Professional Documents
Culture Documents
1.operation manual for 40ST Series of water-cooled stars water chillers 40ST系列螺杆式水冷机组操作手册-EN
1.operation manual for 40ST Series of water-cooled stars water chillers 40ST系列螺杆式水冷机组操作手册-EN
Company Introduction-----------------------------------------------------P2
Product Introduction-----------------------------------------------------P3-4
ChapterⅠ Installation--------------------------------------------------P5-17
ChapterⅡ Operation--------------------------------------------------P18-35
3.1 Summarize
3.2 Maintenance
Operator should be completely familiar with the operation manual and other
necessary files before initial installation and debugging of the water cooled
screw-type chiller. Then read this manual to realize the relevant installation,
debugging, maintenance and requirement. Thereby to assure the installation is
correct and the unit is operated in the optimum condition.
1
Company Introduction:
Establish in 1992,HStars group is a foreign Investment company which has
been professionally manufacturing Central Air-conditioning Equipments,
Industrial Chillers, S&T heat exchangers, Air handling unit, Fan coil units and
whole refrigerating system solution.
The products are widely used in Hotel, Shopping mall, Electronic fields,
Pharmacy, Plastic Injections industry…
From the beginning, we have been focusing on the product’s quality to meet
customer’s requirements. Meanwhile, Stars has been creating the
value-added service. Our system aim at the energy saving, clean and green.
Today, Stars yearly turnover has achieved more than 15 million U.S dollars
and has been one of the biggest AC equipments suppliers in China;
furthermore, our marketing network has covered all Chinese territory.
Based on more than 10 years professional experiences, we get many awards,
such as ISO9001:2000, CE(PED) certificate. Moreover, we also got high
praise from our clients “most reliable manufacturer” many times
Stars will go on moving forwards based on continuous research&
developments to build “Comfortable Environment” for all the end-users. We
would like to join with your hand for our prosperous future.
More information about us, please visit our website: www.chillermaker.com &
www.hstars.net.
Water cooled screw-type low temperature chiller units with heat recovery is a
central air conditioning which take the water as the coolant medium, its
condenser and evaporator adopt the special high efficiency heat tube,
compared to the same cooling capacity air cooled chiller, its more compact,
efficient and small size. The noise is very low because the unit does not has
the condensate blower. The heat recover can reclaim the heat while the unit
operate, and used to get the hot water and heating.
We have developed technique, sophisticated technologies and advanced
testing equipment of manufacturing the water cooled screw-type low
temperature chiller units with heat recovery. Superadd the international
well-chosen components, so that to guarantee the unit operate steady and
high efficient.
2
Product Introduction
1. Unit name plate---generally place on the left side of the control box
2. System Part
Compressor
Equipped with semi-hermetic screw-type compressor with double screw,
differential-pressure feeding for lubrication system, and pump for lubricating oil
not needed. Piston valve applying for multi-stage capacity control, motor of two
poles three phases’ induction motor. Use refrigerant cooling, ensuring correct
driving direction of screw, equipped with protection for wrong phase.
Discharging gas temperature overload protection is set to prevent discharging
gas temperature too high.
Condenser
It applies the tube condenser, the heat exchanger tube is the copper tube, the
end cap is demountable,avail to demount the end cap to clean the copper tube.
The fusible plug on the condenser is to gurantee the cooling system operate
safely.
Evaporator
Dry type shell and tube evaporators and heat exchangers apply inner finned
copper tube, and are equipped with refrigerant distribution device so as to
distribute refrigerant homogeneously to heat exchanging tubes and improve
thermal efficiency. As to chillers with multi-compressors, each compressor has
its evaporator and condenser, and these three units comprise of separate
refrigerating system. As a result of its structure, normally water ways of two
evaporators are connected, but refrigerating circuits still work separately.
Evaporators are covered with heat preservation material to prevent loss of
cooling capacity.
3
Use imported thermal expansion valve to ensure reliability of performance of
refrigeration system, accuracy and long service life of expansion valve.
Heat recovers
Heat recover utilize the effect of refrigerant steam exchange the heat with the
water, transform the exhaust heat to available hot water. So that to achieve
energy-saving. This was called “desuperheater” or “wate heater” in America, is
a kind of commendatory energy-saving equipment, and more and more people
like it now.
