TYPICAL

PROJECT : DOHAT AL KHALEEJI LOCATION FLOOR


4C x 35
ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB -AC OFFICE INCOMING CABLE
sq.mm
1C x 25
ELCB : 100A/100mA - 4 POLE WAYS - 8 TPN FED FROM - METER PANEL EARTH WIRE sq.mm
LOAD IN WATTS
MCB CONDUCTOR
CKT No. RATING IN A SIZE IN Sq.mm. EQUIPMENTS AREA SERVED
R Y B

1 R1 32 3x6.0 1600
2 Y1 32 3x6.0 AC ODU 1 1600
3 B1 32 3x6.0 1600
4 R2 32 3x6.0 1600
5 Y2 32 3x6.0 AC ODU 2 1600
6 B2 32 3x6.0 1600
7 R3 32 3x6.0 1600
8 Y3 32 3x6.0 AC ODU 3 1600
9 B3 32 3x6.0 1600
10 R4 32 3x6.0 1400
11 Y4 32 3x6.0 AC ODU 4 1400
12 B4 32 3x6.0 1400
13 R5 32 3x6.0 AC OUD 5 3000
14 Y5 32 3x6.0 AC ODU 6 3000
15 B5 32 3x6.0 AC ODU 7 3000
16 R6 20 SPARE
17 Y6 20 SPARE
18 B6 20 SPARE
19 R7 20 SPARE
20 Y7 20 SPARE
21 B7 20 SPARE
22 R8 20 SPARE
23 Y8 20 SPARE
24 B8 20 SPARE
9200 9200 9200 27600
1st & 2nd
PROJECT : DOHAT AL KHALEEJ LOCATION
FLOOR

ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB - FF INCOMING CABLE 4C x 25


sq.mm

1C x 16
ELCB : 100A/100mA - 4 POLE WAYS - 12 TPN FED FROM - METER PANEL EARTH WIRE
sq.mm

CONDUCTOR LOAD IN WATTS


MCB
CKT NO. SIZE IN EQUIPMENTS AREA SERVED
RATING IN A
Sq.mm. R Y B

R1 6 3x2.5 LIGHTS LOBBY 500


Y1 6 3x2.5 LIGHTS MASTER BEDROOM 1000
B1 6 3x2.5 LIGHTS KITCHEN 1100
R2 6 3x2.5 LIGHTS FAMILY HALL 800
Y2 15 3x2.5 SOCKETS MASTER BEDROOM 800
B2 15 3x2.5 SOCKETS KITCHEN 800
R3 15 3x2.5 SOCKETS LOBBY 800
Y3 15 3x2.5 SOCKETS MASTER BEDROOM 800
B3 15 3x2.5 SOCKETS KITCHEN 800
R4 15 3x2.5 SOCKETS LOBBY 400
Y4 15 3x2.5 SOCKETS MASTER BEDROOM 800
B4 15 3x2.5 SOCKETS KITCHEN 800
R5 15 3x2.5 SOCKETS FAMILY HALL 800
Y5 15 3x2.5 SOCKETS MASTER BEDROOM 1000
B5 20 3x2.5 RCD KITCHEN 200
R6 15 3x2.5 SOCKETS FAMILY HALL 800
Y6 20 3x2.5 RCD MASTER BEDROOM 200
B6 20 3x4.0 HEATER KITCHEN 1500
R7 15 3x2.5 SOCKETS FAMILY HALL 600
Y7 20 3x4.0 HEATER MASTER BEDROOM 1500
B7 20 3x4.0 AC KITCHEN 2500
R8 20 3x4.0 AC LOBBY 2500
Y8 20 3x4.0 AC MASTER BEDROOM 2500
B8 20 3x4.0 AC KITCHEN 2500
R9 20 3x4.0 AC FAMILY HALL 2500
Y9 20 3x4.0 AC MASTER BEDROOM 2500
B9 32 3x6.0 COOKER KITCHEN 4000
R10 20 3x4.0 AC FAMILY HALL 2500
Y10 20 SPARE
B10 20 SPARE
R11 20 SPARE
Y11 20 SPARE
B11 20 SPARE
R12 20 SPARE
Y12 20 SPARE
B12 20 SPARE
12200 11100 14200
37500
TYPICAL
PROJECT : DOHAT AL KHALEEJ LOCATION
FLOOR
4C x 25
ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB - 3F INCOMING CABLE
sq.mm
1C x 16
ELCB : 100A/100mA - 4 POLE WAYS - 8 TPN FED FROM - METER PANEL EARTH WIRE
sq.mm
LOAD IN WATTS
MCB CONDUCTOR
CKT No. EQUIPMENTS AREA SERVED
RATING IN A SIZE IN Sq.mm.
R Y B

