Warning Lights :
Red Alert
Light of the alarms that the engine is stopped
Eğitim Notu _ Mayıs 2013_
Yellow Alert
Light of the alarms that the engine is not stopped
Maintenance Alarm
Light of the maintenance alarm
Access to record the last 50 events
Access to existing alarm and warning Test Button of all LED indicator status
Value Increase / Up
Engine Running
Index
General Settings :
- Mains Voltages and Frequency Measurements
- Generator Voltages and Frequency Measurements
- “BREAK”, “NO BREAK” and “SOFT” Load Transfer Methods
Eğitim Notu _ Mayıs 2013_
The unit has got voltages, frequency and phase matching feature
for synchron process.
For Example:
09.06.002.Max. Voltage differance: 3Vac and measured Mains Supply Voltage: 230Vac.
if the generator voltage is 227Vac / Syncron is OK.
if the generator voltage is 226Vac / Syncron is NOT ok.
The authorized parameters for this feature are mentioned as following marked table ;
MANUAL VOLTAGE / FREQUENCY ADJUSTMENT
The analogue Governor and AVR outputs provide an isolated, adjustable DC voltage.
• Well known AVR and Governor types and its parameter levels are described
in user manual.
• Auto adjust feature is another alternative to adapt the system AVR and Governor.
• Manual settings are also applicable.
MANUAL VOLTAGE / FREQUENCY ADJUSTMENT
Trans-AMF.Syncro Governor and AVR outputs voltages are -10Vdc /+10Vdc linear scale.
Every Governor and AVR outputs are different such -6Vdc / -2 Vdc etc…
We need to adapt the output voltage in a lineer scale for Trans-AMF.Syncro unit.
Voltage and Frequency values may increase and decrease by buttons and test the reaction.
Eğitim Notu _ Mayıs 2013_001.001
MANUAL VOLTAGE / FREQUENCY ADJUSTMENT
When we try to adjust the Governor Output to make stable engine speed for required frequency
if Trans-Syncro give another control out for Governor (or AVR), setting is not possible.
The same procedure for AVR to adjust NOMINAL 400Vac manually. (Phase/Phase: 400Vac – P/Neutral: 230Vac)
- Using Voltage pot on the AVR
- When we see 400Vac on the Trans-Syncro unit, adjustment is OK.
DIRECT / REVERSE GOVERNOR and AVR CONTROL
GOVERNOR CONTROL : If Trans-AMF.Syncro Governor Output Voltage increase , than frequency increase too.
If voltage decrease, than frequency decrease too. That is DIRECT action. (opposite type is REVERSE action)
AVR CONTROL : If Trans-AMF.Syncro AVR Output Voltage increase, than alternator voltage increase too.
If voltage decrease, than alternator voltage decrease too. That is DIRECT action. (opposite type is REVERSE action)
AUTO ADJUST FEATURE for GOVERNOR and AVR
Unit automatically apply voltage levels back ground and find min/max values and direction.
If auto adjustment is successfull or unsuccessfull; it would show on the screen at the end of
procedure.
After automatic setting done successfully, the following parameters that marked with star, would update.
SYNCHROSCOPE DISPLAY
- Weekly exercise schedule and work hours for each days can be defined.
- Work schedule panel in auto mode is active.
- Trans-I / O expansion modules have 8 configurable digital inputs and 8 configurable relay outputs.
- Additional inputs / NC input type and V-/ V + input polarization can adjust from the program menu.
- The expansion module can be activated from the program menu on the configuration menu.
Trans Serisi Jeneratör Kontrol Panelleri
Eğitim Notu _ Mayıs 2013_
- Status and Temporary Warning indication parameter is selected, the input is active Yellow alarm.
Check back to normal when the alarm is cleared.
- Permanent warning indication when selected input is back to normal again,
but the Yellow alarm data of the alarm must be reset.
- Electrical faults and Stopping elections red alarm and reset the alarm
when the input should be back to normal.