Components of system
Main components of refrigerating system and control system are adopt
imported elements, which is featured with high quality and performance, so as
to ensure accuracy and reliability of refrigerating system.
4
Chapter One Installation
5
not use the forklift to lift or move the unit.
1.2.1.3. If do not have the vertical lifting equipment, horizontal scroll method
can be used, use the jack to lift a certain high, put the roller under the skid
base, take down the skid after the unit was rolled to the position. The strength
can only be put on the frame or the skid by using this method.
skid when haulage or swing, remove the skid unless the unit is in
1.2.2 Placement
After the unit is in right position, remove the skid, adjust horizon by bubble cell,
fix the bottom of the chiller to the base by using anchor bolt. Suggest to put a
15~20 cm anti-vibration cushion between the bottom of the chiller and the
base.
The chiller shall be installed in basement, ground floor or special machinery
room. If install in the building is necessary, make sure the floor can endure the
running weight of the chiller, reinforce the floor board if needed. Meanwhile,
check the floor if it is horizontal. We suggest to set the spring snubber
according to the running weight.
6
1.3 Pipes connection
Do the construction of the water pipes after the chiller has been installed, or
connect the arranged water pipes to the evaporator and condenser.
COOLING TOWER
TEMPERATER
1.3.2.2. The water supply line should be short as soon as possible, the
specification of the pipe should be decided by the water pump’s effective head,
lines flow and rate, but not by the specification of the joint.
1.3.2.3. Drain and exhaust joint should be installed on the condenser pipes.
1.3.2.4. The direction of the condenser water pipe can be changed according
8
to user’s request, please notice the below items:
* Affirm the right clapboard position, using new grommet.
* The temperature of the chilled water, flow measuring equipment need to
be redispose.
* When dismounting the end cap of the water chamber, binding the bolt
need to follow the order: lightly bind the first bolt, then bind the second bolt on
the opposite of the first one, then follow this way bind the third one, then bind
the fourth one which is on the opposite of third one. After binding the first lap
bolts, follow this way bind all the bolts until they accord with the corresponding
torque of tableⅠ(Notice: Do not bind the bolt to its ultimate torque when the
first lap binding. That will make the surface of the flange tilting and water leak.
Use the torque spanner, adjust the torque to one-third of the ultimate torque
when binding the first lap)
TableⅠ Recommend ultimate torque of binding bolt
Seal with rubber flat gasket
Bolt spec.
Min. torque Max. torque
M10 16 24
M12 45 68
M16 95 122
M20 142 210
water outlet pipes, the bypass pipe for rinse and maintenance
9
Ⅲ Chilled water pipe diagram
GATE VALVE
FLOW SWITCH
CLAPPER VALVE
1.3.3.2. Expansion tank should be installed at 1-1.5 meters over the top of the
chiller, the volume of the tank is approximately one tenth of the whole system’s
water capacity.
1.3.3.3. There are drain connection on the evaporator, 3/4 inch brass ball valve
has been installed to the outlet.
1.3.3.4. Avoid any vertical movement of the water pipes, set a manual or
automatic exhaust valve between the high place of the pipe and expansion
tank.
1.3.3.5. Set a thermometer and pressure gauge on the straight length of inlet
and outlet pipes, instead of installed near the syphon. To drain the relict water,
each low place should set a discharge joint. Between the inlet and outlet of the
evaporator, there should be a by-pass line, convenient to rinse, maintenance
and adjust flow.
The flexible joint can reduce the transfer of the vibration.
1.3.3.6. Heat preservation treatment is necessary to the chilled water pipes
and expansion tank, the valve joints should remain some place for
maintenance.
1.3.3.7. Enwind the insulating course after airtightness test, to avoid heat
transfer and sweating, the insulating course should has dampproof
confinement.
