40.
Chapter 4
Contents
4. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Before commissioning:
S Switch off the power supply before connecting or discon-
necting plugs (otherwise this could lead to functional
damage).
Please note
– When unscrewing the adjusting screw, make sure that
you do not unscrew it beyond the resistance, as this
would damage the cover.
– Note that the valve actuators of the flow control valves
or one-way flow control valves (Ident.code P, Q and V)
require a minimum operating pressure of 0.5 bar.
Please note
Before commissioning the CPV valve terminal, note the
specifications concerning the medium, see section 3.3.1
”Auxiliary pilot air” in the chapter ”Installation”.
Manual override
Warning
Before actuating the manual override:
S disconnect the power supply to the valve solenoid coils
of the relevant connections (IC, MP, AS-i, DI or CP con-
nections). You will thereby avoid undesired ernergizing
of the valve solenoid coils.
S Before switching on the operating voltage: make sure
that all manual override locking actuations are in their
basic positions. You will thereby avoid undefined switch-
ing states of the valves.
3
1
4
2
Warning
When pressurizing or re-pressurizing the valve terminal
under the following conditions:
– with the safety start-up valve (slow build up of pressure)
and
– when there are electric signals (e.g. after EMERGENCY
STOP)
apply the auxiliary pilot air separately (3 to 8 bar).
Please note
S Use a blunt pencil for actuating the non-locking manual
override.
S Actuate the manual override with max 30 N.
You will then avoid malfunctioning or damage to the man-
ual override.
Testing
Proceed as follows
S Make sure that all the valves are in their basic positions
before commissioning.
Actuating the manual override with automatic reset Reaction of the valve
(non-locking)
Release the plunger. The spring – moves back to the basic posi-
resets the plunger of the manual tion (not with 5/2-way double-
override to the starting position. solenoid valve, Ident.code J)
Caution
Before commissioning your machine/system:
S make sure that double-solenoid valves (Ident.code J) are
in their basic positions again. To do this actuate manual
override 12 of the relevant valve or apply current to pilot
solenoid 12.
S Bring the locking manual overide actuations into the
basic position again. The valve plates with Ident.code D,
I, C, N, H and the vacuum generator plate with
Ident.code E are each fitted with two valves. With man-
ual override 14 you control the valve on control side 14;
with manual override 12 you control the valve on control
side 112 or 110 (see switching symbols on the valve
plates in chapter 1.2 ”Description of the components”).
In this way you will avoid undefined switching states when
commissioning the machine/system.
Actuating the manual override with stop (locking) Reaction of the valve
Press the plunger of the manual – moves back to the basic posi-
override into the upper position as tion (not with 5/2-way double-
far as possible (basic position). solenoid valve, Ident.code J)
Impairment of function
After switching on the compressed air supply or when subse-
quently testing the individual valves, you can learn the follow-
ing about the operating status of the pneumatic system:
fast reaction sufficient pressure supply via S Exhaust the valve terminal at
pressure supply points the left and right-hand end
plates (3/5, 82/84)
two pressure zones Limiting the pressure zones – subsequent conversion poss-
with a separator plate ible
maximum vacuum (by vacuum – sufficient compressed air S The supply pressure must
generator) supply not break down even when
– minimum supply pressure several vacuum generators
– no back pressure in exhaust are switched on at the same
channel 3/5 time. If necessary, increase
the supply pressure.
S Silencers must not generate
a high back pressure in ex-
haust channel 3/5. If necess-
ary, fit efficient silencers or
increase the supply pressure.
S In order to prevent the valve
exhausting affecting the gen-
eration of vacuum, you must
fit a separator plate with
Ident.code S between the
valve plate and the vacuum
generator plate.
EMERGENCY STOP with pres- Guaranteeing the regulator – The regulator regulates the
sure zones function for the auxiliary pilot auxiliary pilot air of all the
air despite the complete supply valves plates on a valve ter-
being switched off. minal.
Please note
Note the assignment of the LEDs to the relevant manual
override (see also following diagram).
Note the following with the IC connection:
– LED in the front plug connector to upper manual over-
ride (14)
– LED in the rear plug connector to lower manual over-
ride (12)
Note the following with the MP, AS-i, DI and CP connec-
tions:
– Lower LED in the connector cover to upper manual over-
ride (14)
– Upper LED in the connector cover to lower manual over-
ride (12)
1
2
1
2
With valve plates the LEDs indicate the switching status of the
valve solenoid coils. The following table explains the mean-
ings.
Please note
Note the assignment of the LEDs to the relevant relay con-
nection (see also following diagram).