R1 6 3x2.5 LIGHT MAJLIS 500


Y1 6 3x2.5 LIGHTS PASSAGE 800
B1 6 3x2.5 LIGHTS BEDROOM1 800
R2 15 3x2.5 SOCKET MAJLIS 800
Y2 15 3x2.5 SOCKET PASSAGE 800
B2 15 3x2.5 SOCKET BEDROOM1 800
R3 15 3x2.5 SOCKET MAJLIS 800
Y3 20 3x4.0 HEATER COMMON TOILET 1500
B3 15 3x2.5 SOCKET BEDROOM1 600
R4 20 3x4.0 AC MAJLIS 2500
Y4 6 3x2.5 LIGHT KITCHEN 400
B4 20 3x4.0 AC BEDROOM1 2500
R5 6 3x2.5 LIGHT M.BEDROOM 700
Y5 15 3x2.5 SOCKET KITCHEN 600
B5 20 3x2.5 W/P SOCKET M.BEDROOM 200
R6 15 3x2.5 SOCKET M.BEDROOM 400
Y6 15 3x2.5 SOCKET KITCHEN 200
B6 20 3x4.0 HEATER BEDROOM1 1500
R7 15 3x2.5 SOCKET M.BEDROOM 600
Y7 20 3x2.5 W/P SOCKET KITCHEN 200
B7 20 3x4.0 AC KITCHEN 2500
R8 20 3x4.0 AC M.BEDROOM 2500
Y8 32 3x6.0 COOKER KITCHEN 4500
B8 20 SPARE
8800 9000 8900
PROJECT : DOHAT AL KHALEEJI

ISOLATOR : 100A TPN VOLTS - 415V

ELCB : 100A/100mA - 4 POLE WAYS - 12 TPN

MCB CONDUCTOR
CKT No. EQUIPMENTS
RATING IN A SIZE IN Sq.mm.

1 R1 6 3x2.5 LIGHT
2 Y1 6 3x2.5 LIGHT
3 B1 6 3x2.5 LIGHT
4 R2 6 3x2.5 LIGHT
5 Y2 6 3x2.5 LIGHT
6 B2 6 3x2.5 LIGHT
7 R3 6 3x2.5 LIGHT
8 Y3 6 3x2.5 LIGHT
9 B3 6 3x2.5 LIGHT
10 R4 6 3x2.5 LIGHT
11 Y4 6 3x2.5 LIGHT
12 B4 6 3x2.5 LIGHT
13 R5 6 3x2.5 LIGHT
14 Y5 15 3x2.5 SOCKET
15 B5 15 3x2.5 SOCKET
16 R6 15 3x2.5 SOCKET
17 Y6 15 3x2.5 SOCKET
18 B6 15 3x4.0 SOCKET
19 R7 15 3x2.5 SOCKET
20 Y7 20 3x2.5 SOCKET
21 B7 20 3x4.0 SOCKET
22 R8 15 3x2.5 SOCKET
23 Y8 20 3x2.5 SOCKET
24 B8 20 3x4.0 SOCKET
25 R9 15 3x2.5 SOCKET
26 Y9 20 3x4.0 HEATER
27 B9 20 3x4.0 AC
28 R10 15 3x2.5 HEATER
29 Y10 20 3x2.5 AC
30 B10 20 SPARE
31 R11 15 3x4.0 AC
32 Y11 20 SPARE
33 B11 20 SPARE
34 R12 20 SPARE
35 Y12 32 SPARE
36 B12 20 SPARE
TYPICAL
PROJECT : DOHAT AL KHALEEJI LOCATION
FLOOR
4C x 25
TITLE - DB - COMMON INCOMING CABLE
sq.mm
1C x 16
FED FROM - METER PANEL EARTH WIRE
sq.mm
LOAD IN WATTS
AREA SERVED
R Y B