10
1.3.4 Connection of the heat reclaimer pipe (Only for the chiller with the
heat recover)
S C H E M A T IC D IA G R A M O F D O M E S T IC W A T E R M O U N T IN G
H E A T R E C O V E R Y
W A TE R
S U P P LY
W A TE R TA N K
LE G E N D S
P U M P TE M P E R A TE R
D A M P IN G J O IN T P R E S S U R E C O N TR O LLE R
G A TE V A LV E S TO P C O C K
FLO A T V A LV E
C LA P P E R V A LV E
1.3.4.1. Insulation cabinet and circulating water pump need to be installed due
to water inertance, storage volume and usage amount. Keep the storage water
remain the request temperature(50°C-60°C)
1.3.4.2. Insulating course should added to the tank, so as to reduce thermal
热 水 系 统 安 装 说 明
losses. The volume should be designed by the constructional force by the field,
power of the
1.由unit,
于 考 usage
虑 水 amount
惯 性 , 刹and
间 使user’s
用 量 request.
及 储 存 量
,系 统 必 须 配 置 保 温 箱 及
循 环 水 泵 ,让 储 存 热 水 经 常 保 持 在 要 求 温 度 (50 C-60 C)。
1.3.4.3. In order to keep the hot water’s temperature, circulating water pump
need to be long term loading and equipped pump.
1.3.4.4. Two or more pressure water pump need to be installed to the hot
water system, its flow and head are designed to requirement, and controlled by
the pressure controller within 24hours
1.3.4.5. This system supply user ultra-low-cost hot water, but the hot water
flow is determined by the usage of the chiller and season. User should retrofit
another hot water assistant system when use this system, parallel-use.
11
1.3.5 Connection of the water source heat
The cool and heat switching is the water line switching, the connection is as
below:
EXPANSION
TANK
AIR CONDITIONING
END EQUIPMENT
TEMPERATER FLOWSWITCH
P
MANOMETER
BY-PASS VALVE
GATE VALVE
GROUNDWATER
PIPING
FILTER PUMP DAMPINGJOINT SWITCHING BOX FOR HOT AND COLD WATER PIPELINE
12
the same line tube with those conducting wire that larger than 24V.
Caution: In order to avoid loss of life. Cut off the electricity supply
1.5.2 Control
The core control part of central air conditioner of the water cooled screw-type
chiller with heat recovery applies the micro-computer control touch screen
system, the control interface has Chinese and English language, is very
13
convenient to control,
The whole control system is highly automatic with stable performance.
1.5.2.1, Relay is installed in electric cabinet, power line fault indicating lamp,
connection terminal, and programmable controller. The control box type is
depended on different compressor and customer's request.。
1.5.2.2.The front part of electric cabinet is stop switch of control cabinet.
1.5.2.3 . The electric connection must accord with Chinese Standard
Specification, all control circuit is 220 voltages, the connection way refers to
the virable drawing inside.
1.5.2.4, If the chiller is composed by mainframe unit and subsidiary unit, the
communication line between them should apply shrouding wire with protecting
sleeve pipe, and separately laid.
1.5.2.5, All the control output cable in the field should be AC250V-1mm2
(24V).。
1.5.2.6, Notice: Read the electrical connection drawing carefully and connect
all the lines strictly under the connection terminal drawing; The connection line
for the temperature sensor should be three-core shielded
cable(RVVP3×0.5mm2); The connection line for flow switch should be twin
core cable(RVV2×0.5mm2), the point connected to is the point when no water
obtained. The interlocking of cooling tower fan, chilled water pump and cooling
water pump is the parasitic contactor inside the control cabinet. The remote
start and stop can connect two point starting button.
1.5.3 Control accessories interlock
1.5.3.1, The line between the control cabinet and main motor, electrical power
element and pressure temperature and some other transducer components
has been connected. It is very simple for the line connection after the chiller
reached the field. The chiller without cooling tower only have to connect the
chilled, cooling water switch, chilled and cooling water pump gang control lines;
The chiller without cooling tower should connect to cooling water temperature
sensor, chilled and cooling water flow switch, and the gang control line for
chilled and cooling water pumps.
1.5.3.2, No target meter controller was installed to the chilled and cooling
14
water pipes, please install to the outlet of the chilled and cooling water, the
connection for normally open contactor of chilled and cooling water system's
target meter controller should connected to control circuit.
Note: The cabinet may stop the chiller within continuous 10 seconds after it
receive the stop comint, for the tohubohu of the water flow may mistake the
flow switch.
1.5.3.3, Lubricating oil or other grease which will not concrete when it lower
than the outlet temperature of the chilled water should be injected into the
sensing probe installation tube, enabling the heat transfer, the sensor should
insulating and hermetic.