Note the following with the MP, AS-i, DI and CP connec-
tions:
– Lower LED in the connector cover to upper relay connec-
tion
– Upper LED in the connector cover to lower relay connec-
tion
Chapter 5
Contents
Caution
Dirt in the surface silencer can cause an increase in pres-
sure in the exhaust channel.
S Clean the silencer if it is yellow/black or a dark colour or
replace it by a new one.
In this way you can ensure that the surface silencer func-
tions correctly and that the valves operate correctly.
Proceed as follows
Warning
Switch off the following before undertaking installation
and/or maintenance work:
S the compressed air supply
S the power supply for the valve solenoid coils
A (vacuum No limits
generator plate) Please note the recommendations in chapter 3
E (vacuum No limits
generator plate) Please note the recommendations in chapter 3
F (valve plate) without limits without limits only with only every not with
intermediate 2nd. valve CPV10-GE-
plug for plate IL-..
current
reduction
G (valve plate) CPV10/14 If the pneumatic multipin is used with assembly step, the outer
valve plates cannot be fitted with the necessary 5/3G valve actuator.
CPV18 No limits
Ident.code 1) AS-i CP IC MP DI
S (separator plate) Combination depends on end plate combination 2)
Proceed as follows
S Pull the plug and the intermediate plug for the hall cur-
rent reduction carefully away from the terminal lugs. Mark
the sockets.
S Then loosen the upper tie rod and pull it out over the
component to be replaced.
S Unscrew the two lower tie rods so that the screw heads
are flush with the outer surface of the end plate (do not
remove the tie rod).
1 Components to 1
be replaced
2 Tie rod
2
3 Distance approx.
2 mm
3 3
1 2
Please note
– Please note the instructions in the brief description of
the relevant CPV valve terminal with AS-i connection or
the instructions for fitting equipment on the valve plates.
– Please note the instructions on fitting the valve terminal
with valve plates and vacuum generator plates under
“Vacuum generator plates” in chapter 3.
– If the CPV10 valve terminal is fitted with valve plates
with Ident.code F, please note the instructions on fitting
and application in Appendix B1.
– Please note the limits on fitting the CPV valve terminals
with relay plates (Ident.code R). See compatibility list in
this chapter.
Proceed as follows
S Make sure that the seals are correctly seated between the
components on the valve terminal. They must lie correctly
in the appropriate seal grooves.
1 2 3
3 The seal for valve plates with 2/2 or 3/2-way valves (Ident.code D, I or C, H, and
N as well as for all end plates is symmetrical and marked with 3/2 .
Fig. 5/3: Position and designation of the seals with pneumatic spring valves or double-
solenoid valves (only CPV10/14 valve terminals)
Please note
There is only one type of seal for all valve plates on the
CPV18 valve terminal. The position of the seal is the same
on all valve plates.
S Place the component on the front tie rod. Press the com-
ponent so that it snaps onto the tie rod.
S Push the upper tie rod as far as possible into the CPV
valve terminal and screw it in a few turns.
S Tighten first the upper, then the lower tie rod with 0.3 Nm.
Then tighten all the tie rods with 2 Nm.
Please note
The flat seals between the valve block and the sub-base
have been modified. Replace the glued flat seals, which
are more than one year old, by new flat seals.
You can then be sure that your CPV valve terminal is
sealed correctly.
The flat seals are situated on the bottom of the electric sub-
base (see diagram).
1 Flat seals
Floor mounting
S In this case, insert the fastening screws into the right-
hand end plate and tighten the valve terminal.
S use a thin object (e. g. a spatula) to lift the safety clip out
of the support, as shown in 2.
2
1
1 Remove the safety clip by pressing it 2 Removing the safety clip by lifting it
out. out (clip can be re-used)
By exchanging the end plates you can adapt the CPV valve
terminal to new requirements of your machine or system.
The following end plates are available:
Proceed as follows
S Remove the end plate from the CPV valve terminal. Make
sure that the other components remain together.
S Remove the left-hand end plate from the CPV valve ter-
minal.
S Tighten first the centre and then the outer tie rods with
2 + 0.2 Nm (CPV10/14) or 4 Nm (CPV18).
S Fit the CPV valve terminals onto the fastening surface (see
sections ”Fitting onto a wall”, ”Hat rail clamping unit” or
”Fitting on the floor” in the chapter ”Fitting”).
Please note
– Mixed operation of the CPV valve terminal with internal
and external auxiliary pilot air is not intended. The auxili-
ary pilot air channel can be divided into two pressure
zones by means of a separator plate.
