Professional Documents
Culture Documents
Air Control 3 Dynamic: Manual
Air Control 3 Dynamic: Manual
Air Control 3 Dynamic: Manual
Manual
Version: 2.03
as of: 20.10.2008
__________________________________________________
Content
General Information
1 Hardware
1.1 Microprocessorlogic
1.3 Display
- galvanically isolated
- voltage 18 VDC
- 1 input 4-20mA (corresponding to 0-16 bar / apparent ohmic resistance 200 Ohm,
resolution 10 bit)
- 2 inputs for KTY temperature sensors (measurement current 1mA, resolution 10 bit)
- galvanically isolated
- voltage 12 VDC and 24 VDC
- 6 standard digital inputs 24 VDC, 10mA
- 2 inputs for PTC-temperature sensors 12 VDC (optionally usable as standard digital
inputs)
Power supply 10 VAC (5 VA) and 18 VAC (5 VA), +/- 10%, 50/60 Hz
- Connection via Phoenix connectors (type MSTBVA for relay outputs,
type Mini-Combicon for all other connections);
- Compact housing with front plate 240mm*120mm, depth 35mm
- instrument panel mounted with four threaded bolts (3mm)
Pin 36 Sig. B
Pin 37 Sig. A Option:
Pin 38 GNDx connection for
Pin 39 18 Vac MK200-modules
Pin 40 18 Vac
Please note:
Before using an interface module (RS232 or RS485) set the two dip-switches near Pin
35 (on the backside) to “off”!
2 Basic Screen
After connecting the control with the power supply the following start up screen will appear:
After about four seconds it will automatically switch over to the basic screen:
The basic screen shows current status information, line pressure date and time. At the bottom
of the screen the current setting of the soft keys (function keys) F1 to F4 is displayed. As
there are more than four functions available in the basic screen, the setting for the soft keys
can be changed using the keys and from the key pad.
Press the corresponding function key to reach the information you are looking for.
In order to see the current analogue values press the ENTER key.
The first bar graph shows the operation hours and will always fill the complete width of the
screen. All following bar graphs will use the same scaling.
The second bar graph starts off at the left side and shows the current load hours. Bar graph
number 3 shows off load hours and starts at the end of the load hours. That way the relation
between on and off load hours can easily be seen.
The last bar graph shows the stop hours. Should the number of stop hours exceed the
operation hours this graph will be cut short.
Below the bar graphs the so far produced air quantity is displayed. This value will be
calculated using load hours and the maximum delivery quantity as set in the configuration
menu.
The diagram shows the states of up to five compressors of the LLC (with one auxiliary LLC
module).
Off-Load
Ready
Fault
“Fault” and “off load” for the compressors #2-#5 can only be displayed if the corresponding
feedbacks (fault and motor running) are connected to the auxiliary module. Otherwise only
“ready” and “load” will be displayed.
If the LLC includes more than five (up to nine) compressors (two auxiliary modules) the
diagram will look as follows
Off-Load
Ready
Fault
Whereas:
1 – Maintenance interval air filter
Each bar’s length corresponds to the length of the corresponding maintenance interval. The
filling shows the amount of time left until the next maintenance.
Scaling depends on the longest maintenance interval.
If the time until the next maintenance is less than 100 hours the bar will start flashing.
To change the scaling choose the value you would like to change using the up and down keys
and . Press ENTER to switch to edit mode. The cursor will start blinking and the
softkeys F1 to F4 will get the following functionalities:
Use the up and down keys - and - in order to change the current value. Move the cursor
using the function keys F1 and F2.
F3 leaves the edit mode without keeping any changes. Use ENTER to take over the new
value.
Please note that it is not possible to change the time limits of the x-axis if the diagram is in
automatic mode (X-AUTO on) as it will always show the most recent values of the line
pressure.
After leaving the edit mode the line graph adjusts to the new scaling and the functions of the
softkeys F1 to F4 switch back to their original functionalities.
To change the scaling please choose the value you would like to change using the up and
down keys and . Press ENTER to switch to edit mode. The cursor will start blinking and
the softkeys F1 to F4 will get the following functionalities:
Use the up and down keys - and - in order to change the current value. Move the cursor
using the function keys F1 and F2.
F3 leaves the edit mode and ignores all changes. Use ENTER to take over the new value.
Please note that it is not possible to change the time limits of the x-axis if the diagram is in
automatic mode (X-AUTO on) as it will always show the most recent values of the line
pressure.
After leaving the edit mode the line graph adjusts to the new scaling and the functions of the
softkeys F1 to F4 switch back to their original functionalities.
To change the scaling choose the value you would like to change using the up and down keys
and . Press ENTER to switch to edit mode. The cursor will start blinking and the
softkeys F1 to F4 will get the following functionalities:
Use the up and down keys - and - in order to change the current value. Move the cursor
using the function keys F1 and F2.
