Khafji 5 SS - CT Sizing Calculation Rev-A

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 138

APP'D CERT'D

OB
SA
CHEK'D

MZK
ISSUED FOR BASE DESIGN
DESCRIPTION

CT & PT SIZING CALCULATION


DAR
BY

NOV. 2012
DATE
NO.

REVISIONS
DESIGNED

BY:- MZK

DATE:- Nov-12

CHECKED

BY:- SA

DATE:- Nov-12

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE

THIS DRAWING IS NOT


DOCUMENT TITLE INDEX PLANT DOCUMENT NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CT & PT SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL 115/13.8KV Khafji Substation # 5
A NA582 EE-237393 1 OF 86 A
CERTIFIED AND
DATED
KHAFJI SAUDI ARABIA JOB ORDER : XXXX DWG. CONT. SHT. EE-237357
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji115/13.8KV Substation No.5 Rev -A


Sheet 2
INDEX

S.NO. DESCRIPTION Sheet.No


I General 4

II Current Transformer 6

II.1 Line Differential Protection for 115KV Khafji-2 Line (Set-1) 6

II.2 Line Differential Protection for 115KV Khafji-2 Line (Set-2) 12

II.3 Metering for 115KV Khafji-2 Line 17

II.4 Line Differential Protection for 115KV Safaniyah Line (Set-1) 18

II.5 Line Differential Protection for 115KV Safaniyah Line (Set-2) 22

II.6 Metering for 115KV Safaniyah Line 26

II.7 Metering for 115KV Spare Lines 27

II.8 115/13.8KV Transformer T601 , T602 &T603 Differential Protection, HV Side (Set-1) 28

II.9 115/13.8KV Transformer T601 , T602 & T603 Non-Directional OC & EF Protection, HV Side (Set-2) 30

II.10 Metering for 115/13.8KV Transformer T601, T602 & T603 33

II.11 115KV Bus Section Non-Directional OC & EF Protection 34

II.12 115KV Bus Section Metering 36

II.13 115KV Bus Metering 37

II.14 115KV Bus Coupler -1 & 2 Non-Directional OC & EF Protection 38

II.15 115KV Bus Coupler -1 &2 Metering 40

II.16 115KV Bus Bar Differential Protection 41

II.17 115/13.8KV Transformer T601 , T602 & T603 Set-1 REF Protection (LV Side) 43

II.18 115/13.8KV Transformer T601, T602 & T603 Set-2 Neutral OC Protection 46

II.19 Metering for 115KV Transformer T601, T602 & T603 Bushing CT (HV Side) 48

II.20 115/13.8KV Transformer T601, T602 & T603 Set-2 Directional OC & EF Protection (LV side) 49

II.21 115/13.8KV Transformer T601 , T602 & T603 Set-1 Differential Protection (LV Side) 52

II.22 AVR for115/13.8KV Transformer T601, T602 & T603 (LV side) 54

II.23 Metering for 115KV Transformer T601, T602 & T603 Bushing CT(LV side) 55

II.24 13.8kV Out Going Feeder Non-Dir.OC & EF protection 56

II.25 Metering for 13.8KV Outgoing Feeder 58

II.26 13.8KV Station service transformer Feeder Non-Dir OC & EF protection 59

II.27 Metering for 13.8KV Station Transformer Feeder 61

II.28 13.8KV Capacitor Bank Main Feeder-1 Non -Directional O/C & E/F protection 62

II.29 Metering for 13.8KV Capacitor Feeder 64

II.30 13.8KV Bus Tie Non-Dir OC & EF protection 65

II.31 Metering for 13.8KV Bus Tie 67

II.32 13.8KV Bus Bar Differential Protection 68

III Voltage transformer

III.1 115KV Khafji-2 Line 71

III.2 115KV Safaniyah Line 72

III.3 115KV Spare Lines 73

III.4 115KV Transformer T601 , T602 & T603 74

III.5 115KV Bus-1A 75

III.6 115KV Bus-2A 76


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji115/13.8KV Substation No.5 Rev -A


Sheet 3
INDEX

S.NO. DESCRIPTION Sheet.No


III.7 115KV Bus-1C 77

III.8 115KV Bus-2C 78

III.9 13.8KV side of Transformer T601, T602 & T603 79

III.10 13.8KV Bus-1 81

III.11 13.8KV Bus-2 83

III.12 13.8KV Bus-3 85

Attachments:
Annexure-A: ET Drawings
Annexure-B: Data for relay & Meter Burden details.
Annexure-E: CT Consolidated Parameters
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji115/13.8KV Substation No.5 Rev -A


Sheet 4

I. GENERAL
1 Preamble

This document covers 115KV & 13.8 KV CT &VT sizing calculation for the 115KV Lines, 115/13.8KV
Transformer & 13.8 KV Switchgear protection & metring at S/S Khafji 115/13.8KV S/S # 5.

2 Design Basis

2.1 CT and other Details

CT parameters are based on:

i) System X/R ratio is assumed to be 17.

ii)
As mentioned in PTS-11EN1031, Appendix IX, IEC-44, Part-6 and IEC 185, TPS class CT for all protection.
iii) CT secondary excitation limiting E.M.F and other parameters for CT sizing are calculated at adopted Tap as shown in
Relay and metering one line diagram ET-906823
iv) Lead length is considered for 2 ways.

v) Safety margin of 25% is considered forboth protection class CT and for metering class CT as per clause 17.g of PTS-
11EN1031, Appendix IX.

vi) Rct and Rl values are at 75oC.

vii) Zs (source Impedance) is calculated based on CB Interrupting capacity. The line Impedance value will be added to Zs
to derive the fault current (PF & EF) at zone1 end for CT excitation limiting E.M.F calculation. Only on way CT lead
length is considered for PF zone1 Ual calculation & 2way CT lead length is considered for EF zone1 Ual calculation.
CT sizing calculation for close-in fault is done for 3phase fault since 40KA/25KA(115KV/13.8KV respectively) fault
level is considered for 3 phase and 1 phase fault.

viii) The Line parameters for 115KV line between S/S KHAFJI-5 and KHAFJI-2 is assumed for a typical
UG Conductor of length 15.3 Kms

2.2 System Details


i) Nominal system voltage : 115 & 13.8KV

ii) Circuit Breaker interrupting capacity : 40KA (115KV)


: 25KA (13.8KV)
iii) X/R ratio : 17 for 115 KV system

2.3 CT lead size & Resistance


The
ρ
R= Ω/m
A
Where,
ρ = Specific resistance at 20oC
A = Cross-sectional area of conductor
For other temperatures,
ρϑ = ρ20 [1 + α (ϑ - 20)]
ϑ = Temperature
α = Temperature Co-efficient

Value of ρ & α are given in table 2.7 of ABB switchgear manual


reference book for a temperature of 20oC.
Resistance for 6sq.mm cable per meter @ 75OC

= 0.0175
[1 + 0.004(75 - 20)]
6

= 0.0035 ohms/m
Resistance for 6 sq.mm conductor/m @ 75OC = 0.0035 ohms/m
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji115/13.8KV Substation No.5 Rev -A


Sheet 5

2.4 Terminology

Isn : Rated secondary current

Eal : CT excitation limiting E.M.F (Eal = Ual Since leakage is negligible in TPS class CT)
O
Rct : Maximum resistance of secondary winding at 75 C

Rb : Rated resistive burden

ktd : Dimensioning factor

2.5 Important formula for TPS class CT:


Eal = kssc * ktd * (Rct + Rb) * Isn

Ual = kssc * k * (Rct + Rb) * Isn


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [ 1 + 0.004 (75 - 20) ]
Rev -A
Sheet 6

II.1 Line Differential protection for 115KV Khafji-2 Line (Set-1)

System details: Source Impedance


CB interrupting capacity: 40000 A Xs: = (Ph vol./Ph.cu.)*sin(ATAN(X/R))
= (115 x 1000 x sin(ATAN(17))/(sqrt(3) x 40000)
Voltage Level: 115 KV = 1.657 ohms

X/R: 17.00 Rs: = (Ph vol./Ph.cu.)*cos(ATAN(X/R))


= (115 x 1000 x cos(ATAN(17))/(sqrt(3) x 40000)
CT details: = 0.097 ohms
Line feeder: 115KV U/G Cable to Khafji S/S-2 Zs: = Sqrt(1.657^2 + 0.097^2)

CB A606 = 1.66 Ohms

CT core: CT606.B.C1

CT Ratio: 1600-1200-1000-800-600/1A

Adopted Tap: 1000 A

CT sec.: 1A

Rct: 2.000 ohms

Class: TPS

Ual: 1000 V

Ial: 24.0 mA @ Ual

Kssc: 40.00 (40000/1000)

K: 4.17 (Ual/(Kssc*Isn*(RCT+Rb))

Rb: 4.00 Ohms

TRF: 2

SC Rating: 40000 A

Line details: Line Impedance:


Length: 15.300 Kms X1: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 0.361
R1: 0.04595 (Assumed) = 4.419 ohms
(Ohms / Km) X0: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 0.8862
X1: 0.36100 (Assumed) = 10.848 ohms
(Ohms / Km) Xn full line: = 15.3 x 0.361
= 5.524 ohms
R1: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.04595
R0: 0.24070 (Assumed) = 0.563 ohms
(Ohms / Km) R0: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.2407
X0: 0.88620 (Assumed) = 2.947 ohms
(Ohms / Km) Rn full line: = 15.3 x 0.04595
= 0.704 ohms
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 7
Earth loop Impedance (Zone1)
Zn = (R1 + R2 + R0) / 3 + j(X1 + X2 + X0)/3
= (0.563+0.563+2.947) / 3 +j (4.419+4.419+10.848) / 3
= 1.3580 +j 6.562
Earth loop Impedance (100 %) Ze = 1.698 +j 8.203

Other connected Burden 2


Burden: (VA / I ) Ohms
TFR (CICT in set-1 RP): 0.10 VA TFR: = (0.1 /1^2)
0.1000 Ohms
Mutual circuit Imp: 0.15
Relay Mutual circuit 0.15 VA 0.1500 Ohms
Impedance (MICOM P545) Total other equipment burden (0.1 + 0.15):
0.2500 Ohms
Relay (Micom P545) constants
Factors: K : 65
Kmax: 1.40
KRPA: 0.60

Secondary circuit cable details


Distance (120 % of 2 way): 250.00 mtr Sec. Cable resistance: =Distance x res./mtr
(CT to Line Set-1 protn panel) Assumed = (250 x0.0035)
0.875 ohms
Cable resistance(ohms/mtr):
SQmm 6 sq mm 0.00350

Ual Calculation formula

As per manufacturer:

The CT Accuracy Limiting Voltage (Ual) shall meet the following requirements.

A) Ual1 ≥ K x In x (Rct + RL + Rb)

B) Ual2 ≥ KRPA x IFZ1 x (1+X/R) x (Rct + RL + Rb)

C) Ual3 ≥ KMAX x IFMAX x (Rct + RL + Rb)


As per PTS
D) Ual4 = K1*In*(Rct + 2Rl)

E) Ual5 = IF1* (X/R+1)*(Rct + Rl + Rr + Rb)

F) Ual6 = K x IF2 x (Rct + RL + Rr + Rb)


Note:
Since Ual3 & Ual6 are same, Ual6 is not considered for calculation

Ual2,Ual5 = Accuracy Limit Voltage for end of zone1 Line fault (Dist. Protection)

Ual3,Ual6 = Accuracy Limit Voltage for close-in Line fault (Dist. Protection)

Ual1,Ua14 = Accuracy Limit Voltage for through fault (Diff. Protection)

IFZ1 , IF1 = Maximum primary fundamental frequency current for faults at the end of zone 1 reach (Dist. Protection)

IFMAX , IF2 = Maximum primary fundamental frequency current for close-in faults (Dist. Protection)

Isn , In = Rated CT secondary current

Ipn = Rated CT primary current

Rct = CT secondary winding resistance at 75oC


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.56 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 8
o
Rl = Cable lead resistance (Both ways total) at 75 C

KMAX = Factor of the primary time constant for close-in fault

KRPA = Factor of the primary time constant for fault at the end of zone 1 reach

Sr, Rr = Burden of P545 a current input channel (VA)

Rb = Other burdens connected to the CT core

K1 = A constant with value equal to 180In for application where max. value of secondary through fault
current x primary X/R ratio is less than 350In
CT Ual Calculation

PF Fault current (Through fault current)

Total fault Impedance = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)


Sqrt((1.657+5.524)^2+(0.097+0.704)^2)
= 7.23 Ohms
Through-fault current = Ph.vol./Ph.Imp.
= (115*1000/ (7.23 x sqrt(3)))
= 9184 A
Through-fault current at secondary side
(Flt.current/CT ratio) = (9184*1 / 1000) = 9.18 A

PF X/R ratio for through-fault current = (Xs+Xl)/(Rs+Rl)


= (1.657+5.524)/(0.097+0.704)
= 8.97
If x X/R = 9.18 x 8.97
= 82.34
EF Fault current (Through fault current)

Total fault Impedance for earth fault = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)


Sqrt((1.657+8.203)^2+(0.097+1.698)^2)
= 10.02 Ohms
Through-fault current for earth fault = Ph.vol./Ph.Imp.
= (115*1000/ (10.02 x sqrt(3)))
= 6627 A
Through-fault current at secondary side
(Flt.current/CT ratio) = (6627*1 / 1000) = 6.63 A

PF X/R ratio for through-fault current = (Xs+Xl)/(Rs+Rl)


= (1.657+8.203)/(0.097+1.698)
= 5.49
If x X/R = 6.63 x 5.49
= 36.4

Phase Fault current (End of zone1 fault)

Total fault Impedance for end of zone1 fault = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)


Sqrt((1.657+4.419)^2+(0.097+0.563)^2)
= 6.112 Ohms
Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.
= (115*1000/ (6.112 x sqrt(3)))
= 10863.103 A

Ikzone1 (Flt.current/CT ratio) = (10863.103 x 1 / 1000) = 10.863 A


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 9
X/R ratio for end of zone1 3 Phase fault = (Xs+Xl)/(Rs+Rl)
= (1.657+4.419)/(0.097+0.563)
= 9.21

Earth Fault current (End of zone1 fault)

Total fault Impedance for end of zone1 fault = Zs+Zn = (Sqrt(Xs+Xn)^2+(Rs+Rn)^2)


Sqrt((1.657+6.562)^2+(0.097+1.358)^2)
= 8.35 Ohms

Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.


= (115*1000/ (8.35 x sqrt(3)))
= 7951.54 A
Ikzone1 (Flt.current/CT ratio) = (7951.54 x 1 / 1000) = 7.952 A

X/R ratio for end of zone1 3 phase fault = (Xs+Xn)/(Rs+Rn)


= (1.657+6.562)/(0.097+1.358)
= 5.65
Fault current (Close-in fault)

Fault Current = 40000 A

Ikmax (Flt. current/CT ratio) = (40000 x 1 / 1000) = 40.0 A

X/R ratio = 17.00


(Differential calculation)
As per Manufacturer

A) CT Ual1 Calculation

K: Dimensioning factor
'K' is dependent on If (Max. through fault current) & system X/R ratio and 'K'is determined as follows.
For relays set at Is1 = 20%, Is2 = 2 In, K1 = 30%, K2 = 150%:
K > 40 + (0.07 x (If x X/R)) AND: K = 65
This is valid for (If x X/R) < 1000 In

If x X/R = 82.34
(PF values are used since
this is higher than EF)
K > 40 + (0.07 x (If x X/R)) AND: K = 65 (Refer Annexure - B)

K = 40 + (0.07 x (9.18 x 8.97)) AND: 65


= 45.764122 AND: 65
= 65
Ual1(PF) ≥ K x In x (Rct + RL/2 + Rb)

= 65 x 1 x (2 + 0.4375 + 0.25)

= 174.69 V - Result 1A

Ual1(EF) ≥ K x In x (Rct + RL + Rb)

= 65 x 1 x (2 + 0.875 + 0.25)

= 203.13 V - Result 1B
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
As per PTS Sheet 10

If x X/R = 9.18 x 8.97


= 82.34

As per PTS page 8 where maximum value of secondary through fault current x primary X/R ratio is less than 350In, K=180

K = 180

Ual4(PF) ≥ K x In x (Rct + 2 x RL)

= 180 x 1 x (2 + 2 x 0.4375)

= 596.25 V - Result 2A
Ual4(EF) ≥ K x In x (Rct + RL + Rb)

= 180 x 1 x (2 + 0.875 + 0.25)

= 562.50 V - Result 2B

(DISTANCE calculation)

As per Manufacturer

CT Ual Calculation for (End of zone1 fault))

Ual2 (PF) = KRPA x IFZ1 x (1+X/R) x (Rct + RL/2 + Rb)

KRPA = 0.6
1+X/R= 10.21
= 0.6 x 10.863 x 10.21 x (2 + 0.4375 + 0.25)

= 178.84 V - Result 3A

Ual2 (EF) = KRPA x IFZ1 x (1+X/R) x (Rct + RL + Rb)

KRPA = 0.6
1+X/R= 6.65
= 0.6 x 7.952 x 6.65 x (2 + 0.875 + 0.25)

= 99.15 V - Result 3B

CT Ual Calculation for (Close-in fault)

Ual3 (PF) =KMAX x IFMAX x (Rct + RL/2 + Rb)


KMAX = 1.4
= 1.4 x 40 x (2 + 0.4375 + 0.25)
= 151 - Result 4A

Ual3 (EF) =KMAX x IFMAX x (Rct + RL + Rb)


= 1.4 x 40 x (2 + 0.875 + 0.25)
= 175 - Result 4B

As per PTS
CT Ual Calculation for (End of zone1 fault))

Ual5 (PF) = IF1* (X/R+1)*(Rct + Rl + Rr + Rb)


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [ 1 + 0.004 (75 - 20) ]
Rev -A
Sheet 11
= 10.863 x 10.21 x (2 + 0.4375 + 0.25)

= 298.07 V - Result 5A

Ual5 (EF) = IF1* (X/R+1)*(Rct + Rl + Rr + Rb)

= 7.952 x 6.65 x (2 + 0.875 + 0.25)

= 165.25 V - Result 5B

Result 2A is higher than other Results and CT sizing is calculated based on result 2A.