GUARD ROOM 700


COMMON BATHROOM 500
ELE ROOM & ELV ROOM 400
PASSAGE & STAIR CASE LEFT SIDE ( BASMENT AND GROUND FLOOR) 600
PASSAGE & STAIR CASE RIGHT SIDE ( BASMENT AND GROUND FLOOR) 600
PASSAGE & STAIR CASE ( 1ST AND 2ND FLOOR) 1200
PASSAGE & STAIR CASE ( 3RD AND 4TH FLOOR) 1200
PASSAGE & STAIR CASE ( 5TH AND 6TH FLOOR) 1200
PASSAGE & STAIR CASE ( 7TH AND 8TH FLOOR) 1200
PASSAGE & STAIR CASE ( PENTHOUSE FLOOR) 600
PARAPET WALL LIGHTS 900
PARAPET WALL LIGHTS 900
PARAPET WALL LIGHTS 900
PASSAGE ( 3RD AND 4TH FLOOR) 400
PASSAGE ( 5TH AND 6TH FLOOR) 400
PASSAGE ( 7TH AND 8TH FLOOR) 400
PASSAGE ( PENTHOUSE FLOOR ) 200
ROOF FLOOR 800
ROOF FLOOR 800
PUMP ROOM 200
GROUND FLOOR PASSAGE 200
GUARD ROOM 400
GROUND FLOOR PASSAGE 200
ELE ROOM & ELV ROOM 800
GUARD ROOM 200
COMMON BATHROOM 1500
ELECTRIC ROOM 2500
GUARD ROOM 1500
PUMP ROOM 2500
ELV ROOM 2500

9800 8200 8400


26400
PROJECT : DOHAT AL KHALEEJI LOCATION

ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB - SHOP 1 INCOMING CABLE

ELCB : 100A/100mA - 4 POLE WAYS - 6 TPN FED FROM - METER PANEL EARTH WIRE

LOAD IN WATTS
MCB CONDUCTOR
CKT No. EQUIPMENTS AREA SERVED
RATING IN A SIZE IN Sq.mm.
R

1 R1 6 3x2.5 LIGHT SHOP 600


2 Y1 6 3x2.5 SOCKET SHOP
3 B1 6 3x4.0 AC SHOP
4 R2 15 3x2.5 SOCKET SHOP 400
5 Y2 15 3x2.5 SOCKET SHOP
6 B2 20 SPARE
7 R3 6 3x2.5 LIGHT SIGN BOARD 1200
8 Y3 15 3x2.5 SOCKET AUTOMATIC DOOR
9 B3 20 SPARE
10 R4 20 SPARE
11 Y4 20 SPARE
12 B4 20 SPARE
13 R5 20 SPARE
14 Y5 20 SPARE
15 B5 20 SPARE
16 R6 20 SPARE
17 Y6 20 SPARE
18 B6 20 SPARE
2200
LOCATION TYPICAL
FLOOR
4C x 25
INCOMING CABLE
sq.mm
1C x 16
EARTH WIRE
sq.mm
LOAD IN WATTS

Y B

800
2500

800

400

2000 2500 6700


TYPICAL
PROJECT : DOHAT AL KHALEEJI LOCATION
FLOOR
4C x 25
ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB1 - OFFICE INCOMING CABLE sq.mm
1C x 16
ELCB : 100A/100mA - 4 POLE WAYS - 12 TPN FED FROM - METER PANEL EARTH WIRE sq.mm
LOAD IN WATTS
MCB CONDUCTOR
CKT No. RATING IN A SIZE IN Sq.mm. EQUIPMENTS AREA SERVED
R Y B

