Professional Documents
Culture Documents
Institutional Assessment NC II
Institutional Assessment NC II
Institutional Assessment NC II
I. True or False. Indicate whether the statement is TRUE or FALSE. Write T if it is True, F if it is
False and write the correct answer.
1. The pressure in psi that would be indicated by an absolute pressure gauge that is lying on a
workbench and not connected to anything is 0 psi.
2. If a D/P transmitter is used to measure the liquid level inside a pressurized vessel, the High
pressure side is connected at the 0% level tapping.
3. Seventy Five percent output on a 4-20mA transmitter is 15mA.
4. GPM is a unit of measurement for pressure.
5. E/I is the designation used for a transducer that converts current to voltage.
6. When a valve positioner is to be configured such that increasing signal will cause the
actuator stem to retract and close the valve. This valve action is called fail close, air-to-open.
7. In converting the output of a thermocouple to a standard 4-20 mA instrument signal, the
converter to be used with cold junction compensation is called an I/P transducer.
8. Measured Variable/ Process variable is to be maintained at some desired value by means of
manipulating another process variable.
9. A valve that is configured such that the percentage flow through it is equal to the
percentage of stem travel has linear flow characteristic.
10. Hot Work permit is required when High Voltage work is to be done.
11. When checking the calibration of an instrument, the first information you should record is
the Original Span.
12. Using ANSI/ ISA standards, the red insulated wire from a thermocouple extension cable
indicates a positive polarity.
13. If it is not possible to put a stilling well in an electronic DP type level measurement setup,
the rapid fluctuations in level measurement may be reduced by gain adjustment.
14. The dead band of an instrument is the range that an input signal may be changed on reversal
of direction without an observable change in output.
15. A DP cell is mounted one meter below the zero level in an open tank. For a true level
reading, the transmitter should be configured to have increased span.
1. The tool/s needed when installing a thermocouple sensor on a tank with a 1” connection
and a thermowell with a 1” NPT male process connection and hex fitting is.
A. 1 pc adjustable wrench
B. 1 pc plier
C. 1 pc open wrench
D. No tools, just use your hand
Date Developed: Document No. MTRLGX -00-001
March 2014 Issued by:
Date Revised:
Instrumentation and February 2012
Control Servicing NC II Developed by:
Metrologyx Page 1 of
J. Zamora Revision # 01
2. When determining the exact tapping point on a process equipment where an instrument is
to be installed, the three (3) documents that will be needed are:
3. The standard organization to be followed when using instrumentation symbols and standards.
A. ISO
B. IEC
C. ISA
D. IEEE
4. The qualification and specification of hand tools to be used in hazardous areas is that
5. When doing installation in hazardous ares, what basic safety measure must you undertake
regarding the use of PPE and observance of OHS?
6. If you found out that the tank has no process connection, the proper thing to do is:
A. Get the required process connection fitting and attach it to the tank
B. Skip the work and wait for the process connection to be installed
C. Skip the work and tell the mechanical supervisor to install the process connection
D. Submit a report that states the status and problem, and request for the required process
connection
7. The basic material needed for the installation of the thermocouple sensor described in question
No. 1 is:
J. Zamora Revision # 01
8. What are the basic materials needed for the installation of a flange-mounted instrument,
assuming that the process already has a flanged nozzle connection?
9. When a transmitter is to be installed to measure the steam pressure of a boiler, its proper
mounting should be
10. What must be used to prevent the entry of moisture or liquids when a cable enters a
transmitter’s electrical connection without a conduit?
11. Would there be a problem if the electronic transmitter to measure the pressure of a gas in a
pipeline is installed below the level of the pipe? Why?
A. Yes. When the gas is condensing, the liquid fills the impulse piping, causing false
pressure
B. Yes. When a leak occurs, liquid will drift on the transmitter
C. No. The Transformer has no moving parts and can be mounted on any position
D. No Problem as the gas occupies the whole impulse piping not like a liquid
12. If a rotameter is to be installed to measure gas flow, what are the possible mounting positions?
J. Zamora Revision # 01
13. For a pressure gauge with a diaphragm or chemical seal attached, Is it okay to remove the
gauge and install the diaphragm seal first and then re-attach the pressure gauge later? Why?
17. When installing a pneumatic diaphragm valve without a positioner, does it need a pressure
regulator? Why?
A. Yes because there is a pressure of about 3-15 psig which must be regulated
B. Yes, because there is no positioner and the valve will not change its opening correctly
C. No, because the pressure it needs to operate comes from a controller
D. No, because the pressure is already regulated at 20 psig by the air compressor
18. What is the approximate cut-out dimension for a ¼ DIN-size indicator to be mounted on a
control panel?
A. 145 H mm x 145 W mm
B. 144 H mm x 144 W mm
C. 96 mm H x 96 mm W
D. 92 mm H x 92 mm W
J. Zamora Revision # 01
19. The power supply requirement for an I/P converter is.
A. 20 psig
B. 220 VAC
C. 24 VDC
D. NONE
20. What type of recalibration is needed for a transmitter which indicates a calibration plot shown
below.
Actual
21. An electric DP Cell with a calibration plot show below requires calibration to correct for
Actual
A. Span Error
B. Zero Error Transmitter
Output
C. Zero and Span Error
D. Linearity Error Ideal
Process Input
22. The calibration plot shown below for a pneumatic transmitter has;
Actual
A. Hysteresis error
Process Input
J. Zamora Revision # 01
24. When testing for accuracy using a pneumatic comparator with a pressure test gauge, the
pressure reading of the test gauge and the gauge being tested are compared at a number of
test points. Test point are made
A. In no particular sequence
B. As the pressure is increased and as the pressure is decreased
C. Only as pressure is slowly decreased
D. Only as pressure is slowly increased
III. Matching Test. Match Column A with the description in Column B. Write only the letters
corresponding to the correct answer.
Column A Column B
1. The integral function which part of the PID A. Byte
2. The input to the controller that can be
manually set, automatically set or configured
B. Inferential
to determine the desired value of the
controlled variable
3. The flow rate in gallons per minute of water
with a specific gravity of 1 producing a
C. Zero
pressure differential of 1.0 psid through a
fully controlled valve
4. The eight bit segment of a computer word D. Repeatability
5. The range of values over which an input
signal to a transmitter maybe changed upon
E. The nameplate side of orifice
reversal of direction with no observable
change in output
6. A relative measure of time delay between
F. Dead Time
the events, states, or actions.
7. Usually adjusted first when calibrating an
G. Reset
electronic pressure transmitter.
8. The difference between the indication of the
instrument and the actual value of the H. I/P converter
measured variable.
9. Hydrostatic head, weight, radioactive
properties, density, and sonic detectors are
I. Orifice plate
all used in what method of level
measurement?
Date Developed: Document No. MTRLGX -00-001
March 2014 Issued by:
Date Revised:
Instrumentation and February 2012
Control Servicing NC II Developed by:
Metrologyx Page 6 of
J. Zamora Revision # 01
10. An instrument gives the same indication
each time it measures a variable under the J. Three wires, using 1-triad cable
same conditions.
11. All physical measurements are based on
K. Valve coefficient
these fundamental quantities
12. If an electronic controller is to send its
output signal to a pneumatic diaphragm L. Red wire connected to negative terminal
control valve, what accessory is required?
M.
13. Its function is to measure the flow rate of a FI
fluid. 123
J. Zamora Revision # 01