F3 leaves the edit mode and ignores all changes. Use ENTER to take over the new value.
Please note that it is not possible to change the time limits of the x-axis if the diagram is in
automatic mode (X-AUTO on) as it will always show the most recent values of the line
pressure.
After leaving the edit mode the line graph adjusts to the new scaling and the functions of the
softkeys F1 to F4 switch back to their original functionalities.
To change the scaling choose the value you would like to change using the up and down keys
and . Press ENTER to switch to edit mode. The cursor will start blinking and the
softkeys F1 to F4 will get the following functionalities:
Use the up and down keys - and - in order to change the current value. Move the cursor
using the function keys F1 and F2.
F3 leaves the edit mode and ignores all changes. Use ENTER to take over the new value.
Please note that it is not possible to change the time limits of the x-axis if the diagram is in
automatic mode (X-AUTO on) as it will always show the most recent values of the line
pressure.
After leaving the edit mode the line graph adjusts to the new scaling and the functions of the
softkeys F1 to F4 switch back to their original functionalities.
To change the scaling choose the value you would like to change using the up and down keys
and . Press ENTER to switch to edit mode. The cursor will start blinking and the
softkeys F1 to F4 will get the following functionalities:
Use the up and down keys - and - in order to change the current value. Move the cursor
using the function keys F1 and F2.
F3 leaves the edit mode and ignores all changes. Use ENTER to take over the new value.
Please note that it is not possible to change the time limits of the x-axis if the diagram is in
automatic mode (X-AUTO on) as it will always show the most recent values of the line
pressure.
After leaving the edit mode the line graph adjusts to the new scaling and the functions of the
softkeys F1 to F4 switch back to their original functionalities.
This diagram shows the total daily delivery quantity for a time span of one week.
To change the scaling choose the value you would like to change using the up and down keys
and . Press ENTER to switch to edit mode. The cursor will start blinking and the
softkeys F1 to F4 will get the following functionalities:
Use the up and down keys - and - in order to change the current value. Move the cursor
using the function keys F1 and F2.
F3 leaves the edit mode and ignores all changes. Use ENTER to take over the new value.
Please note that it is not possible to change the time limits of the x-axis if the diagram is in
automatic mode (X-AUTO on) as it will always show the most recent values of the line
pressure.
After leaving the edit mode the line graph adjusts to the new scaling.
3 Menu System
In order to reach the menu system, press the INFO button.
The code screen will appear:
Use the up and down keys to change the current digit (wherever thecursor is blinking). Move
the curser to left and right using the soft keys F1 and F2. Enter sets the code and switches to
the main menu or starts the action corresponding to the code (see Annex for a list of possible
codes).
Depending on the code level the parameters in the menus can be either “read only” or
changeable.
The main menu will be displayed:
The keys up and down ( , ) change the digit with the blinking cursor below. In order to
move the cursor, use F1 and F2.
F3 leaves the edit mode without storing the new values. The ENTER key stores the new value
and leaves the edit mode.If the new value is not within the allowed range the parameter is set
to its closest limit.
This menu contains general operation parameters. Use the down key to scroll and reach the
parameters not visible on the page.
This menu contains the maintenance intervals as well as the operation hours.
There are seven timer channels available (C1-C7). These channels are connected with a
logical OR; the compressor will run if at least one of the channels is active and valid.
In the figure above the compressor would be running from Monday to Thursday (6 am-8pm)
and Fridays from 6am to 4 pm. It would be off on weekends.
In order to let the compressor run continuously for one or several days the corresponding days
must be activated and the times must be set to 00:00.
This menu contains the running times of the lead lag control.
There are seven timer channels available (C1-C7). These channels are connected with a
logical OR; the LLC will be active if at least one of the channels is active and valid.
In order to keep the LLC active continuously for one or several days the corresponding days
must be activated and the times must be set to 00:00.
This menu contains the switching times for several sets of priorities for the LLC. Relevant for
LLC master only!
There are seven timer channels available (C1-C7). For each one the switch on and switch off
times as well as the priorities of all compressors can be set.
The search for an active channel starts with channel #1 and stops as soon as one is found. The
corresponding priorities will then replace the current priorities of the LLC. If no active
channel can be found the default values as set in the LLC menu are used.
This screen displays the 20 most current messages (maintenance. warnings and faults)
together with date and time of their occurrence.
Each new message is stored on top of the existing list. So the most recent message is always
at the top.
Each entry starts with position number of the message (01 – 20); follows either the warning
(maintenance/ warning) or the fault symbol. If this icon is flashing the message is still
pending. Next is date and time of the occurance of the message and the message text.
