Professional Documents
Culture Documents
GENERATOR Protections: Prepared By: Farooq Hussain Je-Prd (Uty)
GENERATOR Protections: Prepared By: Farooq Hussain Je-Prd (Uty)
GENERATOR Protections: Prepared By: Farooq Hussain Je-Prd (Uty)
PREPARED BY:
FAROOQ HUSSAIN
JE-PRD (UTY)
INTRODUCTION TO PROTECTION SYSTEM
The purpose of an electrical system is to supply energy economically and reliably. The greatest
threat to the security of a system is short circuit which imposes sudden violent changes to the
system. The large current flow accompanied by release of heat can cause fire and hence great
damage. There are many other abnormal conditions like Overloads, Under-Voltage, Over-
Voltage, Open phase, Unbalanced Phase currents, Reversal of Power, Under Frequency & Over
Frequency, Power Swings against which Protection is needed.
The objectives of electrical protection system and co-ordination are to prevent injury to
personnel, to minimize damage to the system components and to limit the extent of service
interruption.
Generator is the most important part of an electrical power system. The failure of the
generators directly link to the production loss. Generator protection requires some special
consideration of many abnormal conditions that are not present with any other system
elements.
Relays are extensively used in protection systems but fuses and direct acting ac tripping
systems are also used.
The relays detect the fault and supply information to circuit breaker which performs the
function of circuit interruption.
PROTECTIVE RELAY
A Protective relay is a device which detects a fault and initiates the operation of circuit breaker
to isolate the defective element from rest of the system.
Main Components:
Power source
A Trip Coil
F F
AC type relays are actuated by current & Voltage supplied by Current and Potential (or
Voltage) Transformers.
They supply protective relays with current & voltage of magnitude proportional (but
reduced) to those of the power circuit.
They provide insulation against high voltage & protect apparatus & operating personnel
from contact with high Voltage
Protective Relays
Mostly operate by virtue of the current and / or voltage supplied by the PTs & CTs
connected in various combinations to the system element that is to be protected.
Through the individual or relative change in these two quantities, faults signal their
presence, type and location to protective relays.
Having detected the fault the relays operate trip circuit which results in opening of the
circuit breaker and hence disconnection of the faulty circuit.
GENERATOR FAULTS
Stator Winding Faults
These may be earth faults or inter turn faults due to thermal stresses
Field system is normally not grounded therefore single fault does not cause any harm
The second fault will cause short circuit and unsymmetrical field.
Thus a single fault can be tolerated but it should not be allowed to continue
Reduced excitation may occur due to short circuit or open circuit or fault in AVR
– Failure of field
– Unbalanced loading
– Over-loading
– Over-voltage
– Over-speed
– Ventilation failure
V = Voltage applied
I = Current
R = Resistance
Such protections should be provided to stop the generator to continuing to supply short circuit
current to a fault in the adjacent system because the fault may not have been removed by other
protective equipment. Ideally the fault should be isolated by the nearest breaker but if it fails to
do so then this is a backup relay that will protect the generator from damage. Conductor is
designed to pass a limited amount of current excessive flow of current will causes heating up of
conductor. An overcurrent protection device protects the circuit by opening the device when
the current reaches a value that will cause an excessive or dangerous temperature rise in
conductors.
H = I2 R t
H = Heat Generated
I = Current
R = Resistance
t = Time
P = √3 VI cosф
P = Power
V = Voltage
I = Current
Cosф = Power factor
DIFFERENTIAL (87)
Differential relay is used to detect internal generator phase to phase fault. A differential relay
operates by summing the current flowing into and out of a circuit zone. Normally the current
flowing into a circuit zone equals the current flowing out, in which no differential current flows
in the relay. If a fault occurs in the circuit zone part of the current flowing in will be deflected
into the fault and the current flowing out will be less than the current flowing in. Thus there is a
differential current that will flow into the relay.
GENERATOR
I1 I2
i1 Current i2
i1-i2
relay
In a differential protection scheme in the above figure, currents on both sides of the equipment
are compared. The figure shows the connection only for one phase, but a similar connection is
usually used in each phase of the protected equipment. Under normal conditions, or for a fault
outside of the protected zone, current I1 is equal to current I2 . Therefore the currents in the
current transformers secondaries are also equal, i.e. i1 = i2 and no current flows through the
current relay.
If a fault develops inside of the protected zone, currents I1 and I2 are no longer equal, therefore
i1 and i2 are not equal and there is a current flowing through the current relay.
GROUND DIFFERENTIAL (87-G)
Ground differential relay is used to detect internal generator phase ground fault.
GENERATOR
I2
I1
Current i2
i1-i2
relay
i1
In a ground differential protection scheme in the above figure, currents on both sides of the
equipment are compared. The figure shows the connection only for one phase, but a similar
connection is usually used in each phase of the protected equipment. Under normal conditions,
or for a fault outside of the protected zone, current I1 is equal to current I2 . Therefore the
currents in the current transformers secondaries are also equal, i.e. i1 = i2 and no current flows
through the current relay.
If a fault develops inside of the protected zone, currents I1 and I2 are no longer equal, therefore
i1 and i2 are not equal and there is a current flowing through the current relay.
An under voltage relay removes a generator from service when a low-voltage condition
develops, so that the generator will not induce excessive current to compensate for the
decreased voltage. When a generator is connected to a grid with other generators in service, it
can cause flow of current towards the generator as well.
OVER VOLTAGE (59)
During start-up, there is a definite rate of voltage rise with frequency. Similarly during
shutdown the voltage decrease as the frequency decreases. If the generator suddenly gets off-
load then the voltage may rise above the normal. Generator core may heat-up due to saturation.
Voltage increase may cause damage to running load by increasing the current flow (according
to Ohm’s law).
The currents produced during a rotor earth fault can cause excessive vibration and disturb the
magnetic balance inside the alternator. These forces can cause the rotor shaft to become
eccentric and in extreme cases cause bearing failure. Hence, it is necessary that any earthing in
the rotor is detected at the earliest. In slip ring rotors, carbon deposits on the slip rings may
compromise the insulation resistance of the rotor. Hence, the slip rings need to be inspected for
any deposits.
The Rotor Earth Fault Protection Device consists of a current injection device which applies an
AC voltage to the rotor winding by means of a slip ring fitted on the rotor. The current is applied
to the rotor through a coupling capacitor. In the normal condition, the system is floating and the
current flowing through the device is zero as the resistance is high.
NOTE:
86/1 relay = Prime mover trip + main breaker open + excitation breaker opens
86/2 relay = Main breaker open + excitation breaker opens
86/3 relay = Main breaker open
Prepared By:
Farooq Hussain
GENERATOR
CTs 03 Nos. on each phase CTs 03 Nos. on each phase
CTs for 87G and for 87, 32, 51, 40 and for 87, 87G, DCS and panel
51G excitation indication
Generator circuit
breaker, 42 G1 A/B
NGR PT for
Excitation excitation
CTs for
excitation
Earth isolator
28gT1 A/B
DC