R1 6 3x2.5 LIGHT CHAIRMAN ROOM 1000


Y1 6 3x2.5 LIGHT MD OFFICE & OFFICE 1,2 800
B1 6 3x2.5 LIGHT RECEPTION & MEETING ROOM 1200
R2 6 3x2.5 LIGHT OPEN OFFICE FLOOR 1200
Y2 6 3x2.5 LIGHT GENTS & FEMALE TOILETS 600
B2 6 3x2.5 LIGHT OFFICE AREA ENTRANCE 1200
R3 6 3x2.5 LIGHT OPEN OFFICE FLOOR 1200
Y3 6 3x2.5 LIGHT PRAYER ROOM, GM,ADVISOR,VCHAIRMAN ROOM 1200
B3 6 3x2.5 LIGHT DEVISION 1,2 & 3 1000
R4 15 3x2.5 SOCKET CHAIRMAN ROOM 600
Y4 15 3x2.5 SOCKET MD OFFICE 600
B4 15 3x2.5 SOCKET RECEPTION 600
R5 15 3x2.5 SOCKET CHAIRMAN ROOM 600
Y5 15 3x2.5 SOCKET MD OFFICE 600
B5 15 3x2.5 SOCKET MEETING ROOM 800
R6 15 3x2.5 SOCKET FLOOR BOX1&2 1200
Y6 15 3x2.5 SOCKET FLOOR BOX9&10 1200
B6 15 3x2.5 SOCKET FLOOR BOX6,7&8 1200
R7 15 3x2.5 SOCKET FLOOR BOX3&4 1200
Y7 15 3x2.5 SOCKET FLOOR BOX 11&12 1200
B7 15 3x2.5 SOCKET FLOOR BOX 13&14 1200
R8 15 3x2.5 SOCKET FLOOR BOX5 400
Y8 15 3x2.5 SOCKET FLOOR BOX15&16 600
B8 15 3x2.5 SOCKET FLOOR BOX17&18 600
R9 15 3x2.5 SOCKET FLOOR BOX19&20 600
Y9 15 3x2.5 SOCKET FLOOR BOX21&22 600
B9 20 SPARE
R10 20 SPARE
Y10 20 SPARE
B10 20 SPARE
R11 20 SPARE
Y11 20 SPARE
B11 20 SPARE
R12 20 SPARE
Y12 20 SPARE
B12 20 SPARE
8000 7400 7800 23200
TYPICAL
PROJECT : DOHAT AL KHALEEJI LOCATION FLOOR
4C x 25
ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB2 - OFFICE INCOMING CABLE
sq.mm
1C x 16
ELCB : 100A/100mA - 4 POLE WAYS - 12 TPN FED FROM - METER PANEL EARTH WIRE sq.mm
LOAD IN WATTS
MCB CONDUCTOR
CKT No. RATING IN A SIZE IN Sq.mm. EQUIPMENTS AREA SERVED
R Y B

R1 6 3x2.5 LIGHT PANTRY & TOILET 600


Y1 15 3x2.5 SOCKET FLOOR BOX23&24 600
B1 15 3x2.5 SOCKET FLOOR BOX25&26 600
R2 15 3x2.5 SOCKET FLOOR BOX27&28 600
Y2 15 3x2.5 SOCKET FLOOR BOX29&30 600
B2 15 3x2.5 SOCKET FLOOR BOX31&32 600
R3 15 3x2.5 SOCKET FLOOR BOX33&34 600
Y3 15 3x2.5 SOCKET FLOOR BOX 38&39 800
B3 15 3x2.5 SOCKET FLOOR BOX 37 800
R4 15 3x2.5 SOCKET FLOOR BOX 40&41 800
Y4 15 3x2.5 SOCKET FLOOR BOX 42&43 800
B4 15 3x2.5 SOCKET FLOOR BOX 44&45 800
R5 15 3x2.5 SOCKET FLOOR BOX 46&47 800
Y5 15 3x2.5 SOCKET FLOOR BOX 48&49 800
B5 15 3x2.5 SOCKET COMMON AREA PASSAGE 800
R6 15 3x2.5 SOCKET FLOOR BOX 35&36 800
Y6 20 3x4.0 HEATER GENTS TOILET 1500
B6 20 SPARE
R7 20 3x4.0 HEATER PANTRY & TOILET 1500
Y7 32 3x6.0 AC ODU 8 2800
B7 32 3x6.0 AC ODU 9 2800
R8 32 3x6.0 AC ODU 10 2000
Y8 32 3x6.0 AC ODU 11 2000
B8 20 SPARE
R9 20 SPARE
Y9 20 SPARE
B9 20 SPARE
R10 20 SPARE
Y10 20 SPARE
B10 20 SPARE
R11 20 SPARE
Y11 20 SPARE
B11 20 SPARE
R12 20 SPARE
Y12 20 SPARE
B12 20 SPARE
7700 9900 6400 24000
PROJECT : DOHAT AL KHALEEJI LOCATION

ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB - SHOW ROOM1 INCOMING CABLE