Safety margin =25% = 1.25 x 596.25


Ual  746 V

Since the available Ual(1000V) is higher than required Ual (746), the CT is suitably sized.

`
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev - A
Sheet 12

II.2 Line Differential Protection for 115KV Khafji-2 Line (Set-2)

System details: Source Impedance


CB interrupting capacity: 40000 A Xs: = (Ph vol./Ph.cu.)*sin(ATAN(X/R))
= (115 x 1000 x sin(ATAN(17))/(sqrt(3) x 40000)
Voltage Level: 115 KV = 1.657 ohms

X/R: (Assumed) 17.00 Rs: = (Ph vol./Ph.cu.)*cos(ATAN(X/R))


= (115 x 1000 x cos(ATAN(17))/(sqrt(3) x 40000)

CT details: = 0.097 ohms


Line feeder: 115KV U/G Cable to Khafji S/S-2 Zs: = Sqrt(1.657^2 + 0.097^2)

CB A606 = 1.66 Ohms

CT core: CT606.B.C2

CT Ratio: 1600-1200-1000-800-600/1A

Adopted Tap: 1000 A

CT sec.: 1A
Rct: 2.00 ohms
Ial: 24.00 mA
Class: TPS
Kssc 40
K 4.17
Rb 4.00 ohms
Ual: 1000 V

Under Ground Cable details: Line Impedance:


Length: 15.300 Kms X1: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 0.361
R1: 0.0460 = 4.419 ohms
(Ohms / Km) X0: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 0.8862
X1: 0.3610 = 10.848 ohms
(Ohms / Km) X1 full line: = 15.3 x 0.361
= 5.524 ohms
R1: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.04595
R0: 0.2407 = 0.563 ohms
(Ohms / Km) R0: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.2407
X0: 0.8862 = 2.947 ohms
(Ohms / Km) R1 full line: = 15.3 x 0.04595
= 0.704 ohms

Earth loop Impedance (Zone1)


Z = (R1 + R2 + R0) / 3 + j(X1 + X2 + X0)/3
= (0.563+0.563+2.947) / 3 +j (4.419+4.419+10.848) / 3
= 1.3580 +j 6.562
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev - A

Sheet 14
CT Ual Calculation

Phase Fault current (End of zone1 fault)

Total fault Impedance for end of zone1 fault = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)


Sqrt((1.657+4.419)^2+(0.097+0.563)^2)
= 6.112 Ohms

Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.


= (115*1000/ (6.112 x sqrt(3)))
= 10863.103 A

Ikzone1 (Flt.current/CT ratio) = (10863.103 x 1 / 1000) = 10.863 A

X/R ratio for end of zone1 3 Phase fault = (Xs+Xl)/(Rs+Rl)


= (1.657+4.419)/(0.097+0.563)
= 9.21

Sys. Time const. for end of zone1 3ph.fault = (X/R ratio)/(2*PI*F) =(9.21) / (2 x 3.14 x 60)
= 24.43 ms

b = 4.00 (Refer Annexure - B)

Earth Fault current (End of zone1 fault)

Total fault Impedance for end of zone1 fault = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)


Sqrt((1.657+6.562)^2+(0.097+1.358)^2)
= 8.35 Ohms
Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.
= (115*1000/ (8.35 x sqrt(3)))
= 7951.54 A

Ikzone1 (Flt.current/CT ratio) = (7951.54 x 1 / 1000) = 7.952 A

X/R ratio for end of zone1 single phase fault = (Xs+Xl)/(Rs+Rl)


= (1.657+6.562)/(0.097+1.358)
= 5.65

Sys. Time const. for end of zone1 1ph.fault = (X/R ratio)/(2*PI*F) =(5.65) / (2 x 3.14 x 60)
= 14.99 ms

b = 4.00 (Refer Annexure - B)


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev - A

Fault current (Close-up fault) Sheet 15


Fault Current = 40000 A

IF2 (Flt. current/CT ratio) = (40000 x 1 / 1000) = 40.0 A

X/R ratio = 17.00

System time constant for close-up fault = (X/R ratio)/(2*PI*60) = (17) / (2 x PI x 60)
= 45.09 ms

a = 2.00 (Refer Annexuere - B)


Through Fault Current calculation
Fault Impedance = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)
Sqrt((1.657+5.524)^2+(0.097+0.704)^2)
= 7.226 Ohms
Through Fault Current = Ph.vol./Ph.Imp.
= (115*1000/ (7.226 x sqrt(3)))
= 9188.4 A
Itmax (Flt.current/CT ratio) = (9188.4 x 1 / 1000) = 9.188 A
X/R ratio for through fault = (Xs+Xl)/(Rs+Rl)
= (1.657+5.524)/(0.097+2.947)
= 2.36
CT Ual Calculation for case A
Kalf ≥ 30
or
Kalf = Iscc max. (external Fault) = 40

Since Iscc max. (external Fault) > 30 then Kalf = 40.0

Ual1 = Kalf * (Rct + Rl + Rb)

= 40 * ( 0.875 + 0.1 + 2 )

= 119.000 V - Result 1A

CT Ual Calculation for case B and case F

Ual2 (PF) > a * Iscc.max (close-up fault) * (Rct + Rl /2 + Rb)

= 2 x 40 x (2 + 0.4375 + 0.1 )

= 203.000 V - Result 1B

Ual2 (EF) > a* Iscc.max (close-up fault)*(Rct + Rl + Rb)

= 2 x 40 x (2 + 0.875 + 0.1)

= 238.000 V - Result 2B

CT Ual Calculation for case C

Ual3 (PF) > b* Iscc.max (zone 1-end fault)*(Rct + Rl /2+ Rb)

= 4 x 10.863 x (2 + 0.4375 + 0.1 )

= 110.259 V - Result 1C
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation:Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 17
II.3 Metering for 115KV Khafji-2 Line

CT details:

Line Feeder: Line feeder: 115KV U/G Cable to Khafji S/S-2


CB A606
CT core:CT606B.C3
CT Ratio: 1600-1200-1000-800-600/1A
Adopted Tap: 1000 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 12.5
ISF: <5
Rct: 3.40 ohms

Connected Burden:

2
Ammeter 1.0000 VA Ammeter Burden: (VA/I ) = (1 /1^2)
(Assumed) 1.0000 ohms
DPDM 1.0000 VA DPDM Burden: (VA/I2) = (1 /1^2)
(Assumed) 1.0000 ohms
Bay Control Unit(REC670) 0.02 VA BCU Burden: = (0.02 /1^2)
(Refer Annexure-B) (Assumed) 0.0200 ohms

Total burden:
= (1 + 1+0.02)
= 2.0200 ohms
Rct = 3.40 ohms
Secondary circuit cable details

Distance (2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr


(CT to Line LCC panel) (Assumed) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 2.02 + 0.14+3.4


5.5600 ohms
Safety margin =25% 1.25 x 5.56

= 6.95 Ohms
Burden (VA) = I2 * R
= 1^2*6.95 = 6.95 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [ 1 + 0.004 (75 - 20) ]
Rev -A
II.4 Line Differnetial protection for 115KV Safaniyah Line (Set-1) Sheet 18

System details: Source Impedance


CB interrupting capacity: 40000 A Xs: = (Ph vol./Ph.cu.)*sin(ATAN(X/R))
= (115 x 1000 x sin(ATAN(17))/(sqrt(3) x 40000)
Voltage Level: 115 KV = 1.657 ohms

X/R: 17.00 Rs: = (Ph vol./Ph.cu.)*cos(ATAN(X/R))


= (115 x 1000 x cos(ATAN(17))/(sqrt(3) x 40000)
CT details: = 0.097 ohms
Line feeder: 115KV U/G Cable to Safaniyah PP Zs: = Sqrt(1.657^2 + 0.097^2)

CB A609 = 1.66 Ohms


CT core: CT609.B.C1
Note:
CT Sizing Calculation of these CTs will be confirmed after
CT Ratio: 2000-1600-1500-1200-1100-800-500-400-300/5A
site visit of Safaniyah S/S.
Adopted Tap: 2000 A
CT sec.: 5A
Rct: 1.815 ohms
Class: C800
Ual: 800 V
Ial: 91.2 mA @ Ual
Kssc: 20.00 (40000/2000)
K: 1.47 (Ual/(Kssc*Isn*(RCT+Rb))

Rb: 3.63 Ohms


TRF: 2
SC Rating: 40000 A

Line details: Line Impedance:


Length: 15.300 Kms X1: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 0.31945
R1: 0.04745 (Assumed) = 3.911 ohms
(Ohms / Km) X0: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 1.4268
X1: 0.31945 (Assumed) = 17.465 ohms
(Ohms / Km) Xn full line: = 15.3 x 0.31945
= 4.888 ohms
R1: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.04745
R0: 0.34903 (Assumed) = 0.581 ohms
(Ohms / Km) R0: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.34903
X0: 1.42680 (Assumed) = 4.273 ohms
(Ohms / Km) Rn full line: = 15.3 x 0.04745
= 0.726 ohms
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 19
Earth loop Impedance (Zone1)
Zn = (R1 + R2 + R0) / 3 + j(X1 + X2 + X0)/3
= (0.581+0.581+4.273) / 3 +j (3.911+3.911+17.465) / 3
= 1.8120 +j 8.429
Earth loop Impedance (100 %) Ze = 2.265 +j 10.537
Connected Burden

Diff/Dist. relay (REL670): 0.25 VA REL Burden: (VA / I2) = (0.25 /5^2)
(87L, 21 & 67N) 0.0100 Ohms
Relay (REL670) constants
a: 0.87
Time constant: (45.09 ms)
k: 4.00
Time constant: (21.78 ms)
Secondary circuit cable details
Distance (2 way): 250.00 mtr Sec. Cable resistance: =Distance x res./mtr
(CT to Line set-1 protn panel) = (250 x0.0035)
0.875 ohms
Cable resistance(ohms/mtr):
SQmm 6 sq mm 0.00350

Ual Calculation formula


As per manufacturer:
The CT Accuracy Limiting Voltage (Ual) shall meet the following requirements.
A) Ual1 2 -1
= Ikzone1 x k x (Isn / Ipn) x (Rct + Rl + Sr/Ir )

B) Ual2 2 -2
= Ikmax x a x (Isn / Ipn) x (Rct + Rl + Sr/Ir )
As per PTS

C) Ual3 = IF1* (X/R+1)*(Rct + Rl + Rr + Rb) -3

D) Ual4 = K x IF2 x (Rct + RL + Rr + Rb) -4

E) Ual5 = K*In*(Rct + Rl) -5


Note:
Since Ual2 & Ual4 are same, Ual4 is not considered for calculation

Ual1,Ual3 = Accuracy Limit Voltage for end of zone1 Line fault (Dist. Protection)

Ual2,Ual4 = Accuracy Limit Voltage for close-in Line fault (Dist. Protection)

Ual5 = Accuracy Limit Voltage for through fault (Diff. Protection)

Ik zone1 , IF1 = Maximum primary fundamental frequency current for faults at the end of zone 1 reach (Dist. Protection)

Ik max , IF2 = Maximum primary fundamental frequency current for close-in faults (Dist. Protection)

Isn , In = Rated CT secondary current

Ipn = Rated CT primary current


Rct = CT secondary winding resistance at 75oC
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


= Cable lead resistance (Both ways total) at 75oC
6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]

Rl Sheet 20

a = Factor of the primary time constant for close-in fault

k = Factor of the primary time constant for fault at the end of zone 1 reach

Sr, Rr = Burden of REL670 a current input channel (VA)

Rb = Other burdens connected to the CT core

K = A constant with value equal to 180In for application where max. value of secondary through fault
current x primary X/R ratio is less than 350In
CT Ual Calculation

Phase Fault current (End of zone1 fault)


Total fault Impedance for end of zone1 fault = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)
Sqrt((1.657+3.911)^2+(0.097+0.581)^2)
= 5.610 Ohms
Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.
= (115*1000/ (5.61 x sqrt(3)))
= 11835.166 A
Ikzone1 (Flt.current/CT ratio) = (11835.166 x 5 / 2000) = 29.588 A

X/R ratio for end of zone1 3 Phase fault = (Xs+Xl)/(Rs+Rl)


= (1.657+3.911)/(0.097+0.581)
= 8.21

Sys. Time const. for end of zone1 3ph.fault = (X/R ratio)/(2*PI*F) =(8.21) / (2 x 3.14 x 60)
= 21.78 ms
k = 4.00 (Refer Annexure - B)
Earth Fault current (End of zone1 fault)

Total fault Impedance for end of zone1 fault = Zs+Zn = (Sqrt(Xs+Xn)^2+(Rs+Rn)^2)


Sqrt((1.657+8.429)^2+(0.097+1.812)^2)
= 10.27 Ohms
Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.
= (115*1000/ (10.27 x sqrt(3)))
= 6464.98 A
Ikzone1 (Flt.current/CT ratio) = (6464.98 x 5 / 2000) = 16.162 A

X/R ratio for end of zone1 3 phase fault = (Xs+Xn)/(Rs+Rn)


= (1.657+8.429)/(0.097+1.812)
= 5.28

Sys. Time const. for end of zone1 3ph.fault = (X/R ratio)/(2*PI*F) =(5.28) / (2 x 3.14 x 60)
= 14.01 ms
k = 4.00 (Refer Annexure - B)
Phase Fault current (Through fault)

Total fault Impedance for through fault condition. = Zs+Ze = (Sqrt(Xs+Xe)^2+(Rs+Re)^2)


Sqrt((1.657+4.888)^2+(0.097+0.726)^2)
= 6.597 Ohms
Through Fault Current = Ph.vol./Ph.Imp.
= (115*1000/ (6.597 x sqrt(3)))
= 10064.5 A
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.56 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
If (Flt.current/CT ratio) = (10064.5 * 5 / 2000) = 25.161 Sheet 21

X/R ratio for through-fault current = (Xs+Xe)/(Rs+Re)


= (1.657+4.888)/(0.097+0.726)
= 7.95
Fault current (Close-in fault)
Fault Current = 40000 A

Ikmax (Flt. current/CT ratio) = (40000 x 5 / 2000) = 100.0 A

X/R ratio = 17.00

System time constant for close-up fault = (X/R ratio)/(2*PI*60) = (17) / (2 x PI x 60)
= 45.09 ms

a = 0.87 (Refer Annexuere - B)


CT Ual Calculation for case A
2
Ual1 (PF) = Ikzone1 x k x (Isn / Ipn) x (Rct + Rl + Sr/Ir ) -1A

= 29.588 x 4 x (1.815 + 0.4375 + 0.01)

= 267.77 V - Result 1A

2
Ual1 (EF) = Ikzone1 x k x (Isn / Ipn) x (Rct + 2Rl + Sr/Ir ) -1B

= 16.162 x 4 x (1.815 + 0.875 + 0.01)

