Bulletin 100-D IEC Contactors
Bulletin 100-D IEC Contactors
Bulletin 100-D IEC Contactors
50…500 kW @ 400V
60…600 Hp @ 460V
75…700 Hp @ 575V
Electronic and conventional coils
AC & DC
Integrated PLC interface
Low power pick-up & hold-in
Wide voltage ranges
Complete range of accessories
Environmentally friendly
Compact dimensions
The Bulletin 100-D/104-D contactor family, along with a wide range of common accessories and
Bulletin 193 electronic overload relays, provides the most compact and flexible starter
component system available.
Your order must include: cat. no. of the contactor specified with coil voltage code and, if
required, cat. no. of any accessories and/or replacement coils.
Standards Compliance
IEC 60947-4-1
IEC 60947 Type “2” Coordination
CSA C22.2 No. 14
UL 508
Certifications
CE Marked
cULus Listed (File No. E 41850, Guide NLDX, NLDX7)
Product Selection
Electronic [V] 24 42…6 10 110…1 20 208…2 200…2 230…2 27 380…4 380…5 440…4 50
Coil 4 0 30 0 77 20 50 7 15 00 80 0
w/ EI.
Interface
§
100- 50/6 EJ EY EP ED E EA — — —— EN — —
D95...100 0 Hz G
-D300
100-D420 50/6 — — EP ED E EA — — —— EN — —
0 Hz G
100- 50/6 — — EP ED E — EG EA ETEN — EB E
D630…10 0 Hz G M
0-D860
§ Signal voltage of the Cat. No. 100-D… electronic interface: nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0V DC...30.2V DC
Dropout Voltage: –3.0V DC...+5.0V DC.
Not available with 100/104-D300.
For conventional DC coils, the pickup winding must be interconnected with the N.C. late-
breaking auxiliary contact(s).
Signal voltage of the Cat. No. 100-D… electronic interface: nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0V DC...30.2V DC , Dropout Voltage: –3.0V DC...+5.0V DC.
Auxiliary contacts with sequence numbering.
With conventional DC control, the pickup winding must be interconnected with the N.C. late-
breaking auxiliary contacts.
Bulletin 100-D/104-D Accessories
Auxiliary Contacts
Suppressor Modules
For overvoltage category IV (IEC 947 for 100-D...-EI) e.g., lightning protection requirements.
Package Quantity = 1
Connecting Components
Package Quantity = 1
Package Quantity = 2
Interlocks
Package Quantity = 1
Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications
Power ratings at 50 Hz: Preferred values according to Approval pending on Cat. No.
IEC 60072-1 100-D210…D860.
100/104-K100/104-C, 100S/104S-C
05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X X
Electronic — EI — — — — — — — — — — —
Switching of Power Transformers,
AC-6a (50 Hz)
Inrush Current =n
Rated transformer
current
n = 30 230V [A] 2.9 5.4 5.4 10.910.910.910.920 20 23 40.
8
240V [A] 2.9 5.4 5.4 10.910.910.910.920 20 23 40.
8
400V [A] 2.4 4.1 5.4 10.910.910.910.920 20 23 40.
8
415V [A] 2.4 4.1 5.4 10.910.910.910.920 20 23 40.
8
500V [A] 1.8 3.2 3.2 10.910.910.910.920 20 23 40.
8
690V [A] — — — 10.910.910.910.920 20 23 40.
8
1000V [A] — — — — — — — — — — —
230V [kVA] 1.2 2 2 4.3 4.3 4.3 4.3 8 8 9.2 16
240V [kVA] 1.2 2 2 4.5 4.5 4.5 4.5 8.3 8.3 10 17
400V [kVA] 1.7 2.8 3.4 7.5 7.5 7.5 7.5 14 14 16 28
415V [kVA] 1.7 2.8 3.4 7.8 7.8 7.8 7.8 14 14 17 29
500V [kVA] 1.7 2.8 3.4 9.4 9.4 9.4 9.4 17 17 20 35
690V [kVA] 2 4 5 13 13 13 13 24 24 27 49
1000V [kVA] — — — — — — — — — — —
n = 20 690V [A] — — — 16.316.316.316.330 30 34.561.3
n = 15 690V [A] — — — 22 22 22 22 40 40 46 82
60 Hz Peak Inrush/peak rated transformer current
n = 30 [A] — — — 10.910.910.910.920 20 23 40.
8
200V [kVA] — — — 3.8 3.8 3.8 3.8 6.9 6.9 8.0 14.
