Trans Series Gen-Set Controllers


Trans-AMF.Syncro_ May_2018
TRANS-AMF.SYNCRO
Synchronising & Load Sharing Auto Mains Failure Control
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_
Trans Serisi Jeneratör Kontrol Panelleri

Warning Lights :

Red Alert
Light of the alarms that the engine is stopped
Eğitim Notu _ Mayıs 2013_

Yellow Alert
Light of the alarms that the engine is not stopped

Maintenance Alarm
Light of the maintenance alarm
Access to record the last 50 events

Access to existing alarm and warning Test Button of all LED indicator status

Value Increase / Up

Right / Left Page scroll

Value Decrease / Down


Language selection shortcut button
Return to the previous menu Silencing the horn

Access to the program menu


Control Buttons
Mains Contactor On / Off Generator Contactor On / Off
(In Manual Mode) (In Manual Mode)

Mains Voltage OK Generator Voltage OK


Load Can Be Powered From the Mains Generators Can Take the Load

Engine Running
Index

In Manual Mode Off Mode Selection and


Failure Deletion Start Button Engine Stop

Automatic Operation Manual Operation


Mode Selection Mode Selection
Test Button
Activated while there is Mains
Trans Serisi Jeneratör Kontrol Panelleri

General Settings :
- Mains Voltages and Frequency Measurements
- Generator Voltages and Frequency Measurements
- “BREAK”, “NO BREAK” and “SOFT” Load Transfer Methods
Eğitim Notu _ Mayıs 2013_

- Load Sharing with GenSet


* Peak Lopping (Mains or Genset)
* Power Export to Mains
- Load Display
- Mains De-coupling Protection with «R.O.C.O.F» and «Vector Shift» Methods
- Voltages, Frequency and Phase Matching
- Manual Voltage / Frequency Adjustment
- Direct / Reverse Governor and AVR Control
- Auto Adjust Feature for GOVERNOR and AVR
- Synchroscope Display
- Logic Controller Functionality for PLC
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_
MAINS VOLTAGE & FREQUENCY MEASUREMENTS
GENERATOR VOLTAGE & FREQUENCY MEASUREMENTS
(BREAK) , (NO BREAK) and (SOFT)

LOAD TRANSFER METHODS


* (BREAK) Load Transfer Method :

** Interrupted Load Transfer…


(with default 2 second transition time)
* (NO BREAK) Load Transfer Method :

** Uninterrupted Load Transfer…


(with short transition time as default 0.5 second)
* (SOFT) Load Transfer Method :

** Soft Transition Load Transfer…


LOAD SHARING with GENSET

LOAD SHARING : The task of the Trans-AMF.Syncro device;


to provide active and reactive power balancing
between the Mains and Generator.
LOAD SHARING with GENSET

* Peak Looping (Mains) :


LOAD SHARING with GENSET

* Peak Looping (Mains) :


LOAD SHARING with GENSET

* Peak Looping (Genset) :


LOAD SHARING with GENSET

* Peak Looping (Genset) :


LOAD SHARING with GENSET

* Power Export to Mains :


LOAD SHARING with GENSET

* Power Export to Mains :


LOAD DISPLAY

This screen is shown active-reactive power and


PF (Power Factor) status of the Load, Mains and Generator.
MAINS DE-COUPLING PROTECTION METHODS

- «R.O.C.O.F.» and «Vector Shift» Methods :


MAINS DE-COUPLING PROTECTION METHODS

- Mains Decoupling Actions :


VOLTAGE , FREQUENCY and PHASE MATCHING

The unit has got voltages, frequency and phase matching feature
for synchron process.

If the Genset needs to be synchronized with the Mains ;


Now the gensets need to compare and make balance its voltage / frequency / phase angles.
The limits and tolerances to let the snychron or prevent are described with following parameters.

For Example:

09.06.002.Max. Voltage differance: 3Vac and measured Mains Supply Voltage: 230Vac.
if the generator voltage is 227Vac / Syncron is OK.
if the generator voltage is 226Vac / Syncron is NOT ok.