= 174.55 V - Result 1B

CT Ual Calculation for case B


2 -2A
Ual2 (PF) = Ikmax x a x (Isn / Ipn) x (Rct + Rl + Sr/Ir )
= 100 x 0.87 x (1.815 + 0.4375 + 0.01)
= 197 - Result 2A
2
Ual2 (EF) = Ikmax x a x (Isn / Ipn) x (Rct + 2Rl + Sr/Ir ) -2B
= 100 x 0.87 x (1.815 + 0.875 + 0.01)
= 235 - Result 2B
CT Ual Calculation for case C
Ual3 (PF) = IF1* (X/R+1)*(Rct + Rl/2 + Rr + Rb) -3A
= 29.588 x 9.21 x (1.815 + 0.4375 + 0.01)
= 616.544 - Result 3A

Ual3 (EF) = IF1* (X/R+1)*(Rct + Rl + Rr + Rb) -3B


= 16.162 x 6.28 x (1.815 + 0.875 + 0.01)
= 274.043 - Result 3B

Result 3A is higher than other Results and CT sizing is calculated based on result 3A.
Safety margin =20% = 1.2 x 616.544
Ual ≥ 740 V

Since the available Ual(800V) is higher than required Ual (740V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [ 1 + 0.004 (75 - 20) ]
Rev -A
Sheet 22

II.5 Line Differential Protection for 115KV Safaniyah Line (Set-2)

System details: Source Impedance


CB interrupting capacity: 40000 A Xs: = (Ph vol./Ph.cu.)*sin(ATAN(X/R))
= (115 x 1000 x sin(ATAN(17))/(sqrt(3) x 40000)
Voltage Level: 115 KV = 1.657 ohms

X/R: 17.00 Rs: = (Ph vol./Ph.cu.)*cos(ATAN(X/R))


= (115 x 1000 x cos(ATAN(17))/(sqrt(3) x 40000)
CT details: = 0.097 ohms
Line feeder: 115KV U/G Cable to Safaniyah PP Zs: = Sqrt(1.657^2 + 0.097^2)

CB A609 = 1.66 Ohms


CT core: CT609.B.C2

Note:
CT Ratio: 2000-1600-1500-1200-1000-800-500-400-3000/5A
CT Sizing Calculation of these CTs will be confirmed after
site visit of Safaniyah S/S.
Adopted Tap: 2000 A
CT sec.: 5A
Rct: 1.815 ohms
Class: C800
Ual: 800 V
Ial: 91.2 mA @ Ual
Kssc: 20.00 (40000/2000)
K: 1.47 (Ual/(Kssc*Isn*(RCT+Rb))

Rb: 3.63 Ohms


TRF: 2
SC Rating: 40000 A

Line details: Line Impedance:


Length: 15.300 Kms X1: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 0.31945
R1: 0.04745 (Assumed) = 3.911 ohms
(Ohms / Km) X0: 0.8 x Line length x Reactance value / Km
= 0.8 x 15.3 x 1.4268
X1: 0.31945 (Assumed) = 17.465 ohms
(Ohms / Km) Xn full line: = 15.3 x 0.31945
= 4.888 ohms
R1: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.04745
R0: 0.34903 (Assumed) = 0.581 ohms
(Ohms / Km) R0: 0.8 x Line length x Resistance value / Km
= 0.8 x 15.3 x 0.34903
X0: 1.42680 (Assumed) = 4.273 ohms
(Ohms / Km) Rn full line: = 15.3 x 0.04745
= 0.726 ohms
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 23
Earth loop Impedance (Zone1)
Zn = (R1 + R2 + R0) / 3 + j(X1 + X2 + X0)/3
= (0.581+0.581+4.273) / 3 +j (3.911+3.911+17.465) / 3
= 1.8120 +j 8.429

Earth loop Impedance (100 %) Ze = 2.265 +j 10.537


Connected Burden
(Refer Annexure: B)
2
Diff/Dist. relay (P443): 0.04 VA P443 Burden: (VA / I ) = (0.04 /5^2)
(87L, 21 & 67N) 0.0016 Ohms

Relay (P443) constants(Refer Annexure: B)

Kmax 1.40
KRPA 0.60

Secondary circuit cable details

Distance (2 way): 140.00 mtr Sec. Cable resistance: =Distance x res./mtr


(CT to Line set-2 protn panel) = (140 x0.0035)
0.490 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.00350

Ual Calculation formula

As per manufacturer:

The CT Accuracy Limiting Voltage (Ual) shall meet the following requirements.

A) Ual1 = KRPA x IFZ1 x (1+X/R) x (Rct + RL) -1

B) Ual2 -2
= kmax x IFmax x (Rct + RL)

As per PTS

C) Ual3 = IF1* (X/R+1)*(Rct + RL + Rr + Rb) -3

D) Ual4 = K x IF2 x (Rct + RL + Rr + Rb) -4

E) Ual5 = K*In*(Rct + Rl) -5

Note:
Since Ual2 & Ual4 are same, Ual4 is not considered for calculation

Ual1,Ual3 = Accuracy Limit Voltage for end of zone1 Line fault (Dist. Protection)

Ual2,Ual4 = Accuracy Limit Voltage for close-in Line fault (Dist. Protection)

Ual5 = Accuracy Limit Voltage for through fault (Diff. Protection)

IFZ1 = Maximum primary fundamental frequency current for faults at the end of zone 1 reach (Dist. Protection)

IFmax = Maximum primary fundamental frequency current for close-in faults (Dist. Protection)

In = Rated CT secondary current

Ipn = Rated CT primary current

Rct = CT secondary winding resistance at 75oC


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


= Cable lead resistance (Both ways total) at 75oC
6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]

Rl Sheet 24

Rr = Burden of P443 a current input channel (VA)

Rb = Other burdens connected to the CT core

K = A constant with value equal to 180In for application where max. value of secondary through fault
current x primary X/R ratio is less than 350In

KRPA: = Fixed dimensioning factor for zone1 fault= always 0.6

Kmax: = Fixed dimensioning factor for close up fault= always 1.4

CT Ual Calculation

Phase Fault current (End of zone1 fault)

Total fault Impedance for end of zone1 fault = Zs+Zl = (Sqrt(Xs+Xl)^2+(Rs+Rl)^2)


Sqrt((1.657+3.911)^2+(0.097+0.581)^2)
= 5.610 Ohms
Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.
= (115*1000/ (5.61 x sqrt(3)))
= 11835.166 A

IFZ1 (Flt.current/CT ratio) = (11835.166 x 5 / 2000) = 29.588 A

X/R ratio for end of zone1 3 Phase fault = (Xs+Xl)/(Rs+Rl)


= (1.657+3.911)/(0.097+0.581)
= 8.21

Earth Fault current (End of zone1 fault)

Total fault Impedance for end of zone1 fault = Zs+Zn = (Sqrt(Xs+Xn)^2+(Rs+Rn)^2)


Sqrt((1.657+8.429)^2+(0.097+1.812)^2)
= 10.27 Ohms
Fault Current for end of zone1 fault = Ph.vol./Ph.Imp.
= (115*1000/ (10.27 x sqrt(3)))
= 6464.98 A

IFZ1 (Flt.current/CT ratio) = (6464.98 x 5 / 2000) = 16.162 A

X/R ratio for end of zone1 single phase fault = (Xs+Xn)/(Rs+Rn)


= (1.657+8.429)/(0.097+1.812)
= 5.28

Phase Fault current (Through fault)

Total fault Impedance for through fault condition. = Zs+Ze = (Sqrt(Xs+Xe)^2+(Rs+Re)^2)


Sqrt((1.657+4.888)^2+(0.097+0.726)^2)
= 6.597 Ohms
Through Fault Current = Ph.vol./Ph.Imp.
= (115*1000/ (6.597 x sqrt(3)))
= 10064.5 A

Flt.current/CT ratio = (10064.5 * 5 / 2000) = 25.161

X/R ratio for through-fault current = (Xs+Xe)/(Rs+Re)


= (1.657+4.888)/(0.097+0.726)
= 7.95
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 25
Fault current (Close-in fault)

Fault Current = 40000 A

IFmax (Flt. current/CT ratio) = (40000 x 5 / 2000) = 100.0 A

X/R ratio = 17.00

CT Ual Calculation for case A

Ual1 = KRPA x IFZ1 x (1+X/R) x (Rct + RL) -1

= 0.6 x 29.588 x (1+8.21) x (0.245 + 1.815)

= 336.82 V - Result 1

CT Ual Calculation for case B

Ual2 = kmax x IFmax x (Rct + RL) -2


= 1.4 x 100 x (0.49 + 1.815)
= 322.7 - Result 2

Note:
It is not necessary to repeat the calculation for earth faults, as the phase reach (3∅) calculation is the worst case for CT dimensioning.

CT Ual Calculation for case C

Ual3 (PF) = IF1* (X/R+1)*(Rct + Rl/2 + Rr + Rb) -3A

= 29.588 x 9.21 x (1.815 + 0.245 + 0.0016)

= 561.797 - Result 3A

Ual3 (EF) = IF1* (X/R+1)*(Rct + Rl + Rr + Rb) -3B

= 16.162 x 6.28 x (1.815 + 0.49 + 0.0016)

= 234.114 - Result 3B

Result 3A is higher than other Results and CT sizing is calculated based on result 3A.

Safety margin =20% = 1.2 x 561.797


Ual ≥ 675 V

Since the available Ual(800V) is higher than required Ual(675V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation:Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 26
II.6 Metering for 115KV Safaniyah Line

CT details:

Line Feeder: Line feeder: 115KV U/G Cable to Safaniyah P/P


CB A609
CT core:CT609B.C3
CT Ratio: 1600-1200-1000-800-600/1A
Adopted Tap: 1000 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 12.5
ISF: <5
Rct: 3.40 ohms

Connected Burden:

2
Ammeter 1.0000 VA Ammeter Burden: (VA/I ) = (1 /1^2)
(Assumed) 1.0000 ohms
DPDM 1.0000 VA DPDM Burden: (VA/I2) = (1 /1^2)
(Assumed) 1.0000 ohms
Bay Control Unit(REC670) 0.02 VA BCU Burden: = (0.02 /1^2)
(Refer Annexure-B) (Assumed) 0.0200 ohms

Total burden:
= (1 + 1+0.02)
= 2.0200 ohms
Rct = 3.40 ohms
Secondary circuit cable details

Distance (2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr


(CT to Line LCC panel) (Assumed) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 2.02 + 0.14+3.4


5.5600 ohms
Safety margin =25% 1.25 x 5.56

= 6.95 Ohms
Burden (VA) = I2 * R
= 1^2*6.95 = 6.95 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation:Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 27
II.7 Metering for 115KV Spare Lines

CT details:

Line Feeder: Line feeder: 115KV Spare Feeders


CB A608 and CB A611
CT core:CT608B.C3, CT core:CT611B.C3,
CT Ratio: 1600-1200-1000-800-600/1A
Adopted Tap: 1000 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 12.5
ISF: <5
Rct: 3.40 ohms

Connected Burden:

2
Ammeter 1.0000 VA Ammeter Burden: (VA/I ) = (1 /1^2)
(Assumed) 1.0000 ohms
DPDM 1.0000 VA DPDM Burden: (VA/I2) = (1 /1^2)
(Assumed) 1.0000 ohms
Bay Control Unit(REC670) 0.02 VA BCU Burden: = (0.02 /1^2)
(Refer Annexure-B) (Assumed) 0.0200 ohms

Total burden:
= (1 + 1+0.02)
= 2.0200 ohms
Rct = 3.40 ohms
Secondary circuit cable details

Distance (2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr


(CT to Line LCC panel) (Assumed) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 2.02 + 0.14+3.4


5.5600 ohms
Safety margin =25% 1.25 x 5.56

= 6.95 Ohms
Burden (VA) = I2 * R
= 1^2*6.95 = 6.95 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation:Khafji 115/13.8KV Substation No.5 6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 1928
II.8 115/13.8KV Transformer T601 , T602 &T603 Differential Protection, HV Side (Set-1)

Power Transformer detail:

115/13.8KV Transformer T601 , T602 & T603 Rated Pri. Current (HV) = 1000 x MVA
Capacity: 67 MVA sqrt(3) x KV
Base MVA 50 MVA
Voltage: 115 KV = 1000 x 67
Impedance: 22.00 % at 50 MVA (sqrt(3) x 115)
CB inter. capacity: 40000 A
= 337A
CT details:

115/13.8KV Transformer T601 , T602 & T603 Corresponding Sec. Current = 337 x 1
CB A604 , A605 & A607 600
CT core: CT607.B1.C1, CT605.B1.C1, CT604.B1.C1
CT Ratio: 1600-1200-1000-800-600/1A = 0.570 A

Adopted Tap: 600 A


CT sec.: 1A
Rct: 1.20 Ohms
Class: TPS
Ual: 600 V
Ial: 40.0 mA at Ual
Kssc: 66.67 (40000/600)
K: 2.50 (Ual/(Kssc*Isn*(RCT+Rb))
Rb: 2.40 (2 x Rct) Ohms
TRF: 2
SC Rating: 40000A

Connected Burden:

Burden details: (Annexure-B)


RET670 Burden: 0.150 VA TOTAL Burden: (VA/I2) = (0.15) /1^2)
= 0.1500 Ohms

Secondary circuit cable details


Distance (120% 0f 2 way): 250.00 mtr
(CT to Trf Set-1 Protn Panel ) (Assumed) Sec. Cable resistance: =Distance x res./mtr
= 250 x 0.0035
Cable resistance(ohms/mtr): = 0.875 ohms
6 sq mm 0.0035

Ual Calculation formula

RET670 formula (Annexure-B) Ual1 = 30* Int * (Isn/Ipn)*(Rct + RL + Sr/Ir2 + Rb) -1

Ual2 = 2* Itf * (Isn/Ipn)*(Rct + RL + Sr/Ir2 + Rb) -2

As per PTS Ual3 = K * Isn*(Rct + RL + Rr + Rb) -3

Ual1,Ual2,Ual3 = Accuracy limiting voltage


Isn,Ir = Rated CT secondary current(A)
Rr = Relay total Resistance
Rct = CT secondary winding resistance at 75oC
RL = Cable lead resistance (Both ways total) at 75oC
K = Constant as per manufacturer recommendation
Ipn = Rated primary CT current(A)
Rb = Other burdens connected to the CT core
Int = Rated primary current of the transformer(A)
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation:Khafji 115/13.8KV Substation No.5 6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 2029

Itf = Max. primary fundamental frequency current that passes main two CTs and transformer(A)
Sr = Relay Burden

Since the manufacturer formula Ual1 and PTS formula Ual3 are same, we consider manufacturer formula for Ual calculation

CT Ual Calculation

100 x Times of Tr. Full load current


Maximum through fault current =
Tr.% Impedance

Transformer % imp at 67 MVA = Tr. % Imp. at given base MVA x New Base MVA
Given base MVA

= (22 * 67 / 50)
= 29.50
Maximum through fault current = (100/29.50) x (67MVA) / (sqrt(3) x 115KV)
= 1702 A

Ual1 = 30* Int * (Isn/Ipn)*(Rct + RL + Sr/Ir2 )


= (0.57 x 30)* (1.2+0.875+0.15)
= 38.05 V -1

Ual2 = 2* Itf * (Isn/Ipn)*(Rct + RL + Sr/Ir2 )


= (1701.9 x 2)1/600* (1.2+0.875+0.15)
= 12.62 V -2

Result 1 is higher than other Results and CT sizing is calculated based on result 1.