1
208V [kVA] — — — 3.9 3.9 3.9 3.9 7.2 7.2 8.3 14.
7
240V [kVA] — — — 4.5 4.5 4.5 4.5 8.3 8.3 9.6 17.
0
480V [kVA] — — — 9.1 9.1 9.1 9.1 16.616.619.133.
9
600V [kVA] — — — 11.311.311.311.320.820.823.942.
4
660V [kVA] — — — 12.512.512.512.522.922.926.346.
6
60 Hz Peak Inrush/peak rated transformer current
n = 20 [A] — — — 16.316.316.316.330 30 34.561.
3
200V [kVA] — — — 5.6 5.6 5.6 5.6 10.410.412.021.
2
208V [kVA] — — — 5.9 5.9 5.9 5.9 10.810.812.422.
1
240V [kVA] — — — 6.8 6.8 6.8 6.8 12.512.514.325.
5
480V [kVA] — — — 13.613.613.613.624.924.928.751.
0
600V [kVA] — — — 16.916.916.916.931.231.235.963.
7
660V [kVA] — — — 18.618.618.618.634.334.339.470.
1
60 Hz Peak Inrush/peak rated transformer current
n=15 [A] — — — 22 22 22 22 40 40 46 82
200V [kVA] — — — 7.5 7.5 7.5 7.5 13.913.915.928.
4
208V [kVA] — — — 7.8 7.8 7.8 7.8 14.414.416.629.
5
240V [kVA] — — — 9.0 9.0 9.0 9.0 16.616.619.134.
1
480V [kVA] — — — 18.118.118.118.133.333.338.268.
2
600V [kVA] — — — 22.622.622.622.641.641.647.885.
2
660V [kVA] — — — 24.924.924.924.945.745.752.693.
7
100-D, 100S-D
95 110 95 110 140 180 21 25 30 42 630 860
0 0 0 0
Coil Type : Conventional X X — — X X — — — — — —
Electronic — — — X X X X X X X X X X
EI
Conductor Cross Sections - Main
Contacts
Terminal type
(1) [mm — — — — —
conducto 2] — — — — —
r [mm
2
(2) ]
conducto
rs
(1) [mm — — — — —
2
conducto ] — — — — —
r [mm
2
(2) ]
conducto
rs
b max. [mm 20 25 30 52 52
]
c max. [mm 10 12.5 15 22 22
]
s max. [mm 5 5 6 2x8 2x8
]
min. [mm 6.1 8.3 10.5 13 13
]
Recommended [Nm] 9 22 43 68 68
torque
Cross section per [AWG] — — — — —
UL/CSA
Recommended [lb-in] 80 195 380 600 600
torque
With terminal 100- 100- 100- 100- 100- 100-
lug kit DL110‡ DLE110 DL180 DL420‡ DL630 DL860
‡ ‡
Cross section per [AWG] 8…2/0 8…2/0 6…300 (2x) 4…350 (2X) (4X)
UL/CSA MCM MCM 2/0… 2/0…
500MC 500MC
M M
Recommended [lb-in] 90 90 250 250 400 400
torque
With Frame 100- 100-DTB180‡ 100- — —
Terminal DTB110 DTB420
Block ‡
top [mm 16…35 16…35 25…240 — —
opening 2] 16…70 16…95 25…240
bottom [mm
opening 2]
top [mm 16…50 16…50 25…300 — —
opening 2] 16…95 16…120 25…300
bott. [mm
opening 2]
b max. [mm 16 20 25 — —
s top ] 3…9 3…9 4…20
s bottom [mm 3…12 3…14 4…20
]
[mm
]
Recommended [Nm] 12 14 25 — —
torque
Cross section per [AWG] 6…1 / 0 6…1 / 0 AWG 4 — —
UL/CSA top AWG AWG…600
MCM
bottom [AWG] 6…3 / 0 6 AWG…250 4 — —
AWG MCM AWG…600
MCM
Recommended [lb-in] 106 124 220 — —
torque
Coil Data
100/104-D, 100S-D
95/110 140/180 95 110 140 180 210 250 300 420 630 860
Coil Type Conventional X X —— — — — — — — — —
Electronic — EI — — XX X X X X X X X X
Operating Limits
50 Hz, 60 pick-up [x Us] 0.85…1.1 0.85…1.1 0.8…1.1
Hz, 50/60 dropout [x Us] 0.3…0.6 0.3…0.5 0.3…0.8
Hz
DC control pick-up [x Us] 0.85…1.1 0.85…1.1 0.85…1.1
dropout [x Us] 0.3…0.6 0.3…0.5 0.3…0.8
Coil Consumption
50 Hz, 60 pick-up [VA/W] 650/310 380/240 490/270 1915/1720
Hz, 50/60 hold-in [VA/W] 50/10 13/6 18/7 33/30
Hz
DC control pick-up [W] 540 265 340 1980
hold-in [W] 8 6 7 30
Operating Times
AC closing [ms] 20…47 20…45 60…100
delay
opening [ms] 6…12 25…110 70…145
delay
With RC opening [ms] 9…18 — —
module delay
DC closing [ms] 27…47 25…50 60…100
delay
opening [ms] 12…20 35…110 70…145
delay
With opening [ms] 12…20 — —
integrated delay
diode
With opening [ms] — — — —
external delay
diode
Electronic coil drives are designed to minimize power requirements, but this control may
exhibit a higher inrush (540 W, < 10 ms) when energizing. This must be taken into account for
the proper sizing of supply devices, all-or-nothing relays and cross-sections of coil supply lines.
