To Discom

Net meter,CT,PT etc specification


as per Discom regulation

Isolation Transformer,Min.150 KVA,


415V/415V,Delta/Star(WTE Swgr.side),

ACB Min. 1600A with Sync.Check

415 V AC WTE SWGR.,Min.1600A

ACB with Sync.Check

DG Set, Min. 500KVA, 415VAC

02 nos.ACB Min. M
1600A Feeders to
ECO Park loads(typ.)
LT loads as per requirement (Typical)

110V DCDB

Min.40AH Ni-
Cd,110V Battery

110V DCFB-1&2(typ.)

Electrical SLD for proposed WTE plant at Badarpur Eco park.

(For tender purpose only)

General Notes:

1. The selection of LT outgoing feeders (Draw out type) shall be as indicated here under:

(i) Up to 400A-MCCB, (ii) Above 400A-Breaker

2. Control & protection supplies for all switchgears/DBS/Control Panels shall be fed from two different sources/different sections.

3. Spares shall be provided as per requirements of technical specifications.