Safety margin= 25% = 1.25 x 38.048


Ual ≥ 48 V

Since the available Ual(600V) is higher than required Ual(48V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 30

II.9 11513.8KV Transformer T601 , T602 & T603 Non-Directional OC & EF Protection, HV Side (Set-2)

System details:
CB interrupting capacity: 40000 A
Voltage Level: 115.0 KV

CT details:
115/13.8KV Transformer T601, T602 & T603
CB A607, A605 & A604
CT core detail : CT core: CT607.B1.C3, CT605.B1.C3 &
CT604.B1.C3
CT Ratio : 1600-1200-1000-800-600/1A
Adopted Tap: 600 A
CT sec.: 1A
Rct: 1.20 Ohms
Class: TPS
Ual 600.00 V
Ial 40.0 mA at Ual
Kssc: 66.67
K: 2.50 (Ual/(Kssc*K*(RCT+Rb))
Rb: 2.40 ohms
TRF: 2
SC Rating: 40000A

Connected Burden:(Refer : Annexure-B) Burden: (VA / I2) Ohms


(VA/I
50/51 relay Type: Micom P142 50/50N Relay Resistance: =(0.15/1^2)
Micom P142 BURDEN 0.150 VA 0.1500 ohms
50N/51N relay Type: Micom P142 51/51N Relay Resistance: =(0.2/1^2)
Micom P142 BURDEN 0.200 VA 0.2000 ohms

Total Burden 0.3500 ohms

Secondary circuit cable details


Distance : (120% of two Way) Sec.cable resistance: =Distance x res./mtr
(CT to Trf Set-2 protn. Panel) 160.00 mtr =(160) x 0.0035
Cable resistance(ohms/mtr): (Assumed) 0.560 ohms
6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

Relay Manufacturer Formula

For Definite time/IDMTL overcurrent & earth fault protection

Phase fault- Ual ≥ Ifp/2 * (Rct +RL + Rrp + Rb) -1

Earth Fault- Ual ≥ Ifn/2 * (Rct +2RL+ Rrp + Rrn + Rb) -2

For Instantaneous overcurrent & earth fault protection


Phase fault- Ual ≥ Isp * (Rct +RL + Rrp + Rb) -3

Earth Fault- Ual ≥ Isn * (Rct +2RL+ Rrp + Rrn + Rb) -4


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 31

PTS Formula

For Definite time/IDMTL overcurrent & earth fault protection

Phase fault- Ual ≥ Is * (Rct +RL + Rr + Rb) -5

Earth Fault- Ual ≥ Is * (Rct +2RL + Rr + Rb) -6

For Instantaneous overcurrent & earth fault protection

Phase fault- Ual ≥ Is*2 * (Rct +RL + Rr + Rb) -7

Earth Fault- Ual ≥ Is*2 * (Rct +2RL + Rr + Rb) -8

Ual = CT knee point voltage (rms)


Ifp,Ifn = Maximum prospective CT secondary Phase fault & Earth fault current (amps)
Isp,Isn, = Maximum prospective CT secondary Phase fault & Earth fault current or 31 times
I> setting(whichever is lower)(amps)
Is = CT secondary current corresponding to Switchgear interupting Current
Rct = CT secondary winding resistance at 75oC
Rrp = Impedance of Relay phase current input
Rrn = Impedance of Relay neutral current input
RL = Cable lead resistance at 75oC
Rb = Other burdens connected to the CT core

Fault current (external fault)


Fault Current for external fault = CB interrupting capacity
= 40000 A
Isccmax (Flt.current/CT ratio) = (40000 / (600/1)) = 66.670 A

Calculation for Relay manufacurer formula

For Definite time/IDMTL overcurrent & earth fault protection


Phase fault- Ual = Ifp/2 * (Rct +RL + Rrp + Rb)
= (66.67/2)*(1.2+0.28+0.15)
= 54.34 V -1

Earth Fault- Ual = Ifn/2 * (Rct +2RL+ Rrp + Rrn + Rb)


= (66.67/2)*(1.2+0.56+0.15+0.2)
= 70.34 V -2

For Instaneous Over-Current and earth fault Protection

Phase fault- Ual = Isp * (Rct +RL + Rrp + Rb)


Phase current corresponding to instantaneous setting = Isp : 40 times of In (Assumed)
Ifp = 40.0 A
= 40*(1.2+0.28+0.35)
= 73.20 V -3

Earth Fault- Ual = Isn * (Rct +2RL+ Rrp + Rrn + Rb)


Earth current corresponding to instantaneous setting = Isn : 40 times of In (Assumed)
Ifn = 40.0 A
= 40*(1.2+0.56+0.35+0.2)
92.40 V -4
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 32
Calculation for PTS formula

For Definite time/IDMTL overcurrent & earth fault protection


Phase fault- Ual = Is * (Rct +RL + Rr + Rb)
= (66.67)*(1.2+0.28+0.35)
= 122.01 V -5

Earth Fault- Ual = Is * (Rct +2RL + Rr + Rb)


= (66.67)*(1.2+0.56+0.35)
= 140.67 V -6

For Instaneous Over-Current and earth fault Protection

Phase fault- Ual = Is*2 * (Rct +RL + Rr + Rb)


= (66.67)*2*(1.2+0.28+0.35)
= 244.01 V -7

Earth Fault- Ual = Is*2 * (Rct +2RL + Rr + Rb)


= (66.67)*2*(1.2+0.56+0.35)
281.35 V -8

Result 8 is higher than other Results, hence CT sizing is calculated based on result 8.

Safety margin =20% = 1.25 x 281.3474


Ual ≥ 352 V

Since the available Ual(600V) is higher than required Ual(352V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 33
II.10 Metering for 115/13.8KV Transformer T601, T602 & T603

CT details:

115/13.8KV Transformer
CB A607,A604 & A605
CT core: CT607.B.C3, CT605.B.C3, CT604.B.C3
CT Ratio:1600-1200-1000-800-600/1A
Adopted Tap: 600 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 7.5
ISF: <5
Rct: 2.30 ohms

Connected Burden:

Ammeter 1.0000 VA Ammeter Burden: (VA/I2) = (1 /1^2)


(Assumed) 1.0000 ohms
Digital Power Demand meter 1.0000 VA DPDM Burden: (VA/I2) = (1 /1^2)
ACCS Relay 1.0000 VA ACCS Burden: (VA/I2) = (1 /1^2)
(Assumed) 1.0000 ohms
1.0000 ohms
Bay Control Unit(REC670) 0.02 VA BCU Burden: = (0.02 /1^2)
(Refer Annexure-B) (Assumed) 0.0200 ohms

Total burden: (DPDM+A+ACCS+BCU )


= (1 +1+ 1 + 0.02)
= 3.0200 ohms
Rct = 2.30 ohms
Secondary circuit cable details

Distance (120% of 2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr
(CT to Trf LCC panel) (Assumed) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 3.02 + 0.14 + 2.3


5.4600 ohms
Safety margin =25% 1.25 x 5.46

= 6.83 Ohms
Burden (VA) = I2 * R
= 1^2*6.825 = 6.83 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 34

II.11 115KV Bus Section Non-Directional OC & EF Protection

System details:
CB interrupting capacity: 40000 A
Voltage Level: 115.0 KV

CT details:
115KV Bus Section
CB A603
CT core detail :
CT core: CT603.B2.C2
CT Ratio :2000-1600-1200-1000-800-600/1A
Adopted Tap: 2000 A
CT sec.: 1A
Rct: 3.20 Ohms
Class: TPS
Ual 1600.00 V
Ial 15 mA at Ual
Kssc: 20.00
K: 8.33 (Ual/(Kssc*K*(RCT+Rb))
Rb: 6.40 ohms
TRF: 2
SC Rating: 40000A

Connected Burden:(Refer : Annexure-B)


Burden: (VA / I2) Ohms
51 relay Type: Micom P142 51 Relay Resistance: =(0.15/1^2)
Micom P142 BURDEN 0.150 VA 0.1500 ohms
51N relay Type: Micom P142 51N Relay Resistance: =(0.2/1^2)
Micom P142 BURDEN 0.200 VA 0.2000 ohms

Total Burden 0.3500 ohms

Secondary circuit cable details

Distance : (120% of two Way) Sec.cable resistance: =Distance x res./mtr


(CT to BS protn. Panel) 250.00 mtr =(250) x 0.0035
Cable resistance(ohms/mtr): (Assumed) 0.875 ohms
6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

Relay Manufacturer Formula

For Definite time/IDMTL overcurrent & earth fault protection

Phase fault- Ual ≥ Ifp/2 * (Rct +RL + Rrp + Rb) -1

Earth Fault- Ual ≥ Ifn/2 * (Rct +2RL+ Rrp + Rrn + Rb) -2


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 35

Ual = CT knee point voltage (rms)


Ifp,Ifn = Maximum prospective CT secondary Phase fault & Earth fault current or 31 times
I> setting(whichever is lower)(amps)
Isp,Isn, = Stage 2 and 3 setting /fault setting
Is = CT secondary current corresponding to Switchgear interupting Current
Rct = CT secondary winding resistance at 75oC
Rrp = Impedance of Relay phase current input
Rrn = Impedance of Relay neutral current input
RL = Cable lead resistance at 75oC
Rb = Other burdens connected to the CT core

Fault current (external fault)


Fault Current for external fault = CB interrupting capacity
= 40000 A
Isccmax (Flt.current/CT ratio) = (40000 / (2000/1)) = 20.000 A

Calculation for Relay manufacturer formula

For Definite time/IDMTL overcurrent & earth fault protection


Phase fault- Ual = Ifp/2 * (Rct +RL/2 + Rrp + Rb)
= (20/2)*(3.2+0.4375+0.15)
= 37.88 V -1

Earth Fault- Ual = Ifn/2 * (Rct +RL+ Rrp + Rrn + Rb)


= (20/2)*(3.2+0.875+0.15+0.2)
= 44.25 V -2

Result 2 is higher than other Results, hence CT sizing is calculated based on result 2.

Safety margin =25% = 1.25 x 44.25


Ual ≥ 56 V

Since the available Ual(1600V) is higher than required Ual(56V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev - A


Sheet 36
II.12 115KV Bus Section Metering

CT details:

115KV Bus Section


CB A603
CT core: CT603.B1.C2
CT Ratio:2000-1600-1200-1000-800-600/1A
Adopted Tap: 2000 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 25 VA
ISF: <5
Rct: 7.21 Ohms
Connected Burden:

Ammeter 1.0000 VA Ammeter Burden: (VA/I2) = (1 /1^2)


(Assumed) 1.0000 ohms

Bay Control Unit(REC670) 0.02 VA BCU Burden: = (0.02 /1^2)


(Refer Annexure-B) (Assumed) 0.0200 ohms

Total burden:
= (1 + 0.02)
= 1.0200 ohms
Rct = 7.21 Ohms
Secondary circuit cable details

Distance (120% of 2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr
(CT to BS LCC Panel ) (Assumed) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 1.02 + 0.14 + 7.21


8.3700 ohms
Safety margin =25% 1.25 x 8.37

= 10.46 Ohms
Burden (VA) = I2 * R
= 1^2*10.4625 = 10.46 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 37
II.13 115KV Bus Metering

CT details:

115KV BUS

CT core: CT.2B.
CT Ratio: 2000-1600-1200-1000-800-600/1A
Adopted Tap: 2000 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 25 VA
ISF: <5
Rct: 7.21 Ohms
Connected Burden:

Ammeter 1.0000 VA Ammeter Burden: (VA/I2) = (1 /1^2)


(Assumed) 1.0000 ohms

Bay Control Unit(REC670) 0.02 VA BCU Burden: = (0.02 /1^2)


(Refer Annexure-B) (Assumed) 0.0200 ohms

Total burden:
= (1 + 0.02)
= 1.0200 ohms
Rct = 7.21 Ohms
Secondary circuit cable details

Distance (120% of 2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr
(CT to BS LCC panel) (Assumed) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 1.02 + 0.14 + 7.21


8.3700 ohms
Safety margin =25% 1.25 x 8.37

= 10.46 Ohms
Burden (VA) = I2 * R
= 1^2*10.4625 = 10.46 VA

The offered CT is suitable since the Burden is 25VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 38

II.14 115KV Bus Coupler -1 & 2 Non-Directional OC & EF Protection

System details:

CB interrupting capacity: 40000 A


Voltage Level: 115.0 KV

CT details:
115KV Bus Coupler
CB A601 & A602
CT core detail :
CT core: CT602.1A.C2 & CT601.1C.C2

CT Ratio :2000-1600-1200-1000-800-600/1A
Adopted Tap: 2000 A
CT sec.: 1A
Rct: 3.20 Ohms
Class: TPS
Ual 1600.00 V
Ial 15.00 mA at Ual
Kssc: 20.00
K: 8.33 (Ual/(Kssc*K*(RCT+Rb))
Rb: 6.40 ohms
TRF: 2
SC Rating: 40000A

Connected Burden:(Refer : Annexure-B) Burden: (VA / I2) Ohms


51 relay Type: Micom P142 51 Relay Resistance: =(0.15/1^2)
Micom P142 BURDEN 0.150 VA 0.1500 ohms
51N relay Type: Micom P142 51N Relay Resistance: =(0.2/1^2)
Micom P142 BURDEN 0.200 VA 0.2000 ohms

Total Burden 0.3500 ohms


Secondary circuit cable details
Distance : (120% of two Way) Sec.cable resistance: =Distance x res./mtr
(CT to BC protn. Panel) 250.00 mtr =(250) x 0.0035
Cable resistance(ohms/mtr): (Assumed) 0.875 ohms
6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

Relay Manufacturer Formula

For Definite time/IDMTL overcurrent & earth fault protection

Phase fault- Ual ≥ Ifp/2 * (Rct +RL/2 + Rrp + Rb) -1

Earth Fault- Ual ≥ Ifn/2 * (Rct +RL+ Rrp + Rrn + Rb) -2

Ual = CT knee point voltage (rms)


Ifp,Ifn = Maximum prospective CT secondary Phase fault & Earth fault current or 31 times
I> setting(whichever is lower)(amps)
Isp,Isn, = Stage 2 and 3 setting /fault setting
Is = CT secondary current corresponding to Switchgear interupting Current
Rct = CT secondary winding resistance at 75oC
Rrp = Impedance of Relay phase current input
Rrn = Impedance of Relay neutral current input
RL = Cable lead resistance at 75oC
Rb = Other burdens connected to the CT core
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 39
Fault current (external fault)
Fault Current for external fault = CB interrupting capacity
= 40000 A
Isccmax (Flt.current/CT ratio) = (40000 / (2000/1)) = 20.000 A

Calculation for Relay manufacurer formula

For Definite time/IDMTL overcurrent & earth fault protection


Phase fault- Ual = Ifp/2 * (Rct +RL/2 + Rrp + Rb)
= (20/2)*(3.2+0.4375+0.15)
= 37.88 V -1

Earth Fault- Ual = Ifn/2 * (Rct +RL+ Rrp + Rrn + Rb)


= (20/2)*(3.2+0.875+0.15+0.2)
= 44.25 V -2

Result 4 is higher than other Results, hence CT sizing is calculated based on result 4.

Safety margin =25% = 1.25x 44.25


Ual ≥ 56 V

Since the available Ual(1600V) is higher than required Ual(56V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 40
II.15 115KV Bus Coupler -1 & 2 Metering

CT details:

115KV Bus Coupler


CB A601 & A602
CT core: CT601.2C.C2 & CT602.2A.C2
CT Ratio:2000-1600-1200-1000-800-600/1A
Adopted Tap: 2000 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 25 VA
ISF: <5
Rct: 7.21 Ohms
Connected Burden:

Ammeter 1.0000 VA Ammeter Burden: (VA/I2) = (1 /1^2)


(Assumed) 1.0000 ohms

Bay Control Unit(REC670) 0.02 VA BCU Burden: = (0.02 /1^2)


(Refer Annexure-B) (Assumed) 0.0200 ohms

Total burden:
= (1 + 0.02)
= 1.0200 ohms
Rct = 7.21 Ohms
Secondary circuit cable details

Distance (120% of 2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr
(CT to BC LCC Panel ) (Assumed) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 1.02 + 0.14 + 7.21


8.3700 ohms
Safety margin =25% 1.25 x 8.37

= 10.46 Ohms
Burden (VA) = I2 * R
= 1^2*10.4625 = 10.46 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.56 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 41

II.16 115KV Bus Bar Differential Protection

System details:
CB interrupting capacity: 40000 A

Voltage Level: 115 KV

CT details:
All 115KV CBs
CT Ratio:2000-1600-1200-1000-800-600/1A
Adopted Tap: 1600 A
CT sec.: 1A
Rct: 3.200 ohms
Class: TPS
Ual: 1600.0 V
Ial: 15.00 mA @ Ual
Kssc: 25 (40000/1600)
K: 6.67 (Ual/(Kssc*Isn*(RCT+Rb))
Rb: 6.40 Ohms
TRF: 2
SC Rating: 40000 A

Connected Burden

Bus Differential (REB500): 0.02 VA REB Burden: (VA / I2) = (0.02 /1^2)
(87B) 0.0200 Ohms

Secondary circuit cable details

Distance (120 % of 2 way): 250.00 mtr Sec. Cable resistance: =Distance x res./mtr
(CT to BB panel) (Assumed) = (250 x0.0035)
0.875 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.00350

Ual Calculation formula

As per manufacturer:

The CT Accuracy Limiting Voltage (Ual) shall meet the following requirements.
I fmax x
(Rct )
I sn
A) Ual1 ≥ 0 .5 x x + Rl + SR/Ir^2 + Rb
I
pn

I op
(Rct )
x I sn
B) Ual2 ≥ 5 .0 x x + Rl + SR/Ir^2 + Rb
I
pn
Ual1 = Accuracy Limit Voltage for Bus Bar Differential Protection

Ual2 = Accuracy Limit Voltage for Breaker Failure Protection

I f max = Maximum primary fundamental frequency current on the bus bar

I op = The primary operate value


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 42
Isn = Rated CT secondary current

Ipn = Rated CT primary current (Adopted Tap)

Ir = Protection terminal rated current

Rct = CT secondary winding resistance at 75oC

Rl = Cable lead resistance (Both ways total) at 75oC

SR = burden of REB670 a current input channel (VA)

Rb = Other Burdens connected to the CT

Fault current:

Fault Current = 40000 A

Ifmax (Flt. current/CT ratio) = (40000 x 1 / 1600) = 25.0 A

CT Ual Calculation for case A

I fmax x
(Rct )
I sn
Ual1 ≥ 0 .5 x x + Rl + SR/Ir^2 + Rb
I
pn

= 0.5 x 25 x (3.2 + 0.875 + 0.02)

= 51.19 V -1

I op x I
Ual2 ≥ 5 .0 x
sn
x Rct ( + Rl + SR/Ir^2 + Rb )
I
pn
= 5 x 25 x (3.2 + 0.4375 + 0.02)

= 511.88 V -2

Result 2 is higher than other Results and CT sizing is calculated based on result 2.