– With end plates CPV..-EPR-PG (part number 161 373 and
162 543), connection 12/14 is sealed internally.
– Take into account the extra space required for end
plates with surface silencers.
Proceed as follows
Please note
S When installing the CPV valve terminal, note that the
compressed air must be supplied on both sides of the
valve terminal.
S Seal non-required connections (supply or auxiliary pilot
air connections) with blind plugs.
5.8 Converting the CPV valve terminal to a version with different electri-
cal connections
Please note
Please note the instructions in the compatibility list in this
chapter as regards combining versions with different elec-
trical connections with the following plates:
– Single-solenoid 5/2-way valve (Ident.code F)
– Relay plates (Ident.code R).
Proceed as follows
Appendix A
Contents
A.1 Accessories
Components Type
General CPV10/14 CPV18
General
Protection class as per DIN 60 529 IP 65 (with cable from FESTO accessories)
Relative humidity 90 %
Corrosion protection (as per FN940070) KBK 2 (vacuum generator plates: KBK1)
Materials
Plates, covers, pneumatic multipin: AL, AL-GD, Ms, PAXMD6, PET, POM, PPS, PA, ST
Seals: NBR, HNBR
General
General
Pneumatic multipin
– on CPV valve terminals with 2 valve locations 0,120 0,270 0,520
– on CPV valve terminals with 4 valve locations 0,165 0,390 0,750
– on CPV valve terminals with 6 valve locations 0,225 0,510 0,870
– on CPV valve terminals with 8 valve locations 0,270 0,630 1,300
Caution
Operate the CPV valve terminal only with the media de-
scribed below:
– If possible, use non-lubricated auxiliary pilot air
(connections 12/14). Otherwise use hydraulic oil
DIN 51524-HLP32/ISO 6743-4. The oil content in the
auxiliary pilot air must not exceed 3 drops per 1000 l of
air used. This corresponds to 6 bar supply pressure and
a medium flow of approx. 1 drop every 4 minutes.
Please note also the remarks on special oil for service
units in the Festo Pneumatics Catalogue.
– With CPV valve terminals with internally branched auxili-
ary pilot air, the above mentioned remark also applies to
the supply air (connection 1/11).
Pneumatics
Please note
The screw connectors of the pneumatic connections cause
a reduction in the flow rate of the valves.
Pneumatics
Vacuum generator plates - 0.85 bar (the highest possible vacuum is reached
– Vacuum (Vmax.) within the working pressure range.
Operating voltage 24 V DC
Tolerance 20,4 – 26.4 V
Please note
Data on the electrics of the CPV valve terminal with multi-
pin, AS-i or direct connection can be found in the relevant
leaflet supplied with the product.
Appendix B
Contents
The CPV valve terminals are available with the following valve
plates and vacuum generator plates:
Valve plates
82/84 Ident.code D
4 2
Method of operation Two single-solenoid
2/2-way valves closed in basic position
14 112
1 3/5 11
12/14
82/84 4 2 Ident.code I
Method of operation: two single-solenoid
2/2-way valves
14 112 closed in basic position (control side 14) or open
(control side 112)
1 3/5 11
12/14
Ident.code N
82/84 4 2 Method of operation
– Two single-solenoid 3/2-way valves open in
basic position
14 110 – 5/3-way valve, mid position pressurized This
function is implemented with the above men-
tioned 3/2-way valves in basic position open.
1 3/5 11
12/14
82/84 4 2 Ident.code H
Method of operation
– Two 3/2-way valves, on control side 14 closed
14 110 in basic position, on control side 110 open in
basic position.
1 3/5 11
12/14
Ident.code J
82/84 4 2 Method of operation Double-solenoid 5/2-way
valve
14 112
1 11
12/14 3/5
CPV10/14 Ident.code G
4 2 Method of operation 5/3-way valve blocked in
mid-position
CPV10/14
This function is implemented with two 3/2-way
82/84
valves in basic position blocked and the
5/3G valve actuator (two delockable non-return
14 112 valves).
12/14 1 3/5 11
CPV18 CPV18
82/84 4 2 5/3-way valve blocked in mid-position
14 112
1 11
12/14 3/5
14 112
1 3/5 11
12/14
82/84 4 2 Ident.code E
Method of operation Vacuum generator (control
side 14) and a 2/2-way valve closed in basic
position (control side 112) for reject pulse.
