SattCon 05-65/OP65

From Program Version 4.0

SattCon 05-65 and SattCon OP65 are numeric keyboard with 11 function SattCon 05-65/OP65 has the following
two systems in the SattCon 05 Slimline keys. SattCon OP65 can also be used as features:
system family. a traditional operator interface
SattCon 05-65 is a complete system communicating with other systems via ● BASIC provides far more extensive
with all the necessary functions required COMLI. Digital and analogue signals options than normally available in a
for control applications, either are connected via the range of I/O units PLC.
independently or in cooperation with in the SattCon 05 Slimline family. ● PID loops.
other systems. There are two basic The BASIC and SattCon process ● Programming via personal computers
configurations of the SattCon 05-65, control language are combined in a using the DOX 10 or DOX5 program,
one has only digital while the other has unique manner in SattCon 05-65/OP65. alternatively via a VDU.
both digital and analogue inputs and A SattCon 05-65/OP65 program ● Serial communication channels for
outputs. Refer to the data sheet for consists of a BASIC section and a PLC terminal, printers and COMLI
SattCon 05 Slimline for more section. Communication between the communication, including a channel
information about the I/O units and two sections of the program is achieved dedicated and controlled by the
accessories. using registers available to both. The BASIC portion of the program.
SattCon OP65 is a unique control use of BASIC in SattCon 05-65/OP65 ● Ability to expand with analogue and
system where operator interaction and makes is possible to write protocols for digital I/O units and positioning units.
alarm functions are combined in the communication with other units, to
same unit. Advanced control features carry out advanced arithmetic
are standard in the SattCon OP65, calculations and to generate
providing all the functions required for comprehensive reports on screen or on a
modern process control. The SattCon printer.
OP65 has a back-lit LCD display and a
Program Functions Communication Program Documentation
PLC Program SattCon 05-65/OP65 has an optoisolated All programmed functions can be
The software which controls both the serial interface for PLC programming or displayed on a VDU or printed.
process and text output is known as the communication via COMLI. An
PLC program. As well as logical additional COMLI channel and an
instructions SattCon 05-65 can handle undedicated serial channel may be added -------------------------------------------------------------------------------------------------
SattCon 05

three levels of subroutines, shift using a DX232 (not optoisolated) or User:_____________________________________________________

Date 98-11-26
registers and sequencers capable of DX485G communication board. The Project:___________________________________________________
_________________________________________________________
controlling up to 256 sequences of 100 boards are connected to the DXDSUB- Controller No.
---------------------
steps each. SL unit via two D-sub connectors. 00 01 xx xx xx xx xx xx

Controller No 00
SattCon 05-65/OP65 has the The undedicated serial channel may be I/O-addresses On/Off
Controller type (P/P1/PD/PID)
0040
P1

capability to handle input and output used for BASIC programming or for Setpoint
Input
Sample time
(%, AI, R)
(AI, R)
(s)
AI100
AI104
0.8s

signals. In addition to the standard two-way communication with other Gain


Integration time
Deadzone: Input-Setpoint
(..,R)
(s, R)
(%, R)
4.50
200.0s
0.0%

control functions, you can program systems e.g. weighing machines etc. Direct Control
Minimum Out
Maximum Out
(Y/N)
(%, R)
(%, R)
N
0.0%
100.0%

your own limiter modules, ramp There is a character buffer for capturing Digital Output
Output
Cascade Controller
(Y/N)
(AO, R)
(N/M)
N
AO100
N

functions etc. There are instructions for fast incoming data and this can be read Controller No 01
I/O-addresses On/Off 0040

the four basic arithmetic operations, character by character from the BASIC Controller type
Setpoint
Input
(P/P1/PD/PID)
(%, AI, R)
(AI, R)
P1
AI100
AI104

square root extraction and logical program. Sample time


Gain
Integration time
(s)
(..,R)
(s, R)
0.8s
4.50
200.0s

calculations. The results or intermediate The channel can be configured for 7/8 Deadzone: Input-Setpoint
Direct Control
Minimum Out
(%, R)
(Y/N)
(%, R)
0.0%
N
0.0%

values can be stored in 28000 registers. data bits and Odd/Even/None parity. Maximum Out
Digital Output
Output
(%, R)
(Y/N)
(AO, R)
100.0%
N
AO100