Please contact your local Rockwell Automation sales office or Allen-Bradley distributor for
detailed information.
100/104-D, 100S-D
95/110 140/18095 110140180210250300420 630 860
Coil Type : Conventional X X — — — — — — — — — —
Electronic – — — X X X X X X X X X X
El
Short Circuit Coordination (Max.
Fuse or Circuit Breaker Rating)
Per IEC 60947-4-1 (contactor and
fuses only)
DIN Fuses - gG, gL [kVar] 50 kA Available Fault Current
Type "1" (690V) [A] 250 315 250250315355500500630630
Type "2" (400V) [A] 200 250 200200250315400400500500
Type "2" (690V) [A] 200 250 200200250315400400500500
BS88 Fuses 65 kA Available Fault Current
Type "1" (415V) [A] 160 250 200200250250355355450630
Type "2" (415V) [A] 160 250 200200250250355355450560
Per UL 508 and CSA 22.2 No. 14
(contactor and fuses or circuit
breaker only)
UL Class K5 and RK5 Fuses 5 kA Available Fault Current
UL Listed [A] — — — — — — — — — — — —
Combination (600V)
UL Class K5 and RK5 Fuses 10 kA Available Fault Current
UL Listed [A] 225/250350/450225250350450500— — — — —
Combination (600V)
UL Class L Fuses 18 kA Available Fault Current
UL Listed [A] — — — — — — — 7007001000— —
Combination (600V)
UL Class L Fuses 30 kA Available Fault Current
UL Listed [A] — — — — — — — — — — 2000—
Combination (600V)
UL Class L Fuses 42 kA Available Fault Current
UL Listed [A] — — — — — — — — — — — 2500
Combination (600V)
UL Class CC and CSA HRCI- 100 kA Available Fault Current
MISC Fuses
UL verified [A] — — — — — — — — — — — —
combination to IEC
60947-4-1 "Type 2"
UL Class J and CSA HRCI-J 100 kA Available Fault Current
Fuses
UL verified [A] 200 250/300200200250300400400500600
combination to IEC
60947-4-1 "Type 2"
UL Inverse-Time Circuit Breaker 5 kA Available Fault Current
UL Listed [A] — — — — — — — — — — — —
Combination (480V)
UL Listed [A] — — — — — — — — — — — —
Combination (600V)
UL Inverse-Time Circuit Breaker 10 kA Available Fault Current
UL Listed [A] 125/150200/250125150200250300— — — — —
Combination (600V)
UL Inverse-Time Circuit Breaker 18 kA Available Fault Current
UL Listed [A] — — — — — — — 350400500 — —
Combination (600V)
UL Inverse-Time Circuit Breaker 30 kA Available Fault Current
UL Listed [A] — — — — — — — — — — 1200—
Combination (600V)
UL Inverse-Time Circuit Breaker 42 kA Available Fault Current
UL Listed [A] — — — — — — — — — — — 1200
Combination (600V)
To be determined.
General
AC-3
AC-1
AC-4
Dimensions in millimeters. Dimensions are not intended to be used for manufacturing purposes.
Mounting Position
Contactor with mm
Auxiliary contact block 100-DS1… a
100-DS2… a + 13.5 each
Mechanical Interlock 100-DM… a + a
Frame terminal block 100-DTB110b + 7 each
100-DTB180b + 7 each
100-DTB420b + 8.5 each
Label holder c…+ 5
Conventional DC coil contactors will have an additional auxiliary contact block that will add
13.5 mm to the “a” dimension on the right-hand side.