Safety margin =25% = 1.25 x 511.88


Ual ≥ 640 V

Since the available Ual(1600V) is higher than required Ual (640V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


sheet 43
II.17 115/13.8KV Transformer T601 , T602 & T603 Set-1 REF Protection (LV Side)

System details:
CB interrupting capacity: 25000 A
Voltage Level: 13.80 KV

Transformer details:
115/13.8KV Transformer T601 , T602 & T603
Capacity: 67.00 MVA
Voltage: 13.80 KV

CT details:
115/13.8KV Transformer T601 , T602 & T603
CB A604 , A605 & A607
CT core: NBCT-1 & T021-T023.C2

CT Ratio: 4000/1A

Adopted Tap: 4000 A


CT sec.: 1A
Rct: 14.00 Ohms
Class: TPS
Ual: 500 V
Ial: 30 mA
Kssc: 6.25 (25000/4000)
K 1.90 (Ual/(Kssc*K*(RCT+Rb))
Rb: 28.00 (2 x Rct) Ohms
TRF: 1.2
SC Rating: 25000 A

Connected equipment detail (Assumed)


MCAG relay Burden: 1.00 Ohms Metrosil current:I (RMS) = 0.52*(sqrt(2)*Vi / C)1/β
(Relay setting 10% to 40%) 0.10 A C= 900
Metrosil External β= 0.25 1/β =4
Max. no of parallel CTs 4

Secondary circuit cable details


Distance (2 Way): Sec. Cable resistance: (Rl) =Distance x res./mtr
CT to set1 panel 250.00 mtr = 0.0035 x 250
Cable resistance(ohms/mtr): 0.875 ohms
6 sq mm 0.0035

Formula for CT sizing


Ual > 2 * VsA MCAG formula
VsA = (VA/Ir) + Ir Rsr MCAG formula
Vs' > If * (Rs + Rp) MCAG formula
Rsr {Vs' - (VA/Ir)}/Ir MCAG formula
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 44
Ual = excitation limiting E.M.F
VsA = Actual voltage setting
Vs' , Vs = Minimum required stability voltage
If , Ifs = Maximum secondary through-fault current.
Rsr = Series resistor setting value
Rs , Rct = CT secondary winding resistance at 75oC
Rp , RL = Cable lead resistance (Both ways total) at 75oC
VA = Relay operating voltage
Ip = Primary fault current (min. effective)
T = CT ratio
Ir = Relay setting current
n = No. of CTs in parallel
IM = Current taken by voltage limiting device at Vs' volts
K = Constant

CT Ual Calculation (Using manufacturer formula)

If 'K' (PTS formula) is considered as 2.0 then PTS formula and the manufacturer formula are same.

Vs' = If * (Rs + Rp)

Max. through fault current of the transformer (lf)


= 25000 / 4000
= 6.25 A
Vs' = If * (Rs + Rp)
= (6.25 x (14 + 0.875)
= 93 V

Relay operating voltage (VA) = Burden x Relay setting current


The relay will be set at 10% since the setting should be sensitive for REF protn. = 0.10 A
Relay operating voltage = 1 x 0.1 = 0.10 V

Rsr = (93 - 0.1) /0.1 = 929 Ohms

VsA = 0.1 + 929 x 0.1 = 93 Volts

Ual = 2 x VsA = 2 x 93 = 186 V

Safety margin =25% = 1.25 x 186


Ual ≥ 233 V

The available Ual is 500V and the CT sizing is OK.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 45
Minimum Fault sensitivity
The offered CT Im = 30 mA
Ip = T * (Ir + nIm + IM)
Ir = 0.10 A
Im at Ual x VsA
Im at Vs' =
Ual
= 30 x 93 / 500
= 0.006 A
Total Im for 4 CTs = 4 x 0.006
nIm = 0.02400 A
IM at Vs = 0.52*(sqrt(2)*Vi / C)1/β
= 0.52 x (SQRT(2) x 93/ 900)^4
= 0.00024 A

Ip = T * (Ir + nIm + IM)


= 4000 x (0.1 + 0.024 + 0.00024)
= 496.0 A

The primary fault sensitivity is only 12.4% of the CT rating and the CT magnetising current has less effect on the
primary fault sensitivity.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 46

II.18 115/13.8KV Transformer T601, T602 & T603 Set-2 Neutral OC Protection

System details:

CB interrupting capacity: 25000 A


Voltage Level: 13.8 KV

CT details:

115/13.8KV Transformer Bushing CT


CB A607, A604 & A605
CT core detail :
CT core: NBCT-2
CT Ratio :4000-3600-3000-2500-2000-1500/1A
Adopted Tap: 2000 A
CT sec.: 1A
Rct: 7.00 Ohms
Class: TPS
Ual 250.00 V
Ial 30 mA at Ual
Kssc: 12.50
K: 0.95 (Ual/(Kssc*K*(RCT+Rb))
Rb: 14.00 ohms
TRF: 2
SC Rating: 25000

Connected Burden:(Refer : Annexure-B) Burden: (VA / I2) Ohms


(VA/I

51G relay Type: Micom P142 51G2 Relay Resistance: =(0.15/1^2)


Micom P142 BURDEN 0.150 VA 0.1500 ohms
TFR Resistance: =(1/1^2)
TFR Burden 1.000 VA(Assumed) 1.0000 ohms

Total Burden 1.1500 ohms

Secondary circuit cable details


Distance : (120% of two Way) Sec.cable resistance: =Distance x res./mtr
(Trf Bushing CT to set-2 protn. Panel) 170.00 mtr(Approx.) =(170) x 0.0035
Cable resistance(ohms/mtr): 0.595 ohms
6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

For Definite time/IDMTL overcurrent protection

Phase fault- Ual ≥ Ifp/2 * (Rct +RL + Rrp + Rb) -1

Ual = CT knee point voltage (rms)


Ifp = Maxumum prospective CT secondary Phase fault & Earth fault current (amps)
o
Rct = CT secondary winding resistance at 75 C
Rrp = Impedance of Relay phase current input
o
RL = Cable lead resistance at 75 C
Rb = Other burdens connected to the CT core
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 47
Fault current (external fault)
Fault Current for external fault = CB interrupting capacity
= 25000 A
Isccmax (Flt.current/CT ratio) = (25000 / (2000/1)) = 12.500 A

For Definite time/IDMTL overcurrent protection


Phase fault- Ual = Ifp/2 * (Rct +RL + Rrp + Rb)
= (12.5/2)*(7+0.2975+1.15)
= 52.80 V -1

As per PTS, Ual is selected for fault level =25000A and 20% margin
Ual= If (Rct +2RL+ Rrp + Rrn + Rb)
= 12.5(7+0.595+1.15)
= 109.3125 -2

Result 2 is higher than other Results, hence CT sizing is calculated based on result 2.

Safety margin =20% = 1.2 x 109.3125


Ual ≥ 132 V

Since the available Ual(250V) is higher than required Ual(132V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 48
II.19 Metering for 115KV Transformer T601, T602 & T603 Bushing CT (HV Side)

CT details:

115/13.8KV Transformer T601, T602 & T603


CB A607, A605 & A604
CT core: HV-BCT 1 (RYB)
CT Ratio: 600-500-400-300/1A
Adopted Tap: 600 A
CT sec.: 1A
Class: 0.2
TRF 2
Burden: 11.5000 VA
ISF: <5
Rct: 3.00 Ohms
Connected Burden:

PQM 1.00 VA
(Assumed)

PQM Burden: (VA/I2) = (1 /1^2)

1.0000 ohms

Secondary circuit cable details

Distance (120% of 2 way): 250.00 mtr Sec. Cable resistance: =Distance x res./mtr
(Trf Bushing CT to AMR panel) = 250 x 0.0035
0.875 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035 Rct = 3.00 Ohms

Total Burden: = 1 + 0.875 + 3


= 4.8750 ohms

Safety margin =25% 1.25 x 4.875

= 6.09 Ohms

Burden (VA) = I2 * R
= 1^2*6.09375 = 6.09 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 49

II.20 115/13.8KV Transformer T601, T602 & T603 Set-2 Directional OC & EF Protection(LV side)

System details:

CB interrupting capacity: 25000 A


Voltage Level: 13.8 KV

CT details:

132/13.8KV Transformer T601, T602& T603


CB A301,A302 & A303
CT core detail :
CT core: T011-013.C2
CT Ratio : 4000-3600/1A
Adopted Tap: 4000 A
CT sec.: 1A
Rct: 14.00 Ohms
Class: TPS
Ual 500.00 V
Ial 30 mA at Ual
Kssc: 6.25
K: 1.90 (Ual/(Kssc*K*(RCT+Rb))
Rb: 28.00 ohms
TRF: 1.2

Connected Burden:(Refer : Annexure-B) (VA / I2) Ohms


Burden:(VA/I

67/67N relay Type: Micom P142 67 Burden: =(0.15/1^2)


(Assumed) 67 BURDEN 0.150 VA 0.1500 ohms
67N Burden: =(0.2/1^2)
67N BURDEN 0.200 VA 0.2000 ohms
TFR Burden: =(1/1^2)
TFR BURDEN 1.000 VA(Assumed) 1.0000 ohms

Total Burden 1.3500 ohms

Secondary circuit cable details

Distance : (120% of two Way) Sec.cable resistance: =Distance x res./mtr


(CT to Trf Set-2 protn. Panel) 160.00 mtr =(160) x 0.0035
Cable resistance(ohms/mtr): (Assumed) 0.560 ohms
6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

Relay Manufacturer Formula

For Definite time/IDMTL overcurrent & earth fault protection

Phase fault- Ual ≥ Ifp/2 * (Rct +RL + Rrp + Rb) -1

Earth Fault- Ual ≥ Ifn/2 * (Rct +2RL+ Rrp + Rrn + Rb) -2

For Instantaneous overcurrent & earth fault protection


Phase fault- Ual ≥ Isp * (Rct +RL + Rrp + Rb) -3

Earth Fault- Ual ≥ Isn * (Rct +2RL+ Rrp + Rrn + Rb) -4


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 50

PTS Formula

For Definite time/IDMTL overcurrent & earth fault protection

Phase fault- Ual ≥ Is * (Rct +RL + Rr + Rb) -5

Earth Fault- Ual ≥ Is * (Rct +2RL + Rr + Rb) -6

For Instantaneous overcurrent & earth fault protection

Phase fault- Ual ≥ Is*2 * (Rct +RL + Rr + Rb) -7

Earth Fault- Ual ≥ Is*2 * (Rct +2RL + Rr + Rb) -8

Ual = CT knee point voltage (rms)


Ifp,Ifn = Maxumum prospective CT secondary Phase fault & Earth fault current (amps)
Isp,Isn, = Maxumum prospective CT secondary Phase fault & Earth fault current or 31 times
I> setting(whichever is lower)(amps)
Is = CT secondary current corresponding to Switchgear interupting Current
Rct = CT secondary winding resistance at 75oC
Rrp = Impedance of Relay phase current input
Rrn = Impedance of Relay neutral current input
RL = Cable lead resistance at 75oC
Rb = Other burdens connected to the CT core

Fault current (external fault)


Fault Current for external fault = CB interrupting capacity
= 25000 A
Isccmax (Flt.current/CT ratio) = (25000 / (4000/1)) = 6.250 A

Calculation for Relay manufacurer formula

For Definite time/IDMTL overcurrent & earth fault protection


Phase fault- Ual = Ifp/2 * (Rct +RL + Rrp + Rb)
= (6.25/2)*(14+0.28+0.15+1)
= 48.22 V -1

Earth Fault- Ual = Ifn/2 * (Rct +2RL+ Rrp + Rrn + Rb)


= (6.25/2)*(14+0.56+0.15+0.2+1)
= 49.72 V -2

For Instaneous Over-Current and earth fault Protection

Phase fault- Ual = Isp * (Rct +RL + Rrp + Rb)


Isp = 6.3 A
= 6.25*(14+0.28+0.15+1)
= 96.44 V -3

Earth Fault- Ual = Isn * (Rct +2RL+ Rrp + Rrn + Rb)


Isn = 6.3 A
= 6.25*(14+0.56+0.15+0.2+1)
99.44 V -4
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 51
Calculation for PTS formula

For Definite time/IDMTL overcurrent & earth fault protection


Phase fault- Ual = Is * (Rct +RL + Rr + Rb)
= (6.25)*(14+0.28+0.15+1)
= 96.44 V -5

Earth Fault- Ual = Is * (Rct +2RL + Rr + Rb)


= (6.25)*(14+0.56+0.15+1)
= 98.19 V -6

For Instaneous Over-Current and earth fault Protection

Phase fault- Ual = Is*2 * (Rct +RL + Rr + Rb)


= (6.25)*2*(14+0.28+0.15+1)
= 192.88 V -7

Earth Fault- Ual = Is*2 * (Rct +2RL + Rr + Rb)


= (6.25)*2*(14+0.56+0.15+1)
196.38 V -8

Result 8 is higher than other Results, hence CT sizing is calculated based on result 8.

Safety margin =20% = 1.2 x 196.375


Ual ≥ 236 V

Since the available Ual(500V) is higher than required Ual(236V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 52
II.21 115/13.8KV Transformer T601 , T602 & T603 Set-1 Differential Protection (LV Side)

Power Transformer detail:


115/13.8KV Transformer T601,T602 & T603 Rated Pri. Current (LV) = MVA
Capacity: 67 MVA sqrt(3) x KV
Base MVA 50 MVA
Voltage: 13.8 KV = 1000 x 67
Impedance: 22.00 % at 50 MVA (sqrt(3) x 13.8)
CB inter. capacity: 25000 A
= 2804A
CT details:
115/13.8KV Transformer T601,T602 & T603 Corresponding Sec. Current = 2804 x 1
CB A301,A302 & A303 4000
CT core: T021-T023.C1
CT Ratio: 4000-3600/1A = 0.710 A

Adopted Tap: 4000 A


CT sec.: 1A
Rct: 14.00 Ohms
Class: TPS
Ual: 500 V
Ial: 30.0 mA at Ual
Kssc: 6.25 (25000/4000)
K: 1.90 (Ual/(Kssc*Isn*(RCT+Rb))
Rb: 28.00 (2 x Rct) Ohms
TRF: 1.2
SC Rating: 25000A

Connected Burden:
Burden details: (Annexure-B)
RET670 Burden: 0.150 VA RET670 Burden: (VA/I2) = (0.15 /1^2)
= 0.1500 Ohms

Secondary circuit cable details


Distance (120% of 2 way): 250.00 mtr
(CT to Trf Set-1 Protn Panel ) (Assumed) Sec. Cable resistance: =Distance x res./mtr
= 250 x 0.0035
Cable resistance(ohms/mtr): = 0.875 ohms
6 sq mm 0.0035

Ual Calculation formula


RET670 formula (Annexure-B) Ual1 = 30* Int * (Isn/Ipn)*(Rct + RL + Sr/Ir2 + Rb)

Ual2 = 2* Itf * (Isn/Ipn)*(Rct + RL + Sr/Ir2 + Rb)

As per PTS Ual3 = K * Isn*(Rct + Rl + Rr + Rb)

Ual1,Ual2,Ual3 = Accuracy limiting voltage


Isn,Ir = Rated CT secondary current(A)
Rr = Relay total Resistance
Rct = CT secondary winding resistance at 75oC
Rl = Cable lead resistance (Both ways total) at 75oC
K = Constant as per manufacturer recommendation
Ipn = Rated primary CT current(A)
Int = Rated primary current of the transformer(A)
Itf = Max. primary fundamental frequency current that passes main two CTs and transformer(A)
Sr = Relay Burden
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]


Rev -A
Sheet 53
Since the manufacturer formula and PTS formula are same, we consider manufacturer formula for Ual calculation

CT Ual Calculation
100 x Times of Tr. Full load current
Maximum through fault current =
Tr.% Impedance

Transformer % imp at 67 MVA = Tr. % Imp. at given base MVA x New Base MVA
Given base MVA

= (22 * 67 / 50)
= 29.50
Maximum through fault current = (100/29.50) x (67MVA) / (sqrt(3) x 13.8KV)
= 14182 A

Ual1 = 30* Int * (Isn/Ipn)*(Rct + RL + Sr/Ir2 )


= (0.71 x 30)* (14+0.875+0.15)
= 320.03 V -1

Ual2 = 2* Itf * (Isn/Ipn)*(Rct + RL + Sr/Ir2 )


= (14182.1 x 2)1/4000* (14+0.875+0.15)
= 106.54 V -2

Result 1 is higher than other Results and CT sizing is calculated based on result 1.