15
1.6. Screw-type water chiller debugging process
Chilled & cooling water Screw unit powe on 12 hours before test running
switch installation and
connection correct
abnormal labnorma
Check the heater and connection check if there are conducting oil
in temperature detector tube of
the inlet &outlet temperature
transducer
Preparation is ready, electrify to preheat
16
1.6.2. Debugging:
Whether running direction is right Debug water pump Run smoothly,Not too much noise
Open auto-exhaust valve, exhaust the air in the system, water pump
operate over 15 mins, let the water system operate smoothly
Press the Stop button and fine the reason Whether the unit is load 25% 50%
if high pressure turns low while low 75%, the relevant solenoid valve is
pressore turns high electrify untill 100%,then disconnect
5
Load-off by 75% 50% 25% Load-off if the temperature achieve The unit can load by 25% 50%
when the temperature is attain anticipant, then load to run 75% when temperatur rise
17
Chapter two Chiller Operation
Preparation of tools:
Refrigeration tools
Numeric VOM
Clip-on ammeter
Absolute gauge or wet bulb universal indicator
500V high megohmmeter(earthometer)
18
outer connections refer to connection drawing(for instance: cycle
water temperature sensor, switch connection, water pump joint
control); check if the terminal screw tighten. Check if every electrical
control device, instrument are correctly installed, inspect if the
electric cabinet is clean.
2.1.1.7 Inspect if outer system of the chiller accord with start condition(eg.
Cooling and chilled water pump is external control or main-interlock,
external control should start the water pump before run the main
unit)
2.1.2 Inspection of the compressor and pipe system
Check if oil at normal level in compressor, the right level is in middle of sight
galss.
2.1.2.1 Check if the compressor solenoid widing tighten and capillarity
damaged.
2.1.2.2 Turn on all refrigerant valves (angle valve around condenser outlet,
compressor suction and exhaust valve).
2.1.2.3 Check if compressor lubricant warm-up over 8 hours, In order to
prevent chilled oil bubbling, electrify the oil heater to warm-up 8 hours
before test run Oil heat time should be longer if the environment
temperature low. It will be difficult to run and bad load, unload when run the
chiller in low temperature, this because the large viscidity of lubricant,
normally the unit will start only when the lowest temperature of the
lubricant reach 23℃.
2.1.2.4 Confirm the compressor connection to be right. shut down the unit
when compressor is turn on, examine instantaneous system pressure
change, make sure exhaust pressure is rising, and return pressure drop.
Contrariwise the compressor is backrun, should adjust compressor
connection order again.
2.1.2.5 Testing run the chiller when main circuit is disconnected, check it load
in right order. While the right order is: put through the power, star AC
conductor pickup 3 minutes after press the Start button, then the Star AC
conductor break short time later, delta conductor pickup, the chiller will run
with the starting value, progressive loading.
19
2.1.3 Inspection of water system
2.1.3.1 Confirm the chilled & cooling water pipe has been rinsed, there is no
sundries in cooling tower, water basin.
2.1.3.2 Confirm the connection of water side pressure gauge and
thermometer, the pressure gauge perpendicularly installed to water pipes.
Installation of thermometer should ensure the thermoelectric probe insert
to the water pipe.
2.1.3.3 Confirm the cooling illed water side switch correctly installed, and the
flow switch is correctly connected to the control cabinet.
2.1.3.4 Start the cooling illed water pump, check the direction of the rotation.
The right rotation direction of water pump is clockwise, otherwise please
recheck connection.
2.1.3.5 Testing run the cooling illed water pump. Check if the hydraulic
steady. And check water pump inlet/outlet pressure gauge, the manometer
reading and difference of inlet/outlet pressure are exiguity. Examine if the
water pump current in rated current, please check whether resistance is
too large if it is too much different from the rated current, please eliminate
system failure until running current satisfy the requirement.
2.1.3.6 Make sure the cooling towre/expasion water tank is clear, the
auto-exhaust valve can automatic exhaust. If it is a manual exhaust valve,
exhaustion all gas in the pipe by turn on the exhaust valve on
chilled/cooling water pipes.
2.1.3.7 Adjust the water flow and make sure the water pressure drop through
the evaporator and condenser can meet the requirement of normally run.
Which means the differential pressure of chilled/cooling water inlet and
outlet should less than 1Mpa.