Signal status, register values, time etc. Cascade Controller (N/M) N

BASlC Program can be transferred or requested via


The BASIC program communicates COMLI.
with the PLC program, via register and COMLI can also be used to transfer
memory flags, using a number of values and programs between
language extensions not found in SattCon 05-65/OP65 and a personal
standard BASIC. BASIC provides the computer. The system may be
option of carrying out complicated programmed on-line via the COMLI
calculations and writing protocols for network (not valid for BASIC or Hardware
communication with other units. All DOX 10). SattCon 05-65 has a slim profile and a
text processing for the display/screen or very compact construction. The system
printer and data input, is handled by the contains a central unit, an I/O unit and a
BASIC program with the aid of communication board. SattCon OP65
additional special instructions. has also a similarly slim profile and is
designed for flush mounting into the
Timers and Counters Programming and Backup front panel of a control cabinet or
SattCon 05-65/OP65 has 64 timers and PLC programming is carried out using a equivalent.
64 counters. standard VDU terminal or a PC running
the DOX 10 or DOX5 program. These Keyboard
Time Channels allow programs to be developed off-line On the SattCon OP645 there are eleven
There are 16 programmable time with identifiers (plain text programming) function keys in addition to the
channels in the SattCon 05-65/OP65 and comments. The function block numerical keys for entering values.
which can start and stop activities at feature simplifies program development Strips of explanatory text can be
particular weekdays and times of the by allowing code to be reused. When the inserted above the function keys. The
day. program has been transferred to SattCon keys are provided with a “mechanical
05-65/OP65, the program can be click” for distinct input.
Controllers supervised online using DOX 10/DOX5
SattCon 05-65/OP65 has eight which still shows identifiers etc. Display
controllers with P, PI, PD or PID BASIC is programmed on-line via the The operator's unit is fitted with a back-
functions which can be cascaded. The BASIC channel using a VDU or a PC lit LCD display having four rows of 40
sophisticated controllers even allow with the terminal emulator in DOX 10/ characters. The viewing angle can be
gain scheduling to be controlled by a DOX5. adjusted with a potentiometer.
process parameter via the PLC The entire program can be backed up Character sets for seven countries are
program. using the SBUP05 backup unit or a PC included as are certain graphic
with the DOX 10 or DOX5 program. characters.
Error Supervision
SattCon 05-65/OP65 has several Memory
functions which aid troubleshooting Program memory is CMOS with
and commissioning. These include 25 kbytes for the PLC program and
automatic error supervision of analogue 20 kbytes for BASIC instructions. The
inputs/outputs and dynamic display of memory is battery-backed and so
sequencer steps. retains its contents when the power
supply is lost.

I/O
The digital I/O area comprises 3072
memory cells which are used either as
inputs/outputs or working memories;
60 cells are battery-backed.
Expansion Units
The number of inputs and outputs can ● SD32D is a digital I/O unit with 32 ● SDA is a digital/analogue I/O unit
be increased by connecting up to four inputs for 16–32 V DC and 28 with 16 digital optocoupled inputs for
expansion units (up to three for Slimline transistor outputs for 12–50 V DC. 16–32 V DC, 16 digital optocoupled
in addition to the basic unit). The outputs for 12–50 V DC, 4 analogue
following expansion units can be ● The SD24D is a digital I/O unit with inputs for 0–5 V/1–5 V/0–10 V/0–20
combined depending on the user’s 24 optocoupled transistor inputs for mA/4–20 mA with common signal
requirements. 16–32 V DC and 24 optocoupled ground and two analogue outputs for
All outputs must be fused externally. transistor outputs for 15–50 V DC. 0–10 V/0–20 mA/4–20 mA.

● SD24RS is a digital I/O unit with 24 ● SACV is an analogue I/O unit with 12
optocoupled inputs for 16–32 V DC analogue inputs for 0–10 V/0–20 mA/
and 16 relay outputs. 4–20 mA and 4 analogue outputs for
0–10 V/0–20 mA/4–20 mA.
Dimensions

Ø 6,5

Ø12

47
20

276
15

PWR 24V

25
00 40
01 41
02 42
03 43
04 44
05 45
06 46
07 47
10 48
11 49
12 50
13 51
14 52
15 53
16 54
17 55

150

200
20 56
21 57
22 58
23 59
24 60
25 61
26 62
27 63
30 64
31 65
32 66
33 67
34 70
35 71
36 72
37 73
38 78