Safety margin= 25% = 1.25 x 320.033


Ual ≥ 401 V

Since the available Ual(500V) is higher than required Ual(401V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 54
II.22 AVR for115/13.8KV Transformer T601, T602 & T603 (LV side)

CT details:

115/13.8KV Transformer Bushing CT


CB A604 , A605 & A607
CT core: LV-BCT 1 (Yph.)
CT Ratio: 4000-3600-3000-2500-2000-1500/1A
Adopted Tap: 4000 A
CT sec.: 1A
Class: 0.5
TRF 2
Burden: 30 VA
ISF: <5
Rct: 15.00 Ohms
Connected Burden:

AVR (TAPCON 260) 0.02 VA

BCU Burden: (VA/I2) = (0.02 /1^2)

0.0200 ohms

Secondary circuit cable details

Distance (120% of 2 way): 40.00 mtr Sec. Cable resistance: =Distance x res./mtr
(Trf Bushing CT to AVR panel) = 40 x 0.0035
0.140 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035 Rct = 15.00 Ohms

Total Burden: = 0.02 + 0.14 + 15


= 15.1600 ohms

Safety margin =25% 1.25 x 15.16

= 18.95 Ohms

Burden (VA) = I2 * R
= 1^2*18.95 = 18.95 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 55
II.23 Metering for 115KV Transformer T601, T602 & T603 Bushing CT(LV side)

CT details:

115/13.8KV Transformer Bushing CT


CB A604 , A605 & A607
CT core: LV-BCT 2 (RYB)
CT Ratio: 4000-3600-3000-2500-2000-1500/1A
Adopted Tap: 4000 A
CT sec.: 1A
Class: 0.2
TRF 2
Burden: 30 VA
ISF: <5
Rct: 15.00 Ohms
Connected Burden:

2
Revenue Meter 1.00 VA Revenue Meter Burden: (VA/I ) = (1 /1^2)
(Assumed) 1.0000 ohms
2
DPDM 1.00 VA DPDM Burden: (VA/I ) = (1 /1^2)
(Assumed) 1.0000 ohms
BCU(REF615) 0.01 VA BCU Burden: (VA/I2) = (0.01 /1^2)
(Assumed) 0.0100 ohms
Total burden: (BCU+RM+MFM )
= 2.0100 ohms
Secondary circuit cable details

Distance (120% OF 2 way): 250.00 mtr Sec. Cable resistance: =Distance x res./mtr
(Trf Bushing CT to AMR panel) (Assumed) = 250 x 0.0035
0.875 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035 Rct = 15.00 Ohms

Total Burden: = 2.01 + 0.875 + 15


= 17.8850 ohms

Safety margin =25% 1.25 x 17.885

= 22.36 Ohms

Burden (VA) = I2 * R
= 1^2*22.35625 = 22.36 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 56
II.24 13.8kV Out Going Feeder Non-Dir.OC & EF protection
System details:
CB interrupting capacity: 25000 A
Voltage Level: 13.8 KV

CT details:
13.8kV Out Going Feeder
Bus-1 B314-B315-B316-B317-B318-B319-B320-B321-B322-B323-B324
Bus-2 B332-B333-B334-B335-B336-B337-B338-B339-B340-B341-B342-B344
Bus-3 B351-B352- B353-B354- B355-B356- B357-B358-B359-B360-B361
CT core detail : CT core: CT314.B.C1-CT361.B.C1
CT Ratio: 600-400/1A
Adopted Tap: 600 A
CT sec.: 1A
Rct: 2.10 Ohms
Class: TPS
Ual 320.00 V
Ial 40.00
Kssc: 41.67
K: 1.22 (Ual/(Kssc*Isn*(RCT+Rb))
Rb: 4.200 Ohms
TRF: 1.2
SC Rating: 25000A

Connected Burden(Annexure:B) Burden: (VA / I2) Ohms


BCU (50/51/50N/51N) relay Type: (Assumed) REF 615 BCU (50/51/50N/51N )Relay Resistance: =(0.1/1^2)
REF 615 BURDEN 0.100 VA 0.1000 ohms

Total. Resistance:
Secondary circuit cable details 0.1000 ohms
Distance : (120% of two Way)
Sec.cable resistance: =Distance x res./mtr
(Inside Swgr panel) 15.00 mtr =(15) x 0.0035

Cable resistance(ohms/mtr): 0.053 ohms


6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

Manufacturer Formula

For IDMT over current & earth fault protection

Ual = Ikmax. Isn (Rct + RL + Rr+ Rb)/Ipn -1

For Instantaneous definite time over current & earth fault protection

Ual = 1.5.Iop . Isn (Rct + Rl + Rr + Rb)/Ipn -2

Ikmax = Maximum primary current for close-in CT current


Ual = CT knee point voltage (rms)
Iop = The Primary short circuit current
Ip = The Primary Current
Isn = CT secondary current corresponding to Switchgear interupting Current
Rct = CT secondary winding resistance at 75oC
Rrp = Impedance of Relay phase current input
Rrn = Impedance of Relay neutral current input
RL = Cable lead resistance at 75oC
Rb = Other burdens connected to the CT core
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 57
Fault current (external fault)

Fault Current for external fault = CB interrupting capacity


= 25000 A
Isccmax (Flt.current/CT ratio) = (25000 / (600/1)) = 41.670 A

Manufacturer formula

For IDMT over current & earth fault protection

Ual= Ikmax. Isn (Rct + RL + Rr + Rb)/Ipn

= 25000*1*(2.1+0.0525+0.1)/600
= 93.85 V -1

For Instantaneous definite time over current & earth fault protection

Ual= 1.5.Iop . Isn (Rct + Rl + Rr +Rb)/Ipn

= 1.5*25000*1*(2.1+0.0525+0.1))/600
considerinfg Iop value equal the fault level
= 140.78 V -2

Result 2 is higher than other Results, hence CT sizing is calculated based on result 2.

Safety margin =25% = 1.25 x 140.78125

Ual ≥ 176 V

Since the available Ual(320V) is higher than required Ual(176V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 58
II.25 Metering for 13.8KV Outgoing Feeder

CT details:

13.8KV Outgoing Feeder


BUS-1 B314-B315- B316-B317- B318-B319- B320-B321-B322-B323-B324
BUS-2 B332-B-333-B334-B335-B336-B337-B338-B339-B340-B341-B342-B344
BUS-3 B351-B352-B353-B354-B355-B356-B357-B358-B359-B360-B361
CT core: CT314.B.C2-CT361.B.C2
CT Ratio: 600-400/1A
Adopted Tap: 600 A
CT sec.: 1A
Class: 0.5
TRF 1.2
Burden: 10 VA
ISF: <5
Rct: 2.10 Ohms
Connected Burden:

IED REF615 (Assumed) 0.10 VA IED REF615 Burden: = (0.1 /1^2)


(Refer Annexure-B) 0.1000 ohms
Digital Power Demand Meter (Assumed) 1.00 VA DPDM Burden: = (1 /1^2)
1.0000 ohms
Rct = 2.1000 ohms

Secondary circuit cable details

Distance (10% of 2 way): 15.00 mtr Sec. Cable resistance: =Distance x res./mtr
(Inside SWGR panel) (Assumed) = 15 x 0.0035
0.053 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 0.1 + 0.0525+1+2.1


3.2525 ohms
Safety margin =25% 1.25 x 3.2525

= 4.07 Ohms
Burden (VA) = I2 * R
= 1^2*4.065625 = 4.07 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 59
II.26 13.8KV Station service transformer Feeder Non-Dir OC & EF protection

System details:
CB interrupting capacity: 25000 A
Voltage Level: 13.8 KV

CT details:
13.8kV Station Service transformer
C.B B325 & B331
CT core detail : CT core: CT325.B.C1, CT331.B.C1
CT Ratio: 600-400/1A
Adopted Tap: 400 A
CT sec.: 1A
Rct: 1.40 Ohms
Class: TPS
Ual 320.00 V
Ial 40.00
Kssc: 62.50
K: 1.22 (Ual/(Kssc*Isn*(RCT+Rb))
Rb: 2.800 Ohms
TRF: 1.2
SC Rating: 25000A

Connected Burden(Annexure:B) 2
Burden: (VA / I ) Ohms
BCU (50/51/50N/51N) relay Type: (Assumed) REF 615 BCU (50/51/50N/51N) Relay Resistance: =(0.1/1^2)
REF 615 BURDEN 0.100 VA 0.1000 ohms

Total. Resistance:
0.1000 ohms
Secondary circuit cable details
Distance : (120% of two Way) Sec.cable resistance: =Distance x res./mtr

(Inside Swgr panel) 15.00 mtr =(15) x 0.0035

Cable resistance(ohms/mtr): 0.053 ohms


6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

Manufacturer Formula
For IDMTL over current & earth fault protection

Ual = Ikmax. Isn (Rct + RL + Rr+ Rb)/Ipn -1

For Instantaneous definite time over current & earth fault protection

Ual = 1.5.Iop . Isn (Rct + Rl + Rr + Rb)/Ipn -2

Ikmax = Maximum primary current for close-in CT current


Ual = CT knee point voltage (rms)
Iop = The Primary short circuit current
Ip = The Primary Current
Isn = CT secondary current corresponding to Switchgear interupting Current
o
Rct = CT secondary winding resistance at 75 C
Rrp = Impedance of Relay phase current input
Rrn = Impedance of Relay neutral current input
RL = Cable lead resistance at 75oC
Rb = Other burdens connected to the CT core
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 60
Fault current (external fault)

Fault Current for external fault = CB interrupting capacity


= 25000 A
Isccmax (Flt.current/CT ratio) = (25000 / (400/1)) = 62.500 A

Manufacturer formula

For IDMTL over current & earth fault protection

Ual= Ikmax. Isn (Rct + RL + Rr + Rb)/Ipn


= 25000*1*(1.4+0.0525+0.1)/400
= 97.03 V -1

For Instantaneous definite time over current & earth fault protection

Ual= 1.5.Iop . Isn (Rct + Rl + Rr +Rb)/Ipn

= 1.5*25000*1*(1.4+0.0525+0.1))/400
considerinfg Iop value equal the fault level
= 145.55 V -2

Result 2 is higher than other Results, hence CT sizing is calculated based on result 2.

Safety margin =25% = 1.25 x 145.546875

Ual ≥ 182 V

Since the available Ual(320V) is higher than required Ual(182V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 61
II.27 Metering for 13.8KV Station Transformer Feeder

CT details:

13.8KV Station Transformer Feeder


CB B325 & B331
CT core: CT325.B.C2, CT331.B.C2
CT Ratio: 100-50/1A
Adopted Tap: 50 A
CT sec.: 1A
Class: 0.2
TRF 1.2
Burden: 7.5000 VA
ISF: <5
Rct: 1.00 Ohms
Connected Burden:

IED REF615 0.10 VA IED REF615 Burden: = (0.1 /1^2)


(Refer Annexure-B) Assumed 0.1000 ohms

Digital Power Demand Meter 1.00 VA Assumed DPDM Burden: = (1 /1^2)


1.0000 ohms
Revenue Meter 1.00 VA Assumed RM Burden: = (1 /1^2)
1.0000 ohms
Rct = 1.0000 ohms

Secondary circuit cable details

Distance (120% of 2 way): 15.00 mtr Sec. Cable resistance: =Distance x res./mtr
(Inside SWGR panel) = 15 x 0.0035
0.053 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 0.1 + 0.0525+1+1+1


3.1525 ohms
Safety margin =25% 1.25 x 3.1525

= 3.94 Ohms
Burden (VA) = I2 * R
= 1^2*3.940625 = 3.94 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 62
II.28 13.8KV Capacitor Bank Main Feeder-1 Non -Directional O/C & E/F protection

System details:

CB interrupting capacity: 25000 A


Voltage Level: 13.80 KV

CT details:

13.8kV Capacitor Bank Main Feeder-1,2&3


CB B313,B343 & B362
CT core: CT313.B.C1, CT344.B.C1, CT362.B.C1

CT Ratio:1200-600-400/1A

Adopted Tap: 600 A


CT sec.: 1A
Rct: 2.10 Ohms
Class: TPS
Ual 320 V
Ial: 40 mA
Kssc: 41.67 (25000/600)
K 1.22 (Ual/(Kssc*K*(RCT+Rb))
Rb: 4.20 (2 x Rct) Ohms
TRF: 1.20
SC Rating: 25000 A

Connected Burden Ohmic Burden= (VA/I2)


51S/FDR relay (MicomP142): 0.15 VA 51S/FDR (Micom P142) Burden: = (0.15 /1^2)
0.1500 ohms
50S/FDR relay (RXIG22): 0.005 VA 50S/FDR (RXIG22) Burden: = (0.005 /1^2)
0.0050 ohms
50NS/FDR relay (RXIG22): 0.005 VA 50NS/FDR (RXIG22) Burden: = (0.005 /1^2)
0.0050 ohms
51N/FDR relay(MicomP142): 0.20 VA 51NS/FDR (Micom P142) Burden: = (0.2 /1^2)
0.2000 ohms
Total. Burden: (51S/FDR+50S/FDR+50NS/FDR+51NS/FDR)
0.3600 ohms
Secondary circuit cable details

Distance (2 Way): Sec.cable resistance: =Distance x res./mtr


CT to Relay 250.00 mtr =250 x 0.0035
Cable resistance(ohms/mtr): (Assumed) 0.875 ohms
6 sq mm 0.0035

Formula for CT sizing


General formula Ual = IF x (Rct + 2Rl + Rt)

Ual = Excitation limiting E.M.F

IF = Maximum secondary symmetrical fault current

Rct = CT secondary winding resistance at 75oC

2Rl = Cable lead resistance (Both ways total) at 75oC

Rt = Total secondary eqpt. resistance


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 63
CT Ual Calculation

IF = (25000 / 600) = 41.67 A

Ual = IF x (Rct + 2Rl + Rt)


= (41.67 x (2.1 + 0.875 + 0.36))
= 139 V
Safety margin =25% = 1.25 x 139
Ual ≥ 174 V

Ual for Transformer protection = 174 V

The available Ual is 320V and the CT sizing is OK.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji115/13.8KV Substation No.5 Rev -A


Sheet 64
II.29 Metering for 13.8KV Capacitor Feeder

CT details:

13.8KV Capacitor Feeder


CB B313, B344 & B362
CT core: CT313.B.C2, CT344.B.C2, CT362.B.C2
CT Ratio: 1200-600-400/1A
Adopted Tap: 600 A
CT sec.: 1A
Class: 0.5
TRF 1.2
Burden: 10 VA
ISF: <5
Rct: 2.10 Ohms
Connected Burden:

BCU REF615 0.10 VA BCU Burden: = ( /1^2)


(Refer Annexure-B) 0.1000 ohms
Digital Power Demand Meter 1.00 VA DPDM Burden: = ( /1^2)
(Assumed) 1.0000 ohms
Rct = 2.1000 ohms

Secondary circuit cable details

Distance (120% of 2 way): 10.00 mtr Sec. Cable resistance: =Distance x res./mtr
(Inside SWGR panel) (Assumed) = 10 x 0.0035
0.035 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 0.1 + 0.035+1+2.1


3.2350 ohms
Safety margin =25% 1.25 x 3.235

= 4.04 Ohms
Burden (VA) = I2 * R
= 1^2*4.04375 = 4.04 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [[ 1 + 0.004 (75 - 20) ]]
Rev -A
Sheet 65
II.30 13.8KV Bus Tie Non-Dir OC & EF protection

System details:
CB interrupting capacity: 25000 A
Voltage Level: 13.8 KV

CT details:
13.8kV Bus Tie
CB A304 & A305
CT core detail : CT core: CT304.B1.C1, CT305.B2.C1
CT Ratio: 4000-3600/1A
Adopted Tap: 4000 A
CT sec.: 1A
Rct: 14.00 Ohms
Class: TPS
Ual 1400.00 V
Ial 30.00 mA
Kssc: 6.25
K: 5.33 (Ual/(Kssc*Isn*(RCT+Rb))
Rb: 28.000 Ohms
TRF: 1.2
SC Rating: 25000A

Connected Burden(Annexure:B) Burden: (VA / I2) Ohms

BCU 50/51/50N/51N relay Type: REF 615 BCU 50/51/50N/51N Relay Resistan =(0.1/1^2)
REF 615 BURDEN 0.100 VA 0.1000 ohms

Total. Resistance:
0.1000 ohms
Secondary circuit cable details
Distance : (120% of two Way) Sec.cable resistance: =Distance x res./mtr
(Inside Swgr panel) 15.00 mtr =(15) x 0.0035
(Assumed)
Cable resistance(ohms/mtr): 0.053 ohms
6.0 sq mm 0.0035 ohms

CALCULATION FOR THE MINIMUM REQUIRED KNEE-POINT VOLTAGE

For IDMT over current & earth fault protection

Eal > Ealreq = Ikmax. Isn (Rct + RL + Sr/Ir2)/Ipn -1

For Instantaneous definite time over current & earth fault protection

Eal > Ealreq = 1.5.Iop . Isn (Rct + Rl + SR/Ir2)/Ipn -2

Eal = CT Rated Secondary Exitation e.m.f


Ealreq = CT Required Secondary Exitation e.m.f
Isn = Rated Secondary CT current
Ipn = Rated primary CT current
Iop = primary operating CT current
Rct = CT secondary winding resistance at 75oC
RL = Cable lead resistance at 75oC
Ir =relay rated currrent
SR = Relay rated burden
Ikmax = Maximum primary current for close-in CT current
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5


6 [1 + 0 . 0 0 4 ( 7 5 - 2 0 ) ]
Rev -A
Sheet 66
Fault current (external fault)
Fault Current for external fault = CB interrupting capacity
= 25000 A
If (Flt.current/CT ratio) = (25000 / (4000/1)) = 6.250 A

For IDMTL over current & earth fault protection

Ealreq = Ikmax. Isn (Rct + RL + Sr/Ir2)/Ipn


= 25000*1*(14+0.0525+(0.1/(1*1)))/4000
= 88.45 V -1

For Instantaneous definite time over current & earth fault protection

Ealreq = 1.5*Iop* Isn (Rct + RL + Sr/Ir2)/Ipn


= 1.5*25000*1*(14+0.0525+(0.1/(1*1)))/4000
considerinfg Iop value equal the fault level
= 132.68 V -2

Result 2 is higher than other Results, hence CT sizing is calculated based on result 2.