Up to ten entries can be displayed at once. In order to view more use the up and down keys to
scroll the page.
F3 deletes all entries if at least the service code has been entered.
F4 leads back to the main menu.
The parameters in this menu all concern the appearance on the display.
This menu contains all parameters necessary for the diagrams that can be reached from the
basic screen.
This menu contains all freely definable texts for hotline and type plate.
This menu contains the default priorities of all compressors. These are valid only if no timer
channel is active.
This menu contains the current states of the digital inputs and outputs.
With a codelevel service or higher the outputs can also be switched on and off. Choose the
output with F1 and F2 (only possible when all ouputs are “off”). Only one single output can
be active at any time.
4 Program operation
4.1 Operation states
a) compressor is off:
- green LED off
- the icons motor and inlet valve are off (not visisble in the basic screen)
d) compressor on, inlet valve closed, the compressor is not working (start up phase or off-
load)
- green LED on
- icon "motor" visible in the basic screen
- icon “inlet valve” not visible in the basic screen
- if the compressor is operating either in “automatic” or in “automatic + discharge” mode
and the run on time is active the latter will be displayed in the basic screen.
Enter CODE 0088 => All changeable parameters are reset to their default values. Please
note: this also resets all changes that had been made before!
5 Messages
5.1 Faults
The fault icon is blinking and the corresponding error message is displayed together with the
text as set in “hotline” (see section 3.6.2). If more there are several messages pending. the
corresponding texts change every 3 seconds.
Fault Description / Solution
Fault: Parameter wrong At least one parameter is outside its valid range.
Fault: EEPROM?
Fault: Power low Power below the allowed minimum. (this message only
appears if monitoring activated – see section 3.7)
Fault: Power fail Power failure (only if automatic restart active!)
Fault: Adjustment wrong Analogue adjustment parameters are wrong. The control needs
to be sent back to the factory.
Fault: Emergency stop Digital input “emergency stop” open.
Fault: Rotation direction Digital input “rotation direction” open.
Fault: Motor temperature PTC input: motor temperature high
Fault: Oil level Input oil level monitoring open.
Fault: Water cooling Input water cooling open while the compressor is running.
Fault: Oil pump Input oil pump monitoring open.
Fault: Fan Input fan monitoring open.
Fault: Inverter Input inverter monitoring open (only if inverter active).
Fault: Line pressure high Line pressure exceeds the upper limit.
Fault: Oil pressure Input oil pressure monitoring open while compressor is
running and after the start up time of the oil pump.
Fault: Oil pressure 2 Current oil pressure 2 below the limit as set in the menu while
the compressor is running.
Fault: Oil pressure 3 Current oil pressure 3 below the limit as set in the menu while
the compressor is running.
Fault: Engine start No “engine speed ok” feedback from the inverter within the
start-up time.
Fault: Vibration Current vibration exceeds the allowed limit after start up..
nd
Fault: Temp. b. 2 stage Temperature before2nd stage exceeds the allowed limit.
Fault: Temp. a. aftercooler Temperature after after cooler exceeds the allowed limit.
Fault: System pressure System pressure exceeds the allowed limit.
Fault: Oil temperature Oiltemperature exceeds the allowed limit.
Fault: Engine current sensor Sensor monitoring of the motor current sensor reports fault.
Fault: Oil temperature sensor Sensor monitoring for oil temperature sensor reports fault.
Fault: Line pressure sensor Sensor monitoring for line pressure sensor reports fault.
If a fault message is pending the compressor is immediately shut down. The red LED is on
until the cause of the fault has been removed and the message has been acknowledged with
the O-key.
The warning icon is blinking and the corresponding message is displayed together with the
text set in “hotline” (see section 3.6.2). If more there are several messages pending. the
corresponding texts change every 3 seconds.
Maintenance: Air filter Time until the next maintenance of the air filter is less than
100 h
Maintenance: Oil filter Time until the next maintenance of the oil filter is less than
100 h
Maintenance: Separator Time until the next maintenance of the separator is less than
100 h
Maintenance: Motor Time until the next maintenance of the motor is less than
100 h
Maintenance: Compressor Time until the next maintenance of the compressor is less than
100 h
If a warning or maintenance message is pending the compressor is not shut down but
continues to operate. The red LED starts blinking until the cause of the warning is fixed or the
corresponding maintenance interval has been reset.
If the control registers an error in the program store (in the flash EPROM. right after power
on) the display shows the following text:
“Download V...“
6 Annex
6.1 Codes
Code Function
0001 Customer code (parameters with a C in the third column)
5317 Service code (parameters with C or S in the third column)
1923 Factory/ Works code (parameters with C, S or W in the third
column)
9900 Reset operation hours and time until next maintenance.
0088 Reset all parameters. maintenance intervals and time until
next maintenance to their default values.