25
39 79
INPUT OUTPUT

300
320
342
216
203

76
216

203
76

All dimensions are given in mm


Technical Data
CPU Dallas 80C320 or equivalent Power supply 24 V DC -15% +20%. Max. ripple 5%
Program memory 25 kbytes for the PLC program and of nominal power
20 kbytes for the BASIC program Power consumption
Cycle time Minimum 50 ms, can be selected in SattCon 05-65 3.9 W including DX232 *
steps of 50 ms SattCon OP65 6.7 W including DX232 *
Working memory Total of 3072 bits. Reduced by the Environment Industrial premises
number of inputs/outputs. 60 bits are
battery-backed. The working memory Approvals (when CE-marked and meets EMC directive
can be accessed from PLC and BASIC product or 89/336/EEC according to the following
packaging is standards: EN 50081-2 and
Timers 64 pcs., 0.1 s – 9 h 6 m 7 s marked) EN 50082-2.
Counters 64 pcs., 65535 max. count Low Voltage Directive 73/23/EEC with
Registers (16-bit) 28000 pcs. Can be accessed from supplement 93/68/EEC according to
PLC and BASIC the following standard: EN61131-2
Sequencers 256 pcs., 100 steps each UL listed according to UL 508
Time channels 16 pcs. programmable Protection class SattCon 05-65: IP20
SattCon OP65: IP65
Text strings Programmed and controlled from
BASIC Ambient Operating 0 to +50 °C
temperature Non-operating -25 to +70 °C
Controllers 8 pcs. programmable; P, PI, PD or PID
Relative humidity 10–95%, non-condensing
Display (OP65) LCD with back-lighting. 4 rows of 40
characters. Controlled from BASIC Dimensions
Keyboard (OP65) Numerical keyboard and 11 function SattCon 05-65 W342 X H200 X D47 mm
keys. Handled by BASIC SattCon OP65 W216 X H216 X D76 mm
In/outputs (05-65) Panel cutout: H205 X W205 ±1 mm
SACV * 12 analogue inputs and 4 analogue Weight
outputs 0–10 V DC/0–20 mA/4–20 mA SattCon 05-65 2.1 kg
SD24D * 24 digital optoisolated inputs 24 V DC, SattCon OP65 1.8 kg
24 digital optoisolated outputs Order codes
12–50 V DC, 0.8 A
SattCon OP65 SCOP65
SD24RS * 24 digital optoisolated inputs 24 V DC,
16 relay outputs 250 V AC/120 V DC Cable OP65–I/O
unit, 0.3 m I/OCOP0.3M
SD32D * 32 digital inputs 24 V DC and 28 out-
puts, 12–50 V DC, 0.8 A Cable OP65–I/O
unit, 1.0 m I/OCOP1.0M
SDA * 16 digital optoisolated inputs 24 V DC, Cable OP65–I/O
16 digital optoisolated outputs unit, 2.0 m I/OCOP2.0M
12–50 V DC (0.8 A), 4 analogue inputs
0–5 V/1–5 V/0–10 V/0–20 mA/ Cable OP65–
4–20 mA and 2 analogue outputs SBUP05 SBUP05.OP
0–10 V/0–20 mA/4–20 mA. CU05-65/SD32D/
Fused Inputs: internal DX232 CU0565/SD32D/DX232
Outputs: external CU05-65/SD32D/
DX485G CU0565/SD32D/DX485G
Expansion Up to 4 I/O units (up to 3 for Slimline in
addition to the basic unit) CU05-65/SDA/
DX232 CU0565/SDA/DX232
Communication 2 serial channels RS232/RS485,
Master or Slave selectable, controlled CU05-65/SDA/
from PLC. One of the channels also DX485G CU0565/SD32D/D485G
used for PLC-programming. Documentation SattCon 05-65/OP65 (V4), VDU Pro-
1 serial channel for BASIC. Also used gramming
for BASIC programming SattCon OP (V4) Installation and
Programming Maintenance
PLC VDU terminal or PC with DOX 10/ SattCon 05 Slimline (V4) Installation
DOX5; RS232 via 25-pole D-sub con- and Maintenance
nector SattCon OP (V4) DOX 10 Program-
BASIC Via DXDSUB ming
DOX 10 User’s Manual
Backup Total with SBUP05, DOX10 and DOX5
MCS BASIC-52 User’s Manual
Printer connection RS232 via 25-pole D-sub connector.
Controlled from BASIC
00000. AE Andersson Grafiska AB. Printed in Sweden 1999.

* For details see the Installation and Maintenance manual

ABB regional center ABB regional center Americas ABB regional center Germany ABB regional center
Europe and Africa Rochester, USA Munich, Germany Asia Pacific
Västerås, Sweden Phone:+1 716 292 6131 Phone:+49 (0) 89 84000-144 Kuala Lumpur, Malaysia
Phone:+46 (0) 21 34 20 00 Fax:+1 716 273 7014 Fax:+49 (0) 89 84000-100 Phone:+60 (0) 3 973 2685
Fax:+46 (0) 21 13 78 45 Fax:+60 (0) 3 973 9685
Specifications subject to change without notice. 493-0677-11
Printed in Sweden. © 1999 ABB Satt AB. 9908 v. 2-1

You might also like