Safety margin =20% = 1.25 x 132.6796875


Ual ≥ 166 V

Since the available Ual (1400V) is higher than the required Ual (166V), the CT is suitably sized.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 67
II.31 Metering for 13.8KV Bus Tie

CT details:

13.8KV Bus Tie


CB A304 & A305
CT core: CT304.B1.C2-CT305.B2.C2
CT Ratio: 4000-3600/1A
Adopted Tap: 4000 A
CT sec.: 1A
Class: 0.5
TRF 1.2
Burden: 20 VA
ISF: <5
Rct : 14.00 Ohms
Connected Burden:

BCU REF615 0.100 VA BCU Burden: = (0.1 /1^2)


(Refer Annexure-B) 0.1000 ohms
Ammeter 1.000 VA Ammeter Burden: = (1 /1^2)
(Assumed) 1.0000 ohms
Rct = 14.0000 ohms

Secondary circuit cable details

Distance (2 way): 10.00 mtr Sec. Cable resistance: =Distance x res./mtr


(Inside SWGR panel) (Assumed) = 10 x 0.0035
0.035 ohms
Cable resistance(ohms/mtr):
6 sq mm 0.0035

Total Burden: = 0.1 + 0.035+1+14


15.1350 ohms
Safety margin =25% 1.25 x 15.135

= 18.92 Ohms
Burden (VA) = I2 * R
= 1^2*18.91875 = 18.92 VA

The offered CT is suitable since the Total Burden is between 25%-100% of the CT burden.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 68
II.32 13.8KV Bus Bar Differential Protection

System details:
CB interrupting capacity: 25000 A
Voltage Level: 13.80 KV

CT details:
13.8KV Buses
BUS-1, BUS-2 & BUS-3

CT Ratio: 4000/1A

Adopted Tap: 4000 A


CT sec.: 1A
Rct: 14.00 Ohms
Class: TPS
Ual: 500 V
Ial: 30 mA
Kssc: 6.25 (25000/4000)
K 1.90 (Ual/(Kssc*K*(RCT+Rb))
Rb: 28.00 (2 x Rct) Ohms
TRF: 1.2
SC Rating: 25000 A

Connected equipment detail


(Assumed)
MCAG relay Burden: 1.00 Ohms Metrosil current:I (RMS) = 0.52*(sqrt(2)*Vi / C)1/β
(Relay setting 20% to 80%) 0.20 A C= 900
Metrosil External β= 0.25 1/β =4
Max. no of parallel CTs 15

Secondary circuit cable details

Distance (2 Way): Sec. Cable resistance: (Rl) =Distance x res./mtr


CT to set1 panel 300.00 mtr = 0.0035 x 300
Cable resistance(ohms/mtr): 1.050 ohms
6 sq mm 0.0035

Formula for CT sizing

Ual > 2 * VsA MCAG formula


VsA = (VA/Ir) + Ir Rsr MCAG formula
Vs' > If * (Rs + Rp) MCAG formula
Rsr {Vs' - (VA/Ir)}/Ir MCAG formula
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 69
Ual = excitation limiting E.M.F
VsA = Actual voltage setting
Vs' , Vs = Minimum required stability voltage
If , Ifs = Maximum secondary through-fault current.
Rsr = Series resistor setting value
Rs , Rct = CT secondary winding resistance at 75oC
Rp , RL = Cable lead resistance (Both ways total) at 75oC
VA = Relay operating voltage
Ip = Primary fault current (min. effective)
T = CT ratio
Ir = Relay setting current
n = No. of CTs in parallel
IM = Current taken by voltage limiting device at Vs' volts
K = Constant

CT Ual Calculation (Using manufacturer formula)

If 'K' (PTS formula) is considered as 2.0 then PTS formula and the manufacturer formula are same.

Vs' = If * (Rs + Rp)


Max. through fault current of the transformer (lf)
= 25000 / 4000
= 6.25 A
Vs' = If * (Rs + Rp)
= (6.25 x (14 + 1.05)
= 95 V

Relay operating voltage (VA) = Burden x Relay setting current


The relay will be set at 20% since the setting should be sensitive for BB protn. = 0.20 A
The relay will be set at 20% since
1 x 0.2
the setting should be=sensitive
0.20for
V REF protn.

Rsr = (95 - 0.2) /0.2 = 474 Ohms

VsA = 0.2 + 474 x 0.2 = 95 Volts

Ual = 2 x VsA = 2 x 95 = 190 V

Safety margin =20% = 1.2 x 190


Ual ≥ 228 V

The available Ual is 500V and the CT sizing is OK.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 70
Minimum Fault sensitivity
The offered CT Im = 30 mA
Ip = T * (Ir + nIm + IM)
Ir = 0.20 A
Im at Ual x VsA
Im at Vs' =
Ual
= 30 x 95 / 500
= 0.006 A
Total Im for 15 CTs = 15 x 0.006
nIm = 0.09000 A
IM at Vs = 0.52*(sqrt(2)*Vi / C)1/β
= 0.52 x (SQRT(2) x 95/ 900)^4
= 0.00026 A

Ip = T * (Ir + nIm + IM)


= 4000 x (0.2 + 0.09 + 0.00026)
= 1160.0 A

The primary fault sensitivity is only 30.2% of the CT rating and the CT magnetising current has less effect on the
primary fault sensitivity.
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 71
III POTENTIAL TRANSFORMER

III.1 115KV Khafji-2 Line

PT details:

Applicable PTs: PT606

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Bay Control Unit(REC670) 1 0.02 VA (Assumed) 0.02 VA
Line Distance Proten Relay -P545 1 0.15 VA 0.15 VA
Fuse Failure Relay- 98-RXBA4 3 2.00 VA 6.00 VA
Synchronising Check Relay-25 1 1.00 VA (Assumed) 1.00 VA
Volt meter 1 1.00 VA (Assumed) 1.00 VA
DPDM 1 1.00 VA (Assumed) 1.00 VA
TOTAL BURDEN 9.17 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Distance Proten Relay -21-7SD522 1 0.100 VA 0.10 VA
Fuse Failure Relay- 98-RXBA4 3 2.00 VA 6.00 VA
TOTAL BURDEN 6.10 VA

Burden on core-1 & core-2 = 9.17 + 6.1


= 15.270 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x Lead resistance per meter = 250mtr x 0.00854
= 2.135 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
15.27x15.27x2.135
=
66.4 x 66.4
= 0.1129 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 15.27 + 0.1129
= 15.383 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 72

III.2 115KV Safaniyah Line

PT details:

Applicable PTs: PT609

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Bay Control Unit(REC670) 1 0.02 VA (Assumed) 0.02 VA
Line Distance Proten Relay -REL670 1 0.25 VA 0.25 VA
Fuse Failure Relay- 98-RXBA4 3 2.00 VA 6.00 VA
Synchronising Check Relay-25 1 1.00 VA (Assumed) 1.00 VA
Volt meter 1 1.00 VA (Assumed) 1.00 VA
DPDM 1 1.00 VA (Assumed) 1.00 VA
TOTAL BURDEN 9.27 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Line Distance Proten Relay -P443 1 0.020 VA 0.02 VA
Fuse Failure Relay- 98-RXBA4 3 2.00 VA 6.00 VA
TOTAL BURDEN 6.02 VA

Burden on core-1 & core-2 = 9.27 + 6.02


= 15.290 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x Lead resistance per meter = 250mtr x 0.00854
= 2.135 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
15.29x15.29x2.135
=
66.4 x 66.4
= 0.1132 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 15.29 + 0.1132
= 15.403 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 73

III.3 115KV Spare Lines

PT details:

Applicable PTs: PT608 & PT 611

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Bay Control Unit(REC670) 1 0.02 VA (Assumed) 0.02 VA
Fuse Failure Relay- 98-RXBA4 1 2.00 VA 2.00 VA
Synchronising Check Relay-25 1 1.00 VA (Assumed) 1.00 VA
Volt meter 1 1.00 VA (Assumed) 1.00 VA
DPDM 1 1.00 VA (Assumed) 1.00 VA
TOTAL BURDEN 5.02 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 1 2.00 VA 2.00 VA
TOTAL BURDEN 2.00 VA
Burden on core-1 & core-2 = 5.02 + 2
= 7.020 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x Lead resistance per meter = 250mtr x 0.00854
= 2.135 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
7.02x7.02x2.135
=
66.4 x 66.4
= 0.0239 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 7.02 + 0.0239
= 7.044 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 74

III.4 115KV/13.8KV Transformer T601 , T602 & T603

PT details:

Applicable PTs: PT607 , PT605 & PT604

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Volt meter 1 1.00 VA (Assumed) 1.00 VA
Digital Power Demand Meter 1 1.00 VA (Assumed) 1.00 VA
Synchronising Relay 1 1.00 VA (Assumed) 1.00 VA
VAR meter (ACCS) 1 1.00 VA (Assumed) 1.00 VA
Bay Control Unit(REC670) 1 0.01 VA (Assumed) 0.01 VA
Fuse Failure Relay- 98-RXBA4 1 2.00 VA 2.00 VA
TOTAL BURDEN 6.01 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 1 2.00 VA 2.00 VA
Digital Voltmeter 1 1.00 VA (Assumed) 1.00 VA
TOTAL BURDEN 3.00 VA

Burden on core-1 & core-2 = 6.01 + 3


= 9.010 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x Lead resistance per meter = 250mtr x 0.00854
= 2.135 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


= 2
Burden: (PT secondary phase voltage)
9.01x9.01x2.135
=
66.4 x 66.4
= 0.0393 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 9.01 + 0.0393
= 9.049 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Qatif 115/13.8KV Substation No.2 Rev -A


Sheet 75

III.5 115KV Bus-1A

PT details:

Applicable PTs: PT601A

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 9 2.000 VA(Assumed) 18.00 VA
Control Unit(REC670) 5 0.020 VA(Assumed) 0.10 VA
Synchronising Relay 6 1.000 VA(Assumed) 6.00 VA
TOTAL BURDEN 24.10 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Volt meter 1 1.000 VA(Assumed) 1.00 VA
Power Quality meter 1 1.00 VA (Assumed) 1.00 VA
Control Unit(REC670) 1 0.02 VA (Assumed) 0.02 VA
Fuse Failure Relay- 98-RXBA4 9 2.00 VA 18.00 VA
TOTAL BURDEN 20.02 VA

Burden on core-1 & core-2 = 24.1 + 20.02


= 44.120 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = 1.2xLead length x Lead resistance per meter = 1.2x250mtr x 0.00854
= 2.562 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


= 2
Burden: (PT secondary phase voltage)
44.12x44.12x2.562
=
66.4 x 66.4
= 1.1311 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 44.12 + 1.1311
= 45.251 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 76

III.6 115KV Bus-2A

PT details:

Applicable PTs: PT602A

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 9 2.00 VA 18.00 VA
Control Unit(REC670) 4 0.020 VA(Assumed) 0.08 VA
Synchronising Relay 5 1.000 VA(Assumed) 5.00 VA
TOTAL BURDEN 23.08 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Volt meter 1 1.000 VA(Assumed) 1.00 VA
Power Quality meter 1 1.00 VA (Assumed) 1.00 VA
Control Unit(REC670) 1 0.02 VA (Assumed) 0.02 VA
Fuse Failure Relay- 98-RXBA4 9 2.00 VA 18.00 VA
TOTAL BURDEN 20.02 VA

Burden on core-1 & core-2 = 23.08 + 20.02


= 43.100 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = 1.2xLead length x Lead resistance per meter = 1.2x250mtr x 0.00854
= 2.562 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


= 2
Burden: (PT secondary phase voltage)
43.1x43.1x2.562
=
66.4 x 66.4
= 1.0794 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 43.1 + 1.0794
= 44.179 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 77

III.7 115KV Bus-1C

PT details:

Applicable PTs: PT601C

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 8 2.00 VA 16.00 VA
Control Unit(REC670) 4 0.020 VA(Assumed) 0.08 VA
Synchronising Relay 5 1.000 VA(Assumed) 5.00 VA
TOTAL BURDEN 21.08 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Volt meter 1 1.000 VA(Assumed) 1.00 VA
Control Unit(REC670) 1 0.020 VA(Assumed) 0.02 VA
Fuse Failure Relay- 98-RXBA4 8 2.00 VA 16.00 VA
TOTAL BURDEN 17.02 VA

Burden on core-1 & core-2 = 21.08 + 17.02


= 38.100 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = 1.2xLead length x Lead resistance per meter = 1.2x250mtr x 0.00854
= 2.562 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
38.1x38.1x2.562
=
66.4 x 66.4
= 0.8435 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 38.1 + 0.8435
= 38.944 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 78

III.8 115KV Bus-2C

PT details:

Applicable PTs: PT602C

PT Ratio:

CLASS: 0.5 & 3P


Burden : 100VA (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 8 2.00 VA 16.00 VA
Control Unit(REC670) 3 0.020 VA(Assumed) 0.06 VA
Synchronising Relay 4 1.000 VA(Assumed) 4.00 VA
TOTAL BURDEN 20.06 VA

Connected Burden core-2

Description Qty Unit Burden Total Burden


Volt meter 1 1.000 VA(Assumed) 1.00 VA
Control Unit(REC670) 1 0.020 VA(Assumed) 0.02 VA
Fuse Failure Relay- 98-RXBA4 8 2.00 VA 16.00 VA
TOTAL BURDEN 17.02 VA

Burden on core-1 & core-2 = 20.06 + 17.02


= 37.080 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = 1.2xLead length x Lead resistance per meter = 1.2x250mtr x 0.00854
= 2.562 ohms

Lead (Burden on core-1 & core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
37.08x37.08x2.562
=
66.4 x 66.4
= 0.7990 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 37.08 + 0.799
= 37.879 VA

The offered PT is suitable since the Burden is 200VA.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 79

III.9 13.8KV side of Transformer T601, T602 & T603

PT details:

Applicable PTs: PT301, PT302 & PT303

PT Ratio:

CLASS: 0.2 & 3P


Burden : 18VA/PH (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 3 2.00 VA/Ph 6.00 VA
Revenue Meter 1 1.200 VA/Ph 1.20 VA (Assumed)
Volt meter(CELSA) 2 0.200 VA/Ph 0.40 VA (Assumed)
DPDM(CELSA) 1 0.200 VA/Ph 0.20 VA (Assumed)
Control Unit(REF615) 1 0.070 VA/Ph 0.07 VA (Assumed)
Dir. OC & EF protn. Relay(P142) 1 0.020 VA/Ph 0.02 VA (Assumed)
AVR(TAPCON260) 1 0.34 VA/Ph 0.34 VA
Synchronising Relay (KAVS 100) 1 0.005 VA/Ph 0.01 VA
TOTAL BURDEN 8.24 VA
Burden on core-1 = 8.235
= 8.235 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

Lead (Burden on core-1 )2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
8.235x2.562
=
66.4 x 66.4
= 0.0394 VA

Total Burden =Burden on core-1 + Lead Burden

= 8.235 + 0.0394
= 8.274 VA

The proposed PT is suitable since the Burden is 18VA/PH.