2.1.3.8 Note: For the low temperature chiller, examine the concentration of
secondary refrigerant, the secondary refrigerant freezing point should
below user’s demand temperature, avoid any damage to the water pipe
system.
2.1.4 Examine and confirm the fan of cooling tower and other equipment
operate regularly without any noise
21
cut off when outlet temperature of chilled water lower than 4℃ in order to
prevent chilled water in evaporator freezing, and the yellow light will turn on to
alarm; the low temperature will cut off the connection once the outlet chilled
water temperature is higher than 6℃. This device has been set up, user
shouldn’t change it facilely.
22
confirm the compressor’s lubricant oil has been warm-up over eight hours
2.2.1.2.5 Start and run the unit under the daily procedure.
23
water pump.
Step Three: For the single compressor unit, press the start button directly after
cold water pump and cooling water pump system circulate.
Step Four: : Start the chilled water pump first, 2 minutes later start cooling
water pump, 1 minute later start the unit. the compressor will start with star
delta(Y-△), transition time is 5 seconds. 25% energy of compressor will
transform to 50% operation after 30 seconds when start, then control upload
by the temperature.
Step Five: Whether the inlet & outlet temperature of cold water system is
correct (inlet temperature is higher than outlet). Inspect if the operate
current within the standard range.
Step Six: Stop the unit by press stop button, 25% energy of the compressor
will run for 30 seconds before compressor stop; Stop the cooling water pump 1
minute later, and stop the chilled water pump 2 minutes later.
Step Seven: If cooling water pump didn’t interlock with the chilled water pump,
manually stop the cooling water pump after the compressor stopped, and stop
the chilled water pump 2 more minutes.
24
operate, 25% energy of each compressor operate for 30 seconds before stop.
c. The compressor will stop if failure happened to it, remove the failure, and
press the reset button to automatic operate again.
Safety
Important Message
Attention: Please read carefully this manual before carry out the works of installation,
operation and service. Special message list below and appears in unit for
warning of potential danger and risk.
Attention: Only qualified enduser personnel is allowed to operate this equipment. Violation
against the manual instruction, Stars, the manufacturer is not liable to any
responsibility.
25
After press of “Start”button, wait, there is a time lack before unit is started.
Press of “Stop”button, the unitis not stopped instantly. The unit will stop as per the program
sequence, to avoid impact of power supply interruption. When unit is not completed with the
start sequence, no effect to unit even the stop button is pressed.
For emergency stop, turning off the key will disconnect the power supply to the
unit.Attention: donot operate in this way unless in case of emergency. Frequent emergency stop
will cause damage to compressor.
In order to re-start the unit whenever there are fault of : chilled water flow fault, Chilled
water pump overloaded, the unit should be reset. For fault of individual compressor circuit such
as Low-pressure cut off, high pressurecut-off, compressor overload, Phase reverse, only
respective compressor will be stopped. It will not affect the other compressor circuit. After the
fault is rectified, unit capacity control will monior the chilled water temperature to load and
unload as per the control logic.
26
Introduction to Operation
(1)、Start display
Diagram 1
Note: Click button“Chinese”,panel display language in Chinese.
Click button“English”,panel display language in English.
Click button “Enter”,it will go to touch screen control panel.
(2)Main Menu
This is the main menu page, from here, it can go to other menu for
operation, history of fault, user parameter setting;
27
Diagram 2
On the main menu, click to “Operating picture”will open the display as shown in diagram
3. From this display , it shows the compressor status, chilled water in/out temperature, more is
shown as in diagram 3.
Under this menu, click “Start”or“Stop”can start and stop the unit. When there is a fault, the
“Fault query”soft button will flash, click to“Fault" query”,to investigate the fault.
After the fault is rectified, check unit condition is comply with standard (such as power
voltage, control circuit votage). Then click screen button “Start” to start chilled water pump.
28
Diagram 3
1)State query
From menu with “ Operating picture ” , click “ State of the query “ button, to read system
temperature and operation status data as shown in diagram 4.
Diagram 4
2)Fault query
From menu with “Operating picture”, click“Fault query “ button to read present fault as shownin
diagram 5.
Diagram 5
After the fault is rectified, click“Failure reset” to reset unit. Press “History fault”button to read
29
fault history.