ELCB : 100A/100mA - 4 POLE WAYS - 6 TPN FED FROM - METER PANEL EARTH WIRE

LOAD IN WATTS
MCB CONDUCTOR
CKT No. EQUIPMENTS AREA SERVED
RATING IN A SIZE IN Sq.mm.
R

1 R1 6 3x2.5 LIGHT SHOW ROOM 1000


2 Y1 6 3x2.5 LIGHT SHOW ROOM
3 B1 6 3x2.5 LIGHT SHOW ROOM
4 R2 6 3x2.5 LIGHT SIGN BOARD 1200
5 Y2 15 3x2.5 SOCKET SHOW ROOM
6 B2 15 3x2.5 SOCKET SHOW ROOM
7 R3 15 3x2.5 SOCKET ACCESS DOOR 200
8 Y3 20 SPARE
9 B3 15 3x2.5 SOCKET CAMERA
10 R4 20 SPARE
11 Y4 20 SPARE
12 B4 20 SPARE
13 R5 20 SPARE
14 Y5 20 SPARE
15 B5 20 SPARE
16 R6 20 SPARE
17 Y6 20 SPARE
18 B6 20 SPARE
2400
LOCATION TYPICAL
FLOOR
4C x 25
INCOMING CABLE
sq.mm
1C x 16
EARTH WIRE
sq.mm
LOAD IN WATTS

Y B

1000
1000

800
400

200

1800 1600 5800


PROJECT : DOHAT AL KHALEEJI LOCATION

ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB - SHOWROOM DB2 INCOMING CABLE

ELCB : 100A/100mA - 4 POLE WAYS - 6 TPN FED FROM - METER PANEL EARTH WIRE

LOAD IN WATTS
MCB CONDUCTOR
CKT No. EQUIPMENTS AREA SERVED
RATING IN A SIZE IN Sq.mm.
R

1 R1 15 3x2.5 SOCKET SHOW ROOM 800


2 Y1 15 3x2.5 SOCKET SHOW ROOM
3 B1 15 3x2.5 SOCKET CAMERA
4 R2 32 3x6.0 1700
5 Y2 32 3x6.0 AC ODU 1
6 B2 32 3x6.0
7 R3 32 3x6.0 1700
8 Y3 32 3x6.0 AC ODU 2
9 B3 32 3x6.0
10 R4 20 SPARE
11 Y4 20 SPARE
12 B4 20 SPARE
13 R5 20 SPARE
14 Y5 20 SPARE
15 B5 20 SPARE
16 R6 20 SPARE
17 Y6 20 SPARE
18 B6 20 SPARE
4200
LOCATION TYPICAL
FLOOR
4C x 25
INCOMING CABLE
sq.mm
1C x 16
EARTH WIRE
sq.mm
LOAD IN WATTS

Y B

800
400

1700
1700

1700
1700

4200 3800 12200


PROJECT : DOHAT AL KHALEEJI LOCATION

ISOLATOR : 100A TPN VOLTS - 415V TITLE - DB - SHOP 1 INCOMING CABLE

ELCB : 100A/100mA - 4 POLE WAYS - 6 TPN FED FROM - METER PANEL EARTH WIRE

LOAD IN WATTS
MCB CONDUCTOR
CKT No. EQUIPMENTS AREA SERVED
RATING IN A SIZE IN Sq.mm.
R

1 R1 32 3x6.0 1700
2 Y1 32 3x6.0 AC ODU 3
3 B1 32 3x6.0
4 R2 32 3x6.0 1700
5 Y2 32 3x6.0 AC ODU 4
6 B2 32 3x6.0
7 R3 6 3x6.0 1700
8 Y3 15 3x6.0 AC ODU 5
9 B3 20 3x6.0
10 R4 20 SPARE
11 Y4 20 SPARE
12 B4 20 SPARE
13 R5 20 SPARE
14 Y5 20 SPARE
15 B5 20 SPARE
16 R6 20 SPARE
17 Y6 20 SPARE
18 B6 20 SPARE
5100
LOCATION TYPICAL
FLOOR
4C x 25
INCOMING CABLE
sq.mm
1C x 16
EARTH WIRE
sq.mm
LOAD IN WATTS

Y B

1700
1700

1700
1700

1700
1700

5100 5100 15300


SCHEDULE FOR AC(DUCTED)
SL NO ODU NO TR POWER (KW) NOTE
1 ODU 1 4.75 4.8 3 PHASE
2 ODU 2 4.75 4.8 3 PHASE
3 ODU 3 4.75 4.8 3 PHASE
4 ODU 4 4 4.1 3 PHASE
5 ODU 5 3 3.1 1PHASE
6 ODU 6 3 3.1 1PHASE
7 ODU 7 3 3.1 1PHASE
8 ODU 8 2.75 2.82 1PHASE
9 ODU 9 2.75 2.82 1PHASE
10 ODU 10 2 2.1 1PHASE
11 ODU 11 2 2.1 1PHASE
TOTAL 36.75 37.64