14 112
12/14 1 3/5 11
1 Part number
1
CPV..-EPL-E: axial connections, connections 1 and 11 separate 161 374 162 544 163 196
CPV..-EPL-G: axial connections, connections 1 and 11 connected 161 376 162 546 163 198
CPV..-EPL-EU: with surface silencer 188 454 188 458 192 939
CPV..-EPR-EU: with surface silencer 188 455 188 459 192 941
End plate pairs suitable for the pneumatic multipin, User manual
auxiliary pilot air branched internally (internal
auxiliary pilot air)
End plate pairs with surface silencer suitable for User manual
pneumatic multipin
Auxiliary pilot air branched internally (internal
auxiliary pilot air)
End plate pairs with surface silencer suitable for User manual
pneumatic multipin
Auxiliary pilot air branched internally (internal
auxiliary pilot air)
End plate pairs suitable for the pneumatic multipin, User manual
auxiliary pilot air branched externally (external
auxiliary pilot air)
Appendix C
A
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XI
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
Adapter plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10, 1-15
Address assignment, Outputs . . . . . . . . . . . . . . . . . . . . . . 3-17
AS-i connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Auxiliary pilot air
branched internally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
supplied externally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
B
Blanking plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
C
Common pneumatic lines . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Compatibility list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Components
5/3G valve actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Adapter plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
End plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Flow control valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
One-way flow control valve . . . . . . . . . . . . . . . . . . . . . . . 1-9
Pneumatic multipin . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Relay plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Separator plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Vacuum generator plates . . . . . . . . . . . . . . . . . . . . . 1-9, B-3
Valve plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Compressed air, Requirements . . . . . . . . . . . . . . . . . . . . . . A-7
Connecting variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Connections
Electrical display elements (CPV valve terminal with AS-i
connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18
Electrical display elements (CPV valve terminal with CP con-
nection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
D
Danger categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IX
Designation signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-24
DI connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Display elements
CPV valve terminal with AS-i connection . . . . . . . . . . . . 1-18
CPV valve terminal with CP connection . . . . . . . . . . . . . 1-17
CPV valve terminal with IC connection . . . . . . . . . . . . . 1-15
CPV valve terminal with MP connection . . . . . . . . . . . . 1-16
E
Earthing the CPV valve terminal . . . . . . . . . . . . . . . . . . . . 3-15
Emergency stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
End plate pairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7, B-8
F
Fastening accessories
Fitting onto a hat rail . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Fitting onto a wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Fitting kit
Fitting onto a hat rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Fitting onto a wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Simatic ET 200 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Fitting methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Flow control valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Flow rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
H
Hat rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Clamping unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
I
IC connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Identification labels . . . . . . . . . . . 1-14, 1-15, 1-16, 1-17, 1-18
Impairment of function . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Input current consumption . . . . . . . . . . . . . . . . . . . . . . . . A-10
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
L
LED display
Position of the LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Low-pressure operation . . . . . . . . . . . . . . . . . . . . . . 3-12, 4-12
M
Manual override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII, VIII
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Medium, Compressed air requirement . . . . . . . . . . . . . . . A-7
Micro valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Midi valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Mini valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
MP connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
N
Notes on these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . VI
O
One-way flow control valve . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Operating elements, Pneumatic . . . . . . . . . . . . . . . . . . . . 1-14
Operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Operating voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
P
Pictograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
Pneumatic multipin . . . . . . . . . . . . . . . . 2-17, 2-18, 2-21, 2-22
Pneumatic operating status . . . . . . . . . . . . . . . . . . . . . . . 4-12
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
Pressure range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
Pressure zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7, 3-12
pressure zones . . . . . . . . . . . . . . . . . . . . . . . . . 3-6, 3-12, 4-12
R
Relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17, 3-16
Load current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
Switching times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
Relay plate . . . . . . . . . . . . . . . . . . . . . . . . . XII, 1-7, 1-10, 1-12
S
Separator plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
Simatic ET200X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Size of connection of pneumatic screw connectors . . . . . 3-10
SPC 200, Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VIII
Start-up pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Summary of components . . . . . . . . . . . . . . . . . . . . 1-12, 1-13
Supply pressure
External auxiliary pilot air . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Internal auxiliary pilot air . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Surface silencer, Cleaning/replacing . . . . . . . . . . . . . . . . . 5-3
Switching status display . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
T
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
Testing the valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Text markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
Tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Tubing variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
U
User instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IX
V
Vacuum generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Vacuum generator plates . . . . . . . . . . . . . . 1-7, 1-9, 3-13, B-6
Vacuum operation . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12, 4-12
Valve actuator
5/3G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Flow control valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
One-way flow control valve . . . . . . . . . . . . . . . . . . . . . . . 1-9
Valve plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7, B-3
Valve switching times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
W
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6