Diagram 7
1) User preferences setting.
Under this menu, the temperature can be set for loading and unloading temperature
difference, and water pump control mode of manual or auto
30
Diagram 8
Click“Down” to enter time setting menu.
2)Run Time Query Menu
For user convenience, this unit provides time schedule setting. User can set week or day
operating time schedule. When time schedule is set, unit will operate as the set time set for Start
and Stop daily as shown in diagram 9 and 10. Under the menu shown in diagram 8, user can click
“Down” to enter time setting. Select time schedule use or unuse. For example, set Monday use, it
displays Monday schedule will auto run to star and stop the unit as the time set.i If Saturday unuse
is set, the unit will not auto start and stop on Saturday, but the unit can start and stop manually.
Under diagram 10 menu, user can set Start timing (Timing boot) and Stop timing (Timing
shutdown) for 3 schedules. Click the first 3 buttons to select timing use or unused. The rear
buttons input the Start timing (Timing boot) and Stop timing (Timing shutdown). Once timing
schedule is set, unit will start and stop as user set.
Diagram 9
31
Diagram 10
(5)、Control Logic
32
Unloading temperature difference 1℃
(1)Control Logic is as follow:
Set T as Temperature control cycle (interval), and t as Emergency stop cycle
T Actual temp≥13℃ (Loading zone) Increase 1 capacity load unit
2 T 12℃≤Actual temp≤13℃ (unchange zone) Unchange
3 T 12℃≤Actual temp≤13℃ (maintain zone) Unchange
4 T 11℃≤Actual temp≤12℃ (unload zone) Unload 1 capacity load unit
5 T 12℃≤Actual temp≤13℃ (unchange zone) Unchange
6 T 12℃≤Actual temp≤13℃ (unchange zone) Unchange
7 T Actual temp >13℃ (Loading zone) Increase 1 capacity load unit
8 T 12℃≤Actual temp≤13℃ (unchange zone) Unchange
9 T 12℃≤Actual temp≤13℃ (unchange zone) Unchange
10T 11℃≤Actual temp≤12℃ (unload zone) Unload 1 capacity load unit
11T 11℃≤Actual temp≤12℃ (unload zone) Unload 1 capacity load unit
11T+t Actual temp≤11℃ (Emergency) Unload 1 compressor
11T+2t Actual temp≤11℃ (Emergency) Unload 1 compressor
11T+3t Actual temp≤11℃ (Emergency) Unload 1 compressor
11T+3t+T 11℃≤Actual temp≤12℃ (unload zone) Unload 1 capacity load unit
11T+3t+2T 11℃≤Actual temp≤12℃ (unload zone) Unload 1 capacity load unit
11T+3t+3T 12℃≤Actual temp≤13℃ (unchange zone) Unchange
33
2.4 Operation Management and Notice for Stop
2.4.1 Screw-type chiller operation management and notice for stop
2.4.1.1 Start/stop of the unit should strictly according to each step of manufacturer’s
operation instructions.
2.4.1.2 Make record for parameters timely and correctly while the unit is running.
2.4.1.3 Notify maintenance man to inspect the unit prompt if alarm stop occur, contact
the manufacturer if fault can not be removed.
2.4.1.4 Strictly prohibit jump out the water switch when running the unit, avoid to freeze
off the water pipes.
2.4.1.5 Special person should take in charge of the machine room, prevent those people
without fixed duties enter the room and handle the unit.
2.4.1.6 The machine room should equiped safe guarding and maintenance device, for
instance pressure gauge, thermometer and so on. And put these tools in fixed place.
2.4.2 Screw-type chiller Stop Notice:
2.4.2.1 Cut off the main power switch after the unit stop.
2.4.2.2 Discharge all chilled/cooling water in system when the unit long shutdown, tube
ends should tighten.
2.4.2.3 Maintain the unit while long shutdown.
2.4.2.4 To avoid dust, cover all the unit while stop.
2.4.2.5 Keep those people without fixed duties away from the unit while stop.
34
Chapter Ⅲ: Maintenance and Fault Processing
3.1 Summarization
This chapter introduces the prevention and fault maintenance . maintain the units right
and duly is good to ensure this units run in the best condition and high efficiency, and
can extend using time of the units.