Connected Burden core-2

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 3 2.00 VA/Ph 6.00 VA
TOTAL BURDEN 6.00 VA

Burden on core-2 =6
= 6.000 VA
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter Sheet 80
Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

Lead (Burden on core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
6x6x2.562
=
66.4 x 66.4
= 0.0209 VA

Total Burden =Burden on core-2 + Lead Burden

= 6 + 0.0209
= 6.021 VA

The proposed PT is suitable since the Burden is 18VA/ph.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 80

III.10 13.8KV Bus-1

PT details:

Applicable PTs: PT304

PT Ratio:

CLASS: 0.2 & 3P


Burden : 18VA /ph each core (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 4 2.00 VA/Ph 8.00 VA
Synchronising Relay (KAVS 100) 2 0.005 VA/Ph 0.01 VA
DPDM(CELSA) 1 0.200 VA/Ph 0.20 VA (Assumed)
Control Unit(REC670) 1 0.03 VA/Ph 0.03 VA (Assumed)
Control Unit(REF615) 2 0.07 VA/Ph 0.14 VA
Under voltage relay Relay(P922) 1 0.007 VA/Ph 0.01 VA
Over voltage relay Relay(P922) 2 0.007 VA/Ph 0.01 VA
ACCS(REC 670) 1 0.033 VA/Ph 0.03 VA
ABTS(REC 670) 1 0.033 VA/Ph 0.03 VA
Volt meter(CELSA) 1 0.200 VA/Ph 0.20 VA (Assumed)
TOTAL BURDEN 8.44 VA
Burden on core-1 = 8.437
= 8.437 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

Lead (Burden on core-1 )2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
8.437x8.437x2.562
=
66.4 x 66.4
= 0.0414 VA

Total Burden =Burden on core-1 + Lead Burden

= 8.437 + 0.0414
= 8.478 VA

The proposed PT is suitable since the Burden is 18VA/ph each core.

Connected Burden core-2

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 3 2.00 VA/Ph 6.00 VA
Revenue Meter 1 1.200 VA/Ph 1.20 VA Assumed
DPDM(CELSA) 12 0.200 VA/Ph 2.40 VA Assumed
BCU REF615 12 0.07 VA/Ph 0.84 VA Assumed
Transient Fault Recorder 1 0.06 VA/Ph 0.06 VA Assumed
TOTAL BURDEN 10.44 VA

Burden on core-2 = 10.44


= 10.440 VA
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter Sheet 82
Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

2
Lead (Burden oncore-2) x Lead resistance
=
Burden: (PT secondary phase voltage)2
10.44x10.44x2.562
=
66.4 x 66.4
= 0.0633 VA

Total Burden =Burden on core-2 + Lead Burden

= 10.44 + 0.0633
= 10.503 VA

The proposed PT is suitable since the Burden is 18VA/PH each core.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 83
III.11 13.8KV Bus-2

PT details:

Applicable PTs: PT305

PT Ratio:

CLASS: 0.2 & 3P


Burden : 18VA/ph (Each core) (Assumed)

Connected Burden Wdg-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 5 2.00 VA/Ph 10.00 VA
Synchronising Relay (KAVS 100) 1 0.005 VA/Ph 0.01 VA
DPDM(CELSA) 12 0.200 VA/Ph 2.40 VA assumed
Control Unit(REC670) 1 0.03 VA/Ph 0.03 VA assumed
Control Unit(REF615) 12 0.070 VA/Ph 0.84 VA assumed
Under voltage relay Relay(P922) 1 0.007 VA/Ph 0.01 VA
Over voltage relay Relay(P922) 2 0.007 VA/Ph 0.01 VA
ACCS(REC670) 1 0.033 VA/Ph 0.03 VA
Revenue Meter 1 1.200 VA/Ph 1.20 VA assumed
TOTAL BURDEN 14.53 VA
Burden on core-1 = 14.532
= 14.532 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

Lead (Burden on core-1 )2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
14.532x14.532x2.562
=
66.4 x 66.4
= 0.1227 VA

Total Burden =Burden on core-1 + Lead Burden

= 14.532 + 0.1227
= 14.655 VA

The proposed PT is suitable since the Burden is 18VA/PH each core.

Connected Burden Wdg-2

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 5 2.00 VA/Ph 10.00 VA
Synchronising Relay (KAVS 100) 2 0.005 VA/Ph 0.01 VA
BCU REF615 2 0.070 VA/Ph 0.14 VA
Transient Fault Recorder 1 0.020 VA/Ph 0.02 VA
Revenue Meter 1 0.200 VA/Ph 0.20 VA
DPDM 1 0.200 VA/Ph 0.20 VA
TOTAL BURDEN 10.57 VA
Burden on core-2 = 10.57
= 10.570 VA
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter Sheet 84
Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

Lead (Burden on core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
10.57x10.57x2.562
=
66.4 x 66.4
= 0.0649 VA

Total Burden =Burden on core-2 + Lead Burden

= 10.57 + 0.0649
= 10.635 VA

The proposed PT is suitable since the Burden is 18VA/ph each core.


Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Sheet 85
III.12 13.8KV Bus-3

PT details:

Applicable PTs: PT306

PT Ratio:

CLASS: 0.2 & 3P


Burden : 18VA/ph (Each core) (Assumed)

Connected Burden core-1

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 4 2.00 VA/Ph 8.00 VA
Synchronising Relay (KAVS 100) 2 0.005 VA/Ph 0.01 VA
Control Unit(REF615) 2 0.070 VA/Ph 0.14 VA assumed
ACCS(REC 670) 1 0.033 VA/Ph 0.03 VA
Volt meter(CELSA) 1 0.200 VA/Ph 0.20 VA assumed
TOTAL BURDEN 8.38 VA
Burden on core-1 = 8.383
= 8.383 VA

Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter


Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

2
Lead (Burden on core-1 ) x Lead resistance
=
Burden: (PT secondary phase voltage)2
8.383x8.383x2.562
=
66.4 x 66.4
= 0.0408 VA

Total Burden =Burden on core-1 + Lead Burden

= 8.383 + 0.0408
= 8.424 VA

The proposed PT is suitable since the Burden is18VA/ph each core .

Connected Burden core-2

Description Qty Unit Burden Total Burden


Fuse Failure Relay- 98-RXBA4 4 2.00 VA/Ph 8.00 VA
Under voltage relay Relay(P142) 1 0.007 VA/Ph 0.01 VA Assumed
Over voltage relay Relay(P142) 2 0.007 VA/Ph 0.01 VA Assumed
DPDM(CELSA) 13 0.200 VA/Ph 2.60 VA Assumed
Control Unit(REC670) 1 0.033 VA/Ph 0.03 VA Assumed
Transient Fault Recorder 1 0.060 VA/Ph 0.06 VA Assumed
BCU REF615 13 0.070 VA/Ph 0.91 VA Assumed
TOTAL BURDEN 11.62 VA
Burden on core-1 = 11.624
= 11.624 VA
Document Title: CT & PT sizing Calculation Doc no: EE-237393

Substation: Khafji 115/13.8KV Substation No.5 Rev -A


Lead resistance for 2.5 sq.mm copper cable = 0.00854 ohms/meter Sheet 86
Lead resistance: = Lead length x1.2x Lead resistance per meter = 250mtr x1.2x 0.00854
= 2.562 ohms

Lead (Burden on core-2)2 x Lead resistance


=
Burden: (PT secondary phase voltage)2
11.624x11.624x2.562
=
66.4 x 66.4
= 0.0785 VA

Total Burden =Burden on core-1 & core-2 + Lead Burden

= 11.624 + 0.0785
= 11.703 VA

The proposed PT is suitable since the Burden is 18VA/ph each core.


ANNEXURE-A

(PTS Relay and Metering One Line Diagram)


ANNEXURE-B

(Back-up data for relay & Meter Burden detail)


ANNEXURE-C

(Consolidated CT Parameters)
Consolidated CT Parameter for Khafji 115/13.8KV S/S #5

Adopted Burden Rct Rb


sl.no. CT REF CT Core CT Ratio CT Sec Purpose Class CB Inter (A) Ual (V) Ial (mA) Kssc K TRF
Ratio (VA) (Ohms) (Ohms)

115KV GIS
Core-1 Line Set-1 Protn.
B CT data need to be confirmed during site visit.
Core-2 Line Set-2 Protn.
Line Feeder
1 B Core-1 1600-1200-1000-800-600/1A 1000 1A Line Metering 0.5, ISF <5 - - 12.5 VA - - - - - 2
Safaniyah PP
Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
F
Core-2 2000-1600-1200-1000-800-600//1A 1600 1A Spare TPS 40000 1600 - 15.00 3.20 20 8.33 6.4 2

Core-1 1600-1200-1000-800-600/1A 1000 1A Line Set-1 Protn. TPS 40000 1000 - 24 2.00 40 4.17 4 2
B
Core-2 1600-1200-1000-800-600/1A 1000 1A Line Set-2 Protn. TPS 40000 1000 - 24 2.00 40 4.17 4 2
Line Feeder
2 B Core-1 1600-1200-1000-800-600/1A 1000 1A Line Metering 0.5, ISF <5 - - 12.5 VA - - - - - 2
Khafji S/S # 2
Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
F
Core-2 2000-1600-1200-1000-800-600//1A 1600 1A Spare TPS 40000 1600 - 15.00 3.20 20 8.33 6.4 2

Core-1 1600-1200-1000-800-600/1A 1000 1A Line Set-1 Protn. TPS 40000 1000 - 24 2.00 40 4.17 4 2
B
Core-2 1600-1200-1000-800-600/1A 1000 1A Line Set-2 Protn. TPS 40000 1000 - 24 2.00 40 4.17 4 2
Spare Line
3 B Core-1 1600-1200-1000-800-600/1A 1000 1A Line Metering 0.5, ISF <5 - - 12.5 VA - - - - - 2
Feeder
Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
F
Core-2 2000-1600-1200-1000-800-600//1A 1600 1A Spare TPS 40000 1600 - 15.00 3.20 20 8.33 6.4 2

Core-1 1600-1200-1000-800-600/1A 600 1A Trf Differential Protn. TPS 40000 600 - 40 1.20 66.67 2.5 2.4 2
B
115/13.8kV Core-2 1600-1200-1000-800-600/1A 600 1A Trf Non Dir. OC & EF Protn. TPS 40000 600 - 40 1.20 66.67 2.5 2.4 2
4 Transformer B Core-1 1600-1200-1000-800-600/1A 600 1A Trf Metering 0.5, ISF <5 - - 7.5 VA - - - - - 2
Feeder Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
F
Core-2 2000-1600-1200-1000-800-600//1A 1600 1A Spare TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2

Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
1A
Core-2 2000-1600-1200-1000-800-600//1A 2000 1A BS Metering 0.5, ISF <5 - - 25 VA - - - - 2
5 Bus Section
Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
1B
Core-2 2000-1600-1200-1000-800-600//1A 2000 1A BS Non-Dir OC & EF Protn. TPS 40000 1600 - 15.00 3.20 20 8.33 6.4 2

6 Bus 2B Core-1 2000-1600-1200-1000-800-600//1A 2000 1A Bus Metering 0.5, ISF <5 - - 25 VA - - - - - 2

1A/1 Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
C Core-2 2000-1600-1200-1000-800-600//1A 2000 1A BC Non-Dir OC & EF Protn. TPS 40000 1600 - 15 3.20 20 8.33 6.4 2
7 Bus Coupler
2A/2 Core-1 2000-1600-1200-1000-800-600//1A 1600 1A BB Protn TPS 40000 1600 - 15.00 3.20 25 6.67 6.4 2
C Core-2 2000-1600-1200-1000-800-600//1A 2000 1A BC Metering 0.5, ISF <5 - - 25 VA - - - - - 2

Note:
As per PTS Relay and Metering One Line Diagram, Drawing # ET-906823, Sheet 03 of 07, the GIS MRCT Ratio for 115KV Spare Feeders are as follows: 2000-1500-1250-1000-600/1A. But we recommend the ratio as per other GIS bays CT as mentioned above.
Consolidated CT Parameter for Khafji 115/13.8KV S/S #5

Adopted Burden Rct Rb


sl.no. CT REF CT Ratio CT Sec Purpose Class CB Inter (A) Ual (V) Ial (mA) Kssc K TRF
Ratio (VA) (Ohms) (Ohms)

115/13.8KV Transformer Bushing CT

1 HVBCT-1 600-500-400-300/1A 600 /1A 1A Metering 0.2, ISF <5 - - 11.5 VA - - - - - 2

2 NBCT-1 4000/1A 4000 /1A 1A 87 REF TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2
3 NBCT-2 4000-3600-3000-2500-2000-1500/1A 2000 /1A 1A 51G TPS 25000 250 - 30 7.0 12.5 0.95 14 2

4 LVBCT-1 4000-3600-3000-2500-2000-1500/1A 4000 /1A 1A AVR (Bϕ only) 0.5, ISF <5 - - 30 VA - - - - - 2
5 LVBCT-2 4000-3600-3000-2500-2000-1500/1A 4000 /1A 1A Metering 0.2, ISF <5 - 30 VA - - - - - 2
Consolidated CT Parameter for Khafji 115/13.8KV S/S #5

Adopted Burden Rct Rb


Sl.No CT REF CT Core CT Ratio CT Sec Purpose Class CB Inter (A) Ual (V) Ial (mA) Kssc K TRF
Ratio (VA) (Ohms) (Ohms)

13.8KV Incomer
Core-1 4000/1A 4000 /1A 1A 87B1 ,87B2 & 87B3 TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2
Cable Side
Core-2 4000-3600/1A 4000 /1A 1A 67/67N TPS 25000 500 - 30 14.0 6.25 1.9 28 2
1
Core-1 4000-3600/1A 4000 /1A 1A 87T TPS 25000 500 - 30 14.0 6.25 1.9 28 2
Bus Side
Core-2 4000/1A 4000 /1A 1A 87REF TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2

13.8KV Outgoing Feeder


Core-1 600-400/1A 600 /1A 1A 50/51 & 50N/51N TPS 25000 320 - 40 2.1 41.67 1.22 4.2 1.2
Bus Side
2 Core-2 600-400/1A 600 /1A 1A Metering 0.5,ISF <5 - - 10 VA - - - - - 1.2
Cable Side Core-1 4000/1A 4000 /1A 1A 87B1 ,87B2 & 87B3 TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2

13.8KV Outgoing CAPACITOR Feeder


Core-1 1200-600-400/1A 600 /1A 1A 50/51 & 50N/51N TPS 25000 320 - 40 2.1 41.67 1.22 4.2 2
Bus Side
3 Core-2 1200-600-400/1A 600 /1A 1A Metering 0.5,ISF <5 - - 10 VA - - - - - 2
Cable Side Core-1 4000/1A 4000 /1A 1A 87B1 ,87B2 & 87B3 TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2

13.8KV Bus tie


Core-1 4000/1A 4000 /1A 1A 87B1 ,87B2 & 87B3 TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2
Bus-1 Side
Core-2 4000-3600/1A 4000 /1A 1A Metering 0.5,ISF <5 - - 20 VA - - - - - 1.2
4
Core-1 4000/1A 4000 /1A 1A 87B1 ,87B2 & 87B3 TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2
Bus-2 Side
Core-2 4000-3600/1A 4000 /1A 1A 50/51 & 50N/51N TPS 25000 1400 - 30 14.0 6.25 5.33 28 1.2

13.8KV Outgoing STATION TRANSFORMER Feeder


Core-1 600-400/1A 400 /1A 1A 50/51 & 50N/51N TPS 25000 320 - 40 1.4 62.5 1.22 2.8 1.2
Bus Side
5 Core-2 100-50/1A 50 /1A 1A Metering 0.2,ISF <5 - - 7.5 VA - - - - - 1.2
Cable Side Core-1 4000/1A 4000 /1A 1A 87B1 ,87B2 & 87B3 TPS 25000 500 - 30 14.0 6.25 1.9 28 1.2