The authorized parameters for this feature are mentioned as following marked table ;
MANUAL VOLTAGE / FREQUENCY ADJUSTMENT

- GOVERNOR & AVR CONTROL :

The analogue Governor and AVR outputs provide an isolated, adjustable DC voltage.
• Well known AVR and Governor types and its parameter levels are described
in user manual.
• Auto adjust feature is another alternative to adapt the system AVR and Governor.
• Manual settings are also applicable.
MANUAL VOLTAGE / FREQUENCY ADJUSTMENT

- Manuel Voltage / Frequency Adjusment :

Trans-AMF.Syncro Governor and AVR outputs voltages are -10Vdc /+10Vdc linear scale.
Every Governor and AVR outputs are different such -6Vdc / -2 Vdc etc…
We need to adapt the output voltage in a lineer scale for Trans-AMF.Syncro unit.

Governor Control Page : It uses for manual frequency control settings.

AVR Control Page : It uses for manual voltage control settings.


MANUAL VOLTAGE / FREQUENCY ADJUSTMENT

- Manuel Voltage / Frequency Adjusment :

It may use to test for the GOVERNOR and AVR outputs.


Trans Serisi Jeneratör Kontrol Panelleri

Voltage and Frequency values may increase and decrease by buttons and test the reaction.
Eğitim Notu _ Mayıs 2013_001.001
MANUAL VOLTAGE / FREQUENCY ADJUSTMENT

09.01.001.Frequency Control Parameter : It should be active for FREQUENCY CONTROL.


But firstly we need to make disable to Governor settings / system adaptation.

09.02.001.Voltage Control Parameter : It should be active for ALTERNATOR VOLTAGE CONTROL.


But firstly we need to make disable to AVR settings / system adaptation.

When we try to adjust the Governor Output to make stable engine speed for required frequency
if Trans-Syncro give another control out for Governor (or AVR), setting is not possible.

So first we need to adjust NOMINAL 50Hz manually.


- Using Frequency pot (RPM) on the Governor
- When we see 50Hz on the Trans-Syncro unit, adjustment is OK.

The same procedure for AVR to adjust NOMINAL 400Vac manually. (Phase/Phase: 400Vac – P/Neutral: 230Vac)
- Using Voltage pot on the AVR
- When we see 400Vac on the Trans-Syncro unit, adjustment is OK.
DIRECT / REVERSE GOVERNOR and AVR CONTROL

…006.Output direction parameter :


Positive = Direct
Negative = Reverse

GOVERNOR CONTROL : If Trans-AMF.Syncro Governor Output Voltage increase , than frequency increase too.
If voltage decrease, than frequency decrease too. That is DIRECT action. (opposite type is REVERSE action)

AVR CONTROL : If Trans-AMF.Syncro AVR Output Voltage increase, than alternator voltage increase too.
If voltage decrease, than alternator voltage decrease too. That is DIRECT action. (opposite type is REVERSE action)
AUTO ADJUST FEATURE for GOVERNOR and AVR

With this automatic adjustment no need to set Governor/AVR min-max voltage


and direction settings.

Unit automatically apply voltage levels back ground and find min/max values and direction.
If auto adjustment is successfull or unsuccessfull; it would show on the screen at the end of
procedure.

After automatic setting done successfully, the following parameters that marked with star, would update.
SYNCHROSCOPE DISPLAY

This screen is automatically shown when the synchronization process starts.


LOGIC CONTROLLER FUNCTIONALITY for PLC

The Logic Controller is used for configure the unit outputs


or gensets start/stop or the unit operation mode.

For instance, the engine start can be programmed depending on whether


the configurable input is active or a specific time of related day.
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_

- Weekly exercise schedule and work hours for each days can be defined.
- Work schedule panel in auto mode is active.

Outside the time limits set mains voltage goes out,


the mains contactor is disconnection,
but the engine will not run.
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_

- Panel as standard, as well as having the option of English language;


Turkish, Chinese, German, Russian, French, Spanish options are also available.
- Auto scroll the screen with the time sequence of changes is provided at the set time.
- Automatic scrolling will change with the number of screens can be selected.
- With error message display time, the display period of multiple warnings comprising adjustable.
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_

- Trans-I / O expansion modules have 8 configurable digital inputs and 8 configurable relay outputs.
- Additional inputs / NC input type and V-/ V + input polarization can adjust from the program menu.
- The expansion module can be activated from the program menu on the configuration menu.
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_

- Status and Temporary Warning indication parameter is selected, the input is active Yellow alarm.
Check back to normal when the alarm is cleared.
- Permanent warning indication when selected input is back to normal again,
but the Yellow alarm data of the alarm must be reset.
- Electrical faults and Stopping elections red alarm and reset the alarm
when the input should be back to normal.