Customers must have professional maintainer to maintain the units before and after fault
emerging according to this chapter of this instruction book. After the warranty term ,the
customer can sign a maintenance agreement with local customer service section of our
company in order to get right and timely maintenance.
For example ,analyse one-month record of running parameters,it may be found that the
gap between condensation temperature and that of cooling water at outlet is growing, is
suggests that cooling water may be dirty or has larger rigidity, so the inside wall of
heat-exchanging tubes is scaling.At this time ,it is need to intenerate cooling water or
clean tubes.
3.2 Maintenance
3.2.1 Daily maintenance
* Make the units start and stop according to the rule of the instruction everyday.
* Record running parameters of the units rightly in a proper time distance everyday.
* 24 hours after run, clean filters for both chilled water and cooling water.
* Check pressures inside the evaporator and condenser. Check the gap between the
35
evaporation temperature and temperature of chilled water at outlet, and that between
condensation temperature and that of cooling water at outlet .Pay attention to their
change trend.Generally, proper evaporation pressure should be in the range of 380 ~
500KPa,and condensation pressure should be in the range of 380 ~
500KPa.Temperature gap should be in the range of 1~3℃
* Check dryer-filter of refrigerant .If there is frost at the outlet ,jam may be inside
which often emerges along with too low evaporation pressure and increase of difference
between condensation temperature and that of cooling water at outlet. Filtering core
should be replaced in time.
* Check the deepness of oil in the tank, normal condition should be that up level of
oil in the half of the watch mirror. If the deepness decrease large, the oil should be
increased.
* Any fault resulted in stop of the units should be stressed and analysed. It may help
to solve
* The problem that analyse the condition according to this instruction book before our
customer service personnel arriving.
Caution: Must ensure the specification of the lube is right before replacement or
addition. Otherwise the units might be mangled.
38
Chilled & propensity
Charging
Item Unit cooling Corros Scali
water
water ion ng
PH(25℃) 6.5-8.0 6.5-8.0 0 0
Basic
conductivity(25℃) S/cm <200 <800 0 0
Item
Chloride ion Cl- mg Cl-/L <50 <200 0
Sulfate ion SO-2 mg SO-2/L <50 <200 0
Acerbity consumption(PH4.8) mgCaCO3/L <50 <100 0
Tsuen hardness mgCaCO3/L <50 <200 0
Iron(Fe) mg Fe/L 〈0.3 <1.0 0 0
Refer
Sulfide(S2-) mgS2-/L Unable Unable 0
ence
ammonium fixation(NH4+) mgNH4+/L 〈0.2 <1.0 0
ITEM
silicon dioxide(SiO2) mgSiO2/L <30 <50 0
Table 3-3 water quality
39
Water replenisher didn’t Check it, outlet direction should slant towards
work one direction
Cooling tower fan failure Check the fan
2.Low pressure Evaporator under feeding Increase feeding (contact manufacturer)
alarm Chilled water flow Check vessel’s pressure drop, water pump
shortage and filter
Lack of refrigerant Leak hunting, find the reason
Chilled water side scaling Check chilled water quality
Excessive oil in system Release proper chilled oil(contact the
manufacturer
3 . Chiller Lack of electricity No power supply pressure or fuse for main
cannot start-up circuit breakup
Power pressure abnormal Check three phase power accord with this
chiller’s standard
Wrong setting Check set point, run mode
4.High exhaust Expansion valve narrow Extend expansion valve
temperature opened
Less refrigerant in system Inject more refrigerant
Under feeding Check if filter works well, magnetic valve
opened
Condenser cleanout condenser
5 . Exhaust dirty(oversized feeding)
temp. too low Expansion valve opened Turn down properly
too large
Excessive refrigerant in Release proper refrigerant
system cause bad
evaporate
Bad evaporate Check chilled water flow, if water pump be
evacuated or air exist in system
6 . Low temp. Protection trip due to If the control temperature setting too low
alarm chilled water outlet
temperature too low
40
Chilled water flow Check difference in temp between chilled
problem outlet and inlet(standard is 3-5 degree) see if
flow is normal so does water pump
If filter jammed and water Rinse filter, charge enough chilled water
7.Compressor charging system work
overcurrent Check if power voltage Extend wire rod, decrease the pressure drop
alarm accord with the chiller
request
Check if any failure to the Repair winding, rinse lubricate system,
compressor decrease friction energy loss(contact the
manufacturer)
Check chiller’s working Check the chilled & cooling water flow
8.Compressor condition high & low
oil level alarm pressure is in range
The unit leaking Chase leaks, dispose it and charge chilled
oil(contact with manufacturer)
Over feeding flow Adjust feed flow, ensure the suction
superheat temp. and oil return clear
Bad evaporate 1.insufficient anti-freeze fluid concentration
9. compressor 2.chilled water system failure
frosting and run
Chilled water system Air in the water system, exhaust air. irrational
pressure too
failure water pump head
low alarm
The three display lights on the top left corner of the screen are: power light(red), run
light(green), failure light(yellow)
Power light and run light on when regular working, failure light uninterrupted blink when
failure happens, the screen will also show the failure, press the failure query can find
what the failure is.
