CLIENT: CELEC EP - TRANSELECTRIC

Equipment type FP40R30 100 48V SERIAL NUMBER : L15 - 1080

SUBJECT CHECK Emerson Network Comments


Power IS
RECCORD ROOM TEMPERATURE C° 22°
CHARGER ACCESSIBLE FOR SERVICE √
LOCATION VENTILATION ADEQUATE √
BATTERY ACCESSIBLE √
NO TRANSIT DAMAGE √
ALL PACKING REMOVED √
CHARGER SUB-ASSEMBLIES SECURE √
INTERNAL
CUBICLE INTERCONNECTIONS CORRECT √
CHECKS
ALL CONNECTIONS TIGHT √
PLUGS AND SOCKETS SECURE √
CIRCUIT CARD CONFIGURATION √
CONNECTED AS WIRING DIAGRAM √
ALL CONNECTIONS TIGHT √
CABLE SIZES CORRECT √
EXTERNAL CIRCUIT BREAKERS (fuses ) ADEQUATELY RATED √
CABLES RESERVE NEUTRAL EARTHED OR UNSWITCHED √
CUBICLE(S) EARTHED √
REMOTE CONTROL AND MIMIC PANEL/ AS 400 √
RECCORD BATTERYROOM TEMPERATURE C° 22°
BATTERY ENCLOSED FOR SAFETY √
ASSEMBLED CORRECTELY √
END TERMINALS SEPARATED OR INSULATED √
BATTERY PACKING AND VENT PLUGS REMOVED √
LINKS TIGHT AND PROTECTED √
CELLS CLEAN AND DRY √
BATTERY ENCLOSURE / STANDS EARTHED √
POLARITIES CORRECT √
INTERIOR CLEAN √
GENERAL POWER COMPONENTS SERVICEABLE √
ALL FANS RUNNING √

Comments : Rectificador y Bancos de Baterías en el mismo recinto.

COMPANY INSPECTION EMERSON / PROTECOMPU INSPECTION CUSTOMER


NETWORK POWER IS
NAME Rodrigo Torres B. Alvaro Cevallos
DATE 07/junio/2016 07/junio/2016

SIGNATURE

Checked
Date : Origin : Approval by :
by :
PCT 2.0
Page 1/1
Reference :
CHARGER COMMISSIONING
INS-E 09 EN Ind. 7
PRELIMINARY & VISUAL CHECK
Revision Date : 01/08/2014
Model Reference : IMP00-006