WT B1 Renovation Comments

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

# Location Area

1 WSOC AHU Room D, 1a-1


2 WSOC AHU Room C-D, 1a-1
3 WSOC AHU Room C-D, 1a
4 Corridor D-E, 1
5 Hotline/Scheduling/MRO D-E, 3
6 Corridor F-G, 1
7 SCBB Store F-G, 1a-1
8 Corridor F, 1
9 Corridor F-G, 1-2
10 FM OMM E-F, 1a-1
12 IUI Area F-G, 5
13 IUI Area F-G, 5
14 Lab F-G, 3-4
15 KKIVF D-E, 4-5
16 Consult Room 2 D-E, 2-3
17 KKIVF Office C-D, 3-4
18 KKIVF Office B-C, 3-4
19 Staff Pantry A-B, 3-4
20 Staff Pantry A-B, 3-4
21 KKIVF Waiting Area D-E, 3-4
22 Corridor D, 5
23 B1WSOC Pharmacy D, 5-6
24 SA Lab E-F, 8
25 SA Lab E-F, 8
26 WSOC AHU Room A-B, 9-10
Unit Involved Comment
AHU-2 No sensor access for the room AHU-2
AHU-2 FAD/FAL Provision of pre-filter/pre-filter slot for air supply duct AHU
AHU-3 FAD/FAL Provision of pre-filter/pre-filter slot for air supply duct AHU
AHU-2 SAD Relocate return grill/provide with shop drawing of installation of flexible duct
AHU-2 SAD Relocate supply grill/provide with shop drawing of installation of flexible duct
AHU-2 SAD Relocate supply grill/provide with shop drawing of installation of flexible duct
FCU-SCBB Revise FCU distance to provide adequate access for filter tray
FCU-FM Indicate clashes with others
AHU-2 SAD Relocate supply grill/provide with shop drawing of installation of flexible duct
FCU-FM SAD Relocate supply grill/provide with shop drawing of installation of flexible duct
FCU-LAB Revise FCU distance to provide adequate access for filter tray
FCU-LAB Indicate FCU capacity change
FCU-LAB SAD Relocate supply grill/provide with shop drawing of installation of flexible duct
FCU-SER Revise FCU distance to provide adequate access for filter tray
FCU IVF-6 Revise FCU drain route/LCP location
FCU IVF-2 Indicate duct Installation shop drawing
FCU IVF-1 Indicate duct Installation shop drawing
FCU-SP Indicate duct Installation shop drawing
FCU-SP Indicate duct Installation shop drawing
AHU-2 RAD Relocate supply grill/provide with shop drawing of installation of flexible duct
AHU-2 RAD Relocate supply grill/provide with shop drawing of installation of flexible duct
FCU-PH SAD Provision of damper
FCU-SA Relocate FCU
FCU-SA Revise FCU distance to provide adequate access for filter tray
AHU-1 No sensor access for the room AHU-1
Reason
Repair and replacement of sensor difficult due to location
Choke on AHU intake faster especially during haze season
Choke on AHU intake faster especially during haze season
Potential blockage of flexible duct by rigid air duct on route
Potential blockage of flexible duct by rigid air duct on route
Potential blockage of flexible duct by rigid air duct on route
Maintenance of FCU unworkable
Maintenance of FCU potentially unworkable due to area congestion
Potential blockage of flexible duct by abrupt turn
Potential blockage of flexible duct by abrupt turn
Maintenance of FCU unworkable
Potential undersize of unit due to pressure loss from added duct distance
Potential blockage of flexible duct by abrupt turn
Maintenance of FCU unworkable
Potential electrical hazard
Maintenance of FCU potentially unworkable due to blockage of filter access
Maintenance of FCU potentially unworkable due to blockage of filter access
Maintenance of FCU potentially unworkable due to blockage of filter access
Maintenance of FCU potentially unworkable due to blockage of valve access
Potential condensation due to proximity of flexible return duct to AHU SAD
Potential condensation due to proximity of flexible return duct to AHU SAD
Potential pressure loss due to backflow
Maintenance of FCU potentially unworkable due to limited access to area
Maintenance of FCU unworkable
Repair and replacement of sensor difficult due to location