Renewal Parts
Coils, Continued
AC Operating Coils
Used with Cat. Nos. 190-A40, 190-CPS40, and 190R-CPS40
Voltage [V] Frequency [Hz] Cat. No.
24 50 JB407
24 60 JB013
110 50 JB473
120 60 JB473
208 60 JB049
220 50 JB474
240 60 JB474
380 50 JB454
415 50 JB457
440 50 JB475
480 60 JB475
550 50 JB476
600 60 JB476
Contact kits for Cat. Nos. 100-A09…100-A30 are not available as replacement parts.
AC Operating Coils
Used with 193-GPD Devices
Voltage Frequency [Hz]Cat. No.
24V AC 50 HA407
24V AC 60 HA013
110V AC 50 HA473
110 V AC60 —
120 V AC50 —
120V AC 60 HA473
208 V AC50 —
208V AC 60 HA049
220V AC 50 HA474
220V AC 60 HA051
240V AC 50 HA442
240V AC 60 HA474
277V AC 60 HA060
380V AC 50 HA454
380 V AC60 —
415V AC 50 HA457
440V AC 50 HA475
440V AC 60 HA071
480 V AC50 —
480V AC 60 HA475
500V AC 50 HA464
500 V AC60 —
600V AC 60 HA476
Conventional AC Conventional DC
AC Standard AC 100- 100- 100- DC DC 100- 100- 100-
Control Voltages Coi D95…D D210…D D630…D Standar Coi D95…D D210…D D630…D
l 180 420 860 d l 180 420 860
50 Hz 60 50/60 Co Cat. No. Cat. No. Cat. No. Control Co Cat. No. Cat. No. Cat. No.
Hz Hz de Voltage de
s
24V — — K TG407 — — 12V ZQ TG708 — —
— 24 — J TG013 — — 24V ZJ TG714 — —
V
32V 36 — V TG481 — — 36V ZWTG719 — —
V
36V 42 — W TG410 — — 48V ZY TG724 — —
V
48V — — Y TG414 — — 60V ZZ TG774 — —
42V 48 — X TG482 — — 110V ZD TG733 — —
V
— — 100V KP TG861 — — 125V ZS TG737 — —
110V 120 — D TG473 — — 130V ZF TG738 — —
V
— — 110V KN TG856 — — 220V ZA TG761 — —
— 208 — H TG049 — — 240V ZL TG750 — —
V
— — 200V KG TG862 — — 250V ZT TG751 — —
— — 220V KL TG857 — —
220…2 240 — A TG441 — —
30V V
240V 277 — T TG480 — —
V
— — 277V KT TG060 — —
— — 230V KF TG851 — —
— — 240V KA TG858 — —
380…4 440 — N TG071 — —
00V V
415V 480 — B TG475 — —
V
440V — — G TG478 — —
500V — — M TG479 — —
550V 600 — C TG476 — —
V
Electronic AC Electronic DC
AC Standard AC 100- 100-D420100- DC DC 100- 100-D420100-
Control Voltages Coi D95…D D630…D Standar Coi D95…D D630…D
l 300 860 d l 300 860
50 Hz 60 50/60 Co Cat. No. Cat. No. Cat. No. Control Co Cat. No. Cat. No. Cat. No.
Hz Hz de Voltage de
— — 24V EJ TGE855 — — 24V EZ TGE708 — —
J
— — 42…64 EY TGE864 — — 48…72 EZ TGE779 — —
V V Y
— — 100V EP TGE861 THE861 TJE861 110…13EZ TGE780 THE780 —
0V D
— — 110…13ED TGE865 THE865 TJE865 ED — — TJE865
0V
— — 200V EG TGE862 THE862 — 200…25EZ TGE781 THE781 —
5V A
— — 208…27EA TGE866 THE866 — EA — — TJE879
7V
— — 200…22EG — — TJE878
0V
— — 230…25EA — — TJE879
0V
— — 277V ET — — TJE880
— — 380…50EN TGE867 THE867 —
0V
— — 380…41EN — — TJE867
5V
— — 440…48EB — — TJE868
0V
— — 500V EM — — TJE869
— 600 — EC — — TJE870
V
AC Coil Code100-G1000...100-G1200
Standard Coil Cat. No. Supply Module Cat.
Control No.
Voltages
50/60 Hz
110…115V KD TZ734 TZS734
220…230V KF TZ747 TZS747
380…400V KN TZ779 TZS779
440V KB TZS780 TZS780