41
1.No display 1)check the electrify to transformer output
AC9.8V
2)check the socket connector
3)check the connection
4)check if any adust smell or trail
5)check if water can go in
6)check if connection flexible
2.Touch screen response 1)confirm press strength and position
only after press 2)come into menu adjust touch screen
several times
3.Display shows dim 1)check the electrify to transformer output
AC9.8V
2)come into adjust reduced property
4.Stop without reason 1 ) confirm voltage is fluctuate within
reasonable range
2)check if button damage or distortion
5 . Compressor cannot 1)if the unit pause when temp. is reached
load or uninstall 2)confirm adopt the outlet water or back
water control point
3)confirm the time delay
4)confirm temp. probe without fault and
temperature shows normal
6.Communication fault 1 ) check touch screen and backboard
power supply, and power light is on
2 ) check whether backboard skipped
stitches
3)check touch screen parameter setting
4)check the communication lines
5)check if backboard fuse blow-out
7 . Many faults shows at 1)bad contact
the same time, but can 2)confirm connection right
42
run after reset 3 ) confirm connection lines and
heavy-current are separated
4 ) Let connection line away from the
heavy-current wire,as far as it can
5)adopt connection line with the shield
6)output adopt filter and contactless coil
has pressure sensivity resistanor.
8.Input fault alarm 1 ) if chiller’s switch status the same
setting as computer
2)check input point relevant indicator light
is on or off
3)reset fault
9.No output 1)if unit is started
2)if any output showed by screen
3 ) if output relay goes through(use
multimeter)
4)if backboard fuse is blow-out
5)check common output voltage
10.Screen dazedly 1)if any damage
2)re-electrify
3)initialize parameter
43
AttachmentⅠ Plastic insulated wire safe current carrying capacity(Ampere)
( squar
millimeter) cop alumi cop alum cop alum cop alum cop alum cop alum cop alum cop alumi cop alumi Single Doubl
per num per inum per inum per inum per inum per inum per inum per num per num core e core
0.5 7 8 7
0.75 13 10.5
0.8 11 9 14 11
1.0 17 12 11 10 10 10 9 13 9.6 17 13
1.5 21 16 17 13 15 11 14 10 14 11 13 10 11 9 17 13 10 8 21 17
2.0 19 13 25 18
2.5 28 22 23 17 21 16 19 13 21 16 18 14 17 12 23 17 17 14 29 21
4 37 28 30 23 27 21 24 19 27 21 24 19 22 17 30 23 23 19
6 48 37 41 30 36 28 32 24 36 27 31 23 28 22 37 29 28 22
10 65 51 56 42 49 38 43 33 49 36 42 33 38 29 57 44 45 35
16 91 69 71 55 64 49 56 43 62 48 56 42 49 38
25 120 91 93 70 82 61 74 57 82 63 74 56 65 50
35 147 113 115 87 100 78 91 70 104 78 91 69 81 61
50 187 143 143 108 127 96 113 87 130 99 114 88 102 78
70 230 178 177 135 159 124 143 110 160 126 145 113 128 100
95 282 216 216 165 195 148 173 132 199 151 178 137 160 121
44
120 324 246 250 190 224 168 198 148 233 173 207 155 185 138
150 371 281 285 216 259 194 229 173 263 198 237 179 216 160
185 423 328 328 296 294 220 259 198 307 229 268 203 242 183
240
300
40
500
45
Attachment Ⅱ Stars chiller operation data form
46